HomeMy WebLinkAboutREVIEW ACTIONS - 06-00184 - Madison Memorial Hospital - Addition44
I T Y O F
REX13URG
June 8, 2006
Permit Number: 06 00184
Project Name:
Project Type:
Review Action
Madison Memorial Hospital Addition
Commercial Addition
Review, Item
Building Department Review
Accessibility Review
Height and Area Review
Building Type Compliance
Complies with approved Site Plan Review
Mechanical Review
Energy Conservation Compliance Review
Exiting ie
Building Code Fire Compliance Review
Structural Review
&P-Mcm-s-Re-q-uired .for Aprova�
Meets the requirements of the 20i33
International Building Code (113C).
Building meets height and area requirements,
Building Type is IB,
Site plan has been reviewed. ,Are additional
handicapped parking spaces required as per
i BC Sections 1106.3 and 1106-4?
lVlechanicai and electrical components must be
connected to structure as per IBC Section
1621.
Provide lighting review as ,per the 2p03
International Energy Conservation Code
(! ECC).
The exit court must meet the requirements of
the !BC for fire seperatiQn. The doors and
windows in the court must be rated. Identify
locations identified for Areas of Refuge. Include
all requirements identified by IBC Section
1007-6.
The corridor walls at the MRI area must be
rated. Provide smoke control at all corridor
uti+alis.
Please provide a letter from the Special
Inspection's Firm that identifies the inspections
that they will be performing and thefrequency of
those inspections. Provide Fabricator approWal
as per !BC Section 1704-2.2. Provide a
schedule for Structural Observations as per
IBC Section 1709. Structural fill is required
between footings and bedrock. The engineer
requires 4000 psf fill. Please provide
information from Geotechnical firm tto
substantiate as till is placed.
P-0 Box 280
Rexburg, kiaho $3440
Phone {208} 359-3020
Fax (2Q8) 359-3022
05/19/2006
05/19/2006
05/19/2006
14
REXBURG
Aeyl� Family
June 8, 2006
Permit Number: 06 00184
Project Name:
Project Type:
Review Item
Review Action
Madison Memorial Hospital Addition
Commercial Addition
—_
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing Potable Water Review
Water and Sewer Service
Parcel #'s RPROOOR0007900
Actilons–R-e-q uired f o
TA
ppxoval
Al! drain lines are to be installed according to
the Uniform Plumbing code.All drain Lines are
required to be tested and inspected before
covering.
Resubmit plumbing that meets requirements of
the Uniform Plumbing Cade 2p03 edition.
Storm drains are requied to be tested and
inspected before covering. Strom drains are
required to be installed and sized according to
the Uniform Plumbing Code.
Resubmit plumbing that mets requirements of
the Uniform Plumbing Cade X0(33 edition.
All potable water piping is require! to have the
proper backflow prevention device installed,
tested and inspected with a copy of the
backflow test sent to the City water department
prior to final inspection.
AIS potable water piping shall be installed, tested
and inspected before covering.
Resubmit plumbing that meets requirements of
the Uniform Plumbing Code 2(]D3 edition.
A I plumbing services are required to tested
and inspected before covering. Water meter is
to be installed in approved location by the City
Wader Department before installation.
Resubmit plumbing that meets requirements of
the Uniform Plumbing Code 2043 edition.
P.0 Box 280
19 E_ Main St.
Rexburg, Idaho 83440
Phone (2Q8) 359-3020
Fax (208) 359-3022
mm_
ITY0F
X B U, R G
-w-- , -I. .
Amerira� Family Community
June 8, 2006
Permit Number: 06 00184
Project Name:
Project Type:
Review Action
Madison Memorial Hospital Addition
Commerc'l'al Addition
Review Item
Fire Department Review
Standpipes
Required Fire Flow
''Fater Supply
Commercial Cooking
Other Comments
Alarm Systems
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Parcel #'s RPROOOR0007900
AC-tiOris—R-equire-dfor
A"raval _
N/A
See site plan review.
See site plan review.
Please submit specifications on all cooking
hoods dor approval. All type 1 hoods are
required to have fire protection and connect to
the fire alarm system.
Lock box is required for this occupancy. Form
can be obtained from the Rexburg Fire
Department. Lock box is required to be installed
before final inspection.
Occupancy requires fire alarm system. Please
submit letter of intent from certified alarm
contractor.
Submit plans for approval for the firs alarm
system prior to installation,
See site plan review.
Fire extinguishers are required for this
occupancy. Please submit plan showing
locations of fire extinguishers.
Automatic fire sprinkler system required for this
occupancy. Submit plans to State dire Marshall
for approval. Plans are required to be approved
before installation of the fire sprinkler system is
installed. Approved plans required an Job site,
P.0 Box 280
1 F- Mala St.
Rexburg, Idaho $3440
Phone (208) 359-3020
Fax {2D8} 359-3022
A roved
05/17/2006