HomeMy WebLinkAboutPLANS - 21-00002 - BYUI Hart Building - Phase 3 RemodelVICINITY MAP
DRAWING INDEX
SITE MAP
SCALE: A1 DETAIL
XXX
2
XX
X
XX.XX
ROOM
NUM
NAME
SYMBOLS LEGEND
ROOM IDENTIFICATION
NUMBER
DOOR NUMBER
REFERENCE NOTE
GLAZING TYPE
PARTITON WALL TYPE
INTERIOR ELEVATION
WALL SECTION
EXTERIOR ELEVATION
DETAIL
REVISION DELTA
ROOM NUMBER
ELEVATION
NUMBER
SHEET NUMBER
ELEVATION
NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
REVISION NUMBER
BUILDING SECTION
DETAIL TITLE
ROOM NAME
SHADE INDICATES
ELEVATED WALLA1
A2A4
A3
AFF
CMU
EIFS
ABOVE FINISH FLOOR
CONCRETE MASONRY UNIT
EXTERIOR INSULATED FINISH
EQ EQUAL
MAX MAXIMUM
MIN MINIMUM
NIC NOT IN CONTRACT
O.C. ON CENTER
SPEC SPECIFICATION
SIM SIMILAR
TYP TYPICAL
T.O. TOP OF
B.O. BOTTOM OF
ABBREVIATIONS
RCP REFLECTED CEILING PLAN
DEMO DEMOLITION
EXTG. EXISTING
EQUIP. EQUIPMENT
RMS ROOMS
MEP MECHANICAL, ELECTRICAL &
PLUMBING
STRU. STRUCTURAL
HT. HEIGHT
WD. WIDTH
FIN. FINISH
CLG. CEILING
MATERIAL LEGEND
CONCRETE
STUD WALL
GRAVEL
COMPACTED FILL
AND/OR EARTH
BATT INSULATION
RIGID INSULATION
CMU (CONCRETE MASONRY UNIT)
GYPSUM BOARD OR
CONCRETE
SURFACE
PROJECT NUMBER:
PROJECT ARCHITECT
www.ffkr.com
www.ffkr.com
www.ffkr.com
www.ffkr.com
FFKR ARCHITECTS
730 PACIFIC AVE.
SALT LAKE CITY, UT 84104
801-512-6186
TBSE INC
233 N 1250 W #201
CENTERVILLE, UT 84014
801-298-8795
HEATH ENGINEERING
377 W 800 N,
SALT LAKE CITY, UT 84103
801-322-0487
PAYNE ENGINEERING
1823 E CENTER ST.
POCATELLO, ID 83201
208-232-4439
STRUCTUAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
JOHN W. HART BUILDING PHASE 3 REMODEL
CONSTRUCTION DOCUMENTS - PERMIT SET
11/23/2020
JOHN W. HART BUILDING PHASE 3 REMODEL20054
PROJECT TEAM
SHEET NO.SHEET NAME
GENERAL INFORMATION
G000 COVER
G001 LEVEL 1 (71'-0") LIFE SAVETY PLAN AND CODE ANALYSIS
G002 LEVEL 2 (91'-0") LIFE SAFETY PLAN
G003 LEVEL 3 LIFE SAFETY PLAN
G004 MAIN GYM SEATING - SMALL USE
G005 MAIN GYM SEATING CAPACITY - MID USE
G006 MAIN GYM SEATING CAPACITY - MAX USE
G006A MAIN GYM SEATING CAPACITY - MAX USE (BASKETBALL EVENT)
ARCHITECTURAL
AD101 OVERALL LEVEL 1 (71'-0") DEMO PLAN
AD101A LEVEL 1 (71'-0") AREA DEMO PLANS
AD102 OVERALL LEVEL 2 (91'-0") DEMO PLAN
AD102A LEVEL 2 (91'-0") AREA DEMO PLANS
AD111 OVERALL LEVEL 1 (71'-0") DEMO REFLECTED CEILING PLAN
AD111A LEVEL 1 AREA DEMO REFLECTED CEILING PLAN
AD112 OVERALL LEVEL 2 (91'-0") DEMO REFLECTED CEILING PLAN
AD112A LEVEL 2 (91'-0") AREA DEMO REFLECTED CEILING PLANS
AD112B LEVEL 2 (91'-0") MAIN GYM DEMO REFLECTED CEILING PLAN
AD410 LEVEL 1 (71'-0") DEMO PLANS - ALTERNATE
AE100 LEVEL 1 (71'-0") & LEVEL 2 (91'-0") SLAB PLANS
AE101 OVERALL LEVEL 1 (71'-0") FLOOR PLAN
AE101A LEVEL 1 (71'-0") AREA PLANS
