HomeMy WebLinkAboutLOAD SHORT FORM - 21-00118 - 2428 W 880 S - New SFRBold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Load Short Form Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7568Inside db (°F) 0Fireplaces1474Design TD (°F) H-Daily range 5050Inside humidity (%) -3157Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-** AHRI ref 4805339 Coil CH35-36C++TDR+TXV AHRI ref 7623033 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh20300 Heating output Btuh64000 Latent cooling Btuh8700 Temperature rise °F58 Total cooling Btuh29000 Actual air flow cfm1200 Actual air flow cfm967 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.086 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room7 320 6985 1202 191 104 Room9 288 4865 1355 133 117 Room11 162 1309 237 36 20 Room12 165 3733 934 102 80 Room14 60 810 131 22 11 Room15 180 4254 1430 116 123 Room16 210 2900 1323 79 114 Room18 363 5399 1741 148 150 Room5 432 7809 1937 214 167 Room6 288 4784 765 131 66 Room1 105 987 167 27 14 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S Entire House d 2573 43834 11224 1200 967 Other equip loads 3617 684 Equip. @ 0.94 RSM 11193 Latent cooling 0 TOTALS 2573 47451 11193 1200 967 2021-Feb-23 14:57:59 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Building Analysis Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor:7568Indoor temperature (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F)SimplifiedMethod)H(34-Daily range (°F) AverageConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 40.4191527.5Walls 13.5642424.4Glazing 0.523311.1Doors 4.822691.5Ceilings 10.951643.43.4Floors 22.3105913.8Infiltration 00Ducts00Piping00Humidification7.63617Ventilation0Adjustments100.047451Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 15.918890.7Walls 37.3443916.9Glazing 0.5582.8Doors 10.812880.8Ceilings 1.51730.1Floors 8.610260.4Infiltration 00Ducts5.7684Ventilation19.72350Internal gains 00Blower0Adjustments100.011908Total Latent Cooling Load = 0 BtuhOverall U-value = 0.077 Btuh/ft²-°F Data entries checked. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Component Constructions Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temperature (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) AverageConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1560.4715794.8122.00.065328n 2851.09288611.122.00.150260n 1800.4718284.8122.00.065380e 3151.09319711.122.00.150288e 1660.4716794.8122.00.065349s 2661.09269311.122.00.150243s 1800.4718284.8122.00.065380w 3421.09346311.122.00.150312w 18890.74191527.5422.00.1502540all Partitions (none) Windows61C: 61C; NFRC rated (SHGC=0.30)73910.3175024.400.33072n 61910.3146524.400.33060n 78532.758624.400.33024e 54318.173324.400.33030s 140218.1189024.400.33077s 408915.5642424.400.330263all Doors metal: Door, mtl pur core type 582.7823311.16.00.15021s Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 12880.8422691.4850.00.0201533 Floors19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 5/8" gypsum board int fnsh 1730.409142.1130.00.034433 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 0015226.310.00.3556 00409826.310.00.355156 00425026.310.00.355162all 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Project Summary Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F68 Inside db °F75Design TD °F74 Design TD °F14Daily range HRelative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh43834 Structure Btuh11224DuctsBtuh0DuctsBtuh0Central vent (53 cfm)3617 Btuh Central vent (53 cfm)Btuh684Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh47451 Use manufacturer's data nRate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh11193 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh-427Ducts Btuh0Central vent (53 cfm)Btuh-951CoolingHeatingOutside air25732573Area (ft²)Equipment latent load Btuh02266422664Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh11193Equiv. AVF (cfm)79155 Req. total capacity at 0.70 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOXModelML195UH070XP36B-*Cond 13ACXN030-230-**AHRI ref 4805339 Coil CH35-36C++TDR+TXVAHRI ref 7623033Efficiency95 AFUE Efficiency 11.0 EER, 13 SEERHeating input Btuh66000 Sensible cooling Btuh20300Heating output Btuh64000 Latent cooling Btuh8700Temperature rise °F58 Total cooling Btuh29000Actual air flow cfm1200 Actual air flow cfm967Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.086Static pressure in H2O0.70 Static pressure in H2O0.70Space thermostat Load sensible heat ratio 1.00 2021-Feb-23 14:57:59 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:AED Assessment Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temperature (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F))H(34-Daily range (°F) 60-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 36.9%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 350 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Entire House Room7 2 Exposed wall 314.0 ft 56.0 ft3Room height 8.8 dft 10.0 heat/coolft 4 Room dimensions ft20.0x16.0 5 Room area 2573.0 ft²320.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 400 328 1579 156 0 0 0 0.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 72 0 1750 739 0 0 0 0.