HomeMy WebLinkAboutREVIEW ACTIONS - 06-00330 - AMET Building(0 CITY OF REXBURG America's Iamily Commuviiy July 19, 2006 Review Action Permit Number: 06 00329 Project Name: AMET Building -Site Plan Project Type: Review Item Site Plan Review Fire Department Review Water Supply PLEASE PROVIDE THE FOLLOWING INFORMATION FOR MORE ACCURATE SITE PLAN REVIEW: 1. PROPOSED FIRE HYDRANT LOCATIONS 2. EXITING FIRE HYDRANT FLOWS AND ESTIMATED PROPOSED FIRE HYDRANT FLOWS 3. IS BUILDING TO BE FULLY FIRE SPRINKLERED? 4. OCCUPANCY TYPE 5. CONSTRUCTION TYPE 6. WHICH PHASES OF THE BUILDING WILL BE CONSTRUCTED FIRST? Fire Access Roads _ BUILDING HEIGHT DICTATES THAT 2003 IFC SECTION D105 IS REQUIRED. PLEASE PROVIDE MORE DETAILS. Fire Lane Signage MAY BE REQUIRED DEPENDING UPON FINAL SITE PLAN Additional Comments PLEASE PROVIDE ADDITIONAL INFORMATION ARE REQUESTED. IF YOU HAVE QUESTIONS PLEASE CONTACT CHRIS AT 705-1312. Parcel ft RPRRXBP2030030 RO Box 280 19 E Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 (W CITY OF REXBURG ne+ Amerim's Pomiiy Conm�m,iry May 17, 2007 Review Action Permit Number: 06 00330 Project Name: AMET Building Foundation ONLY! Project Type: Commercial New P.O Box 280 19 E. Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Approved Planning Staff Review Development Standards Review South building facade, being over 100 et in 09/13/2006 le th, is required to incorporate wall proj tions or recesses a minimum 3 foot depth nd a minimum of 20 conti ous feet in length. \ 2. Buildin facades shall be bro en up horizontally very 30 feet by color change, texture chan , material m ule change, or 1 architectural st ctural ba . 3. South wall is r quried o vary height of roof lines every 100 lin ar f et. 4. Parking between ilding and streets must be screened. 5. Sidewalks alon pub' right of way are required to be a east 6 f t wide. 6. Internal ped strian we[ s need to be connected t ublic right of w walkways. Development Standards Review The issue isted above were ap ved in a 09/13/2006 Design eview meeting - 9/13/200 . Development Standards Review Developer must submit a landscaping plan to screen the parking from the street, and to visually break up the north side of the building - as noted in the design review meeting - 9/13/2006. Trees must be approximately 100 feet apart - to substitute for the design standards requirement. Landscaping must be completed with the building project.tliti Development Standards Review The west facade of phase 2 must incorporate 2 1 ..M foot deep, 20 foot long recess or projection Or N/"Tm every 100 lineal feet. (Y)A. to `�-L D4m Development Standards Review % North and West facades do not meet section l 3.9.160.a.ii - Detail Features. Each facade O� must include a repeating pattern every 30 feet Development Standards Review The west facade must break up the roofline every 100 feet. See section 3.19.160.a.iii - 0 ��� M`�ns Parking Schedule ....� employees Full Time 8 to 5 Shift 37 First Shift 3 Second Shift 3 Offsite Staff 3 Part Time 3 Total Employees 49 Peak Working Hours/Assembly & High Bay Areas Employees 18 Peak Working Hours/First & Second Floor Gross Square Footage 15,040 Standard Space Size 9' x 18' Compact Space Size 8' x 15' Handicapped Space Size 10' x 19' Access 6' x 19' Code Requirements 18x1.2= 21.6or22 1,5040 x 2= 30080 or 30 Total Stalls Required Total Stalls As Drawn 52 59 City Meeting/AMET May 21, 2007 Site Plan Review Requirement: Parking must not be located in the first 10' of front yard setback. Action: 10' front yard set back will be adhered to and reflected on the civil plans Requirement: The minimum parking stall size is 9 x 18 feet, not 8.5 x 19. The compact size is 8 x 15 feet. Action: Proper parking stall sizes will be adhered to. Requirement: 79 total parking stalls are required, 20 of which may be compact. Action: 59 stalls will be provided for this facility per code. This information is reflected on the parking schedule spreadsheet provided. Requirement: Garbage containers must be screened. Please show type of screening on the site plan. Action: Garbage containers will be screened with fencing, and will be reflected on the civil plans. Requirement: All parking areas shall be screened from the public right-of-way with fences, hedges, berms, and landscaping. Please submit a detailed landscaping plan for review. Action: Screening of parking will be adhered to per requirements. A landscaping plan will be submitted for review reflecting screening. Requirement: It is recommended that the internal pedestrian connection be located on the south end of the lot. The code requires this pathway to include adjoining landscaped areas that include trees, shrubs, benches, flower beds, ground covers, or other such materials for no less than 50 percent of its length. Action: Will not provide internal pedestrian connection to right of way for following reasons. 