HomeMy WebLinkAboutINSPECTION REPORT - 19-00520 - HEADWATERS CONSTRUCTION, FHM #4CITY OF REXBURG ry Ammm1 Famdy Community Public Works Water Department 35 North I- East Rexburg, ID 83440 (208)359-3020 Inspection: #39412 WTR-Backflow Test (DC) Inspected By: Harper, Ivan Priority: .. Status: CLOSED Inspection Date: 09/10/2019 Inspection Details Initiated By: Harper, Ivan 9/10/19 2:38 pm Inspected By: Harper, Ivan 9/10/19 3:15 pm Closed By: Harper, Ivan 9/10/19 3:15 pm Location: FHM 4 tion Observations Line Pressure at Time of Test (lbs.): 80 1st Check - PSI: 2,9 1st Check - Leaked: 515 N 5 W 2nd Check - PSI: 2.6 2nd Check - Leaked: 2.00 Air Gap Inspection (Required minimum air Wllklns gap separation provided): 950 XLT Were repairs made?: No Repairs Needed What was the repair: What Materials were used for the repair: 1st Check - PSI: 2nd Check - PSI: Water Service Restored: yes Initial Test By: Ivan Harper License Number: 19651 Initial Test Date: 9/10/2019 3:08:27 PM Repaired By: Repaired Data: Final Test By: Final Test Date: Fail/Pass: Pass Inspection Comments Asset Information Facility ID: CW-CV00046 Location: FHM 4 Address: 515 N 5 W Valve Type: Double Check Diameter: 2.00 Manufacturer: Wllklns Model 9: 950 XLT Serial# : 1816321 Observation: Headwaters construction, Donald Thorpe, phone number 208-313-9210, 480 S. 12th W. The gasket has been over tightened and ruined and the first primary screen seems to been hit by a rock or something. 1 of 2 Print Date: 9/10/2019