Review Action
Fax (208) 359-3022
March 13, 2006
Permit Number: 05 00271
Project Name: Temple (structural steel/framing only)
Project Type: Commercial New
Review Item _ _ _
Action3 Required for Appr- v I _ -Approved
Building Department Review
Complies with approved Site Plan Review
Site plan has been reviewed. 08/25/2005
Structural Review
Strustural review performed for steel framing 08/31/2005
only. The structural plans were incomplete.
Provide fabricator special inspections
certification. Provide letter from special
inspections firm for all other special
inspections. Letter should indicate inpections
(including frequency) that will be performed.
Parcel Ws RPRXBCA0310002
oco
Goa4
05
00alJ4o jjA0,A
P.O Box 280
`•h ,� CITY O f
19 E Main St.
MXBURG Rexburg, Idaho 83440
Phone (208) 359-3020
Amric6 Family Community
Review Action
Fax (208) 359-3022
March 13, 2006
Permit Number: 05 00271
Project Name: Temple (structural steel/framing only)
Project Type: Commercial New
Review Item Actions Required for Approval Aaproved
-
Lit
Required Fire Flow 08/15/2005
Water Supply 08/15/2005
Fire Access Roads 08/15/2005
Fire Extinguishers 08/15/2005
Automatic Fire Extinguishing Systems 08/15/2005
Standpipes 08/15/2005
Commercial Cooking 08/15/2005
Alarm Systems 08/15/2005
Other Comments PLEASE REFER TO PREVIOUS TEMPLE 08/15/2005
SUBMITTALS FOR COMMENTS ... NONE AT
THIS TIME ON STRUCTURAL FRAMING.
Parcel #'s RPRXBCA0310002
REXBUgG- RO Box 280
y CITY_or 19EWin St.
°
REXBURG Rexburg, Idaho 83440
"" — Phone (208) 359-3020
'.; Amcricu's fiemily Comniauiity
Fax (208) 359-3022
Review Action
March 3, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item
Building Department Review
Water and Sewer Service
Water service is required to have an reduced
01 /23/2006
pressure backflow preventor if potable water
supply is with in 1700 ft of the fire system.
Water service requires inspection and testing
before covering.
Sewer services are required to be tested and
inspected before covering.
Plumbing Potable Water Review
All water lines are required to be tested and
01 /23/2006
inspected before covering.
All waterlines required to be installed according
to Chapter 6 of the 2003 Uniform Plumbing
Code.
Plumbing Storm Drain Review
All roof drains are required to be tested and
01/23/2006
inspected before covering. Required to be sized
according to the Uniform Plumbing Code 2003
edition.
Plumbing Sewer Drain Review
Please submit revised drawings showing
01 /23/2006
proper drain, waste and venting. Current plans
submitted do not meet 2003 Uniform Plumbing
Code.
Complies with approved Site Plan Review
A site plan has been approved.
03/02/2006
Accessibility Review
Meets accessible requirements.
03/02/2006
Exiting Review
Exits are sized properly. All egress
03/02/2006
components meet code requirements.
Height and Area Review
Height and area meet requirements of IBC
03/02/2006
Table 503.
Building Type Compliance
Building is Type IB
03/02/2006
Mechanical Review
Meets code requirements.
03/02/2006
Energy Conservation Compliance Review
Meets the requirements of the 2003
03/02/2006
International Energy Conservation Code.
o� aexaua� P.O Box 280
�o CITY OF - -- 1� � 19EWin St.
REXBURG Rexburg, Idaho 83440
- ` Amesica's Famitp CommunCommunitynity
_ Phone (208) 359-3020
^'.
Review Action Fax (208) 359-3022
March 3, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item
Interior Environment All wall, ceiling and floor finishes must meet the 03/02/2006
requirements of I BC Sections 803 and 804.
Building Code Fire Compliance Review The laundry chute must comply with Sections
707.13.1 and 707.4 of the 2003 International
Building Code. Please make the necessary
changes and provide copies to the City of
Rexburg Building Department.
Waste Water Grease Trap Form
Waste Water Application
Structural Review Provide information and documentation from
off -site steel fabricator as per IBC Section
1704.2. Provide manufacture's requirements
for all equipment seismic connections as per
IBC Section 1621.
Parcel Vs RPRXBCA0310002
o�atxeuRc P.O Box 280
ci'ry oe 19EWin St.
_ -- -- - -- -
", RE)MURG Rexburg, Idaho 83440
CW - Phone (208) 359-3020
Ameriuu Family Community
Review Action Fax (208) 359-3022
March 3, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item Actions Required for Approval —Approved
Fire Department Review
Commercial Cooking No Commercial cooking devices are to be 01/23/2006
installed. No review is required.
Required Fire Flow
Water Supply
Alarm Systems Please submit fire alarm plans for review and
approval.
Letter of intent is required from company
installing the fire alarm system. Fire alarm
plans are required to be reviewed and approved
before fire alarm system is installed.
Other Comments Lock box is required for this occupancy. Please
contact the Rexburg Fire Department for
application. (208) 359-3010.