AE102 OVERALL LEVEL 2 (91'-0") FLOOR PLAN
AE102A LEVEL 2 (91'-0") AREA PLANS
AE102B LEVEL 2 (91'-0") AREA PLAN
AE103 EXISTING CATWALK FLOOR PLAN
AE104 OVERALL ROOF PLAN
AE104A ROOF AREA PLAN
AE111 OVERALL LEVEL 1 REFLECTED CEILING PLAN
AE111A LEVEL 1 (71'-0") AREA REFLECTED CEILING PLANS
AE112 OVERALL LEVEL 2 (91'-0") REFLECTED CEILING PLAN
AE112A LEVEL 2 (91'-0") REFLECTED CEILING PLANS
AE112B LEVEL 2 REFLECTED CEILING PLAN
AE300 BUILDING SECTION
AE301 BUILDING SECTION
AE302 BUILDING SECTION
AE310 WALL SECTIONS
AE311 WALL SECTIONS
AE400 RESTROOM & SHOWER ROOM FLOOR PLANS
AE401 STAIR PLAN, SECTIONS & DETAILS
AE402 STAIR PLAN, SECTIONS & DETAILS
AE410 CUSTODIAN ROOM 176 (ALTERNATE 1)
AE411 EQUIPMENT ROOM (ALTERNATE 2)
AE413 STEAM ROOM PLAN & ELEVATION (ALTERNATE 3)
AE414 STEAM ROOM PLAN, SECTION & DETAILS (ALTERNATE 3)
AE500 DETAILS
AE501 DETAILS
AE502 DETAILS
AE503 DETAILS
AE504 ROOF DETAILS
AE505 FLOOR TRANSITION DETAILS
AE600 DOOR, WINDOW SCHEDULE & DETAILS
AE610 WALL, CEILING, FLOOR TYPES & FINISH LEGEND
AE700 INTERIOR ELEVATION
AE701 INTERIOR ELEVATION
AE702 INTERIOR ELEVATION
AE703 INTERIOR ELEVATION
AE704 INTERIOR ELEVATION
AE705 INTERIOR ELEVATION
AE706 INTERIOR ELEVATION
AF100 LEVEL 1 & 2 FINISH PLANS
AF101 ENLARGED FINISH PLANS
STRUCTURAL DRAWINGS
SE-001 GENERAL NOTES
SE-002 INSPECTIONS
SE-003 INSPECTIONS
SE-004 SCHEDULES
SE-006 3D RENDERING
SE-111 STAGE FRAMING PLAN
SE-121 LOW ROOF FRAMING PLAN
SE-122 CURTAIN SUPPORTS
SE-201 ENLARGED FRAMNING PLANS
SE-511 FRAMING DETAILS
MECHANICAL DRAWINGS
M-001 MECHANICAL SCHEDULES
M-002 MECHANICAL SCHEDULES
MD101 LEVEL 1 OVERALL MECHANICAL DEMOLITION PLAN
MD101.1 LEVEL 1 MECHANICAL DEMOLITION PLAN
MD102 LEVEL 2 OVERALL MECHANICAL DEMOLITION PLAN
MD102.1 LEVEL 2 AREA 2G MECHANICAL DEMOLITION PLAN
MD102.2. LEVEL 2 AREA 2A MECHANICAL DEMOLITION PLAN
MD102.3 LEVEL 2 AREA 2B MECHANICAL DEMOLITION PLAN
MH101 LEVEL 1 OVERALL MECHANICAL REMODEL PLAN
MH101.1 LEVEL 1 AREA 1G MECHANICAL REMODEL PLAN
MH101.3 LEVEL 1 MECHANICAL PLANS
MH101.4 MAIN LEVEL MECHANICAL PLANS
MH101.5 MECHANICAL REMODEL PLANS-ADD. ALTERNATES
MH102 LEVEL 2 OVERALL MECHANICAL REMODEL PLAN
MH102.1 LEVEL 2 AREA 2G MECHANICAL REMODEL PLAN
MH102.3 LEVEL 2 AREA 2B MECHANICAL REMODEL PLAN
MH102.4 LEVEL 2 AREA 2C MECHANICAL PLANS
MH301 MECHANICAL SECTIONS
MH501 MECHANICAL DETAILS
MH502 MECHANICAL DETAILS
MP501 MECHANICAL PIPING DETAILS
MP601 CHILLED WATER FLOW DIAGRAM
MP602 HEATING WATER FLOW DIAGRAM
MI601 MECHANICAL CONTROL DIAGRAM
MI602 MECHANICAL CONTROL DIAGRAM
MI603 MECHANICAL CONTROL DIAGRAM
PLUMBING DRAWINGS
P-001 PLUMBING SCHEDULES
PD101 LEVEL 1 OVERALL PLUMBING DEMOLITION PLAN
PD102 LEVEL 2 OVERALL PLUMBING DEMO PLAN
