HomeMy WebLinkAboutREVIEW ACTION 2 - 07-00433 & 434 - The Bank of CommerceITY 0 F
--EXBURG
AmericO Family ily orptmun [
October 8, 200�
Permit Number: 07 00434
Project Name:
Project Type:
Review Item
Review Action
The Bank of Commerce
Commercial New
Administrative Review
Permit Tech Notes
Parcel #'s IRPRHNRFOO10061
Act -ions Require. or_ AppLoyal
General contractor info ion needed
including Idaho registration #,
Plumbing contractor information & signature
needed.
Mechanical contractor information & signature
needed.
Electrical contractor information & signature
needed.
19 E Main St.
Rexburg, Idaho 83440
Phone {2b8} 359-3020
Fax (208) 359-3022
CT TY 0 F
EXBURG
Americas' Famay Community
October 8, 2007
Permit Number: 07 00434
Project Name:
Project Type;
Review Item
Review Action
The Bank of Commerce
Commercial New
Building Department Review
Accessibility Review
Exiting Review
Building Type Compliance
Height and Area Review
Mechanical Review
Interior Environment
Energy Conservation Compliance Review
Electrical Service Review
Electrical energy Lighting Compliance Review
Electrical Circuits Review
Building Code Fire Compliance Review
Structural Review
Waste Water Grease Trap Form
Waste Water Application
Plumbing Sewer Drain Review
Plumbing Storm Drain Review
Plumbing Potable Water Review
Water and Sewer Service
ao
19 F. Main St.
F�exbtarg, Idaho 8344
Phone (208) 359-3020
fax (208) 359-3422
Actions Required for, royal qrkproved
Meets code requirements. 0912712007
Meeks rode requirements. 09,I27/2007
Building is Type VB. 09/27/2007
Meets code requirements. 09/27/2007
Meets code requirements. 09I212D07
Meets code requirements. 09,r27/ �7
Meets cede requirements. 09,r2712007
Storage room must be 1 hour seperated.
Provide rated door and ceiling. identify draft
stopping in attic space.
Special inspections are required for foundation
and any structural fills. Provide name of firm
that will perform the inspections. Provide truss
details prioto frame inspection.
10/04/2007
10/04/2007
10/04/2007
I TY OF
ine 's Family `ommunn
October 8, 2007
roo
Review Action
Permit Number: 07 00434
Project Name: The Bank of Commerce
Project Type:
Review Item
Miscellaneous
Commercial New
Parcel #'s RPRENRF00100611
1
19 E Main 5t.
Rexburg, Idaho $344
Phone (208) 359-3020
Fax (2{]$) 359-3022
Actions RequiredrQvec[provalApp—
Flashing
and weepholes are required at bottom
of brick.
YYF
MXB.URG
October 8, 2007
Permit Number: 07 00434
Project Name:
Project Type:
Review Item
Review Action
The Bank of Commerce
Commercial New
Fire Department Review
Required Fire Flow
Water Supply
Fire Access Reads
Fire Extinguishers
Automatic Fire Extinguishing Systems
Standpipes
Commercial Gawking
Alarm Systems
Other Comments
Parcell #'s RPRHNUO010061
Acti
rov►a E
19 E Main St.
Rexburg, Idaho 8344
Phone (208) 359-3020
Fax (208) 359-3022
N V T*le; =-@
4
S;
Nielson -% j
0
Bodily & Assoc iates PA
Architects
07 `433 & 07 00434��,V�v,-�
The Bank of Commerce
Revisions 12/14/2007
TRANSMITTAL
9 -YO John anis Par * P. `, ox 2212 • ho Falls, I 83403- .1 * Tele
le 2081522-8779 -* Fax 2 0,31522-878.
Date: December 10, 2007 To: JaNiell Hansen
City of Rexburg
Subject,- Bank of Commerc 9E.M Iain
Rexburg Rexburg, Idaho 834
TRANSMITTED HEREWITH:
L__
i
r.
