HomeMy WebLinkAboutCOMCHECK - 07-00492 - Big 5 Sporting Goods - RemodelC0Mcheck Software Version 3.4.2
Lighting Compliai
07 Ot)492
Big - Sporting (foods-lntenor Remodel
2003 IECC
Report Date: 09/17/07
Data filename: P:\2007\07075-BIG 5 REXBURG, ID\ENERGY COMPLIANCE\Big 5- Rexburg, Idaho.cck
Section 1: Project Information
Project Title: Big 5 - Rexburg, Idaho
Construction Site: OwneriAgent: Designer/Contractor:
North 2nd. East (highway 191) Michael John Voigtlander
Rexburg, ID 83440 BWF Consulting Engineers
510 Myrtle Avenue
South San Francisco, CA 94080
(650) 871-0220
mvoigtlander@bwfce.rwm
Section 2: General Information
Building Use Description by: Activity Type EL CTRICAL I TOR
Project Type: New Construction
Activity Tyoe(sl Floor Area
Retail Sales, Wholesale Showroom 7310
Office 127
Storage, Industrial and Commercial 2376
Corridor, Restroom, Support Area 238 ^ 2
Section 3: Requirements Checklist D IIIVJ' �C D
Interior Lighting: SEP 2 2007
ref 1. Total actual watts must be less than or equal to total allowed wafts.
Y't Allowed Watts Actual Watts Complies
19313 16875 YES CITY OF REXBURG
TsG 2. Exit signs 5 Watts or less per side.
i Exterior Lighting:
pl 3. Efficacy greater than 45 lumens/W.
7� Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting; low -voltage landscape
lighting.
Controls, Switching, and Wiring:
4. Independent controls for each space (switch/occupancy sensor).
J� Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
5. Master switch at entry to hotel/motel guest room.
6. Individual dwelling units separately metered.
7. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions:
Only one luminaire in space;
Page 1 of 3
An occupant -sensing device cols the area;
• The area is a corridor, storeroom, restroom, public lobby or guest room;
Areas that use less than 0.6 Watts/sq.ft.
8. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
]� Exceptions:
Areas with only one luminaire, corridors, storerooms, restrooms, or public lobbies.
j� 9. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
�( 10.Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions:
Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2003 IECC,
Chapter 8, requirements in COMcheck Version 3.4.2 and to comply with t mand ory re ents in the Requirements Checklist.
t Guo• tE� v a ey 41.E o E�
/7 0�
Name - Title Signature Date
Page 2 of 3
COMcheck Software Version 3.4.2
Lighting Application Worksheet
2003 IECC
Report Date:
Data filename: P:\2007\07075-BIG 5 REXBURG, ID\ENERGY COMPLIANCE\Big 5- Rexburg, Idaho.cck
Section 1: Allowed Lighting Power Calculation
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts 1 ft2
(B x C)
Retail Sales, Wholesale Showroom
7310
1.7
12427
Allowance: Merchandise Display / Fix. ID: C1
290(a)
1.6
413(b)
Allowance: Merchandise Display / Fix. ID: C2
3800(a)
1.6
4218(b)
Office
127
1.1
140
Storage, Industrial and Commercial
2376
0.8
1901
Corridor, Restroom, Support Area
238
0.9
214
Total Allowed Watts =
19313
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
Section 2: Actual Lighting Power Calculation
A
Fixture ID : Description I Lamp I Wattage Per Lamp I Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Retail Sales, Wholesale Showroom (7310 sq.ft.)
Linear Fluorescent 1: Al & A3: 2x4 3L Fluorescent Fixture / 48" T8 32W /
3
98
89
8722
Electronic
Linear Fluorescent 3: Cl: tx4 21- Fluorescent Fixture / 48" T8 32W / Electronic
2
7
59
413
Linear Fluorescent 4: C2: 1x8 41 Fluorescent Fixture / 48" T8 32W / Electronic
4
37
114
4218
Linear Fluorescent 6: S: 1x8 21- Fluorescent Fixture / 48" TS 32W / Electronic
2
1
59
59
Office (127 sq.ft.)
Linear Fluorescent 7: A2: 2x4 3L Fluorescent Fixture / 48" T8 32W / Electronic
3
2
102
204
Storage, Industrial and Commercial (2376 sq.ft.)
Linear Fluorescent 8: DI & D2: 8' 4L Strip fluorescent / 48" T8 32W / Electronic
4
26
114
2964
Linear Fluorescent 10: D3: 4' 2L Strip fluorescent / 48" T8 32W / Electronic
2
1
59
59
Corridor, Restroom, Support Area (238 sq.ft.)