PD401 ENLARGED PLUMBING DEMOLITION PLANS
PD402 ENLARGED PLUMBING DEMOLITION PLANS
PD403 ENLARGED PLUMBING DEMOLITION PLANS
PL101 LEVEL 1 OVERALL PLUMBING REMODEL PLAN
PL102 LEVEL 2 OVERALL PLUMBING REMODEL PLAN
PL401 ENLARGED PLUMBING REMODEL PLANS
PL402 ENLARGED PLUMBING REMODEL PLANS
PL403 ENLARGED PLUMBING REMODEL PLANS
PL404 ENLARGED PLUMBING REMODEL PLANS
PL501 PLUMBING DETAILS
PL601 DOMESTIC WATER FLOW DIAGRAM
ELECTRICAL DRAWINGS
EG100 ELECTRICAL SYMBOLS & DETAILS
EG101 FIRST LEVEL OVERALL PLANS
EG102 SECOND LEVEL OVERALL PLANS
EG200 ELECTRICAL DETAILS & SCHEDULES
EG201 ELECTRICAL ELEVATIONS
ED100 LOWER LEVEL EXISTING ELECTRICAL
ED101 UPPER LEVEL EXISTING ELECTRICAL
ED102 MAIN GYM EXISTING ELECTRICAL
EE100 ACTIVITY STORAGE, WELLNESS CENTER & RESTROOMS ELECTRICAL PLAN
EE101 SPINNING ROOM, ACTIVITY STORAGE & NORTH HALL
EE102 MEN'S & WOMEN'S LOCKER ROOMS ELECTRICAL PLANS
EE103 SOUTHEAST & SOUTHWEST EXITS
EE104 MAIN GYM ELECTRICAL PLAN
EE105 HAVC UPGRADE
EE106 BARBIZON DRAWINGS - FOR REFERENCE ONLY
EE107 BARBIZON DRAWINGS - FOR REFERENCE ONLY
FIRE SPRINKLER
FP101 FIRE PROTECTION PLAN LEVEL 1
FP102 FIRE PROTECTION PLAN LEVEL 2
CLASSROOM
1564 SF/20=78 OCC
STUDIO / CLRM.
943 SF/20=47 OCC
CLASSROOM
662 SF/20=33 OCC
CLASSROOM
649 SF/20=22.5 OCC
CLASSROOM
495 SF/20=24.5 OCC
PHY. COND. CLRM.
640 SF/20=32 OCC
EXERCISE PHYS. CLRM
1937 SF/20=96.8 OCC
STO,
47 SF/300=0.1 OCC
MECH.
533 SF/300=1.8 OCC
MECH.
179 SF/300=0.6 OCC
ELEC.
264 SF/300=0.9 OCC
STO,
193 SF/300=0.6 OCC
STO,
831 SF/300=2.8 OCC
TELECOM. RM.
151 SF/300=0.5 OCC STO,
75 SF/300=0.3 OCC
STO,
69 SF/300=0.2 OCC
STO,
108 SF/300=0.4 OCC
STO,
428 SF/300=1.4 OCC
EQUIP. STO.
1272 SF/300=4.2 OCC
STO,
32 SF/300=0.1 OCC
ELEV. EQP.
53 SF/300=0.2 OCC
ELEC./MECH.
119 SF/300=0.4 OCC
J/C
33 SF/300=0.1 OCC
ACT. STO.
688 SF/300=2.3 OCC
J/C
195 SF/300=0.7 OCC
LAUNDRY RM.
333 SF/100=3.3 OCC
FITNESS CTR
20927 SF/50=418 OCC
SPINNING RM.
696 SF/50=13.9 OCC
PRACTICE ROOM
831 SF/50=16.2 OCC
RQBL. CT. 1
633 SF/50=12.6 OCC
RQBL. CT. 2
633 SF/50=12.6 OCC RQBL. CT. 3
633 SF/50=12.6 OCC
RQBL. CT. 4
633 SF/50=12.6 OCC RQBL. CT. 5
633 SF/50=12.6 OCC
NEW WELLNESS CTR.
895 SF/100=9 OCC
ELEV. EQP.
33 SF/300=0.1 OCC
WELLNESS CTR
1674 SF/100=16.7 OCC
STO,
85 SF/300=0.3 OCC
STO,
160 SF/300=0.5 OCC
ACT. STO.
639 SF/300=2.1 OCC
MECH.
265 SF/300=0.7 OCC
POOL SERVICE
1159 SF/300=3.8 OCC
STO,
64 SF/300=0.2 OCC
STO,
78 SF/300=0.3 OCC
STO,
2477 SF/300=8.3 OCC
STO,
625 SF/300=2.1 OCC
J/C
311 SF/300=1 OCC
EQUIP. REPAIR
213 SF/300=0.7 OCC
46' to common path of travel
175' to exit stair
120' to exit stair90' to exit 89' to exit 106' to exit 181' to exit
6 3 ' to e x it 145' to exit stair
62' to common path of travel100' to exit 212 OCC.
