Loading...
HomeMy WebLinkAbout20023-C-06-24-2020 FP 1 of 4 sfProject Name: Client: Mix Number: Project Number: Ticket Number: Load Amount: Admixtures: Tested By: Date and Time: Compressive Strength of Concrete Test Specimens Field Test Data: (ASTM C143, C138, C173, C231, C31, C1064, and C511) Slump (Inches): Entrained Air (%): Concrete Temperature: Ambient Temperature: Test Results:Minimum:Maximum: Cylinder # Lab Test Data: (ASTM C39, C42, C617, and C1231) Break Age Cylinder Diameter (in) Area (in² ) Break Date Maximum Load (lbs) Break Type Compressive Strength (psi)Required 28 day Strength (psi) °F °F Reviewed By: Supplier: Test Location: Unit Weight (PCF):Set # : Cylinders Picked Up By: Date and Time: Hi / Low Temperatures Remarks: 28-day Average Strength лйсͨтрйͨплмрϝϝϝͨωϕϔϔϋωϚϋϔύϘͨωϕϓнкймΎпйоΗΜϛϏϚϋкΛϏύψϟͥΒ΍смннл 4,959 PSI MACU Call Center Mills Concrete 192F MACU 20023 15057 150 of 208 yards MP 322, MA AE 90 F Pelton 06-24-2020, 8:30 am 5 6 71.2 53 24 47 151A 151E 151C 151B 151D 4 4 4 4 07/01/20 07/22/20 07/22/20 07/22/20 07/22/20 42,085 61,685 62,285 63,045 53,5003,348 4,907 4,955 5,015 Digitally signed by Jacob P Christensen Date: 2020.07.22 09:29:18 -06'00' 12.57 Walters Ready Mix Western exterior wall 7 28 28 28 H 12.57 12.57 12.57 15 gallons of water was added, which increased the slump. 1 S. Edwards 06/25/2020 1 2 5