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 320 260 2886 285 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 60 0 1465 619 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 380 380 1828 180 200 200 962 95 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 312 288 3197 315 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 24 0 586 785 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 400 349 1679 166 160 109 524 52 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 30 0 733 543 30 0 733 543DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 21 21 233 58 21 21 233 58 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 320 243 2693 266 0 0 0 0GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 77 0 1890 1402 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 380 380 1828 180 200 200 962 95 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 312 312 3463 342 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 1533 1533 2269 1288 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 433 433 914 173 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 60 6 152 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 1040 156 4098 0 320 56 1471 0 6 c) AED excursion 350 155 Envelope loss/gain 33243 7847 4885 998 12 a)Infiltration 10591 1026 2100 204 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 5 1150 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13)43834 11224 6985 1202 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal438341122469851202 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 43834 11224 6985 1202 Air required (cfm)Air required (cfm)1200 967 191 104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room9 Room11 2 Exposed wall 34.0 ft 9.0 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft18.0x16.0 ft18.0x9.0 5 Room area 288.0 ft²162.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 128 98 1088 107 72 72 799 79 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 30 0 733 309 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 0 0 0 0GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 144 144 1598 158 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 288 288 426 242 162 162 240 136 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -20 -4 Envelope loss/gain 3845 796 1039 211 12 a)Infiltration 1020 99 270 26 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4865 1355 1309 237 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal486513551309237 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4865 1355 1309 237 Air required (cfm)Air required (cfm)133 117 36 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 3S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room12 Room14 2 Exposed wall 26.0 ft 5.0 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.0x15.0 ft5.0x12.0 5 Room area 165.0 ft²60.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 120 90 999 99 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 30 0 733 309 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 88 88 977 96 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 0 0 0 0GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 40 40 444 44CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 165 165 244 139 60 60 89 50 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 60 60 127 24 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -14 -2 Envelope loss/gain 2953 629 659 116 12 a)Infiltration 780 76 150 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3733 934 810 131 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal3733934810131 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3733 934 810 131 Air required (cfm)Air required (cfm)102 80 22 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 4S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room15 Room16 2 Exposed wall 27.0 ft 15.0 ft3Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft15.0x12.0 ft210.0x1.0 5 Room area 180.0 ft²210.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 8 8 89 9 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 96 66 733 72 104 74 821 81GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 30 0 733 543 30 0 733 543WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 120 120 1332 131 8 8 89 9CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 180 180 266 151 210 210 311 176 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 180 180 380 72 193 193 408 77 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 152 153 Envelope loss/gain 3444 1122 2450 1049 12 a)Infiltration 810 79 450 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)4254 1430 2900 1323 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal4254143029001323 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4254 1430 2900 1323 Air required (cfm)Air required (cfm)116 123 79 114 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 5S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room18 Room5 2 Exposed wall 35.0 ft 66.0 ft3Room height 8.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft363.0x1.0 ft18.0x24.0 5 Room area 363.0 ft²432.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 240 218 1050 104.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 22 0 529 224.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 160 136 1510 149 0 0 0 0 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 24 0 586 785 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 240 240 1154 114 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 120 103 1139 112 0 0 0 0GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 17 0 425 315 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 180 180 866 85 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 363 363 537 305 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 60 6 152 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 432 66 1734 0 6 c) AED excursion -26 -29 Envelope loss/gain 4349 1640 5333 497 12 a)Infiltration 1050 102 2475 240 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13)5399 1741 7809 1937 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal5399174178091937 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 5399 1741 7809 1937 Air required (cfm)Air required (cfm)148 150 214 167 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:57:59Right-Suite® Universal 2019 19.0.13 RSU20477 Page 6S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Right-J® Worksheet Date:Entire House Vince ByramBy:Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room6 Room1 2 Exposed wall 34.0 ft 7.0 ft3Room height 10.