42" REQ'D
72" PRVVD
180 OCC.
42" REQ'D
72" PRVVD
212 OCC.
42" REQ'D
72" PRVVD
700 OCC.
140" REQ'D
216" PRVVD
360 OCC.
FROM LEVEL 2
320 OCC.
FROM LEVEL 2
300 OCC.
60" REQ'D
108" PRVVD
51 OCC.
10" REQ'D
72" PRVVD
96 OCC.
19" REQ'D
36" PRVVD
160 OCC.
FROM LEVEL 2
Applicable Codes
Code Year
International Building Code (IBC)2015
International Mechanical Code (IMC)2015
International Fire Code (IFC)2015
International Energy Conservation Code (IECC) 2015
National Electrical Code (NEC)2017
ADA Accessibility Guidelines 2010
International Plumbing Code (IPC)2017
International Building Code (IBC) Analysis
Construction Type I-B Sect. 602
Building Occupancies A-3 Sect. 303.4
Design Building Area (Existing) 170,633 Sf
Allowed Building Area Unlimited Sf Sect. 506.1 Per Equation 5-1
Allowed Building Height (Ft) 180 Ft Sect. 504.3
Allowed Building Height (Stories) 12 Stories Sect. 504.4
Building Square Footage
Level 1 74,030 Sf
Level 2 91,175 Sf
Level 3 5,256 Sf
Fire Resistance Ratings for Building Elements - Hours (Table 601 - Substitution 903.2)
Building Element Tabular Notes Substituted
Primary Structural Frame (See Section 202) 2 A 2
Bearing Walls - Exterior 2 - 2
Bearing Walls - Interior 2 A 2
Nonbearing Walls & Partitions - Exterior See Table 602
Floor Construction (See Section 202) 2 - 2
Roof Construction (See Section 202) 1 B&C 1
Shaft Enclosure Fire Rating 2
Shaft Enclosure Fire Rating - Hours (Section 708.4)
Catwalks 172 Sf
Total 170,633 Sf
Nonbearing Walls & Partitions - Interior 0 - 0
International Existing Building Code (IEBC)2015
Design Building Height (Ft) 56 Ft
Design Building Height (Stories) 3 Stories
Building Occupancy & Construction Type
Occupancy of Building Single Separated Occupancies - Table 508.4
Most Restrictive Occ. A-3 Construction Type 1-B Chapter 6
No. of Occ.
@ Level
No. of Occ. from
Level Above
Total Occ.
Combined
No. of Occ. Exit
at Level (1)
No. of Occ. Exit
to Level Below (2)
Level 1 911 1,040 1,883 1,883 N/A
Occupant Count Analysis
Level 2 4,718 572 5,290 4,250 1040
Level 3 572 0 572 0 572
Total 6,201
Stair Width ( Section 1005.3.1)
No. of Occ. Exit
to Level Below (2)
Factor in
Inches
Required in
Inches
Provided in
Inches
Level 2 1,040 0.3 312 312
Level 1 N/A N/A N/A N/A
Level 3 572 0.3 176 192
Exit Width ( Section 1005.3.2)
No. of Occ. Exit
at Level (1)
Factor in
Inches
Required in
Inches
Provided in
Inches
Level 2 4,250 0.2 850 1,008
Level 1 1,883 0.2 376 612
Level 3 572 N/A N/A N/A2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:52:44 AMG001
LEVEL 1
(71'-0") LIFE
SAVETY
PLAN AND
CODE
ANALYSISJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 LEVEL 1 (71'-0") LIFE SAFETY PLAN
OCCUPANCY AREA CALCULATIONS
ROOM OCCUPANCY TYPE AREA LOAD FACTOR OCCUPANTS
LEVEL 2
ACTIVITIES SPACE ASSEMBLY 3708 SF 50 GROSS 74.1
CLOSET ACCESSORY 42 SF 300 GROSS 0.1
DANCE OFFICE BUSINESS 515 SF 100 GROSS 5.2
DANCE STUDIO 1 ASSEMBLY 1707 SF 50 GROSS 34.1
DANCE STUDIO 2 ASSEMBLY 1741 SF 50 GROSS 34.8