1- Providing an additional invitation to the general public is not desired for safety and privacy reasons. 2- Projected use if any by employees will not serve the intended purpose. 3- The facility is in a light industrial area and will not see a heavy flow of the general public. 4- Additional cost incurred .,i u Requirement: Northeast parking area will force vehicles to us the right-of-way to turn around or move from one area of the lot to another. The ordinance prohibits this. Action: This area of parking will be removed and specified as a loading and unloading area on plans. Development Standards Requirement: Developer must submit a landscaping plan to screen the parking from the street, and to visually break up the north side of the building as noted in the design review meeting 9-13-06. Action: A landscaping plan will be submitted for approval. Landscaping plan will reflect screening the parking. Requirement: Trees must be approximately 100' apart to substitute for the design standards requirement. Landscaping must be completed with the building project. Action: Design standards will be adhered to regarding the landscape work. Landscaping will be completed as part of the building project. Requirement: The West facade of phase 2 must incorporate 2 foot deep, 20 foot long recess or projection every 100 lineal feet. Action: Will not incorporate 2 food deep, 20 foot long recess or projection. - The West facade will be broken up by vertical columns and windows as shown on the architectural drawings. - The columns shown will still provide a break-up on the West side providing a nice look to this side of the facility. Meeting the design standard for this side of the facility will increase the cost of the building and adds no value to the owner. Requirement: The West facades do not meet section 3.9.160.a.ii — Detail Features. Each facade must include a repeating pattern every 30 feet. Action: Will not incorporate this design standard. - These standards will increase cost, and adds no value to the owner. - The materials planned for the exterior of the facility are not substandard. - The exterior look of the building will be aesthetically dominant to the existing buildings in this light industrial area. Requirement: The West facade must break up the roofline every 100 feet. See section 3.19.160.a.iii. Action: Will not incorporate this design standard. - These standards will increase cost, and adds no value to the owner. aC+auq —CITY OF REXBURG A,nenrni Fw dy Cmn.,,Wfy May 24, 2007 Permit Number: 06 00330 Project Name: AMET Building Project Type: Commercial New Review Item Administrative Review Permit Tech Notes Parcel Ws RPRRXBP2030030 19 E. Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Review Action Fax (208) 359-3022, Actions Required for Approval Approved Plumbing, Mechanical, & Electrical signatures needed for Phase 2 if contractors have changed. � °'psnuRc CITY 0 FF 19 E. Main St. Rex vLW V 1�� burg, Idaho 83440 -- cw — - Phone (208) 359-3020 Americas Family Community ' Review Action Fax (208) 359-3022 May 24, 2007 Permit Number: 06 00330 Project Name: AMET Building Project Type: Commercial New Review Item Actions Required for Approval Approved _- Building Code Fire Compliance Review Provide details that identify how fire blocking will be constructed at the space between the steel building and the interior construction. Waste Water Grease Trap Form Exiting Review Identify on plans emergency lighting and all exit signs. The second required exit from the upstairs passes through the "assembly area". Section 1013.2 requires that egress shall not pass "through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served". The assembly area is not accessory to the offices that are on the second floor. Egress continuity will be lost with the current configuration. Please revise this egress component. Also, the travel distance from the exercise room and the storage room on the second floor exceed the allowable distance from IBC Table 1015.1. The area under the stairs must be 1-hr. rated construction. Structural Review Provide engineered structural details for the interior construction. The steel building is not engineered for the loads that will be generated by the interior construction. Include shear walls, floor joist and footing details for the interior. Special inspections are required for the concrete foundation, high strength bolting and any welding. Provide