FIRE ALARM MATERIAL SUBMITTALS - 21-00141 - Teton River Flats Apartments - Fire Alarm
Page 1 of 1 Idaho Owned and Operated FAX # 1-208-232-0449 FIRE ALARM MATERIAL SUBMITTALS for the TETON RIVER FLATS PHASE I DN-60955:C • 7/16/2018 — Page 1 of 4 NFW-50X Intelligent Addressable FACP with Communicator General The FireWarden-50X (NFW-50X) is the latest intelligent address- able fire alarm control panel (FACP) within the FireWarden Series and is a direct replacement for the FireWarden-50 (NFW-50). The NFW-50X comes with a pre-installed communicator and supports up to 50 addressable devices in any combination of detectors or mod- ules. With an extensive list of powerful features, the NFW-50X pro- grams just like FireWarden-100 products, yet fits into applications previously served only by conventional panels. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedi- cated business telephone lines. Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-N. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel’s USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system volt- ages by means of a USB flash drive. The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polar- ity/city box transmitter (4XTM). Features • Listed to UL Standard 864, 10th edition • Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- phone Service) Central Station Communicator •Optional CELL-MOD or CELL-CAB-N GSM Central Station Com- municator over AlarmNet® • Compatible with SWIFT® wireless devices • Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address • Two independently programmable, built-in Style Z (Class A) or Style Y (Class B) NAC circuits • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices • Notification Appliance Circuit End of Line resistor matching • Four programmable function keys for ease of maintenance • Two programmable relays and one fixed trouble relay • Built-in Programmer • Integral 80-character LCD display with backlighting • Real-time clock/calendar with automatic daylight savings control • History file with 1,000 event capacity • Addressable sounder base • Control module delay timer • Automatic detector sensitivity testing (NFPA 72 compliant) • Automatic device type-code verification • Point trouble identification • Waterflow selection per module point • Alarm verification selection per detector point • Maintenance alert warns when smoke detector dust accumula- tion is excessive • One-person audible or silent walktest with walktest log & printout • System alarm verification selection per detector point • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) • Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus • Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator • Upload/Download of program and data via USB with optional FS- Tools Programming Utility SLC COMMUNICATION LOOP • Supports FlashScan® and CLIP protocols • SLC operates up to 10,000 ft. (3,000 m) in FlashScan mode with twisted, unshielded wire • Single addressable SLC loop which meets NFPA Class B and Class A requirements • 50 addressable device capacity (any combination of addressable detectors and modules) • Compatible with NOTIFIER FireWarden & ONYX Series address- able devices (refer to the FireWarden SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NACS) • Two independently programmable output circuits. Circuits can be configured for the following outputs: –Style Y (Class B) –Style Z (Class A) • Silence Inhibit and Autosilence timer options • Continuous, March Time, Temporal, or California code for main circuit board NACs with two-stage capability • Selectable strobe synchronization per NAC • 2.5 A special application, 250mA regulated, total power for NACs NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A PROGRAMMING AND SOFTWARE • Autoprogramming (learn mode) reduces installation time • Custom English labels (per point) may be manually entered or selected from an internal library file • Two programmable Form-C relay outputs • 50 software zones • Continuous fire protection during online programming Page 2 of 4 — DN-60955:C • 7/16/2018 • Program Check automatically catches common errors not linked to any zone or input point •OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows®-based software package, and upload/download system programming locally. Offline program- ming requires an ethernet connection. FS-Tools is available on www.notifier.com. User interface LED INDICATORS KEYPAD Product Line Information NFW-50X: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre-installed IPOTS- COM communicator, chassis with transformer, backbox with door, plastic bag containing screws, cables, key, etc. FS-Tools: Programming software for Windows®-based PC com- puter. Available for download at www.notifier.com. CELL-CAB-N/CELL-MOD: Optional GSM communicators. IPOTS-COM: Dual technology (POTS and IP) communicator. (replacement board) DP-ES-R: Optional dress panel for the NFW-50XR (red). DP-ES-B: Optional dress panel for NFW-50X (black). TR-CE-B: Optional trim ring for semi-flush mounting. (Black. For red, order TR-CE.) BB-XP: Optional cabinet for one or two modules. BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AH batteries & CHG-75. NFS-LBB: Battery box, houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi-modules in a BB-25 cabinet. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. CHG-120: Remote battery charging system for lead-acid batteries with a rating of 55 to 120 AH. Requires additional NFS-LBB for mounting. NOTE: CHG-120 or CHG-75 required for batteries larger than 18AH. BAT Series: Batteries, see data sheet DN-6933. PRN Series: UL listed compatible event printer. Uses tractor-fed paper. OPTIONAL MODULES 4XTM Reverse Polarity Transmitter Module: Provides a super- vised output for local energy municipal box transmitter, alarm and trouble. Includes a disable switch and disable trouble LED. COMPATIBLE ANNUNCIATORS N-ANN-80: Remote, black LCD annunciator mimics the information displayed on the FACP LCD display. Recommended wire type is un- shielded. N-ANN-100: Remote LCD annunciator mimics the information dis- played on the FACP LCD display. Recommended wire type is un- shielded. For use in FM applications only. (Basic model is black; order R for red.) N-ANN-I/O: LED Driver Module provides connections to a user sup- plied graphic annunciator. (See DN-7105.) N-ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DN-60242.) N-ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DN-60242.) N-ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DN-7107.) N-ANN-S/PG: Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. (See DN-7103.) ADDRESSABLE DEVICES FSP-951: Addressable low-profile photoelectric smoke detector. FlashScan only. FSP-951-IV: Addressable low-profile photoelectric smoke detector. Ivory. FlashScan and CLIP mode. NP-200: Addressable low-profile photoelectric smoke detector. B300-6 base included, FlashScan only. NP-200-IV: Addressable low-profile photoelectric smoke detector. Ivory, B300-6-IV base included. FlashScan and CLIP mode. FSP-951T: Addressable low-profile photoelectric smoke detector with thermal sensor. FlashScan only. FSP-951T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory. FlashScan and CLIP mode. NP-200T: Addressable low-profile photoelectric smoke detector with thermal sensor. B300-6 base included. FlashScan only. NP-200T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory, B300-6-IV base included. FlashScan and CLIP mode. FSP-951R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. FlashScan only. FSP-951R-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory. FlashScan and CLIP mode. NP-200R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. FlashScan only. NP-200R-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory, FlashS- can and CLIP mode. FST-951: Low-profile 135°F fixed thermal sensor. FlashScan only. FST-951-IV: Low-profile 135°F fixed thermal sensor. Ivory. FlashS- can and CLIP mode. NH-200: Low-profile 135°F fixed thermal sensor. B300-6 base included, FlashScan only. NH-200-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6-IV base included, FlashScan and CLIP mode. FST-951R: Low-profile, intelligent, rate-of-rise thermal sensor. FlashScan only. FST-951R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. FlashScan and CLIP mode. NH-200R: Low-profile 135°F fixed thermal sensor. B300-6 base included, FlashScan only. NH-200R-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6- IV base included, FlashScan and CLIP mode. FST-951H: Low-profile intelligent 190°F/88°C fixed thermal sensor. FlashScan only. FST-951H-IV: Low-profile intelligent 190°F/88°C fixed thermal sen- sor. Ivory. FlashScan and CLIP mode. NH-200H: Low-profile intelligent 190°F/88°C fixed thermal sensor. B300-6 base included, FlashScan only. • Fire Alarm (red) • CO Alarm (red) • AC Power (green) • Supervisory (yellow) • Trouble (yellow) • Ground fault (yellow) • Battery fault (yellow) • Disabled (yellow) • Maintenance (yellow) • Communication (yellow) • Alarm Silenced (yellow) • F1-F4 Programmable Function Keys (yellow) • 16 key alpha-numeric pad • Acknowledge • Alarm Silence • Drill (Manual Evacuate) • Four (4) programmable function keys • Reset (lamp test) DN-60955:C • 7/16/2018 — Page 3 of 4 NH-200H-IV: Low-profile intelligent 190°F/88°C fixed thermal sen- sor. Ivory. B300-6-IV base included, FlashScan and CLIP mode. Legacy Devices FSP-851: Addressable low-profile photoelectric smoke detector. NP-100: Addressable low-profile photoelectric smoke detector. FSP-851T: Addressable low-profile photoelectric smoke detector with thermal sensor. NP-100T: Addressable low-profile photoelectric smoke detector with thermal sensor. FSP-851R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. NP-100R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. FST-851: Fast-response, low-profile heat detector. NH-100: Fast-response, low-profile heat detector. FST-851R: Fast-response, low-profile heat detector with rate-of-rise option. NH-100R: Fast-response, low-profile heat detector with rate-of-rise option. FST-851H: Fast-response, low-profile heat detector that activates at 190°F/88°C. NH-100H: Fast-response, low-profile heat detector that activates at 190°F/88°C. FAPT-851: Addressable low-profile multi-sensor detector. NP-A100: Addressable low-profile multi-sensor detector. B200S: Programmable, addressable sounder base. B200SR: Addressable sounder base. DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order FSP-851R, FSP-951R, or NP-100R separately.) DNRW: InnovairFlex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight. (Order FSP-851R, FSP-951R, or NP-100R separately.) Addressable Modules FMM-1: Addressable Monitor Module for one zone of normally-open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B (Class B) or Style D (Class A) IDC. NMM-100: Addressable Monitor Module for one zone of normally- open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Mod- ule may be configured for either a Style B (Class B) or Style D (Class A) IDC. FDM-1: Dual Monitor Module. Same as NMM-100 except it provides two Style B (Class B) only IDCs. NDM-100: Dual Monitor Module. Same as NMM-100 except it pro- vides two Style B (Class B) only IDCs. FMM-101: Miniature version of NMM-100. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. NMM-100P: Miniature version of NMM-100. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. FZM-1: Similar to NMM-100. Addressable Monitor Module for one zone of conventional two-wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. NZM-100: Similar to NMM-100. Addressable Monitor Module for one zone of conventional two-wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. FCM-1: Addressable Control Module for one Style Y/Z (Class B/A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. NC-100: Addressable Control Module for one Style Y/Z (Class B/A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. FRM-1: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. NC-100R: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. NBG-12LX: Addressable manual pull station with interface module mounted inside. NOT-BG12LX: Addressable manual pull station with interface mod- ule mounted inside. ISO-X: Fault Isolator Module. N100-ISO: Fault Isolator Module. ISO-6: Six-fault isolator module. Mount one or two modules in a BB- XP cabinet (optional). Mount up to six modules on a CHS-6 chassis in a CAB-3/CAB-4 series cabinet. SMB500: Used to mount all modules except FMM-101/NMM-100P. NMM-100-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. NZM-100-6: Six-zone interface module. Mount one or two modules in a BB-XP cabinet (optional). Mount up to six modules on a CHS-6 chassis in a CAB-3/CAB-4 series cabinet. SWIFT Wireless Devices FWSG: Wireless Gateway FWD-200P: intelligent, wireless photo detector. FWH-200ROR135: LiteSpeed intelligent wireless rate of rise (135°) heat detector. FWD-200ACCLIMATE: Wireless Acclimate Detector FWH-200FIX135: intelligent wireless fixed-temperature (135°) heat detector. FW-MM: Intelligent wireless monitor module. FW-RM: Intelligent wireless relay module. NBG-12LW: Intelligent wireless pull station. WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: Intelligent AV bases. W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools. SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. NOTE: For more information on Compatible Addressable Devices for use with the FireWarden-50X, see the following data sheets (document numbers): NP-200 Series (DN-60979), NH-200 Series (DN-60980), FSP-851 Series (DN-6935), FSP-951 Series (DN-60977), FST-851 Series (DN-6936), FST-951 Series (DN-60975), FAPT-851 (DN-6937), N100-ISO (DN-6994), NP-100 series (DN-6995), NH-100/NH-100R (DN-6997), DNR/InnovairFlex (DN-60424, DN-60429), NP-A100 (DN-6998), NMM-100/NMM-100P/NDM-100/NZM-100 (DN-6999), NC-100 (DN-7000), NC-100R (DN-60383), NMM-100-10 (DN-6990), MM-1/FDM-1/FZM-1/FMM-101 (DN-6720), FCM-1/FRM-1 (DN-6724), NOT-BG12LX (DN-7001), NBG-12LX (DN-6726), and FireWarden SLC Manual (52304). ADDRESSABLE DEVICE ACCESSORIES End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly supervises the FMM-1/NMM-100-10, FDM-1/ NDM-100, FMM-101/NMM-100P, and FCM-1/NC-100 module cir- cuits. The 3.9k ohm assembly supervises the XP6-MA/NZM-100-6 module circuit. These resistors are included with each module. Power Supervision Relay: Supervises the power to 4-wire smoke detectors and notification appliances. Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interfer- ence. Refer to the panel manual for wiring details. AlarmNet®, NOTIFIER®, FireWarden®, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Country of Origin: USA NOTIFIER 12 Clintonville Road Northford, CT 06472 203.484.7161 www.notifier.com SPECIFICATIONS System Capacity • Intelligent Signaling Line Circuits................................................1 • Addressable device capacity....................................................50 • Programmable software zones.................................................50 • Annunciators.............................................................................16 Electrical Specifications AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Capacity: 7-18 AH (FireWarden-50X cabinet holds maximum of two 18 AH batteries.) Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Terminal Block provides connec- tions for two NACs, Style Y (Class B) or Style Z (Class A). Special Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 amps special application, 250mA regulated. End-of-Line Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC; system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the NOTIFIER Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Con- tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, non-power-limited, non-supervised. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR- CE/B): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.) high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. NFPA Standards The FireWarden-50X complies with the following NFPA 72 Fire Alarm Systems requirements: – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). – AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTM). – REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervi- sory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTM is required.) – PROPRIETARY (Automatic, Manual and Waterflow). – CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). –OT, PSDN (Other Technologies, Packet-switched Data Net- work) – IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). – CBC 2007 (Seismic) Agency Listings and Approvals The listings and approvals below apply to the basic FireWarden-50X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S635 •CSFM: 7165-0028:0505 •FDNY: COA #6268 Commercial Fire Alarm Cellular &/or IP Fire Alarm LTE Communicators COMMERCIAL FIRE CELLULAR & IP • Sole Path Cellular and Dual Path Cellular &/or IP Models • Choice of LTE Networks, Verizon or AT&T models • Choice of plans (varies by model) - check-ins from 200 seconds to 5-minutes, and from 1 hour; up to 6 hours for dual path • Patented Signal Boost™ and Dual Diversity Antennae for maximum signal acquisition & null avoidance, receiving signals simultaneously on both antennae • Money-saving Tradeup incentive credit for security professionals, on new or retrofit fire systems, i.e., tradeup missing/retired POTs lines, old radios & networks or new installations • Bonus: Full High-Speed Napco Panel remote uploading/ downloading • COMPLIANCES: NFPA 72 Editions: 2019, 2016, 2013, 2010, 2007; UL 864, 10th Ed., UL1610, UL985, UL1023, NYCFD; CSFM; LAFD Napco StarLink