HomeMy WebLinkAboutREVIEW ACTION - 07-00165 - Mr G's Dairy Delights - New BuildingI TY OF
REXBURGOwAmericas, Ftftly Community
May 18, 2007
Permit Number:
Project Name.
Project Type:
0
Dairy Delights
Commercial New
Review Action
Review Item Actions Required for A
Miscellaneous
Electrical Circuits Review
Electrical Service Review
Accessibility Review
Waste Water Grease Trap Form
Waste Water Application
Mechanical Review
Building Code Fire Compliance Review
Exiting Review
Parcel #'s RPRPNRV4020020
rov
Provide crawRspace ventillation.
The plans that were submitted were extremely
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
A09 A, 0
��....... ....... v oGc a F.,aH t:;r ,[.:rleC]lJle, $e.'rviC►e.`
plan/size, and switching in main area and GF1
requirements. Meed revisions for these items.
Need to make sure that everything meets the
20D5 NEC.
ReStrooms do not meet the requirements of
ICC/ANSI 117.1 603.2 and 604.3.
Provide mechanical sizing and details.
Walls and door to the storage roam must be 1
hour rated as per IBC Table 3Q2.7.1. Do -or
must be self closing.
Without having a dining roam layout and using
IBC Table 1004.1.2 If assembly Unconcentrated
stables and chairs}" , the dining room
occupancy is calculated at 76. Two exits are
required. Doors must open with the flaw of the
exits. Exit signs are required. Egress can not
pass through a storage space.
eow
ITY 0 F
---------America'sRtmily Community
_
May 18, 2007
Permit Number:
Project Name:
Project Type:
0700150
NO
Review Action
Dairy Delights -Site Pian
Site Plan Review
Review Item Ac_flons Required for
Public Works Review
Qnnrnwarl (Zi#n DI.�.,
&Lq
royal
a•' 1. How is the parking area lighted? Lighting
plan needed.
2. Trash enclosure size dyes not allow for
truck pickup.
3. Sidewalk needs to run the entire length of
the property. Are there handicap ramps at the
entrance?
4. Truncated domes need to be in the
handicap ramp at south end.
5. What is to be done with storm water?
+6. Plan does not Shaw water and sewer hook
UPS.
Please revise site plan & re -submit.
Parcel #'s RPRPNRV002002.0
19 E. Main St.
Rexburg, Idaho 83440
Phone {20g} 359-3020
Fax (2D8) 359-342
05/17/2007'
s
Revised site plan received 5/11/07
Lighting plan needed 0 need to see fixtures
to be used). � �►tD
2. Sanitation enclosure as show n c
an nat be
accessed by truck.
3. Truncated domes need to be showy an site
plan.
r4. Service lines need to. be shown.
Date/T'ime:
May,io. 2,VV7 !J:53AV
TX Result Report 1 May. 18, 200r
0 : 54 AM ) *
FI q
III
� Y
I i
V o e
at P a g e
— — —j 0 n
— ---_ _ S n
�-
- IA1 _ ' — —7 9_ — � — — � — ^ � — ! — 1 ` —S —N i— —., f — ...�. Y.. �� � f �� i I! ` � f� 1 f.r i . . . . . . _! f
�AU r y TA
P. 3 OK
eascri for e r r o r — __-- — — — —_—_—_---_�--_---- —
E. No answe r Busy
E. ) Exceeded max. E—rna I i E, CS i a co"`r act ion
Fax
3-5&817 9
t
`=V.qjt)
Fri [JaINWHIOInsen
May 1, 2DD7
D urgent C] Fay jRoaom,mem L] P
kaff
iq ply ate
+C.aenmenFs:
The 5tumad iteM5L (3Re ihe r1aw 00 MMant that nL-ed b be 0d C Thlase item ore
pI(" �.� I i1 Wim) Gnd BretStoddard j8ecf6cdl I c for). �s � m �+� �
P , I �c�n't kt�r if cad h� rt,i� � Mair art ���� �5/11. 1� e
II k in am Mc n d sand � I s Mitis him. I C0
rl�.l t�i7s]�: if you rred or, ad,or�oi I al � �f P��'s ���
a
thu fdb r c�--rtmen 0 pubricBjlcflingi� tri P. a
Of r ;;s when �� hove �e. n madp
jes
Thank You,
Jo ell H rrts;-,
I
r
k
i
ri
f
i
a
f
SAX Br
CITY OF
]REXBURG,
May 11, 2007
Permit Number:
Project Name:
Project Type:
Review Item
0700165
Dairy Delights
Commercial New
Planning Staff Review
Development Standards Review
Development Standards Review
Review Action
Actions Re�c wired for A�aprqrra!