Rernarks.-
Nielson
Boddy &Assoclates P,4
Graicy G. Karst
Nielson � � Bodily & Associates PA
a
` i s
990 John A dams Pa ' & P. 0, .fox 2212 a Idaho F a [Is, 183403-2212 * Tele hone 2081522-8779 a Fax 2 081522y 8785
December 10, 2007
JaNell Hansen
City of Rexburg
12 N. Center St.
Rexburg, Idaho 83440
fie: Bank of commerce
Rexburg, Idaho
JaNiell,
I have reviewed your comments on the above referenced project. The following ars comments or
corrections intended for this project:
Item #1 : Permit Tech Notes:
The Contractor has not been chosen at this time. The successful Contractor will provide
you with this data.
Item # 2: Water and Sewer Services:
T'he Contractor will notify the City of Rexburcr when inspections are needed.
Item Water Lin'e-s:
All water lines will be inspected and tested prior to thein being covered.
IternA14: I Hour Separation.,
The Storage Room will have 1 -HR construction as indicted per your comments.
item # 5: special Inspection:
The Owner will Procure a licensed testing agency to provide all required testing,,
Rem 96.. weep Hales and Flashing:
We have revised the documents to Shaw weep holes and flashing at all masonry.
Item #7-, Fire Extinguishers.,
The Owner will install Fire Extinguishers in Mechanical Roomy 1.3 and Work
Room 107.
Scott L. Nielson, AJA Kevin R. Bodily} A,LA
Members of The Ani-2rican Instilute of rchiteits
item #8: Fire Detection System:
R
IP
Iia Fire Detection System �s required or indicated.
item #9,- No Parking in Setback:
We have revised to drawings to show no parking in the front yard setback. (See
attached revised Site Plan)
Item #10: Lighting Pian:
Site Licyhting is shown on the Electn'cal Drawings Sheet ELOO
Item #11: internal Pedestrian Walkway:
We have provided walkways surrounding the bui'lding to accommodate better
circulation from. the right-of-way. (See attached Site Plan)
Item #12.- Trash. Receptacles:
We will adjust the vacation of the trash receptacle 20 feet from any ricylit of way.
Item # 13: Parking in Front Yard S etback:
We have revised the drawings is show no parkingin the Front Yard Setback. (See
attached revised Site Plan)
item #144- LPlan:
The lighting is indicated an Sheet El. I
item #,15,-, Fire Water:
on the Electrical Drawing.
This building 'is not Fiore Sprinkled. The Contractor/City Will perform a test on the
adjacent fire hydrants pnor to construction.
Thank you for your cooperation in this matter. If you have any questions or concerns,
please contact our office.
Nielson Bodil
Craig Karst
CGIC/kl
Attachments:
associates, P.A.
2 sets Civil Site Drawings
2 sets Landscape Drawings
9
N�k
2007 8:32AM
I T Y 0 P
REXBURG
}meq �,yJ ��}+.��..g+��r�r/��,+j'..�r
r Y. f l"'f �7p�i+ dli�'Fi ��:1 y11
October 10, 2007
Permit Number: 07 00434
Project Name:
Project Type,,
evlew Itarn
Review Action
The Bank of Commerce
Commercial New
Permit Tech Nates
Parcel #'s RPRBNRFOO 10061
ion
D
No. h086 P.
General contractor information needed
I
ncluding Idaho registration 4.
Plumbing contractor information & signature
neEc#ed,
Mechanical contractor information & signature
needed.
Electrical contractor information & signature
needed.
19 E Win St.
Rexburg, Idaho 83440
None {208) 359-3020
Fax (2a8) 359-3022
1
15 �+ j� a
0 t
r
hp
Fk prof
f'wy
t
10, 2007 8:32AM
CITY 0 P
REXBURG
October 10, 2007
Permit Number: 07 00434
Project Name,.5
Prefect Type:
eview ire
No. 5086 P. 3_.___
Review Action
The Bank of Commerce
Commercial New
Arcessib1lity Review
Exiting Review
BuNding Type Compliance,
Height and Area Review
Machanical Ravlaw
Intarlar Environ mens
Energy Conservation Compliance Review
Electrical Service Review
Electrical Ciricuits Review
Ele-ctrical Energy Lighting Compliance Review
Water and Sewer 8arvice
Flumb'Ilng Potable Water Review
Plumbing Dewar Drain Risview
I
Meets coda requirements. -
Meets code requirements.