Universal Fire Alarm Communicators • Universal full event sole & dual path cellular &/or IP commercial fire alarm reporting from any panel brand, virtually anywhere nationwide • Code-compliant, replaces 2 POTs lines per FACP saves thousands of dollars per year over the leased landlines • Supports 12V-24V control panels and FACPs that communicate using Contact ID and 4/2 (such as on legacy panels), as primary or backup • Full data Reporting to any Central Station nationwide, via choice of LTE Networks, Verizon® or AT&T®. Communicate critical life and safety alarm reports on LTE (Long Term Evolution) 10+ year life, cyber-protected multi-billion dollar cellular network, for maximum life safety & liability protection. • Proven to work even where other’s won’t - using Signal Boost™ & twin dual diversity antennas - Max. signal acquisition & null avoidance (receives signals simultaneously on both antennas) • Easiest installation, powered by panel, NO extra power supply, NO extra conduit. (Excludes Direct AC-Powered “-PS” models, with transformer option.) † • Dual Path Cellular/IP Models Save Time & Money - Uniquely including 4 programmable EOLR zone inputs; 2 Form C Relay outputs (no extra supervision modules to buy or install); plus, 2 Telephone-style jacks for easy FACP-connection. Self-supervised on 4 wires. • Preactivated to ensure communications - saves time and labor onsite • LED Status /Trouble Indicators 3 Radio Status LED Indicators (visible from outside standard model housing) - Green, Signal Strength; Amber- Busy/Activation; Red-Trouble (4 additional LEDs, not visible, for network status & troubleshooting). Power LED indicator viewable on outer metal enclosure models. • Over-the-Air Upgradable Communicator Firmware. Remote ability for critical/mandatory updates, without a truck-roll • Cost-saving models and plans for any code requirement. Dramatic savings over monthly dedicated landline charges. UL and NFPA 72 Fire Code-Compliant, the StarLink Series Wireless Commercial Fire Alarm Sole Path & Dual Path Communicators provide universal support for any brand 12V to 24V fire alarm control panel, reporting in Contact ID and 4/2. With broadest LTE coverage footprint, Verizon or AT&T, using proven StarLink circuitry , they are also available in locking metal models. All provide the most economical solution for easy, versatile installation. Also regional compliances, i.e., CSFM, NYCFD, LAFD and more. Easy, Universal Installation at Every Application; Panel-Powered Technology™. StarLink Fire Communications are easily connected to any panel or Fire Alarm Control Panel (FACP) standardly operating between 12V and 24V. Flexible in any application, StarLink Fire also comes in standard, or models in metal housings, with code-compliant supervision, and choice of power options, Panel-Powered Technology™ (powered by the panel), or direct-connect 120VAC models. Signal Boost circuitry & dual diversity antennae for maximum signal acquisition & null avoidance, receiving signals simultaneously on both antennae. Flexible Performance & Reporting Options. StarLink Fire provides full data reporting, in sole and dual path, as a primary or backup, to any central station of your choice, without requiring any special equipment on premises. Ultra-affordable plans are available to meet various codes and requirements, with supervisory check-ins from 200 seconds, to 5 minutes; and/or from 1 to 6 hours. The units are very easily activated, plans and options are selected, and 24/7 account management is provided all through www.napcocomnet.com. Code-compliant standard or metal models on choice of Verizon or AT&T LTE networks. Commercial Fire Alarm Cellular &/or IP Fire Alarm LTE Communicators COMMERCIAL FIRE CELLULAR & IP FL-32FACP-LTEV Firewolf 8 Zone 24V Conventional Commercial Fire Alarm Control Panel with onboard StarLink Fire® Sole Path, Verizon LTE Cellular Alarm Communicator and integral menu-driven LCD annunciator, w/ 4amp, 24V power supply. Optionally expandable up to 32 points/zones via commercial addressable, wireless or conventional fire devices (2 onboard NACs providing up to 4A notification power). Locking, metal red enclosure,(surface or flush mount*) removable 16”x17” door w/14.25”x16” base. Houses 16Ah battery backup. FireLink™ Integrated Fire Alarm Control Panel w/ StarLink Fire LTE Built In LTE Network Cell IP WiFi Option** Unique Onboard Labor/Cost-Saver Features Electrical Input Patings Inputs Input Ratings Outputs Output Ratings Other Power Supply (option)† STANDARD MODELS (ABS) 5.38 x 7.88 x 1.88" (HWD) SOLE PATH SLE-LTEA-FIRE AT&T Yes No No Panel-Powered Tech’y:†† Input Voltage/Input Current: 10V = 90mA; 12-25V = 71mA, 200mA peak during transmissions IN1, IN2, IN3 IN1: 9-25VDC Max input current 2mA IN2,IN3: 9-25VDC Max input current 1.2mA PGM1, PGM2, PGM3 Open Collector Outputs Max 3V when active, Max 25V when not active. Max current 24mA@ 25VSLE-LTEV-FIRE Verizon Yes No No DUAL PATH SLE-LTEAI-FIRE AT&T Yes Yes Yes 2 TelCo jacks for EZ FACP Connect; 4 Programmable EOLR zone inputs; 2 Form C Relay outputs (avoids reqt for supervision module) Panel-Powered Tech’y:†† Input Voltage:10-25VDC: Input Current: 162mA to 100mA standby; 300mA peak during transmissions IN1, IN2, IN3, IN4, IN5 IN1: 9-25VDC Max input current 2mA IN2,IN3,IN4,IN5: 9-25VDC Max input current 1.2mA OUT1, OUT2, PGM3 OUT1,OUT2:Dry Contact, Form C Relay, 30V AC/DC, 500mA Max PGM3: Open Collector Outputs Max 3V when active, Max 25V when active. Max current 24mA@ 25VSLE-LTEVI-FIRE Verizon Yes Yes Yes MODELS IN METAL ENCLOSURE 9.63 x 11.75 x 3.38" (HWD) SOLE PATH SLE-LTEA-CFB AT&T Yes No No Panel-Powered Tech’y:†† Input Voltage/Input Current: 10V = 90mA; 12-25V = 71mA, 200mA peak during transmissions IN1, IN2, IN3 IN1: 9-25VDC Max input current 2mA IN2,IN3: 9-25VDC Max input current 1.2mA PGM1, PGM2, PGM3 Open Collector Outputs Max 3V when active, Max 25V when not active. Max current 24mA@ 25VSLE-LTEV-CFB Verizon Yes No No SLE-LTEA-CFB-PS AT&T Yes No No Direct AC-Powered: Input Voltage: 120VAC nominal Input Current: 150mA max; maximum charging current: 200mA IN1, IN2, IN3 IN1: 9-25VDC Max input current 2mA IN2,IN3: 9-25VDC Max input current 1.2mA PGM1, PGM2, PGM3 Open Collector Outputs Max 3V when active, Max 25V when not active. Maximum current 24mA@ 25V Transformer (TRF12 16VAC, 20VA transformer) SLE-LTEV-CFB-PS Verizon Yes No No DUAL PATH SLE-LTEAI-CFB AT&T Yes Yes Yes 2 TelCo jacks for EZ FACP Connect; 4 Programmable EOLR zone inputs; 2 Form C Relay outputs (avoids reqt for supervision module) Panel-Powered Tech’y:†† Input Voltage:10-25VDC: Input Current: 162mA to 100mA standby; 300mA peak during transmissions IN1, IN2, IN3, IN4, IN5 IN1: 9-25VDC Max input current 2mA IN2,IN3,IN4,IN5: 9-25VDC Max input current 1.2mA OUT1, OUT2, PGM3 OUT1,OUT2:Dry Contact, Form C Relay, 30V AC/DC, 500mA Max PGM3: Open Collector Outputs Max 3V when active, Max 25V when active. Max current 24mA@ 25VSLE-LTEVI-CFB Verizon Yes Yes Yes SLE-LTEAI-CFBPS AT&T Yes Yes Yes 2 TelCo jacks for EZ FACP Connect; 4 Programmable EOLR zone inputs; 2 Form C Relay outputs (avoids reqt for supervision module) Direct AC-Powered: Input Voltage: 120VAC nominal Input Current: 200mA max; maximum charging current: 200mA IN1, IN2, IN3, IN4, IN5 IN1: 9-25VDC Max input current 2mA IN2,IN3,IN4,IN5: 9-25VDC Max input current 1.2mA OUT1, OUT2, PGM3 OUT1,OUT2:Dry Contact, Form C Relay, 30V AC/DC, 500mA Max PGM3: Open Collector Outputs Max 3V when active, Max 25V when active. Max current 24mA@ 25V Transformer (TRF12 16VAC, 20VA transformer) SLE-LTEVI-CFBPS Verizon Yes Yes Yes Free Commercial Fire LTE Tradeup Trifold Brochures / Mailers/Stuffers (A747) 333 Bayview Ave., Amityville, NY 11701 • 1-800-645-9445 • www.napcosecurity.com Note: Always consult technical manual and/or AHJ for compliance requirements for your area/appllication. StarLink, StarLink Fire, FireLink, SignalBoost, Panel-Powered Technology, Gemini & Gemini Commercial are trademarks of Napco. AT&T, Verizon, LTE, etc. are trademarks of their respective companies. *StarLink offers full data coverage in US from virtually all panel brands reporting in Contact ID or 4/2. †† For Panel-Powered technology, regulated auxiliary power outputs are required on Listed FACP. **Add 40mA to input current & Standby Battery requirement. †Where permitted by AHJ; requires conduit.. For full details on the StarLink tradeup incentive see online under http://www.napcosecurity.com/starlink/starlink4gupgrade/ †Promo subject to change w/o prior notice. LTE lifespan claims are based on those of carriers. ©NAPCO, NAPCO Security Technologies Inc. (NASDAQ:NSSC) A734A 2019.8 Model Ordering & Specifications ACCESSORIES: SLE-WIFI-MODULE Optionally connects supported dual path models to Internet via WiFi, eliminating Ethernet cable connection. Requires 7AH batt’y. (**See