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Parcel Vs RPRXBCA0310002
Please show location of all fire extinguishers on
plans.Please list which plan extinguishers are
on if already shown.
Automatic fire suppression system is required
to have the approval of the State Fire Marshall.
Approval is required before the fire sprinkler
system is installed. Please send a letter of
intent from the contractor installing the fire
suppression system. Contractor is required to
have the proper certifications submitted with the
letter of intent.
o� V,F.x a VRc P.O Box 280
:; --- - CITY o h �� 19 E Main St.
REXBURG Rexburg, Idaho 83440
Phone (208) 359-3020
America's Family Contnnmify
. Review Action Fax (208) 359-3022
March 2, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item
wilding Department Review
Water and Sewer Service Water service is required to have an reduced 01/23/2006
pressure backflow preventor if potable water
supply is with in 1700 ft of the fire system.
Water service requires inspection and testing
before covering.
Sewer services are required to be tested and
inspected before covering.
Plumbing Potable Water Review All water lines are required to be tested and 01/23/2006
inspected before covering.
All waterlines required to be installed according
to Chapter 6 of the 2003 Uniform Plumbing
Code.
Plumbing Storm Drain Review All roof drains are required to be tested and 01/23/2006
inspected before covering. Required to be sized
according to the Uniform Plumbing Code 2003
edition.
Plumbing Sewer Drain Review Please submit revised drawings showing 01/23/2006
proper drain, waste and venting. Current plans
submitted do not meet 2003 Uniform Plumbing
Code.
Complies with approved Site Plan Review A site plan has been approved. 03/02/2006
Accessibility Review Meets accessible requirements. 03/02/2006
Exiting Review Exits are sized properly. All egress 03/02/2006
components meet code requirements.
Height and Area Review Height and area meet requirements of IBC 03/02/2006
Table 503.
Building Type Compliance Building is Type IB 03/02/2006
Mechanical Review Meets code requirements. 03/02/2006
Energy Conservation Compliance Review Meets the requirements of the 2003 03/02/2006
International Energy Conservation Code.
o�aexsuao P.O Box 280
.o c i T Y 0 H �/ �� 19 E Main St.
MXBURG Rexburg, Idaho 83440
F
America's Family Communily Phone (208) 359-3020
Review Action Fax (208) 359-3022
March 2, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item Actions Required for Approval Ap roved
Interior Environment All wall ceiling and floor finishes must meet the 03/02/2006
Building Code Fire Compliance Review
Waste Water Grease Trap Form
Waste Water Application
requirements of IBC Sections 803 and 804.
The laundry chute must comply with Sections
707.13.1 and 707.4 of the 2003 International
Building Code. Please make the necessary
changes and provide copies to the City of
Rexburg Building Department.
Structural Review Provide information and documentation from
off -site steel fabricator as per IBC Section
1704.2. Provide manufacture's requirements
for all equipment seismic connections as per
IBC Section 1621.
Parcel Vs RPRXBCA0310002
� AOQ RO Box 280
C I T Y OF ^ \� 19 E Main St.
REXBURG Rexburg, Idaho 83440
-- �' -- - Phone (208) 359-3020
. America's FinnilyConmurnNy
Review Action Fax (208) 359-3022
March 2, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item Actions Required for Approval Approved
Fire Department Review
Commercial Cooking No Commercial cooking devices are to be 01/23/2006
installed. No review is required.
Required Fire Flow
Water Supply
Alarm Systems
Other Comments
Fire Access Roads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Parcel #'s RPRXBCA0310002
Please submit fire alarm plans for review and
approval.
Letter of intent is required from company
installing the fire alarm system. Fire alarm
plans are required to be reviewed and approved
before fire alarm system is installed.
Lock box is required for this occupancy. Please
contact the Rexburg Fire Department for
application. (208) 359-3010.
Please show location of all fire extinguishers on
plans.Please list which plan extinguishers are
on if already shown.
Automatic fire suppression system is required
to have the approval of the State Fire Marshall.
Approval is required before the fire sprinkler
system is installed. Please send a letter of
intent from the contractor installing the fire
suppression system. Contractor is required to
have the proper certifications submitted with the
letter of intent.
r�*Xcv
Dom^ 0 op,� bK
1,18*- C JO#
01pV)" rt. bus.
rlrs .uez�5
//J 14'14,6 -4
)4kl IN
P 10 r-�,
o�a�xnt,gc P.O Box 280
C l T Y o r____ 19 E Main St.
REXB V RG Rexburg, Idaho 83440
CW _— Phone (208) 359 3020
America's Family Community
Review Action Fax (208) 359-3022
March 2, 2006
Permit Number: 06 00024
Project Name: Temple (Phase 3)
Project Type: Commercial New
Review Item Actions Required for Approval ARpoved
Administrative ftvlew,
Permit Tech Notes 02/22/2006
Parcel #'s RPRXBCA0310002 n
� po ikpY
C/ J 0/i
'4�7e�f
', 0 14 /.4?J