HomeMy WebLinkAboutCOMPLIANCE CERTIFICATE & LETTER - 07-00028 - 265 Polo Dr - New SREScheck Software Version 4.0.1
Compliance Certificate
Project Title: Henderson Addition
Report Date: 02/08/07
Data filename: C:\DOCUME-1\Me\MYDOCU-1\MASONS-1\HENDER-1.RCK
Energy Code:
2003 IECC
Location:
Rexburg, Idaho
Construction Type:
Single Family
Glazing Area Percentage:
20%
Heating Degree Days:
8693
Construction Site:
Block 7 Lot 13
Rexburg, ID 83440
Crooner/Agent:
Mason Haycock
Designer/Contractor:
Chuck Doman
Compliance: Passes Maximum UA: 366 Your Home UA: 366 --> 0.0% Better Than Code (UA)
Calling 1: Flat Ceiling or Scissor Truss:
Wall 1: Wood Frame, 16" o.c.:
Door 1: Solid:
Door 2: Solid:
Door 3: Glass:
Window 1: Vinyl Frame, Double Pane with low-E:
RG Lyfnl' Basement Wall 1: Wood Frame:
Wall height: 8.0'
Depth below grade: 7.0'
Insulation depth: 8.0'
Floor 3: All -Wood Joist/rruss:Over Unconditioned Space:
Furnace 1: Forced Hot Air: 85 AFUE
1900 1700
38.0
1740
21.0
20
20
40
303
1700
21.0
28 21.0
0.0
51
6.0
62
0.350
7
0.540
11
0,500
20
0.450
136
0.0
78
8.0 1
Compliance Statement The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2003 IECC requirements in
REScheck Version 4.0.1 and to comply with the mandatory requirements listed In the REScheck Inspection Checklist.
Name -Title
Signature
uace
Henderson Addition Page 1 of 1
`wr
Permit #
Permit Date
REScheck Software Version 3.7.3
Compliance Certificate
Report Date: 02/08/07
Data filename: C:\Program Files\Check\REScheck\Basic.rck
Energy Code:
2003 IECC
Location:
Rexburg, Idaho
Construction Type:
Single Family
Glazing Area Percentage:
19%
Heating Degree Days:
8693
Construction Site:
Owner/Agent:
Designer/Contractor:
Ceiling 1: Flat Ceiling or Scissor Truss:
1800
38.0
0.0
54
Wall 1: Wood Frame, 16" o.c.:
1780
21.0
0.0
84
Window 1: Vinyl Frame:Double Pane with Low-E:
227
0.450
102
Door 1: Solid:
40
0.350
14
Door 2: Glass:
40
0.500
20
Basement Wall 1: Solid Concrete or Masonry:
1424
21.0
0.0
57
Window 2: Vinyl Frame:Double Pane:
96
0.500
48
Floor 1: All -Wood Joist/Truss:Over Outside Air:
28
21.0
0.0
1
Furnace 1: Forced Hot Air: 90 AFUE
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2003 IECC requirements in
REScheck Version 3.7.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Builder/Designer Company Name Date
Page 1 of 4
12REScheck Software Version 3.7.3
.f Inspection Checklist
Date: 02/08/07
Ceilings:
❑ Ceiling 1: Flat Ceiling or Scissor Truss, R-38.0 cavity insulation
Comments:
Above -Grade Walls:
❑ Wall 1: Wood Frame, 16" o.c., R-21.0 cavity insulation
Comments:
Basement Walls:
❑ Basement Wall 1: Solid Concrete or Masonry, 8.0' ht17.0' bg/8.0' insul, R-21.0 cavity insulation
Comments:
Windows:
❑ Window 1: Vinyl Frame:Double Pane with Low-E, U-factor._ 0.450
For windows without labeled U-factors, describe features:
#Panes Frame Type Thermal Break? Yes No
Comments:
❑ Window 2: Vinyl Frame:Double Pane, U-factor: 0.500
For windows without labeled U-factors, describe features:
#Panes Frame Type Thermal Break? Yes No
Comments:
Doors:
❑ Door 1: Solid, U-factor. 0.350
Comments:
❑ Door 2: Glass, U-factor: 0.500
Comments:
Floors:
❑ Floor 1: All -Wood Joist/Truss:Over Outside Air, R-21.0 cavity insulation
Comments:
Heating and Cooling Equipment:
❑ Furnace 1: Forced Hot Air: 90 AFUE or higher
Make and Model Number:
Air Leakage:
❑ Joints, penetrations, and all other such openings in the building envelope that are sources of air leakage must be sealed.
