HomeMy WebLinkAboutINSPECTION REPORT - 19-00520 - HEADWATERS CONSTRUCTION, FHM #4CITY OF
REXBURG
ry
Ammm1 Famdy Community
Public Works
Water Department
35 North I- East
Rexburg, ID 83440
(208)359-3020
Inspection: #39412
WTR-Backflow Test (DC)
Inspected By: Harper, Ivan
Priority: .. Status: CLOSED Inspection Date: 09/10/2019
Inspection Details
Initiated By: Harper, Ivan
9/10/19 2:38 pm
Inspected By: Harper, Ivan
9/10/19 3:15 pm
Closed By: Harper, Ivan
9/10/19 3:15 pm
Location: FHM 4
tion Observations
Line Pressure at Time of Test (lbs.):
80
1st Check - PSI:
2,9
1st Check - Leaked:
515 N 5 W
2nd Check - PSI:
2.6
2nd Check - Leaked:
2.00
Air Gap Inspection (Required minimum air
Wllklns
gap separation provided):
950 XLT
Were repairs made?:
No Repairs Needed
What was the repair:
What Materials were used for the repair:
1st Check - PSI:
2nd Check - PSI:
Water Service Restored:
yes
Initial Test By:
Ivan Harper
License Number:
19651
Initial Test Date:
9/10/2019 3:08:27 PM
Repaired By:
Repaired Data:
Final Test By:
Final Test Date:
Fail/Pass:
Pass
Inspection Comments
Asset Information
Facility ID:
CW-CV00046
Location:
FHM 4
Address:
515 N 5 W
Valve Type:
Double Check
Diameter:
2.00
Manufacturer:
Wllklns
Model 9:
950 XLT
Serial# :
1816321
Observation: Headwaters construction, Donald Thorpe, phone number 208-313-9210, 480 S. 12th W.
The gasket has been over tightened and ruined and the first primary screen seems to been hit by
a rock or something.
1 of 2 Print Date: 9/10/2019