Loading...
HomeMy WebLinkAboutFAULT CURRENT CALCULATIONS - 21-00048 - Barney Dairy Lift Station - ElectricalBret   I was asked to send this over to you for the Barney Dairy lift station project.   From RMP we have a 75 K transformer 480y/277 pad mounted transformer Looking a RMP 105F worksheet we have 5,575 amp of fault current at the transformer With the Bussmann info. / The Gear is 200 amp 600 10 ka   This is a screen shot from the submittal   /   This is the screen shot of the Short circuit current with a infinite bus   Short Circuit Transformer Bus Current Assuming an Infinite Bus1    Table 1: 480Y/277 Three Phase Pad Mounted Transformer         Information provided by Manufacturer     Transformer kVA Stock Number % IR %IX X/R ratio Transformer  %Z Calculated Fault Current (Amps)    75 4710090 1.01 2.92 2.89 1.62 5,575    112.5 4700091 0.98 2.52 2.57 2.70 5,018    150 4700228 0.89 2.97 3.34 3.18 5,680    225 4700229 0.8 3.74 4.68 3.52 7,698    300 4700094 0.78 3.66 4.69 1.61 22,439    500 7991410 0.74 3.88 5.24 1.94 31,037    750 7991371 0.73 5.68 7.78 5.63 16,042    1000 9174749 0.62 5.74 9.26 5.45 22,096    1500 7992507 0.69 5.65 8.19 5.46 33,083    2000 4700159 0.69 5.62 8.14 5.66 42,553    2500 9175845 0.63 5.65 8.97 5.39 55,855       James Ball, Office: 208-754-9389 // Cell: 208-860-8424 Shipping: 3896 East 600 North Rigby, Idaho 83442 Mailing: PO Box #142 Menan Idaho, 83434