HomeMy WebLinkAboutCOMCHECK 2 - 08-00440 - Boice BuildiCOMcheck Software Version 3.5.3
Exterior Lighting Compliance
Certificate — - - -- - -
2006 IECC
Report Date: 10/02/08
Data filename: C:\Program Files\Check\C0Mcheck\boice2.cck
Section 1: Project Information
Project Type: New Construction
Project Title: Boice Office
Construction Site: Owner/Agent:
08 004-39
131dg
Designer/Contractor.
Section 2: Exterior Lighting Area/Surface Power Calculation
A B
C D
E
F
Exterior Area/Surface Quantity
Allowed Tradable
Allowed
Proposed
Watts Wattage
Watts
Watts
/Unit
(Cx D)
Parking area(s) 3000 ft2
0.15 Yes
450
750
Driveway 1000 ft2
0.15 Yes
150
975
Main entry/exit 600 it of door width
30 Yes
18000
400
Total Tradable Watts' =
18600
2125
Total Allowed Watts =
18600
Total Allowed Supplemental Watts" =
930
Wattage tradeoffs are only allowed between tradable areas/surfaces.
'• A supplemental allowance equal to 5% of total allowed wattage may be applied toward compliance of both non -tradable and tradable
areastsurfaces.
Section 3: Exterior Lighting Fixture Schedule
A B C D E
Fixture ID : Description / Lamp I Wattage Per Lamp I Ballast Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt
Parking area(s) (3000 ft2): Tradable Wattage
HID 1: Metal Halide 15OW / Electronic 1 5 150 750
Driveway (1000 ft2): Tradable Wattage
Incandescent l: Incandescent 65W 1 15 65 975
Main entrylexit (600 ft of door width): Tradable Wattage
HID 2: Metal Halide 100W / Electronic 1 4 100 400
Total Tradable Proposed Watts = 2125
Section 4: Requirements Checklist
Lighting Wattage:
1. Within each non -tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable
areas/surfaces, total proposed watts must be less than or equal to total allowed wafts.
Compliance: Passes.
Controls, Switching, and Wiring:
2. All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
3. All nonexempt lighting fixtures shall be controlled by a photosensor or astronomical time switch that is capable of automatically turning
off the fixture when sufficient daylight is available or the lighting is not required.
Project Title: Boice Office Report date: 10/02/08
Data filename: C:\Program Flles\Check\C0Mcheck%oice2.cck Page 4 of 5
Exterior Lighting Ellice
4. All exterior building grounds mminaires that operate at greater than 100W have minimu�fflcecy of 60 lumen/watt.
Exceptions:
Exterior Lighting PASSES. Design 8996 better than code.
Section 5: Compliance Statement
Compliance Statement., The proposed exterior lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC
requirements in COMcheck Version 3.5.3 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title
Project Tite: Boice Office
Data filename: C:\Progmm Files\Check\COMcheck\boice2.cck
Signature Date
Report date: 10/02108
Page 5 of 5
COMcheck Software Version 3.5.3
Interior Lighting Compliance
Certificate
2006 IECC
Report Date: 10/02/08
Data filename: C:\Program Files\Check\COMcheck\boice2.cck
Section 1: Project Information
Project Type: New Construction
Project Title: Boice Office
Construction Site: Owner/Agent: Designer/Contractor.
Section 2: General Information
Building Use Description by: ActivityType
Activity Tvoefs) Floor Area
Office 3500
Section 3: Requirements Checklist
Interior Lighting:
O 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies
3500 3456 YES
Controls, Switching, and Wiring:
❑ 2. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
3. Master switch at entry to hotel/motel guest room.
o 4. Individual dwelling units separately metered.
O 5. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions.,
Only one luminaire in space;
An occupant -sensing device controls the area;
The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
Areas that use less than 0.6 Watts/sq.ft
F1 6. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
Li 7. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
8. Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions:
Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair.
Project Title: Boice Office
Data filename: C:1Program Files\Check\COMcheck\boice2.cck
Report date: 10/02/08
Page 1 of 5
Section 4: Complianl..�tatement �®.✓
Compliance Statement. The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC
requirements in COMcheck Version 3.5.3 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title Signature Date
Project Title: Bolce Office Report date: 10/02/08
Data filename: C:1Program FileslChecklCOMcheck%oice2.cck Page 2 of 5
COMcheck Software Version 3.5.3
Interior Lighting Application
Worksheet
2006 IECC
Report Date:
Data filename: C:\Program Files\Check\COMcheck\boice2.cck
Section 1: Allowed Lighting Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts 1112 IS x C)
Office 3500 1 3500
Total Allowed Watts = 3500
Section 2: Proposed Lighting Power Calculation
A B C D E
Fixture ID : Description I Lamp I Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt
Office (3500 sq.ft.)
Linear Fluorescent 1: 48' T8 32W / Electronic 4 27 128 3456
Total Proposed Watts = 3456
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Proposed Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 3500
Total Proposed Watts = 3456
Project Compliance = 44
Interior Lighting PASSES: Design 1% better than code.
Tide: Boice Office
Data filename: C:\Program Files\Check\COMchecMbolce2.cck
Report date: 10/02/08
Page 3 of 5