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft18.0x16.0 ft7.0x15.0 5 Room area 288.0 ft²105.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 160 110 529 52 0 0 0 0.GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 50 0 1221 516 0 0 0 0.WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 nn 11.1011.10 1.091.09 0 0 0 0 0 0 0 0 .GG 61C61C 0.3300.330 nn 24.4224.42 10.3210.32 0 0 0 0 0 0 0 0 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 180 180 866 85 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ee 11.1011.10 1.091.09 0 0 0 0 56 56 622 61 GG 61C61C 0.3300.330 ee 24.4224.42 32.6932.69 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0DDmetalmetal0.1500.150 ss 11.1011.10 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ss 11.1011.10 1.091.09 0 0 0 0 0 0 0 0GG61C61C0.3300.330 ss 24.4224.42 18.1218.12 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.150Frm wall, vnl ext, 3 0.150 ww 11.1011.10 1.091.09 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 0 0 0 0 105 105 155 88 FF 19A-30bscp19A-30bscp 0.0340.034 --2.112.11 0.400.40 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.2726.27 0.000.00 288 34 893 0 0 0 0 0 6 c) AED excursion -12 -3 Envelope loss/gain 3509 642 777 147 12 a)Infiltration 1275 124 210 20 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4784 765 987 167 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal4784765987167 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4784 765 987 167 Air required (cfm)Air required (cfm)131 66 27 14 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-23 14:58:00 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Loads for Multiple Orientations Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temperature (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) )H(34-Daily range (°F) 60-Wet bulb (°F) 7.515.0Wind speed (mph) House North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)11612 14441 14925 13281 11193 13557 14776 13557 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)11612 14441 14925 13281 11193 13557 14776 13557 Heating AVF (cfm)1200 1200 1200 1200 1200 1200 1200 1200 Cooling AVF (cfm)967 967 967 967 967 967 967 967 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction House faces 0 5000 10000 15000 N NE E SE S SW W NW House faces SouthCurrent Orientation: House faces EastHighest Cooling Load: Job #: SF12B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 1 Right-Suite® Universa l 2019 19.0.13 RSU20477 2021-Feb-23 14:59:09 ...ightsoft\SF12B14 huntington.rup N Main Room5 Room6 Room7 6" Mechanical Damper for Fresh Air 107 cfm 65 cfm 96 cfm 107 cfm 65 cfm 96 cfm 536 cfm 6 " 14x3.25 2-14x3.25 14x3.25 8 "6 " 6 " 6 "6 " 6 "6 " 6 " 8 " 6 " 16 x 8 6 " 16 x 8 14x3.25 6 " 12 x 8 4-14x3.25 6 " 6 " Job #: SF12B14 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 2 Right-Suite® Universa l 2019 19.0.13 RSU20477 2021-Feb-23 14:59:09 ...ightsoft\SF12B14 huntington.rup N 2nd floor Room9 Room11 Room12 Room14 Room15 Room16 Room18 Room1 75 cfm 143 cfm 138 cfm 170 cfm 114 cfm 27 cfm 75 cfm 36 cfm 102 cfm 133 cfm 22 cfm 123 cfm 133 cfm 114 cfm Bold/italic values have been manually overridden 2021-Feb-23 14:58:02 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S SF12B14Job:Duct System Summary Date:Entire House Vince ByramBy: Huntinton PlanPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.269 / 0.091 in H2O in H2O0.269 / 0.091 Lowest friction rate in/100ft0.079in/100ft0.079 Actual air flow cfm967cfm1200 Total effective length (TEL)ft453 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1325.013.0ShMt0x06.00.0791427987hRoom1 st1325.013.0ShMt0x06.00.07920361309hRoom11 st1325.013.0ShMt0x08.00.079801023733hRoom12 st2325.013.0ShMt0x06.00.0791122810hRoom14 325.013.0ShMt0x06.00.0791231161430cRoom15 st1325.013.0ShMt0x06.00.079114791323cRoom16 st1325.013.0ShMt0x06.00.0797574871cRoom18 st1325.013.0ShMt0x06.00.0797574871cRoom18-B st2325.013.0ShMt0x06.00.079831073904hRoom5 st1325.013.0ShMt0x08.00.079831073904hRoom5-A st1325.013.0ShMt0x06.00.07933652392hRoom6 st1325.013.0ShMt0x06.00.07933652392hRoom6-A st1325.013.0ShMt0x06.00.07952963493hRoom7 st1325.013.0ShMt0x06.00.07952963493hRoom7-A st1325.013.0ShMt0x06.00.0791171334865hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 955 749 0.079 1074 13.0 16x8 ShtMetl st2 Peak AVF 129 95 0.079 194 6.7 12x8 ShtMetl Bold/italic values have been manually overridden 2021-Feb-23 14:58:02 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF12B14 huntington.rup Calc = MJ8 House faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 5360 336 115.0 0.079 424 11.4 4-3.25x14 4-10x36 SJSp rt1 rb8 0x 790 114 115.0 0.079 360 6.4 3.25x14 10x9 SJSp rt1 rb1 0x 1330 117 115.0 0.079 422 6.8 3.25x14 10x9 SJSp rt1 rb6 0x 1380 101 115.0 0.079 437 6.9 3.25x14 10x9 SJSp rt1 rb7 0x 1700 161 115.0 0.079 269 7.4 2-3.25x14 2-10x18 SJSp rt1 rb5 0x 1430 138 115.0 0.079 123 7.0 x14 12 ShMt Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1057 829 0.079 1189 13.8 16x8 ShtMetl