Material Preparation:
Flame Control E-119 2 Hour must be thoroughly mixed
before application. Failure to do so will compromise the
protective capabilities of Flame Control Flame Control E-
119 2 Hour. We recommend mechanical stirring with a
high speed drill and a paddle appropriate for the size
container. Contents should be stirred from the bottom up,
making sure to scrape the bottom and sides with a paint
stick as you go. Contents should be stirred to a creamy
consistency with no lumps.
Flame Control E-119 2 Hour is a water based product and
slight thinning will not hurt the product (less than 5%). It
should be noted that thinning increases the likelihood of
not applying the proper film thickness, resulting in
decreased fire protection capabilities. It is the sole
responsibility of the applicator to ensure the proper film
thickness has been applied.
Flame Control E-119 2 Hour should never be mixed with
other materials, however tinting using universal paint tint
is acceptable.
Application Equipment:
Flame Control E-119 2 Hour can be applied by brush, roller
or airless sprayer.
Brushing: Use top quality polyester/nylon blend brushes
Rolling: 3/8" polyester blend nap roller covers generally
work well when applying Flame Control E-119 2 Hour by
roller.
Spraying:
Airless Spray Minimum:
PSI: 3000 PSI or higher or equivalent
Filter: 30 mesh, removal of filter is recommend from gun
and machine
Hose: 1/4" diameter airless spray line for the first 50'
from pump and %" x 6' whip
Tip: 517 — 531
GPM:.95
For best results, use Hose: 3/8" diameter airless spray line
for the first 50' from pump and %" x 6' whip and no filters
gun and machine.
FLAME CONTROL E-119 2 Hour
Interior Intumescent Latex Paint providing a 2 -hour rating
A Low VOC, Water Based Product
For Smaller Commercial and Residential Jobs:
Pump: (Titan) 740 Impact or equivalent
PSI: 3300 / 227
GPM:.80
Tip: 517-531 or equivalent.
Filter: 30 mesh, removal of filter is recommend from gun
and machine
Hose: 1/4" diameter airless spray line for the first 50'
from pump and %" x 6' whip
Pump: (Graco) Ultra Max 11 795 Hi -Boy or equivalent
PSI: 3300 / 227
GPM:.95
Tip: 517 — 531 or equivalent.
Filter: 30 mesh, removal of filter is recommend from gun
and machine
Hose: 1/4" diameter airless spray line for the first 50'
from pump and %" x 6' whip
Pump: (SprayTex) GPX 130 or equivalent
PSI: 3300 / 227
GPM: 1.30
Tip: 517 - 531 or equivalent.
Filter: 30 mesh, removal of filter is recommend from gun
and machine
Hose: 1/4" diameter airless spray line for the first 50'
from pump and %" x 6' whip
For Best results: For all Jobs big or small:
Pump: (Graco) Mark 4 or 5 or equivalent
PSI: 3300 / 227
GPM: 1.35
Tip: 517 - 533 or equivalent.
Filter: 30 mesh, removal of filter is recommend from gun
and machine
Hose: 3/8" diameter airless spray line for the first 50'
from pump and %" x 6' whip
Revised 12/14
Coatings cottla
Product Description:
FLAME CONTROL E-119 2 Hour
Interior Intumescent Latex Paint providing a 2 -hour rating
A Low VOC, Water Based Product
Flame Control E-119 2 Hour is a water-based, interior, intumescent, latex paint designed for use on walls to increase
the time rating of the drywall assembly. Flame Control E-119 2 Hour has been tested in accordance with ASTM E-119
test methodology and has achieved a two hour rating (wall construction assembly listed separately) while also
SHCCPUfHIIy PICCi lg the hose :Arcam test.
Flame Control E-119 2 Hour is a low VOC product, and can be Topcoated with Flame Control 40-40A or 400 for varying
appearance and added durability. Flame Control E-119 dries to a flat finish while having the appearance of conventional
flat latex paint. In the presence of heat, Flame Control E-119 2 Hour intumesces or puffs up, forming a dense protective
char that insulates the substrate.
Flame Control E-119 2 Hour can be applied in a single coat, saving application time and reducing labor costs.
Characteristics:
sh
r
Flat
Shelf Life 1 Year
e of Cure
rApplication
Off -White
Coalescence
VOC Less Than 40 g/I
Temperature
50°F (10°C) *** See Application
Flash Point None
Reducer/Cleaner
Temperature Section
Water
Solids By Weight
65%
Tintingg
Universal Paint Colorant: 2 Fluid ounces
Packaging
g 1, 5 & 55 gal. containers
Application
per gallon maximum
Brush, Roller, Spray
Drying Time @ 77°F (25°C) &
50% R.H.
To touch: 1- 2 Hours
2 hour rating spread 20 mils WFT/10.3 mils DFT:
To Recoat: 2 —4 hours
rate 80 Sq. Ft/Gallon
Surface Preparation:
All surfaces to be painted must be clean and cured.
Surface preparation should be carried out according to
good painting practices. All dirt, grease, oil, wax, and
other surface contaminants should be properly removed
prior to application of Flame Control E-119 2 Hour
intumescent coating
Previously Painted Surfaces:
Flame Control E-119 2 Hour coating may be applied
directly to existing paint that is tightly adherent and in
good condition. All glossy surfaces should be dulled with
sandpaper. Spot priming where necessary should be
carried out to ensure proper adhesion and dry film
thickness.
Temperature:
Flame Control E-119 2 Hour coating is a water based
product which will freeze and become unusable at
temperatures below 32°F. PROTECT FROM FREEZING
DURING SHIPMENT AND STORAGE. Do not store material
at temperatures below 50°F. Do not apply Flame Control
E-119 2 Hour when ambient air and substrate
temperatures fall below 50°F. Store between 50°F and
80T.
Important:
Humidity 65% and higher must use fans to move air for
curing. High humidity may require longer cure times.
Please consult with your local code officials to verify that your application complies with the appropriate code requirements.