details WI2191) SLE-ANTEXT75 Optional extended range omni. antenna w/ 75’ cable, premium low-loss cable & full mounting hardware & ground fault isolation mounting plate SLE-ANTEXT50 As above, with 50’ cable SLE-ANTEXT30 As above, with 30’ cable TRF12 Optional Plug in AC Transformer, 16.5V / 20VA (use is subject to local code compliance)† DF-52301:A2 • 5/17/13 — Page 1 of 4 FCPS-24FS6 24 Volt, 6 Amp Power Supply Power Supplies/Accessories DF-52301:A2 • D-025 General The Fire•Lite FCPS-24FS6(C/E) is a compact, cost-effec-tive, 6-amp remote power supplies with battery charger. The FCPS-24FS6(C/E) may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may stand-alone. Primary appli- cations include notification appliance (bell) circuit (NAC) expansion (to support ADA requirements and NAC synchroni- zation) or auxiliary power to support 24 volt system accesso- ries. The FCPS provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either two Class B (Style Y) and Class A (Style Z, with ZNAC-4 option module) or four class B only. Alternately, the four outputs maybe configured as any combination of resettable/non-resettable power outputs (optimal for powering four-wire smoke detec- tors. The FFCPS-24FS6(C/E) also contains a battery chargercapable of charging up to 7.0 Amp hour batteries. FCPS- 24FS6(C/E) is ULC-listed. NOTE: Unless otherwise specified, the term FCPS-24FS6 used in this document refers to the standard FCPS-24FS6, FCPS- 24FS6C, FCPS-24FS6E Features • UL-Listed Notification Appliance Circuit (NAC) synchroniza- tion using System Sensor, Wheelock, or Gentex “Com- mander2” appliances. • Operates as a “sync-follower” or as a “sync-generator” (default). See note on page 2. • Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma- nently “ON” (stand-alone mode). • Two Class B (Style Y) or Class A (Style Z, with ZNAC-4 module) NACs (circuits 1 & 3) • 6-amp full load output, with 3 amps maximum/circuit, in NAC expander mode (UL 864). • 4-amp continuous output in stand-alone mode (UL 1481). • Compatible with coded inputs; signals passed through. • Optional power-supervision relay (EOLR-1). • In stand-alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two. • Fully regulated and filtered power output - optimal for pow- ering four-wire smoke detectors, annunciators, and othersystem peripherals requiring regulated/filtered power. • Power-limiting technology meets UL power-limiting require- ments. • Form-C normally-closed trouble relay. • Fully supervised power supply, battery, and NACs. • Selectable earth fault detection. • AC trouble report selectable for immediate 2-hour delay. • Works with virtually any UL 864 fire alarm control which uti- lizes an industry-standard reverse-polarity notification cir- cuit (including unfiltered and unregulated bell power). • Requires input trigger voltage of 9 - 32 VDC. • Self-contained in compact, locking cabinet - 15”H x 14.5”W x 2.75”D (cm: 38.1H x 36.83W x 6.985D). • Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. • Battery charger may be disabled via DIP switch for applica- tions requiring larger batteries. • Fixed, clamp-type terminal blocks accommodate up to 12AWG (3.1mm2) wire. Specifications Primary (AC) Power: • FCPS-24FS6: 120 VAC, 60 Hz, 3.2A maximum. • FCPS-24FS6/E: 240 VAC, 50 Hz, 1.6A maximum. • Wire Size: minimum #14 AWG (2.0mm 2) with 600 V insula- tion. Control Input Circuit: •Trigger Input Voltage: 9 to 32 VDC. •Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mAmaximum. Output Circuits: • +24 VDC filtered, regulated. • 3.0 A maximum for any one circuit. • Total continuous current for all outputs (stand-alone mode): –FCPS-24F: 4.0 A maximum. • Total short-term current for all outputs (NAC expander mode): –FCPS-24F: 6.0 A maximum. Page 2 of 4 — DF-52301:A2 • 5/17/13 Secondary Power (Battery) Charging Circuit: • Supports lead-acid batteries only. • Float-charge voltage: 27.6 VDC. • Maximum current charge: 250 mA. • Maximum battery capacity: 7.0 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A. Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP noti- fication appliance circuits will activate the FCPS when reverse- polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24-volt system power up to 4.0 A. Both resettable and non-reset- table power options are available. Resettable outputs are cre- ated by connecting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications. For example, an addressable control module is used to acti-vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable controlmodule. *NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 10,000 feet (3,046 meters) . Sync Follower/Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24FS6 can track (i.e. “follow”) the strobe synchronization timing pulses onthe existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS-24FS6 is configured (via DIP switch settings) as a “sync follower,” the FCPS’s NAC outputs track the strobe synchronization pulses present at the FCPS’s sync input ter- minal. The pulses originate from an upstream FACP or other power supply. When the FCPS-24FS6 is configured (via DIP switch settings) as a “sync generator,” the FCPS’s sync input terminals are not used. Rather, the FCPS is the originator of the strobe synchro-nization pulses on the FCPS’s NAC outputs. In “sync genera- tor” mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS-24FS6 complies with the following standards: •NFPA 72 National Fire Alarm Code. •UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). •UL 1481 Power Supplies for Fire Alarm Systems. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. •UL Listed: S2424, S1287 • ULC Listed: S2424 •CSFM Approved: 7315-0076:176 •MEA: 387-94E Ordering Information FCPS-24FS6:6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24FS6 is ULC-listed. FCPS-24FS6E:6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. ZNAC-4:Class A (Style Y) NAC option module. EOLR-1:12/24 VDC end-of-line relay for monitoring four-wire smoke detector power. BAT-1270:Battery, 12-volt, 7.0 AH (two required). PS-1270:Battery, 12-volt, 7.0 AH (two required). 90286: Optional module mounting kit, is required to install an addressable module on the power supply main circuit board. DF-52301:A2 • 5/17/13 — Page 3 of 4 6 9 2 7 b l o k . w m f Simplified Block Diagram Page 4 of 4 — DF-52301:A2 • 5/17/13 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com System Sensor® and FireLite® Alarms are registered trademarks ofHoneywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. Made in the U.S. A. Board Layout DN-60977:A • 4/17/18 — Page 1 of 3 FSP-951 Series Intelligent Plug-In Photoelectric Smoke Detectors Intelligent/Addressable Devices DN-60977:A FSP-951 in B300-6 Base General The NOTIFIER FSP-951 Series intelligent plug-in smoke detectorsare designed for both performance and aesthetics. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combus- tion sources in accordance with more stringent code standards. The FSP-951 Series detector sensitivity can be programmed in the con- trol panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronicthermistors add 135°F (57°C) fixed temperature thermal sensing on the FSP-951T. The FSP-951R is a remote test capable detector for use with DNR Series duct detector housings. FSP-951 series detec-tors are available for both FlashScan® and CLIP applications as designated. Features • New modern profile for improved aesthetics. • Designed to meet UL268 7th Edition. • Stable communication technique with noise immunity. • Low standby current. • Two-wire SLC connection. • Compatible with FlashScan® and CLIP protocol systems. • Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems). • Optional remote, single-gang LED accessory. • Dual LED design provides 360° viewing angle. • Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan sys- tems only). • Remote test feature from the panel. • Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only). • Built-in functional test switch activated by external magnet. • Built-in tamper-resistant feature. • Sealed against back pressure. • Expanded color options. • SEMS screws for wiring of the separate base. • Optional relay, isolator, and sounder bases. Specifications Sensitivity: • UL Applications: 0.5% to 4.0% per foot obscuration. • ULC Applications: 0.5% to 3.5% per foot obscuration. Size: 2.0" (5.3 cm) high; base determines diameter. –B300-6: 6.1" (15.6 cm) diameter. –B501: 4" (10.2 cm) diameter. For a complete list of detector bases see DN-60981. Shipping weight: 3.4oz (96.4g) Operating Temperature range: • FSP-951, 0°C to 50°C (32°F to 122°F). • FSP-951T, 0°C to 38°C (32°F to 100°F). • FSP-951R installed in a DNR/DNRW, -20°C to 70°C (-4°F to 158°F). UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts. Relative Humidity: 10%-93% noncondensing. Thermal Ratings: Fixed-temperature