DRESSING ASSEMBLY 136 SF 50 GROSS 2.7
ELEC. ACCESSORY 105 SF 300 GROSS 0.4
EQP. ISSUE ACCESSORY 1484 SF 300 GROSS 4.9
EQP. ISSUE ACCESSORY 1171 SF 300 GROSS 3.9
FAC. OFFICE BUSINESS 270 SF 100 GROSS 2.7
FITNESS STUDIO ASSEMBLY 1670 SF 50 GROSS 33.4
GYM-BLEACHER SEATS ASSEMBLY 2291 SF 18 INCH 765
GYM-BLEACHER SEATS ASSEMBLY 2711 SF 18 INCH 777
GYM-BLEACHER SEATS ASSEMBLY 564 SF 18 INCH 164
GYM-BLEACHER SEATS ASSEMBLY 561 SF 18 INCH 163
GYM-FIXED SEATS ASSEMBLY 6181 SF 0 NET 1380
GYM-FLOOR ASSEMBLY 5046 SF 7 NET 720
J/C ACCESSORY 56 SF 300 GROSS 0.2
LAUNDRY RM. BUSINESS 216 SF 100 GROSS 2.2
MECH. ACCESSORY 32 SF 300 GROSS 0.1
MEN'S LOCKER RM. ASSEMBLY 2058 SF 50 GROSS 41
NORTH FOYER ASSEMBLY 1530 SF 15 GROSS 102
OFFICE BUSINESS 205 SF 100 GROSS 2
OFFICE BUSINESS 206 SF 100 GROSS 2
OFFICE BUSINESS 314 SF 100 GROSS 3.1
OFFICE BUSINESS 371 SF 100 GROSS 3.7
OFFICE BUSINESS 744 SF 100 GROSS 7.4
OFFICE BUSINESS 133 SF 100 GROSS 1.3
OFFICE BUSINESS 321 SF 100 GROSS 3.2
OFFICE BUSINESS 150 SF 100 GROSS 1.5
OFFICE BUSINESS 150 SF 100 GROSS 1.5
OFFICE BUSINESS 87 SF 100 GROSS 0.9
STAGE ASSEMBLY 1744 SF 15 NET 129.7
STO. ACCESSORY 214 SF 300 GROSS 0.7
STO. ACCESSORY 710 SF 300 GROSS 2.4
STO. ACCESSORY 234 SF 300 GROSS 1
STO. ACCESSORY 90 SF 300 GROSS 0.3
STO. ACCESSORY 131 SF 300 GROSS 0.4
STO. ACCESSORY 432 SF 300 GROSS 1.7
SWIMMING POOL ASSEMBLY 3210 SF 50 GROSS 64.2
SWIMMING POOL DECK ASSEMBLY 1843 SF 15 GROSS 123
TELECOM. RM. ACCESSORY 79 SF 300 GROSS 0.3
WOMEN'S LOCKER RM. ASSEMBLY 1570 SF 50 GROSS 31.4
WRESTLING ROOM ASSEMBLY 1205 SF 50 GROSS 24.1
LEVEL 3
BDF. ACCESSORY 80 SF 300 GROSS 0.3
BOX SEATS BUSINESS 373 SF 100 GROSS 3.7
DRESSING RM. ASSEMBLY 209 SF 50 GROSS 4.2
DRESSING RM. ASSEMBLY 368 SF 50 GROSS 7.4
M.B. BUSINESS 182 SF 100 GROSS 1.8
MECH. ACCESSORY 9059 SF 300 GROSS 30.2
POOL-BLEACHER SEATS ASSEMBLY 813 SF 18 INCH 230
POOL-BLEACHER SEATS ACCESSORY 557 SF 18 INCH 134
POOL-BLEACHER SEATS ACCESSORY 596 SF 18 INCH 146
SOUND/LIGHT CONTROL BUSINESS 433 SF 100 GROSS 4.3
SPOTLIGHT PLATFORM BUSINESS 68 SF 100 GROSS 0.7
SPOTLIGHT PLATFORM BUSINESS 66 SF 100 GROSS 0.7
STOR. ACCESSORY 2187 SF 300 GROSS 7.3
STOR. ACCESSORY 649 SF 300 GROSS 2.2
TOTAL OCCUPANTS 6201
OCCUPANCY AREA CALCULATIONS
ROOM OCCUPANCY TYPE AREA LOAD FACTOR OCCUPANTS
LEVEL 1
ACT. STO. ACCESSORY 688 SF 300 GROSS 2.3
ACT. STO. ACCESSORY 639 SF 300 GROSS 2.1
CLASSROOM EDUCATIONAL 1564 SF 20 NET 78
CLASSROOM EDUCATIONAL 662 SF 20 NET 33
CLASSROOM EDUCATIONAL 649 SF 20 NET 22.5
CLASSROOM EDUCATIONAL 495 SF 20 NET 24.5
ELEC. ACCESSORY 264 SF 300 GROSS 0.9
ELEC./MECH. ACCESSORY 119 SF 300 GROSS 0.4
ELEV. EQP. ACCESSORY 53 SF 300 GROSS 0.2
ELEV. EQP. ACCESSORY 33 SF 300 GROSS 0.1
EQUIP. REPAIR ACCESSORY 213 SF 300 GROSS 0.7
EQUIP. STO. ACCESSORY 1272 SF 300 GROSS 4.2
EXERCISE PHYS. CLRM EDUCATIONAL 1937 SF 20 NET 96.8
FITNESS CTR ASSEMBLY 20927 SF 50 GROSS 418
J/C ACCESSORY 33 SF 300 GROSS 0.1
J/C ACCESSORY 195 SF 300 GROSS 0.7