Linear Fluorescent 9: El: Ix4 Fluorescent Fixture / 48" T8 32W / Electronic
2
4
59
236
Total Actual Watts =
16875
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 19313
Total Actual Watts = 16875
Project Compliance = 2438
Design
Page 3 of 3
COMcheck Software Version 3.4.2
Lighting Compl 0700492
Big 5 Sporting Goods -Interior Remodel
2003 IECC
Report Date: 09/17/07
Data filename: P:12007\07075-13IG 5 REXBURG, ID\ENERGY COMPLIANCE\Big 5- Rexburg, Idaho.cck
Section 1: Project Information
Project Title: Big 5 - Rexburg, Idaho
Construction Site: Owner/Agent: Designer/Contractor:
North 2nd. East (highway 191) Michael John Voigtlander
Rexburg, ID 83440 BWF Consulting Engineers
510 Myrtle Avenue
South San Francisco, CA 94080
(650) 871-0220
mvoigtiander@bwfce.com
Section 2: General Information
Building Use Description by: Activity Type
Project Type: New Construction
Activity Type(s)
Floor Area
Retail Sales, Wholesale Showroom
7310
Office
127
Storage, Industrial and Commercial
2376
Corridor, Restroom, Support Area
238
Section 3: Requirements Checklist
Interior Lighting:
)yi 1. Total actual watts must be less than or equal to total allowed watts.
Allowed Watts Actual Watts Complies
19313 16875 YES
xy 2. Exit signs 5 Watts or less per side.
SEP 2 7 2007
CITY OF RE BX URG
Exterior Lighting:
�r 3. Efficacy greater than 45 IumensfW.
T Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or security lighting; low -voltage landscape
lighting.
Controls, Switching, and Wiring:
lX 4. Independent controls for each space (switch/occupancy sensor).
'Y� Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
Li 5. Master switch at entry to hotel/motel guest room.
6. Individual dwelling units separately metered.
7. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions:
Only one luminaire in space;
Page 1 of 3
An occupant -sensing devic llfts�trols the area;
The area is a corridor, storeroom, restroom, public lobby or guest room; 1*MV
Areas that use less than 0.6 Wattslsq.ft.
is 8. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
Areas with only one luminaire, corridors, storerooms, restrooms, or public lobbies.
9. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
10.Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions:
Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2003 IECC,
Chapter 8, requirements in COMcheck Version 3.4.2 and to comply with the mandatory re ' ments in the Requirements Checklist.
/bttLHA•6V t/11-A-v 0X- 47117
Name - Title Signature Date
j:�)
Page 2 of 3
CONIcheck Software Version 3.4.2
Lighting Application Worksheet
2003 IECC
Report Date:
Data filename: P:\2007\07075-BIG 5 REXBURG, ID\ENERGY COMPLIANCE\Big 5- Rexburg, Idaho.cck
Section 1: Allowed Lighting Power Calculation
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts 1 ft2
(B x C)
Retail Sales, Wholesale Showroom
7310
1.7
12427
Allowance: Merchandise Display / Fix. ID: Ci
290(a)
1.6
413(b)
Allowance: Merchandise Display / Fix. ID: C2
3800(a)
1.6
4218(b)
Office
127
1.1
140
Storage, Industrial and Commercial
2376
0.8
1901
Corridor, Restroom, Support Area
238
0.9
214
Total Allowed Watts =
19313
(a) Area claimed must not exceed the illuminated area permitted
for this allowance type.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Section 2, whichever is less.
Section 2: Actual Lighting Power Calculation
A
Fixture ID : Description I Lamp / Wattage Per Lamp I Ballast
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
Retail Sales, Wholesale Showroom (7310 sq.ft.)
Linear Fluorescent 1: At & A3: 2x4 3L Fluorescent Fixture / 48" T8 32W /
3
98
89
8722
Electronic
Linear Fluorescent 3: Cl: 1x4 2L Fluorescent Fixture / 48" T8 32W / Electronic
2
7
59
413
Linear Fluorescent 4: C2: 1x8 41 Fluorescent Fixture I48" T8 32W / Electronic
4
37
114
4218
Linear Fluorescent 6: S: lx8 2L Fluorescent Fixture / 48" T8 32W / Electronic
2
1
59
59
Office (127 sq.ft.)
Linear Fluorescent 7: A2: 2x4 3L Fluorescent Fixture / 48" T8 32W / Electronic
3
2
102
204
Storage, Industrial and Commercial (2376 sq.ft.)
Linear Fluorescent 8: D1 & D2: 8' 4L Strip fluorescent / 48" T8 32W / Electronic
4
26
114
2964
Linear Fluorescent 10: D3: 4' 2L Strip fluorescent / 48" T8 32W / Electronic
2
1
59
59
Corridor, Restroom, Support Area (238 sq.ft.)
Linear Fluorescent 9: Et: 1x4 Fluorescent Fixture / 48" T8 32W / Electronic
2
4
59
236
Total Actual Watts =
16875
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 19313
Total Actual Watts = 16875
Project Compliance = 2438
Lighting PASSES: Design 13-A better than code�
Page 3 of 3