setpoint 135°F (57°C). DETECTOR SPACING AND APPLICATIONS NOTIFIER recommends spacing detectors in compliance with NFPA72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com ELECTRICAL SPECIFICATIONS Voltage Range: 15-32 volts DC peak. Standby Current (max. avg.): 200μA @ 24VDC (one communica- tion every five seconds with LED enabled). LED Current (max.): 4.5mA @ 24 VDC (“ON”). Installation FSP-951 series plug-in detectors use a separate base to simplify installation, service, and maintenance. Mount base (all base types) on an electrical backbox which is atleast 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60981. NOTE: 1) Because of inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring. 2) When using relay or sounder bases, consult the ISO-X(A) installation sheet I56-1380 for device limita- tions between isolator modules and isolator bases. Page 2 of 3 — DN-60977:A • 4/17/18 Agency Listings and Approvals These listings and approvals apply to the detectors specified in this document. In some cases, certain detectors or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL/ULC Listed: S911 • FM Approved • CSFM: 7272-0028:0503 Product Line Information NOTE: • Detectors must be mounted to one of the Intelligent Bases listed below. • “A” suffix indicates ULC Listed model. • “IV” suffix indicates FlashScan® and CLIP device. FSP-951: White, low-profile intelligent photoelectric sensor, FlashS- can only. FSP-951A: Same as FSP-951 but with ULC listing. FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor. FSP-951A-IV: Same as FSP-951-IV but with ULC listing. FSP-951T: White, same as FSP-951 but includes a built-in 135°F(57°C) fixed-temperature thermal device. FlashScan only. FSP-951TA: Same as FSP-951T but with ULC listing. FSP-951T-IV: Ivory, same as FSP-951T but includes a built-in 135°F (57°C) fixed-temperature thermal device. FSP-951TA-IV: Same as FSP-951T-IV but with ULC listing. FSP-951R: White, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FlashScan only. FSP-951RA: Same as FSP-951R but with ULC listing. For use with DNRA. FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor,remote test capable. For use with DNR/DNRW. FSP-951RA-IV: Same as FSP-951R-IV but with ULC listing. For use with DNRA. INTELLIGENT BASES NOTE: For details on intelligent bases, see DN-60981 B300-6: White, 6” base, standard flanged low-profile mounting base. B300-6-IV: Ivory,6” base, standard flanged low-profile mounting base. B300A-6: Same as B300-6, ULC listed. B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, ULC listed. B300-6-BP: Bulk pack of B300-6, package contains 10 B501-WHITE: White, 4” standard European flangeless mounting base. UL/ULC listed. B501-BL: Black, 4” standard European flangeless mounting base. UL/ULC listed. B501-IV: Ivory color, 4” standard European flangeless mounting base. UL/ULC listed. B501-WHITE-BP: Bulk pack of B501-WHITE contains 10. B224RB-WH: White, relay base. B224RB-IV: Ivory, relay base. B224RBA-WH: White, relay base, ULC listing. B224RBA-IV: Ivory, relay base, ULC listing. B224BI-WH: White, isolator detector base. B224BI-IV: Ivory isolator detector base. B224BIA-WH: White, isolator detector base, ULC listing. B224BIA-IV: Ivory isolator detector base, ULC listing. B200S-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone.Uses FlashScan protocol. B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3,ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B200SA-WH: Same as B200S-WH, ULC listing. B200SA-IV: Same as B200S-IV, ULC listing. B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications. B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications, ULC listing. B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet theNFPA 72 sleeping space requirement. B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended forretrofit applications. B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SRA-WH: Same as B200SR-WH with, ULC listing. B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing. B200SR-LF-WH: White, Low Frequency Intelligent, programmablesounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica-tions. B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base. TR300-IV: Ivory, replacement flange for B210LP(A) base. RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B300(A)- 6. M02-04-00: Test magnet. M02-09-00: Test magnet with telescoping handle. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 3 of 3 — DN-60977:A • 4/17/18 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (800) 627-3473, FAX: (203) 484-7118.www.notifier.com DN-6726:D • 4/13/2012 — Page 1 of 2 NBG-12LX Addressable Manual Pull Station Intelligent/Addressable Devices DN-6726:D • H-240 The NBG-12LX Addressable Manual Pull Station 6 6 4 3 c o v 1 .jp g ‘General The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e.,requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection toSLC loop (accepts up to 12 AWG/3.25 mm² wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. • Smooth dual-action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. • Up to 99 NBG-12LX stations per loop on CLIP protocol loops. • Up to 159 NBG-12LX stations per loop on FlashScan® pro-tocol loops. • Dual-color LED blinks green to indicate normal onFlashScan® systems. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications •Shipping Weight: 9.6 oz. (272.15 g) •Normal operating voltage: 24 VDC. •Maximum SLC loop voltage: 28.0 VDC. •Maximum SLC standby current: 375 μA. •Maximum SLC alarm current: 5 mA. •Temperature Range: 32°F to 120°F (0°C to 49°C) •Relative Humidity: 10% to 93% (noncondensing) •For use indoors in a dry location Installation The NBG-12LX will mount semi-flush into a single-gang, dou- ble-gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O sur- face backbox. If the NBG-12LX is being semi-flush mounted,then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word “ACTI- VATED” (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed ofred-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches(2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or Page 2 of 2 — DN-6726:D • 4/13/2012 NOTIFIER® and FlashScan® are registered trademarks of HoneywellInternational Inc.©2012 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Made in the U.S. A. 4" (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing thestate of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. The loop poll LED shall be clearly visible through the front ofthe station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm. Product Line Information NBG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) NBG-12LXSP: Spanish/English labelled version. NBG-12LXP: Portuguese labelled version. SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17021: Keys, set of two. NY-Plate: New York City trim plate. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. •UL/ULC Listed: S692 (listed for Canadian and non-Cana- dian applications). •MEA: 67-02-E. •CSFM: 7150-0028:0199. •FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030). •BSMI: CI313066760047. • U.S. Coast Guard. • Lloyd’s Register. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. DN-6720:C • 10/06/2010 — Page 1 of 4 FMM-1(A), FMM-101(A), FZM-1(A) & FDM-1(A) Monitor Modules with FlashScan® Intelligent/Addressable Devices DN-6720:C • H-220 General Four different monitor modules are available for Notifier’s intel-ligent control panels for a variety of applications. Monitor mod- ules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (FZM-1(A)). FMM-1(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. FMM-101(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that super- vises a Style B (Class B) circuit of dry-contact input devices.Its compact design allows the FMM-101(A) to be mounted in a single-gang box behind the device it monitors. FZM-1(A) is a standard-sized module that monitors and super-vises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. FDM-1(A) is a standard-sized dual monitor module that moni- tors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems. FlashScan® (U.S. Patent 5,539,389) is a communication pro-tocol developed by NOTIFIER that greatly increases the speed of communication between analog intelligent devices. Intelli- gent devices communicate in a grouped fashion. If one of thedevices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. FMM-1(A) Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the control panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 159 on FlashScan loops; 01 – 99 on CLIP loops. • LED flashes green during normal operation (this is a pro- grammable option) and latches on steady red to indicate alarm. The FMM-1(A) Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of eachmodule is selected using the built-in rotary switches. It pro- vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm andsupervisory devices. The module has a panel-controlled LED indicator. The FMM-1(A) can be used to replace MMX-1(A) modules in existing systems. FMM-1(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be usedto monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. FMM-1(A) OPERATION Each FMM-1(A) uses one of the available module addresseson an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita- tions on the loop). FMM-1(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 350 μA (LED flashing), 1 com-munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 40 ohms. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box. FMM-1(A) (Type H) 69 9 9 c o v . j p g Page 2 of 4 — DN-6720:C • 10/06/2010 FMM-101(A) Mini Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • Tinned, stripped leads for ease of wiring. • Direct-dial entry of address: 01 – 159 on FlashScan loops;01 – 99 on CLIP loops. The FMM-101(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The FMM-101(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat-ing device circuit for normally-open-contact fire alarm and security devices. The FMM-101(A) can be used to replace MMX-101(A) modules in existing systems. FMM-101(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit.A 47K ohm End-of-Line Resistor (provided) terminates the cir- cuit. FMM-101(A) OPERATION Each FMM-101(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). FMM-101(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 μA, 1 communication every5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 40 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 400 μA. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. FZM-1(A) Interface Module • Supports compatible two-wire smoke detectors. • Supervises IDC wiring and connection of external powersource. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 159 on FlashScan loops, 01 – 99 on CLIP loops. • LED flashes during normal operation; this is a programma- ble option. • LED latches steady to indicate alarm on command from control panel. The FZM-1(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (nor- mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni- tored must be UL compatible with the module. The FZM-1(A)can be used to replace MMX-2(A) modules in existing sys- tems. FZM-1(A) APPLICATIONS Use the FZM-1(A) to monitor a zone of two-wire smoke detec- tors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of theStyle B or D (class B or A) circuit (maximum IDC loop resis- tance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. FZM-1(A) OPERATION Each FZM-1(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita-tions on the loop). FZM-1(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 ohms. Average operating current: 300 μA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrmsmaximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. 6 7 2 0 m 1 0 1 . w m f DN-6720:C • 10/06/2010 — Page 3 of 4 FDM1(A) Dual Monitor Module The FDM-1(A) Dual Monitor Module is intended for use in intelli- gent, two-wire systems. It provides two independent two-wireinitiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices; or either normally open or nor- mally closed security devices. The module has a single panel- controlled LED. NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits ONLY. Style D (Class A) IDC circuits are NOT supported in any application. FDM-1(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 μA (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 μA EOL resistance: 47K ohms. Maximum SLC Wiring resistance: 40 Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x2.125" (5.398 cm) deep. FDM-1(A) AUTOMATIC ADDRESSING The FDM-1(A) automatically assigns itself to two addressable points, starting with the original address. For example, if the FDM-1(A) is set to address “26”, then it will automatically assign itself to addresses “26” and “27”. NOTE: “Ones” addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. Installation FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directlyto a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 sur- face-mount box. Mounting hardware and installation instruc- tions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only. The FMM-101(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S635 •ULC: S635 • FM Approved •CSFM: 7300-0028:0219 •MEA: 457-99-E •U.S. Coast Guard: –161.002/23/3 (AFP-200: FMM-1/-101, FZM-1) –161.002/42/1 (NFS-640: FMM-1/-101) •Lloyd’s Register: –03/60011/E1 (FMM-1/-101, FZM-1) –94/60004/E2 (AFP-200: except FDM-1) –02/60007 (NFS-640: FDM-1) •FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058(NFS2-3030) Product Line Information NOTE: “A” suffix indicates ULC-listed model. FMM-1(A): Monitor module. FMM-101(A): Monitor module, miniature. FZM-1(A): Monitor module, two-wire detectors. FDM-1(A): Monitor module, dual, two independent Class B cir- cuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51253. !CAUTION: Avoid duplicating addresses on the system. Page 4 of 4 — DN-6720:C • 10/06/2010 FlashScan® and NOTIFIER® are registered trademarks and FireWatch™ isa trademark of Honeywell International Inc.©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com Made in the U.S. A. DN-6724:B3 • 2/17/2011 — Page 1 of 2 FCM-1(A) & FRM-1(A) Series Control and Relay Modules Intelligent / Addressable Devices DN-6724:B3 General FCM-1(A) Control Module: The FCM-1(A) Addressable Con-trol Module provides Notifier intelligent fire alarm control pan- els a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be acti- vated, either manually or through panel programming, on a select (zone or area of coverage) basis. FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for acti- vating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming,on a select basis. FlashScan® (U.S. Patent 5,539,389) is a communication pro- tocol developed by NOTIFIER Engineering that greatlyenhances the speed of communication between analog intelli- gent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor- mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features • Built-in type identification automatically identifies thesedevices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers). • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated. • LED blink may be deselected globally (affects all devices). • High noise immunity (EMF/RFI). • The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. • Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops. • Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z). Applications The FCM-1(A) is used to switch 24 VDC audible/visual power, high-level audio (speakers). The FRM-1(A) may be pro- grammed to operate dry contacts for applications such as door holders or Air Handling Unit shutdown, and to reset four-wire smoke detector power. NOTE: Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM-1(A). Refer to the FCM-1-REL datasheet (DN-60390) for new FlashScan® releasing applications. Construction • The face plate is made of off-white heat-resistant plastic. • Controls include two rotary switches for direct-dial entry of address (01-159). • The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The FRM-1(A) provides two Form-C dry contacts that switch together. Operation Each FCM-1(A) or FRM-1(A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notifica- tion Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits. Upon code command from the panel, the FCM-1(A) will dis- connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the com- munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-inTYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a module and a sen- sor address. Specifications for FCM-1(A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). Average operating current: 350 μA direct poll, 375 μA group poll with LED flashing, 485 μA Max. (LED flashing, NAC shorted.) FCM-1(A) 70 0 0 c o v . J P G Page 2 of 2 — DN-6724:B3 • 2/17/2011 Notifier® and FlashScan® are registered trademarks of HoneywellInternational Inc. ©2011 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Made in the U.S. A. Maximum NAC Line Loss: 4 VDC. External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, thecurrent rating is 3A; For class A wiring system, the current rat- ing is 2A. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Specifications for FRM-1(A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). Average operating current: 230 μA direct poll; 255 μA group poll. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Agency Listings and Approvals In some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S635 •ULC: S3705 (A version only) • FM Approved •CSFM: 7300-0028:0219 •MEA: 14-00-E •FDNY: COA #6067, #6065 Contact Ratings for FRM-1(A) NOTE: Maximum (Speakers): 70.7 V RMS, 50 W Product Line Information NOTE: “A” suffix indicates ULC Listed model. FCM-1(A): Intelligent Addressable Control Module. FRM-1(A): Intelligent Addressable Relay Module. A2143-20: Capacitor, required for Class A (Style Z) operation of speakers. SMB500: Optional Surface-Mount Backbox. CB500: Control Module Barrier — required by UL for separat- ing power-limited and non-power limited wiring in the samejunction box as FCM-1(A). NOTE: For installation instructions, see the following documents: •FCM-1(A) Installation document I56-1169. •FRM-1(A) Installation document I56-3502. •Notifier SLC Wiring Manual, document 51253. Current Rating Maximum Voltage Load Description Application 3 A 30 VDC Resistive Non-Coded 2 A 30 VDC Resistive Coded .9 A 110 VDC Resistive Non-Coded .9 A 125 VDC Resistive Non-Coded .5 A 30 VDC Inductive (L/R=5ms)Coded 1 A 30 VDC Inductive (L/R=2ms)Coded .3 A 125 VAC Inductive (PF=0.35)Non-Coded 1.5 A 25 VAC Inductive (PF=0.35) Non-Coded .7 A 70.7 VAC Inductive (PF=0.35) Non-Coded 2 A 25 VAC Inductive (PF=0.35) Non-Coded AVDS910-01 • 10/1/2019 • Page 1 Horns only: 7135-1653:0516 Horn/Strobes: 7125-1653:0517 PR452768 S4011 Features • 520 Hz ± 10% square wave tone, NFPA compliance • Full candela range plus High/Low tone options to optimize current draw for a wide variety of applications • Compact, standard, and round ceiling options • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Rotary switch for High and Low, Temp3 and Temp4 settings • Plug-in design with minimal intrusion into the back box • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices (Direct replacement for HW/R-LF and P2R/WH-LF) • Compatible with MDL3 sync module • Sounders listed for ceiling and wall mounting • Sounder Strobe listed for wall mounting • Updated modern aesthetics The L-Series offers the most versatile and easy-to-use line of low frequency sounder and low frequency sounder strobes in the industry. With white and red plastic housings, listed for wall and ceiling mounting, L-Series Low Frequency can meet virtually any application requirement. The low frequency sounder and low frequency sounder strobes were designed to address the NFPA 72 sleeping space requirements that require a low frequency notification appliance that operates within frequency range of 520 Hz ± 10% and is of a square wave tone. Like the entire L-Series product line they include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, L-Series uses a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, 24- volt operation, and a rotary switch for 520 Hz low frequency sounder tones. Indoor Selectable- Output Low Frequency Sounders and Low Frequency Sounder Strobes System Sensor L-Series audible visible notification products are rich with features guaranteed to maximize profits with lower current draw and modern aesthetics. Agency Listings AVDS910-01 • 10/1/2019 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series low frequency sounder and low frequency sounder strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit (0°C to 49°C) from a regulated DC or full-wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, 185. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking on the housing that reads “low frequency sounder”. Low Frequency Sounder The low frequency sounder shall be a System Sensor L-Series Model _______ listed to UL 464 and shall be approved for fire protective service. The low frequency sounder and the Sync•Circuit™ MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 24 volts (includes fire alarm panels with built-in sync). When used with the Sync•Circuit Module MDL3, 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between temporal three or temporal four pattern, non- temporal (continuous) pattern and coded supply within the frequency range of 520Hz ± 10% square wave tone. The low frequency sounder shall operate on a coded or non-coded power supply with high and low volume settings. Low Frequency Sounder Strobe Combination The low frequency sounder strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three or temporal four pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The low frequency sounder on low frequency sounder strobe models shall operate on a non-coded power supply with high and low volume settings. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Class B circuits or one Class A circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Frequency Range 520 Hz ± 10% Strobe Flash Rate 1 flash per second Nominal Voltage Low Frequency Sounder Regulated 24 DC/FWR1 Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1 Operating Voltage Range 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Sounder Strobe (including lens)5.6" L x 4.7" W x 1.9" D (142 mm L x 119 mm W x 49 mm D) Standard Wall Sounder 5.6" L × 4.7" W × 1.5" D (142 mm L × 119 mm W × 38 mm D) Compact Wall Sounder 5.25" L x 3.46" W x 1.5" D (133mm L x 88mm W x 38mm D) Ceiling Sounder 6.8" diameter x 1.4" high (173mm diameter x 36mm high) Standard Wall Sounder with SBBRL/SBBWL Surface Mount Back Box 5.7” L x 4.8” W x 3.3” D (145 mm L x 120 mm W x 87 mm D) Compact Wall Sounder with SBBGRL/SBBGWL Surface Mount Back Box 5.4” L x 3.6” W x 3.0” D (137 mmL x 91mm W x 76 mm D) Low Frequency Ceiling Sounder with SBBCRL/SBBCWL Surface Mount Back Box 6.9" diameter x 3.9" high (175mm diameter x 99mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. AVDS910-01 • 10/1/2019 • Page 3 UL Current Draw and Sound Output Data Low Frequency Wall Sounder Strobe Current Draw (mA) and Sound Output (dBA) Current Draw (mA) Sound Output (dBA) Pos Tone Volume Setting 16-33 VDC 16-33 FWR 16-33 V 15cd 30cd 75cd 95cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd DC FWR 1 Temporal 3 High 98 115 158 173 182 212 266 136 153 188 206 228 258 304 80 80 2 Temporal 3 Low 98 102 141 162 173 202 255 150 150 176 194 216 242 280 76 76 3 Temporal 4 High 98 108 137 151 178 202 252 200 198 169 188 212 242 290 80 80 4 Temporal 4 Low 102 104 122 136 163 187 237 176 174 154 173 197 227 275 76 76 5 Continuous High 141 158 198 216 234 264 305 190 207 249 268 289 321 368 80 80 6 Continuous Low 120 128 179 196 215 244 285 165 182 226 244 266 297 342 76 76 UL Max. Low Frequency Sounder Current Draw (mA RMS) Volume Setting Current Draw (mA) Sound Output (dBA) Reverberant 16–33 Volts 16–33 Volts Pos Tone DC FWR DC FWR 1 Temporal 3 High 108 150 80 80 2 Temporal 3 Low 78 76 76 76 3 Temporal 4 High 111 151 80 80 4 Temporal 4 Low 80 76 76 76 5 Continuous High 111 151 80 80 6 Continuous Low 80 76 76 76 7 Coded High 111 151 80 80 8 Coded Low 80 76 76 76 *NOTE: For coded tones, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the sounder output will remain constantly on. Coded ratings provided are for continuous voltage. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS910-01 • 10/1/2019 Part No.Description Red White Low Frequency Sounder Strobes P2RL-LF P2WL-LF LF Sounder Strobe, Wall Low Frequency Sounders HRL-LF HWL-LF LF Sounder, Wall HGRL-LF HGWL-LF Compact LF Sounder, Wall HCRL-LF HCWL-LF LF Sounder, Ceiling Accessories MDL3R MDL3W Sync•Circuit™ Module, UL-listed SBBRL SBBWL Surface Mount Back Box, Wall SBBCRL SBBCWL Surface Mount Back Box, Ceiling SBBGRL SBBGWL Surface Mount Back Box, Wall, Compact L-Series Dimensions Wall LF Sounder Strobe Wall LF Sounder Compact Wall LF Sounder 3.455 1.453 5.265 Ceiling LF Sounder 6.830 1.438 System Sensor® is a registered trademark and Sync•Circuit™ is a trademark of Honeywell International, Inc. 4.700 1.453 5.670 Agency Listings Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) AVDS01201 SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2012 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet.AVDS01201 • 3/12 SpectrAlert Advance Diagrams Model Description Wall Horn Strobes P2RK*†2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*†2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*†2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*†2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RK†4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*†Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*†Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*†Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*†Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRK†Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box SpectrAlert Advance Ordering Information Notes: * Add “-P” to model number for plain housing (no “FIRE” marking on cover), e.g., P2RK-P. † Add “-R” to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW. “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝Dia. 2.5˝ 2.5˝ Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box All specifications referenced are nominal measurements unless otherwise noted. T 800.379.1191 | www.smartwire.com | © Copyright 2014 