Building is Type VB.
Meets crude requirements,
Meets Bode requirements.
Meets code requirements,
Meets coda requirements.
All plumbing services are required to be
installed, tested and inspected before wue�nq.
All water lines are required to be installed
according to the 2p03 edition of th e Uniform
Plumbing Code. All water lines are to be tested
and inspected before cowering.
Approved as shown on pians,
Rumbing Storm Drain Review N/A
SutIcfing Code Fire compliance Review Storages room mint be 1. hour seperated.
Provide raked doer and ceiling_ Identify draft
stopping in attic space,
Structural Review Special inspections are required for foundation
and any structural fills, Provide name of ftrm
that will perform ihe inspections. Provide truss
details prioto frame insp-ectfon.
tNas#e Water Grease Trap Form
19 E iin St.
Rexburg, idaho 830
P;14na (203) 35$-3024
Fax (208) 359-3422
09/27/2007
09/27/2007
08/27/2007
09127/2007
09/27/2007
09/27/20D7
09/27/20-07
10/04/2007
10/04/2,007
10/ 04/20 0 7
10/09/20D7
10/09/2007
10!09!2007
10/09/2007
I
F„
}
10. 2007 8:32AM
L;IiY 0 F
RR)MURG
�rxttr
October 10, 2007
Permit Number,,,, 07 00434
Project Name:
Project Type:
ba
Review Action
The Bank of Commerce
Commercial New
Review Item I Ad[
Waste Wader Application
Miscallansou%Sr
Pareal #'s
ISM"UX11��J 111 11
1- 10 . I I
r
No, P, 4... .-.f y -w
Flashing and weephoies ars required at bottom
of brick.,
fth
19 AE Nbln St,
Rexburg, fda,�0 830
Phone (208) 359-3020
Fax (2f}$) 359-302
wMal
=,= L *"
=
r
4
I
or
C f
XQ 9-1 (-O.
1a. 2407 8.332AM
CITY OF
REXBUR-G
-- CW
Ameriea'sFnmify (:amrtTuh�ry
No, X086 P.
Review Action
October 10, 2007
Permit
Number.,
07
00434
Project
Name.'
The
Bank of Commerce
Project TypeA
Review Item
Cornmercial New
NMI'-��
�}
Y.
i� �..r�w+�,i�i�.+r`a�Ar�'L�.•'.aJ��ti..�u�riJeL+r441b�ir���rl ���.. •F�I��`�'e J�3Cw
P L
eqUlred Fire Flow
Water Supply
Fig Access Roads
Fire ExHi n u i
Automatic Firs Extinguishing Systems
Standpipes
Commarcia) Cooking
Alarm Systems
See site pian review.
See site plan review.
See site plan review.
Required to be installed in this oCCUpanCy,
Install according to NFPA and Interna.flonal Fire
Codi regulations,
Not required as shown on pens.
N/A
NIA
If fire alarm system is installed, plans are
required to be approved before install'Ing the
system.
1F-Wnst,
Rexburg, Idaho $440
Phone (2D8) 358-3020
fax (20$) 359-3022
10/09/2007
'410/09/2007
1 0/0 912 0 0 7
1010912007
10/09/2007
I M R161 h5voKoh
10/0912007
10/09/2007
Other Comments If fire alarm system is installed a lock box will be 10/09/2007
required for occupancy.