Left elevation must include a repeating
horizontal pattern sof color chane, texture
charge, material module change, etc. every 30
feet as required in section 4.a.iii - !Detail
features} of the development rode.
Site must provide at least 2 of the pedestrian
amenities required in section 4-a.xi (Central
Features and community Spaces) of the
development code. (patio/seating area,
pedestrian plaza, outdoor play area, Etc.)
'4 ir Acv
site plan.
Parcel #'s RPRPNRV0020,020
vered
patio
sealing
area is
shown on the
Must
provide
at
feast
2 features.
P.0 Box 280
19 E. Main St.
Rexburg, Idaho 83440
Phone (20g) 359,302()
Fax (208) 359-3022
05/11/2007
Y TY o r -
P -0 Box 280
dr 19 E. main St.
_,... . , _ Rexburg, Idaho 83440
Ametica'-r Farnil)? Canrnufjij�v Phone (208) 359-3020
Review
3022
May 11, 2007
Permit Number:
Project Mame:
Project Type;
Review Item
Parcel #`s
Dairy Dell-ghts-Site Plan
Site Plan Review
93
RPRPNRV0020020
Actions ReA
qL- -pproval
street with landscaping. Please submit
landscaping plan for review.
A detailed 1.k#s4q p
Ian is still required.
Ie�fV�.Scc, pi e�
Arav
ed
CITY F
REXBURG
May 11, 2007
Permit Number:
Project Name:
Project Type:
Review Item
FRO
Review Action
0700150
Dairy Delights -Site Plan
Site Pian Review
Planning.Staff
Re view
...
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
Approved Site Plan
nV
ma
Actions Reiredufor Approval
All signage will require a separate permit, and
is not a part of this review.
Parking is not allowed in the required front yard
setback. 6 parking Malls are shown
encroaching into the setback area along
Pioneer Rd. & Handcart Ln.
Site must comply to ADA handicap
requirements.
Garbage container is not allowed to be within
20 feet of a public; street or sidewalk. Also, all
garbage containers must be screened.
Interna! ,pedestrian walkway needs to connect
to the sidewalk along the right of way. See
design standards dor specifications.
Revision sows required walkway connection.
NOTE: All internal pedestrian walkways shall
be distinguished from driving surfaces throught
the use of durable, low maintenance surface
materials such as payers, bricks, or scored
concrete. (See section 4-a.x (5) of the
Commercial Design Standards.)
Required number of parking stalls is
determined by occupancy. Please provide
seating information.
Revision showed 16 seats and 32 feet of
bench, requiring a total of 8 parking stalls, 14
stalls are shown.
One-way Vehicle isles are required to be at
least 13 feet wide. Also, these isles must be
designated as " ani way," it that is the indent.
All lighting must conform to commercial lighting
standards. Please submit a lighting plan,
OYincluding light distribution information, dor
revieuv.
Parking must be screened firom view of the
P-0 Box 280
1,9 E, Main St,
Rexburg, idaho 83440
Phone (20$) 359-3020
Fax (208) 353-3022
04/19/2007
05/11/2007
05/11/2007
05/11/2007
05/11/2007
05/11/2007
05111/2007
I T fir' 0 r'
RE- -X,BU.RG
trf c Family Community
April 26, 2007
Permit Number: 07 00165
Project Name:
Project Type:
Review item
Dairy Delights
Commercial New
Building Department Review
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Potable Water Review
Height and Area Review
Structural Review
Building Type Compliance
Complies with approved Site Plan Review
Plumbing Storm Drain Review
Energy Conservation Compliance Review
Waste Water, Grease Trap Form
Review Action
Actions Requir
19 E Win St.
Rexburg, Idaho 83440
Phone (2+D8) 359-3020
Fax (208) 359-3022
Water and sewer services are required to be
tested and inspected before covering.
Water service is required to be 2" to meet the
requirements for kitchen equipment and
restraam5.
All drains are required to be tested and
F
nspected before covering. All drains will be
installed according to the Uniform Plumbing
Code 2003 edition.