Windy City Wire, Inc. | All rights reserved. PART NUMBER 728100 UL Listed and Rated Type FPLR Multi-Conductor Non-Shielded Non-Plenum Fire Alarm CABLE SPECIFICATIONS DESCRIPTION 16 AWG 2 Conductor Bare Copper, Non-Shielded Non-Plenum Fire Alarm, FPLR (UL) CONDUCTOR 16 (Solid Bare Copper) INSULATION PVC .010" COLOR CODE Black/Red SHIELD N/A DRAIN WIRE N/A JACKET PVC .018" JACKET COLOR Red Jacket MARKING FIRE/LIFE SAFETY CONTROL CABLE INIT. / IND. DEVICE / ZONE A B C D E 0 1 2 3 4 5 6 7 8 9 16 AWG FPLR (UL) 75C ROHS MADE IN THE USA OVERALL DIAMETER .178" Nom. CABLE WEIGHT 29 Lbs/Mft. CAPACITANCE 26 pF/Ft. Nom. IMPEDANCE 72 Ohms/Mft. DC RESISTANCE 4.10 Ohms/Mft @ 20 deg. C TEMPERATURE RATING 0 C to 75 C / 300 Volt INDUSTRY STANDARDS AGENCY APPROVALS NEC Article 800, 760; FPLR (UL), RoHS Compliant, Made in the USA All specifications referenced are nominal measurements unless otherwise noted. T 800.379.1191 | www.smartwire.com | © Copyright 2014 Windy City Wire, Inc. | All rights reserved. PART NUMBER 729100 UL Listed and Rated Type FPLR Multi-Conductor Non-Shielded Non-Plenum Fire Alarm CABLE SPECIFICATIONS DESCRIPTION 14 AWG 2 Conductor Bare Copper, Non-Shielded Non-Plenum Fire Alarm, FPLR (UL) CONDUCTOR 14 (Solid Bare Copper) INSULATION PVC .010" COLOR CODE Black/Red SHIELD N/A DRAIN WIRE N/A JACKET PVC .018" JACKET COLOR Red Jacket MARKING FIRE/LIFE SAFETY CONTROL CABLE INIT. / IND. DEVICE / ZONE A B C D E 0 1 2 3 4 5 6 7 8 9 14 AWG FPLR (UL) 75C ROHS MADE IN THE USA OVERALL DIAMETER .206" Nom. CABLE WEIGHT 45 Lbs/Mft. CAPACITANCE 26 pF/Ft. Nom. IMPEDANCE 72 Ohms/Mft. DC RESISTANCE 2.57 Ohms/Mft @ 20 deg. C TEMPERATURE RATING 0 C to 75 C / 300 Volt INDUSTRY STANDARDS AGENCY APPROVALS NEC Article 800, 760; FPLR (UL), RoHS Compliant, Made in the USA Aquaseal Water Resistant Cables® No equal. If your installation calls for cables to run from one building to another, in conduit or directly buried in a wet location, have complete confidence in Aquaseal Water Resistant Cables®. With our water blocking tape, sunlight and moisture resistant jacket, you’re assured signal integrity. Don’t chance the install and settle for second best. When it comes to Aquaseal, there is no equal. PRODUCT INDEX: SHIELDED FPL DIRECT BURIAL AQUASEAL ........................................ UNSHIELDED FPL DIRECT BURIAL AQUASEAL ................................. SHLD AND UNSHLD IN-CONDUIT AQUASEAL........................... 1 2 3 WEST PENN WIRE 800-245-4964 www.westpenn-wpw.com Applications: Indoor/Outdoor Use: • Low Voltage Industrial Process Control • Power-Limited Circuits • Power-Limited Fire Alarm Circuits • Power-Limited Tray Cable PLTC • Line Level Audio Aquaseal® Water Blocking Cable Multi-Conductor/300 Volts Power-Limited Shielded Catalog No. No. of Cond. Conductor Type & Nom. D.C.R Insulation Type & Thickness Shielding % Coverage Jacket Type & Thickness Nom. O.D. NEC Type Nom. Capacitance Jacket Color AQ293 1 Pair 18 AWG (7x26) 6.2Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .040 .310 CL3CL3/FPL/FPL PLTCPLTC 32 pf/ft* 58 pf/ft**Black AQ3244 4 18 AWG (7x26) 6.2Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .040 .371 CL3CL3/FPL/FPL PLTCPLTC 32 pf/ft* 58 pf/ft**Black AQ294 1 Pair 16 AWG (7x24) 4.2Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .040 .328 CL3CL3/FPL/FPL PLTCPLTC 37 pf/ft* 67 pf/ft**Black AQ3245 4 16 AWG (7x24) 4.2Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .050 .415 CL3CL3/FPL/FPL PLTCPLTC 37 pf/ft* 67 pf/ft**Black Standard spool size 1000ft. Rating: • NEC Type FPL or PLTC or CL3 • (UL) Listed • Meets 300V requirements as specified in the NEC • Direct Burial • Flame Rating: UL1685 Description: • ASTM Bare Copper • PVC insulation with Nylon • Twisted pair or cabled construction • Overall shield 100% coverage of aluminum polyester foil with drain wire • Waterblocked Construction • Overall Sunlight/ Moisture Resistant PVC jacket AQ295 1 Pair 14 AWG (19x27) 2.7Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .040 .350 CL3CL3/FPL/FPL PLTCPLTC 46 pf/ft* 83 pf/ft**Black AQ296 2 12 AWG (19x25) 1.7Ω/Mft PVC .015 Nylon .005 Al. Foil- 100% 24 Strd. .040 .375 CL3CL3/FPL/FPL PLTCPLTC 54 pf/ft* 97 pf/ft**Black * Capacitance between conductors. ** Capacitance between one conductor and the other connected to the shield Color Code All Cables 1. Black, 2. Red, 3. Brown, 4. Blue JACKET: Black Special Notes: • Aquaseal Water Resistant Cables is a Registered Trademark of West Penn Wire • Orange ripcord under jacket Inches Inches Inches Aquaseal Alarm Cables 8 0 0 - 2 4 5 - 4 9 6 4 • w w w . w e s t p e n n - w p w . c o m Direct Burial WEST PENN WIRECABLE WITH CONFIDENCE1 Applications: Indoor/Outdoor Use: • Low Voltage Industrial Process Control • Power-Limited Circuits • Power-Limited Fire Alarm Circuits • Power-Limited Tray Cable PLTC • Speaker Level Aquaseal® Water Blocking Cable Multi-Conductor/300 Volts Power-Limited Catalog No. No. of Cond. Conductor Type & Nom. D.C.R Insulation Type & Thickness Shielding Jacket Type & Thickness Nom. O.D. NEC Type Nom. Capacitance Jacket Color AQ224 1 Pair 18 AWG (7x26) 6.2 Ω/Mft PVC .015 Nylon .005 None .035 .270 CL3CL3/FPL/FPL PLTCPLTC 25 pf/ft*Black AQ244 4 18 AWG (7x26) 6.2 Ω/Mft PVC .015 Nylon .005 None .040 .327 CL3CL3/FPL/FPL PLTCPLTC 25 pf/ft*Black AQ225 1 Pair 16 AWG (7x24) 4.2 Ω/Mft PVC .015 Nylon .005 None .040 .295 CL3CL3/FPL/FPL PLTCPLTC 28 pf/ft*Black AQ245 4 16 AWG (7x24) 4.2 Ω/Mft PVC .015 Nylon .005 None .040 .355 CL3CL3/FPL/FPL PLTCPLTC 28 pf/ft*Black AQ226 1 Pair 14 AWG (19x27) 2.7 Ω/Mft PVC .015 Nylon .005 None .040 .310 CL3CL3/FPL/FPL PLTCPLTC 32 pf/ft*Black AQ246 4 14 AWG (19x27) 2.7 Ω/Mft PVC .015 Nylon .005 None .040 .395 CL3CL3/FPL/FPL PLTCPLTC 32 pf/ft*Black AQ227 1 Pair 12 AWG (19x25) 1.7 Ω/Mft PVC .015 Nylon .005 None .040 .340 CL3CL3/FPL/FPL PLTCPLTC 36 pf/ft*Black Description: • ASTM Bare Copper • PVC insulation with nylon • Twisted pair or cabled construction • Waterblocked Construction • Overall Sunlight/ Moisture Resistant PVC jacket Rating: • NEC Type FPL or PLTC or CL3 • (UL) Listed • Meets 300V requirements as specified in the NEC • Direct Burial • Flame Rating: UL1685Standard spool size 1000ft. Color Code All Cables 1. Black,2. Red, 3. Brown, 4. Blue JACKET: Black Inches Inches Inches Special Notes: • Aquaseal Water Resistant Cables is a Registered Trademark of West Penn Wire • Orange ripcord under jacket Aquaseal Alarm Cables * Capacitance between conductors. 80 0 - 2 4 5 - 4 9 6 4 • w w w . w e s t p e n n - w p w . c o m WEST PENN WIRE CABLE WITH CONFIDENCE 2 Direct Burial WEST PENN WIRECABLE WITH CONFIDENCE3 8 0 0 - 2 4 5 - 4 9 6 4 • w w w . w e s t p e n n - w p w . c o m Applications: Indoor/Outdoor Use: • Intercom Systems • Security Systems • Sound and Audio • Background Music • Power-limited Control Circuits • Speaker Level Aquaseal® Water Blocking Cable 1 Pair /Unshielded Catalog No. No. of Cond. Conductor Type & Nom. D.C.R Insulation Type & Thickness Shielding % Cov. Drain Wire Jacket Type & Thickness Nom. O.D. NEC Type Nom. Capacitance Jacket Color Standard spool size 1000ft. Rating: • NEC Type CM / CL3 or FPL • (UL) Listed • Meets 300V requirements as specified in the NEC • Flame Rating: UL1685 Description: • ASTM Bare Copper • PVC Insulation • Short overall twist construction • Unshielded • Waterblocked Construction • Overall Sunlight/ Moisture Resistant PVC Jacket Inches Inches Inches Underground- In-Conduit AQC225 1 Pair 16 AWG (19x29) 4.2Ω/Mft PVC .010 None PVC .025 .242 CMCM/CL3 FPL 35pf/ft Gray AQC293 1 Pair 18 AWG (7x26) 6.2 Ω/Mft PVC .010 Al. Foil- 100% 24 Strd. PVC .025 .257 CMCM/CL3 FPL 39 pf/ft* 70 pf/ft**Gray AQC224 1 Pair 18 AWG (7x26) 6.2Ω/Mft PVC .010 None PVC .025 .218 CMCM/CL3 FPL 30pf/ft Gray Applications: Indoor/Outdoor Use: • Intercom Systems • Security Systems • Sound and Audio • Background Music • Power-limited Control Circuits • Line Level Audio Aquaseal® Water Blocking Cable Two & Multiple Conductor / Shielded Catalog No. No. of Cond. Conductor Type & Nom. D.C.R Insulation Type & Thickness Shielding % Coverage Drain Wire Jacket Type & Thickness Nom. O.D. NEC Type Nom. Capacitance Jacket Color Description: • ASTM Bare Copper • PVC insulation • Short overall twist lengths • Overall shield 100% coverage of aluminum polyester foil with drain wire • Waterblocked construction • Overall Sunlight/ Moisture Resistant PVC jacket Rating: • NEC Type CM / CL3 or FPL • Flame Rating: UL1685Standard spool size 1000ft. Inches Inches Inches Underground- In-Conduit AQC294 1 Pair 16 AWG (19x29) 4.2Ω/Mft PVC .010 Al. Foil- 100% 24 Strd. PVC .025 .281 CMCM/CL3 FPL 46 pf/ft* 83 pf/ft**Gray AQC226 1 Pair 14 AWG (19x27) 2.7Ω/Mft PVC .015 None PVC .025 .294 CL3 FPL 34pf/ft Gray AQC295 1 Pair 14 AWG (19x27) 2.7Ω/Mft PVC .015 Al. Foil- 100% 24 Strd. PVC .025 .333 CL3 FPL 48 pf/ft* 86 pf/ft**Gray Aquaseal Audio & Alarm Cables