J/C ACCESSORY 311 SF 300 GROSS 1
LAUNDRY RM. BUSINESS 333 SF 100 GROSS 3.3
MECH. ACCESSORY 533 SF 300 GROSS 1.8
MECH. ACCESSORY 179 SF 300 GROSS 0.6
MECH. ACCESSORY 265 SF 300 GROSS 0.7
NEW WELLNESS CTR. BUSINESS 895 SF 100 GROSS 9
PHY. COND. CLRM. EDUCATIONAL 640 SF 20 NET 32
POOL SERVICE ACCESSORY 1159 SF 300 GROSS 3.8
PRACTICE ROOM ASSEMBLY 831 SF 50 GROSS 16.2
RQBL. CT. 1 ASSEMBLY 633 SF 50 GROSS 12.6
RQBL. CT. 2 ASSEMBLY 633 SF 50 GROSS 12.6
RQBL. CT. 3 ASSEMBLY 633 SF 50 GROSS 12.6
RQBL. CT. 4 ASSEMBLY 633 SF 50 GROSS 12.6
RQBL. CT. 5 ASSEMBLY 633 SF 50 GROSS 12.6
SPINNING RM. ASSEMBLY 696 SF 50 GROSS 13.9
STO, ACCESSORY 47 SF 300 GROSS 0.1
STO, ACCESSORY 193 SF 300 GROSS 0.6
STO, ACCESSORY 831 SF 300 GROSS 2.8
STO, ACCESSORY 75 SF 300 GROSS 0.3
STO, ACCESSORY 69 SF 300 GROSS 0.2
STO, ACCESSORY 108 SF 300 GROSS 0.4
STO, ACCESSORY 428 SF 300 GROSS 1.4
STO, ACCESSORY 32 SF 300 GROSS 0.1
STO, ACCESSORY 85 SF 300 GROSS 0.3
STO, ACCESSORY 160 SF 300 GROSS 0.5
STO, ACCESSORY 64 SF 300 GROSS 0.2
STO, ACCESSORY 78 SF 300 GROSS 0.3
STO, ACCESSORY 2477 SF 300 GROSS 8.3
STO, ACCESSORY 625 SF 300 GROSS 2.1
STUDIO / CLRM. EDUCATIONAL 943 SF 20 NET 47
TELECOM. RM. ACCESSORY 151 SF 300 GROSS 0.5
WELLNESS CTR BUSINESS 1674 SF 100 GROSS 16.7
DN
DN
DN
BLEACHER SEATS: 2,975 OCC.
TOTAL: 3,695 OCC. OFFICE
205 SF/100=2 OCC
OFFICE
206 SF/100=2 OCC
OFFICE
314 SF/100=3.1 OCC
OFFICE
371 SF/100=3.7 OCC
OFFICE
744 SF/100=7.4 OCC
OFFICE
133 SF/100=1.3 OCC
LAUNDRY RM.
216 SF/100=2.2 OCC
FAC. OFFICE
270 SF/100=2.7 OCC
OFFICE
321 SF/100=3.2 OCC
DANCE OFFICE
515 SF/100=5.2 OCC
OFFICE
150 SF/100=1.5 OCC
OFFICE
150 SF/100=1.5 OCC
OFFICE
87 SF/100=0.9 OCC
DRESSING
136 SF/50=2.7 OCC
STO.
214 SF/300=0.7 OCC
J/C
56 SF/300=0.2 OCCCLOSET
42 SF/300=0.1 OCC
STO.
710 SF/300=2.4 OCC
WRESTLING ROOM
1205 SF/50=24.1 OCC
DANCE STUDIO 2
1741 SF/50=34.8 OCC
DANCE STUDIO 1
1707 SF/50=34.1 OCC
ACTIVITIES SPACE
3708 SF/50=74.1 OCC
FITNESS STUDIO
1670 SF/50=33.4 OCC
STO.
234 SF/300=1 OCC
TELECOM. RM.
79 SF/300=0.3 OCC
EQP. ISSUE
1484 SF/300=4.9 OCC
EQP. ISSUE
1171 SF/300=3.9 OCC
MEN'S LOCKER RM.
2058 SF/50=41 OCC
WOMEN'S LOCKER RM.
1570 SF/50=31.4 OCC
SWIMMING POOL
3210 SF/50=64.2 OCC
SWIMMING POOL DECK
1843 SF/15=123 OCC
STO.
90 SF/300=0.3 OCC
5' - 0"
NORTH FOYER
1530 SF/15=102 OCC
STAGE
1744 SF/15=129.7 OCC
STAIR
2-OMEN'S
128A
WOMEN'S
128B
ELEC.
105 SF/300=0.4 OCC
MECH.
32 SF/300=0.1 OCC
STO.
131 SF/300=0.4 OCC
STO.
432 SF/300=1.7 OCC
GYM-FLOOR
5046 SF/7=720 OCC
117' to exit127' to exit stair1
2
0' to e
xit130' to exit235' to exit210' to exitGYM-FIXED SEATS
6181 SF/0=1380 OCC
GYM-BLEACHER SEATS
2711 SF/18=777 OCC
GYM-BLEACHER SEATS
2291 SF/18=765 OCC
GYM-BLEACHER SEATS
561 SF/18=163 OCC
GYM-BLEACHER SEATS
564 SF/18=164 OCC
360 OCC.
72" REQ'D
72" PRVVD
AT 81'-0"
1,080 OCC.
216" REQ'D
216" PRVVD
72 OCC.
14" REQ'D
72" PRVVD
72 OCC.
14" REQ'D
72" PRVVD
200 OCC.
60" REQ'D
60" PRVVD
320 OCC.
96" REQ'D
96" PRVVD
160 OCC.
48" REQ'D
96" PRVVD
1,260 OCC.