letter from special inspection firm. Mechanical Review Provide mechanical details and sizing. Electrical Service Review Energy Conservation Compliance Review Need to see a plan for the circuits and the service for what is to be installed. Revisions required. Need to see a lighting energy compliance. Nothing was submitted. � pbxaugG; C I T Y OF 19 E. Main St. m REXBURG Rexburg, Idaho 83440 0 ----- OW— Phone (208) 359.3020 J'. America's Family Comm Plity Review Action Fax (208) 359-3022 May 24, 2007 Permit Number: 06 00330 Project Name: AMET Building Project Type: Commercial New Review Item Actions Required for Approval Approved Miscellaneous Building classification is B, F-1, S-1 and S-2. The review for building size was based on a "nonseperated uses" approach. Therefore, the materials that are allowed in the building must meet the requirements of the 2003 International Building Code Table 307.7(1). Please provide a letter that identifies that the table has been reviewed and that the quantities of applicable materials that will be present in the building will meet these requirements. Energy Conservation Compliance Review Provide energy review for mechanical, lighting and envelope. Electrical Circuits Review Need to see and review a plan for what is planning on being installed electrically. Revisions required. Nothing was submitted electrically. Parcel Ws RPRRXBP2030030 ~; �pbxnugC�> 0 CITY OF REXBURG llft� :Imerlta's Family Community Review Action May 24, 2007 Permit Number: Project Name: Project Type: 0600330 AMET Building Commercial New 19 E. Main St. Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 Review Item Actions Required for Approval Approved Miles R ItiNVi-IN Required Fire Flow See site plan review 05/23/2007 Fire Extinguishers All fire extinguishers are required to be installed before final fire inspection. Standpipes Not required according to plans submitted Alarm Systems Other Comments Commercial Cooking Automatic Fire Extinguishing Systems Water Supply Fire Access Roads Parcel Vs RPRRXBP2030030 Submit letter of intent from certified Fire Alarm contractor. Fire alarm drawings are required to be reviewed and approved before installing any part of the fire alarm system. Submit a letter to the building official stating that the occupancy will not exceed the allow amount of hazardous materials that would require the occupancy to be classed as a hazardous occupancy. Lock box is required for this occupancy. Forms are available at the Rexburg Fire Department. N/A Plans are required to be submitted to the State Fire Marshall and approved prior to any installation of the Fire Sprinkler System. Submit letter of intent from a certified Fire Sprinkler Contractor See site plan review See site plan review 05/23/2007 05/23/2007 05/23/2007 05/23/2007 05/23/2007 P. 1 MemTry TX Result Report ( May.24. 20To 3:32PM ) • 1) 2) Date/Time: May.24. 2007 3:31PM File Page No. Mode Destination Pg(s) Result Not Sent ---------------------------------------------------------------------------------------------------- 4267 Memory TX 6560400 P. 5 OK ---------------------------------------------------------------------------------------------------- Reason for error E. 1) Hang up or line fail E. 2) Busy E. 3) No answer E. 4) No facsimile connection E. 5) Exceeded max. E—mail size a1vv a• rs8M6BaigID Fj WZZH .=XM REXS W Fax rW tia Iayttas9eP tt= JottelHorssen PbOM Dchx May24.20V am cc o U19cad a Far Rowtow a Prove Conmseas o Penn try► o Ptws Recto I .caanrft Here >z the bu]dr>O reNlew action+ fw AME7. n doesn't tnctude any design standards notes because En*sotd you had warned those detail out. shaft YOM JaNel Kamen 0 tiy�� pE7tsu�r,'o . D � !_CITY OF REXBURG OW Anericai Family Community July 12, 2006 P.O Box 280 19 E Main St. Rexburg, Idaho 8M40 Phone (208) 359-3020 Review Action Fax (208) 359-3022 Permit Number: 06 00329 Project Name: AMET Building -Site Plan Project Type: Site Plan Review Review Item P 'b�Iic�irtRr;�e Approved Site Plan 1. The proposed phase 1 portion of this project 07/11/2006 is approved. 2. Prior to the final approval additional information must be submitted showing details of the storm water collection system. 3. The location of the refuse collection bin must be at a location the is accessable to a right side pick-up collection truck. 4. Additional information must be supplied for the parking and area lighting. The fixture type, wattage, location and light curves must be submitted. 5. If a fire sprinkler system is required for the comlpleted building a connection to the mainline will be required. This connecton will require a street corssing. Parcel Vs RPRRXBP2030030