A grease trap or interceptor will be required for
this occupancy. Type of trap or interceptor will
depend on the number of fixtures.
Na pians provided for plumbing.,,
All water lines are shall be installed according to
the Uniform Plumbing Cade 2003 edition. All
water lines are required to have the proper
backflow prevention installed prior to final
plumbing inspection.
Meet code requirtements.
Special inspections are required on the
foundation. Provide a letter from the firm who
will be doing these inspections.
Building is Type VB.
Site plan has been reviewed.
N/A
Need the lighting switched in accordance with
the 2x03 IECC code. No indication was noted
on the plans to obtain this. Need revisions. The
energy compliance review for the envelope
used Idaho Falls instead of Rexburg as the
location,
04/24/2007
04/24/2007
04/24/2007
04/24/2007
04/24/2007
04/24/2007
04/24!2007
04/24/2007
I< T7, C54,:dn A. i >
J TY F
'OREXBURG
lirr
April 26, 2007
501
Permit Number: 07 00165
Project Name:
Proi ect Type:
Review Item
dairy delights
Commercial New
Waste Water Application
Mechanical Review
Building Code Fire compliance Review
Exiling Review
Accessibility Review
Electrical Service Review
Miscellaneous
Electrical Circuits Review
Parcel #'s RPRPNRV0020020
Review Action
Re�cuir�ador A&C-IiOnspprvyal
Provide mechanical sizing and details.
Walls and door to the storage room must be 1
hour rated as per IBC Table 3Q2.7 .7. Door
must be self closing.
Wiout having a dining room layout and using
IBS Table 100-4.1.2 "assembly Unconcentrated
stables and chairs}", the dining room occupancy
is calculated at 76. two exitq arp rpni i«-orA
Doors must ape
n with the flow of the exits. Exit
signs are required. Egress can not pass
through a storage space.
Restrooms do not meet the requirements of
ICC/ANSI 117.1 603.2 and 664.3.
Provide craw(space ventfllatian.
The plans that were submitted were extremely
vague, need to seg a paned schedule, service
plan/size, and switching in main area and GFI
requirements. Need revisions for these items.
19 E Main St.
Rexburg, fdaho 83440
Phone (208) 359-302
Fax {208) 359-3022
qj 0
#sake '
I TY OF
REXBURG
America's Family omm,411
April 26, 2007
bo
Permit Number: 07 00165
Project Name:
Project Type:
Dairy Delights
Commercial New
Review Item
Fire Department Review
Required Fire Flow
Other Comments
Alarm Systems
Commercial Cooking
Water Supply
Fire Access Roads
Fire Extinguishers
Standpipes
Automatic Fire Extinguishing Systems
Parcel #'s RPRPNRV0020020
Review Action
19 E Main St.
Rexburg, kiaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Actin R it d far Approval Apt3roved
See site plan review 04/26/2007
Lock box is not required for this occupancy. 04/26/2007
Forms for lock foxes are available at the
Rexburg Fire Department.
Not required for this occupancy. D412512007
if there is any cammercial coaking in 04f6/2p07
occupancy a commercial cooking hood will be
required. Hood Type would be determined by the
type of cooking preformed. No cooking area
shown on plans.
See site plan review 04/26/2007
See site plan review 04/26/2007
Fire extinguishers are required for this 04/ 6/2 0�
occupancy. Minimum of 2A10BC extinguishers
are required. No extinguishes shown on plans.
Please cal! prior to final fare inspection for
extinguisher locations.
N/A 04/26/2007
Not required for this occupancy. 04/26/2007
aSIO
ITY OF
7R BURG
�._.. . ....
America's
April 26, 2007
Permit Number: 07 00765
Project Name:
Project Type:
Daisy Delights
Commercial New
Review Item
Planning Staff Review
Development Standards Review
Development Standards Review
Parcel #'s
RPRPNRV0020020
Review Action
.Main St.
Rexburg, Idaho 8340
Phare {208} 359-3020
Fax (2Q8) 359-3022
Actions Rewired for ,o,�roval —Approved
Left elevation.must include a repeating
horizontal pattern of color change, texture,
change, material module change, etc. every 30
feet as required in section 4.a.ili - (Detail
features) of the development code.
Site must provide at least 2 of the pedestrian
amenities required in section 4-a.xi (Central
Features and community Spaces) of the
development code. (Patio/seating area,
pedestrian plaza, outdoor play area, etc.)