❑ Recessed lights must be 1) Type IC rated, or 2) installed inside an appropriate air -tight assembly with a 0.5" clearance from
combustible materials. If non -IC rated, the fixture must be installed with a 3" clearance from insulation.
Skylights:
❑ Minimum insulation requirement for skylight shafts equal to or greater than 12 inches is R-19.
Vapor Retarder.
❑ Required on the warm -in -winter side of all non -vented framed ceilings, walls, and floors.
Page 2 of 4
L=5
r""FA
Materials Identification:
❑ Materials and equipment must be installed in accordance with the manufacturer's installation instructions.
❑ Materials and equipment must be identified so that compliance can be determined.
❑ Manufacturer manuals for all installed heating and cooling equipment and service water heating equipment must be provided.
❑ Insulation R-values, glazing U-factors, and heating equipment efficiency must be clearly marked on the building plans or
specifications.
Duct Insulation:
❑ Supply ducts in unconditioned attics or outside the building must be insulated to R-11.
❑ Return ducts in unconditioned attics or outside the building must be insulated to R-6.
❑ Supply ducts in unconditioned spaces must be insulated to R-11.
❑ Return ducts in unconditioned spaces (except basements) must be insulated to R-2.
❑ Where exterior walls are used as plenums, the wall must be insulated to R-11.
❑ Insulation is not required on return ducts in basements.
Duct Construction:
❑ Duct connections to flanges of air distribution system equipment must be sealed and mechanically fastened.
❑ All joints, seams, and connections must be securely fastened with welds, gaskets, mastics (adhesives),
mastic -plus -embedded -fabric, or tapes. Tapes and mastics must be rated UL 181A or UL 181 B.
Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at less than 2 in. w.g. (500
Pa).
❑ The HVAC system must provide a means for balancing air and water systems.
Temperature Controls:
❑ Thermostats are required for each separate HVAC system. A manual or automatic means to partially restrict or shut off the
heating and/or cooling input to each zone or floor shall be provided.
Service Water Heating:
❑ Water heaters with vertical pipe risers must have a heat trap on both the inlet and outlet unless the water heater has an integral
heat trap or is part of a circulating system.
❑ Insulate circulating hot water pipes to the levels in Table 1.
Circulating Hot Water Systems:
❑ Insulate circulating hot water pipes to the levels in Table 1.
Swimming Pools:
❑ All heated swimming pools must have an on/off heater switch and require a cover unless over 20% of the heating energy is from
non-depletable sources. Pool pumps require a time clock.
Heating and Cooling Piping Insulation:
❑ HVAC piping conveying fluids above 105 degrees F or chilled fluids below 55 degrees F must be insulated to the levels in Table
2.
Page 3 of 4
Table 1: Minimum Insulation Thickness for Circulating Hot Water Pipes
Insulation Thickness in Inches by Pipe Sizes
Non -Circulating Runouts
Circulating Mains and Runouts
Heated Water
Temperature (°F)
Up to 1"
Up to 1.25"
1.5" to 2.0" Over 2"
170-180
0.5
1.0
1.5 2.0
140-169
0.5
0.5
1.0 1.5
100-139
0.5
0.5
0.5 1.0
Table 2: Minimum Insulation Thickness for HVAC Pipes
Insulation Thickness in Inches by Pipe Sizes
Fluid Temp.
Piping System Types
Range(OF)
2" Runouts 1" and Less
1.25" to 2.0"
2.5" to 4"
Heating Systems
Low PressurelTemperature
201-250
1.0
1.5
1.5
2.0
Low Temperature
106-200
0.5
1.0
1.0
1.5
Steam Condensate (for feed water)
Any
1.0
1.0
1.5
2.0
Cooling Systems
Chilled Water, Refrigerant and
40-55
0.5
0.5
0.75
1.0
Brine
Below 40
1.0
1.0
1.5
1.5
NOTES TO FIELD: (Building Department Use Only)
It
Page 4 of 4
\No/ `'r.✓
i
January 31, 2007
City of Rexburg,
Heating calculation for Nomarco Construction, New home in Henderson Subdivision,
Rexburg, Idaho.
As per the REScheck provided by the contractor the heat loss for the home is figured as
follows.
UA value: 393
Design indoor temp. = 70 F
Design outdoor condition = -20 F
Delta T: 90 F
Heat loss = 35,370 BTU
Infiltration value:.95% = 37,335 BTU
Minimum BTU required = 72,705 BTU
It is proposed to install a 100,000 BTU furnace with a 4 ton blower.
Johnson Heating LLC
HVAC License # 1327
State of Idaho