Parcel #'s RPRHNRFOO10061
I
I
10. 2007 8:32AM
C I T y F
REXBURG
4��r'FT�
CXMMUnI 7
October 10, 2007
Permit Number: 07 00433
Project Name;
Fraject Type:
Rgv,[Aw Item
Review Action
The Bank of Commerce-S)"te Plan
Site Flan review
Additional Comments
Parcel #'s
No, 8 P, tr.�
19 F. NuIn'Stp
Riaz burg, Idahio 83440
Phone (208) 350_3020
Fox (208) 353022
—do
10. 2007
CITY OF
REXBURG,
October 10, 2007
Not 5086 P, 801P
Review Action
Permit Number: 07 00433
Project Name: The Bank of Commerce -Site Pian
Project Type: Site Pian Review
Review Item
Approved Site Pian
Approved Site Plan
approved Site Plan
Approved Site. Plan
Approved Site Puri
Approved Site Plan
approved Site Plan
Approved Site Pian
Mb
Elevadons and site flan layout do not match up.
T. No parking is allowed in the required 20 foot
front yard setback. The setback mint be
appropriately landscaped,
2. No lighting plan isincluded
3 parking spaces per 1000 sq, ft. of dross float
area are required,
Intemal pedestrian walkways must connect to
the sidewalk a�vng the right-af-way,. Please
also show 1nte=nnec:fiv1tY with other building's
walkways within the development.,
No more than fiQ
percent
of
the
parking may
be
located between
the front
of
the
bundling
and
the
right-of-way,.
I F
2 pedestrian amenities {i.e, PaTloiseating area,
pedestrian plaza wl benches, outdoor play
ares; Mask area, water feature, flag pale, etc:,)
are required on the sits.
Trash receptacles must beat least 20 feet from
the right of way, and be placed the Maximum
feasible distance from' an internal pedestrfi�n
walkway. Receptacles must also be fully
screened from the. right-of-way,
All lighting must conform to the commercial
lighting,5tandards. Please. submit a detailed
lighting plan, includ[ng Photometric Isyaui data,
for review.
19 F. Main $1,
Rexburg, Idaho 8:3440
Ffiane (24$) 3$9-34201
FAX (2{3S) 359-3022
09/2812007
x
IF
10, 0018 F *32AM
IT y 0 V
1
�U
October 10, 2007
Permit Number: 07 00433
Project Name:
Project Type;
R6viaw lb�rn
Review Action
The Bank of Commerce -Site Plan
Site Plan Review
�.W4-
Approvad
f7mrti �Fd o i'a.J7 'J �P1�L Sir
fir{'"y_Y�''i4- �ai7, Bite Plea
Parcel Ws
A,PfISA41
or
W.
No. 5086 P. 9.-.—_.
1.'No parking is allowed within the setback on
commercial.
2. No iighffng plan was submitted.
19 E Min stl
Rsxburg, Idaho 83440
Fhona (248) 359-3020
FaX (208) 359-30 2
IM-60 GJ R!
I
x15t0c t, 10. 2007 8 : 32AM
REXBURG
■
Revzie%w Action
October 1 0, 2007
Permit Number. 07 X0433
Pro�ec� Name, The Bank of Commerce -Site Pian
project Type: Site Plan Review
Raview Item
Fire Apparates Access
A=esa to Hydrants
Fire Line Signage
Vicinity Map Provided
Existing .hydrants
Prcpased Hydrants
Hydrant Flows Provided
V
www ■��Gk`� � ++
PROVIDED
F re Sprinkler System Required
Required Fire Flow
Parcel Ws
R-PRBNRF0010061
PROVIDED
NOT REQUIRED
TWO FIRE HYDRANTS SHOWN
NO, 5086 P. 1 0. ---
19 E Main St.
Rexburg, Idaho B33440
Phone {2Q&} 3s91-3o2D
Fax (20&) 355-3022
NONE SHOWN, UNKNOWN OF ADDITIONAL
HYDRANTS REQUIRED
PLEASE PROVIDE HYDRANT FLOWS
UNKNOWN BUILDING SIZE OR HEIGHT,
PLEASE PROVIDE MORE DETAILS.
UNKNOWN FIRE FLOWTARrLPLEASE PROVIDE
BUILDING CONTRUCTION, SQUARE
FOOTAGE, HEIGHT, ETC. FOR MORE
ACCURATE DETERMINATION.
09/12!2007
09/12/2007
09/12/2007
09!12!2007
09!12/2007