Loading...
HomeMy WebLinkAboutCOMCHECK 2 - 08-00440 - Boice BuildiCOMcheck Software Version 3.5.3 Exterior Lighting Compliance Certificate — - - -- - - 2006 IECC Report Date: 10/02/08 Data filename: C:\Program Files\Check\C0Mcheck\boice2.cck Section 1: Project Information Project Type: New Construction Project Title: Boice Office Construction Site: Owner/Agent: 08 004-39 131dg Designer/Contractor. Section 2: Exterior Lighting Area/Surface Power Calculation A B C D E F Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed Watts Wattage Watts Watts /Unit (Cx D) Parking area(s) 3000 ft2 0.15 Yes 450 750 Driveway 1000 ft2 0.15 Yes 150 975 Main entry/exit 600 it of door width 30 Yes 18000 400 Total Tradable Watts' = 18600 2125 Total Allowed Watts = 18600 Total Allowed Supplemental Watts" = 930 Wattage tradeoffs are only allowed between tradable areas/surfaces. '• A supplemental allowance equal to 5% of total allowed wattage may be applied toward compliance of both non -tradable and tradable areastsurfaces. Section 3: Exterior Lighting Fixture Schedule A B C D E Fixture ID : Description / Lamp I Wattage Per Lamp I Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt Parking area(s) (3000 ft2): Tradable Wattage HID 1: Metal Halide 15OW / Electronic 1 5 150 750 Driveway (1000 ft2): Tradable Wattage Incandescent l: Incandescent 65W 1 15 65 975 Main entrylexit (600 ft of door width): Tradable Wattage HID 2: Metal Halide 100W / Electronic 1 4 100 400 Total Tradable Proposed Watts = 2125 Section 4: Requirements Checklist Lighting Wattage: 1. Within each non -tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable areas/surfaces, total proposed watts must be less than or equal to total allowed wafts. Compliance: Passes. Controls, Switching, and Wiring: 2. All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting. 3. All nonexempt lighting fixtures shall be controlled by a photosensor or astronomical time switch that is capable of automatically turning off the fixture when sufficient daylight is available or the lighting is not required. Project Title: Boice Office Report date: 10/02/08 Data filename: C:\Program Flles\Check\C0Mcheck%oice2.cck Page 4 of 5 Exterior Lighting Ellice 4. All exterior building grounds mminaires that operate at greater than 100W have minimu�fflcecy of 60 lumen/watt. Exceptions: Exterior Lighting PASSES. Design 8996 better than code. Section 5: Compliance Statement Compliance Statement., The proposed exterior lighting design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC requirements in COMcheck Version 3.5.3 and to comply with the mandatory requirements in the Requirements Checklist. Name - Title Project Tite: Boice Office Data filename: C:\Progmm Files\Check\COMcheck\boice2.cck Signature Date Report date: 10/02108 Page 5 of 5 COMcheck Software Version 3.5.3 Interior Lighting Compliance Certificate 2006 IECC Report Date: 10/02/08 Data filename: C:\Program Files\Check\COMcheck\boice2.cck Section 1: Project Information Project Type: New Construction Project Title: Boice Office Construction Site: Owner/Agent: Designer/Contractor. Section 2: General Information Building Use Description by: ActivityType Activity Tvoefs) Floor Area Office 3500 Section 3: Requirements Checklist Interior Lighting: O 1. Total proposed watts must be less than or equal to total allowed watts. Allowed Watts Proposed Watts Complies 3500 3456 YES Controls, Switching, and Wiring: ❑ 2. Independent controls for each space (switch/occupancy sensor). Exceptions: Areas designated as security or emergency areas that must be continuously illuminated. Lighting in stairways or corridors that are elements of the means of egress. 3. Master switch at entry to hotel/motel guest room. o 4. Individual dwelling units separately metered. O 5. Each space provided with a manual control to provide uniform light reduction by at least 50%. Exceptions., Only one luminaire in space; An occupant -sensing device controls the area; The area is a corridor, storeroom, restroom, public lobby or sleeping unit. Areas that use less than 0.6 Watts/sq.ft F1 6. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft. Exceptions: Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security. Li 7. Photocell/astronomical time switch on exterior lights. Exceptions: Lighting intended for 24 hour use. 8. Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts). Exceptions: Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair. Project Title: Boice Office Data filename: C:1Program Files\Check\COMcheck\boice2.cck Report date: 10/02/08 Page 1 of 5 Section 4: Complianl..�tatement �®.✓ Compliance Statement. The proposed lighting design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC requirements in COMcheck Version 3.5.3 and to comply with the mandatory requirements in the Requirements Checklist. Name - Title Signature Date Project Title: Bolce Office Report date: 10/02/08 Data filename: C:1Program FileslChecklCOMcheck%oice2.cck Page 2 of 5 COMcheck Software Version 3.5.3 Interior Lighting Application Worksheet 2006 IECC Report Date: Data filename: C:\Program Files\Check\COMcheck\boice2.cck Section 1: Allowed Lighting Power Calculation A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts 1112 IS x C) Office 3500 1 3500 Total Allowed Watts = 3500 Section 2: Proposed Lighting Power Calculation A B C D E Fixture ID : Description I Lamp I Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt Office (3500 sq.ft.) Linear Fluorescent 1: 48' T8 32W / Electronic 4 27 128 3456 Total Proposed Watts = 3456 Section 3: Compliance Calculation If the Total Allowed Watts minus the Total Proposed Watts is greater than or equal to zero, the building complies. Total Allowed Watts = 3500 Total Proposed Watts = 3456 Project Compliance = 44 Interior Lighting PASSES: Design 1% better than code. Tide: Boice Office Data filename: C:\Program Files\Check\COMchecMbolce2.cck Report date: 10/02/08 Page 3 of 5