HomeMy WebLinkAboutSTAFF REVIEWS - 06-00347 - Trejo Professional Plaza - Bldg #2 - Site PlanX B V
CITY 0
� BI
EXE MG
August 7, 2006
Permit Number: 06 00347
Project Mame;
Project Type:
Review Item
Review Action
Trejo Professions! Plaza Bldg #2
Site Plan Review
Building Department Review
Number of Parking Spaces
Snow Storage
Fire Separation
Setbacks and Propertly Lines
Fri Churton
Miscellaneous
Parcel #'s
RPRTREJOOIOOIO
P.0 Box 280
19 E. Main St,
Rexburg, Idaho 83440
Phone (2Q8) 359-3020
Fix (20 359-3Q22
Ac-,Vions Requilrect-forApq roval _ Aprvrred
Provide parking count for existing parking !at 08/0712006
and the use of the existing building.
Meets requirements. 08/07/2006
The North and East walls will be required to be o8/07/20r%^
0o
gated wars.
Setback at Trejdo is a fron# yard setback? Defer
to Public Works Director.
Identify handicapped parking at building.
Provide pedestrian access to the public right-of-
way without using the driveways.
R..EXBURG
CW
Anterica_� Family �nu��it
August 7, 2006
ka
Permit Number: 06 00347
Project Name:
Project Type:
Review Action
Trejo Professional Plaza Bldg #2
Site Plan Review
Review Item
Fire Department Review
Fire Access Roads
Fire Lane Signage
Additional Comments
Water Supply
Parcel #'s
FOO
P.0 Box 280
19 E fairy St.
Rexburg, Idaho 83440
Phone (208) 359-302
Fax (208) 359-3022
Acfia����.ired for Approval A Loved.
Provided
Not required
Please provide �dditional information as noted.
If there are questions please contact Chas at
705-1312 regarding this site plan review.
Plans indicate 64a0 square foot, type V -B
construction. 2003 IFC requires two fire
hydrants within 45p feet with a minimum fire
flow of X250 GPM,
-Pease provide location of additional fire
hydrants.
-Unknown what final occupancy will he,
structure may require fire suppression system.
0 711 8/2 0 0 6
07/18/2006
07/18/2006
I .
I T Y
EXBURG
_— — CW —
AnzFatnily CVrn�nU11i1js
August 71 2006
Permit Number: 06 00347
Project Name:
Project Type:
Review item
Review Action
Trej'o Professional Plaza Bldg #2
Site flan Review
Planning Staff Review
Approved Site Plan
Parcel #'s
RPRTREJOOIOOIO
RO Box 280
Rexburg, Idaho 83440
Phone (208)359-3020
Fax {208} 359-3022
Actions Required for A►ppr mal
A9-prved
1. Front yard setback is required to be at least
20'. The setback shaven is only 16-47,
2. The sidewalk along the front of the building
must be separated from the facade of the
building by at least 6° to provide for landscaping.
Fax
1
AIT, C
208-339.3020 -x,326
�.,��, or Fes:• 208.359.
t
I PMO)>.
�- -M .1 1� 1-1�
CITY OF
RE.xBuRG
An'. *rk4 Family GOMMM.No�
E] Urgent ❑Far Review E] Please CoMment ❑Please Reply D Pease Recycle
• Comments:
Herm are the review notes That were faxed to DAFAB Construction for the Te Baleg
Building. Please call if you have any questions. � y