252" REQ'D
252" PRVVD
1,080 OCC.
216" REQ'D
216" PRVVD
34 OCC.
9" REQ'D
36" PRVVD
360 OCC.
72" REQ'D
72" PRVVD
360 OCC.
108" REQ'D
108" PRVVD
43 OCC. FROM
LEVEL 3
240 OCC.
FROM LEVEL 3
240 OCC.
FROM LEVEL 32"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:52:56 AMG002
LEVEL 2
(91'-0") LIFE
SAFETY
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 LEVEL 2 (91'-0") LIFE SAFETY PLAN
DN
DN
UPPER AUXILIARY GYMNASIUM
UPPER SWIMMING POOL
UPPER STAGE
UPPER MAIN GYMNASIUM
UPPER FOYER
MECH.
9059 SF/300=30.2 OCC
BOX SEATS
373 SF/100=3.7 OCC
M.B.
182 SF/100=1.8 OCC
BDF.
80 SF/300=0.3 OCC
STOR.
2187 SF/300=7.3 OCC
BLEACHER SEATS: 210 OCC.
BLEACHER SEATS: 130 OCC.BLEACHER SEATS: 140 OCC.
SPOTLIGHT PLATFORM
68 SF/100=0.7 OCC
SPOTLIGHT PLATFORM
66 SF/100=0.7 OCC
SOUND/LIGHT CONTROL
433 SF/100=4.3 OCC
DRESSING RM.
209 SF/50=4.2 OCC
DRESSING RM.
368 SF/50=7.4 OCC
STOR.
649 SF/300=2.2 OCC
240' to exit245' to exit
240 OCC.
72" REQ'D
72" PRVVD
240 OCC.
72" REQ'D
72" PRVVD
43 OCC.
13" REQ'D
48" PRVVD2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:53:07 AMG003
LEVEL 3
LIFE
SAFETY
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A2 LEVEL 3 LIFE SAFETY PLAN
DN
SECTIONS: FLOOR, F, G, R, S
TOTAL: 1,036 1
2
3
SEATING CAPACITY
CONFIGURATIONS
3A
SMALL USE
MID USE
MAX USE
OPTION 1:
THEATRICAL
FLOOR (Removable seats):
LEFT 180
CENTER 312
RIGHT 180
ADA + COMP. 16 (Included)
TOTAL:672
LOWER BOWL (Fixed seats):
A 90
B 130
C 135
D 135
E 81
F 140
G 140
H 83
I 135
J 135
K 130
L 90
ADA + COMP. 14
TOTAL: 1,438
INDIVIDUAL SECTION CAPACITY:
MAX USE
OPTION 2:
BASKETBALL
SECTIONS: FLOOR, LOWER BOWL, R, R1, S, S1
TOTAL: 2,437
SECTIONS: FLOOR, LOWER & UPPER BOWLS
TOTAL: 3,979
SECTIONS: FLOOR 1, LOWER & UPPER BOWLS
TOTAL: 3,421
FLOOR 1 (Removable seats):
COURT SIDE L 41
COURT SIDE R 65
ADA + COMP. 8
TOTAL:114
UPPER BOWL (Marked seats):
M 224
N 119
O 96
P 189
Q 137
R 42
R1 121
S 42
S1 122
T 137
U 187
V 123
W 110
X 220
TOTAL: 1,869
FLOOR
LEFT
CENTER
RIGHT
ADA + COMP.
TOTAL:
FLOOR 1
COURT SIDE L
COURT SIDE R
ADA + COMP.
TOTAL:
LOWER BOWL
A
B
C
D
E
F
G
H
I
J
K
L
ADA + COMP.
TOTAL:
UPPER BOWL
M
N
O
P
Q
R
R1
S
S1
T
U
V
W
X
TOTAL: 1,869
LEFT
180
RIGHT
180
CENTER
312
F
140
G
140
R
42
S
42
MAIN GYM
250A
336 OCC.
67" REQ'D
72" PRVVD
336 OCC.
67" REQ'D
72" PRVVD
140 OCC.
42" REQ'D
96" PRVVD
224 OCC.
67" REQ'D
288" PRVVD2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:53:10 AMG004
MAIN GYM
SEATING -
SMALL USEJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 MAIN GYM SEATING CAPACITY - SMALL USE
LEFT
180
RIGHT
180
CENTER
312
A
90
B
130
C
135
D
135
E
81
F
140
H
83
G
140
L
90
K
130
J
135
I
135
R
42
S
42
MAIN GYM
250A
R1
121
S1
122
336 OCC.
67" REQ'D
72" PRVVD
336 OCC.
67" REQ'D
72" PRVVD
140 OCC.
42" REQ'D
96" PRVVD
100 OCC.
20" REQ'D
288" PRVVD
216" PRVVD
286 OCC.
57" REQ'D
96" PRVVD
285 OCC.
57" REQ'D
96" PRVVD
285 OCC.
57" REQ'D
60" PRVVD
287 OCC.
57" REQ'D
60" PRVVD
100 OCC.
20" REQ'D
60" PRVVD
100 OCC.
20" REQ'D
60" PRVVD
216" PRVVD
100 OCC.
20" REQ'D
60" PRVVD
100 OCC.
20" REQ'D
60" PRVVD
SECTIONS: FLOOR, F, G, R, S
TOTAL: 1,036 1
2
3
SEATING CAPACITY
CONFIGURATIONS
3A
SMALL USE
MID USE
MAX USE
OPTION 1:
THEATRICAL
FLOOR (Removable seats):
LEFT 180
CENTER 312
RIGHT 180
ADA + COMP. 16 (Included)
TOTAL:672
LOWER BOWL (Fixed seats):
A 90
B 130
C 135
D 135
E 81
F 140
G 140
H 83
I 135
J 135
K 130
L 90
ADA + COMP. 14
TOTAL: 1,438
INDIVIDUAL SECTION CAPACITY:
MAX USE
OPTION 2:
BASKETBALL
SECTIONS: FLOOR, LOWER BOWL, R, R1, S, S1
TOTAL: 2,437
SECTIONS: FLOOR, LOWER & UPPER BOWLS
TOTAL: 3,979
SECTIONS: FLOOR 1, LOWER & UPPER BOWLS
TOTAL: 3,421
FLOOR 1 (Removable seats):
COURT SIDE L 41
COURT SIDE R 65
ADA + COMP. 8
TOTAL:114
UPPER BOWL (Marked seats):
M 224
N 119
O 96
P 189
Q 137
R 42
R1 121
S 42
S1 122
T 137
U 187
V 123
W 110
X 220
TOTAL: 1,869
FLOOR
LEFT
CENTER
RIGHT
ADA + COMP.
TOTAL:
FLOOR 1
COURT SIDE L
COURT SIDE R
ADA + COMP.
TOTAL:
LOWER BOWL
A
B
C
D
E
F
G
H
I
J
K
L
ADA + COMP.
TOTAL:
UPPER BOWL
M
N
O
P
Q
R
R1
S
S1
T
U
V
W
X
TOTAL: 1,8692"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:53:14 AMG005
MAIN GYM
SEATING
CAPACITY -
MID USEJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 MAIN GYM SEATING CAPACITY - MID USE
LEFT
180
RIGHT
180
CENTER
312
A
90
B
130
C
135
D
135
E
81
F
140
H
83
G
140
L
90
K
130
J
135
I
135
M
224
N
119
O
96
P
189
Q
137
X
220
W
110
V
123
U
187
T
137
R
42
S
42
MAIN GYM
250A
R1
121
S1
122
18' - 8"
336 OCC.
67" REQ'D
72" PRVVD
336 OCC.
67" REQ'D
72" PRVVD
280 OCC.
56" REQ'D
96" PRVVD
895 OCC.
179" REQ'D
288" PRVVD
216" PRVVD
480 OCC.
96" REQ'D
96" PRVVD
480 OCC.
96" REQ'D
96" PRVVD
285 OCC.
57" REQ'D
60" PRVVD
287 OCC.
57" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
216" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
SECTIONS: FLOOR, F, G, R, S
TOTAL: 1,036 1
2
3
SEATING CAPACITY
CONFIGURATIONS
3A
SMALL USE
MID USE
MAX USE
OPTION 1:
THEATRICAL
FLOOR (Removable seats):
LEFT 180
CENTER 312
RIGHT 180
ADA + COMP. 16 (Included)
TOTAL:672
LOWER BOWL (Fixed seats):
A 90
B 130
C 135
D 135
E 81
F 140
G 140
H 83
I 135
J 135
K 130
L 90
ADA + COMP. 14
TOTAL: 1,438
INDIVIDUAL SECTION CAPACITY:
MAX USE
OPTION 2:
BASKETBALL
SECTIONS: FLOOR, LOWER BOWL, R, R1, S, S1
TOTAL: 2,437
SECTIONS: FLOOR, LOWER & UPPER BOWLS
TOTAL: 3,979
SECTIONS: FLOOR 1, LOWER & UPPER BOWLS
TOTAL: 3,421
FLOOR 1 (Removable seats):
COURT SIDE L 41
COURT SIDE R 65
ADA + COMP. 8
TOTAL:114
UPPER BOWL (Marked seats):
M 224
N 119
O 96
P 189
Q 137
R 42
R1 121
S 42
S1 122
T 137
U 187
V 123
W 110
X 220
TOTAL: 1,869
FLOOR
LEFT
CENTER
RIGHT
ADA + COMP.
TOTAL:
FLOOR 1
COURT SIDE L
COURT SIDE R
ADA + COMP.
TOTAL:
LOWER BOWL
A
B
C
D
E
F
G
H
I
J
K
L
ADA + COMP.
TOTAL:
UPPER BOWL
M
N
O
P
Q
R
R1
S
S1
T
U
V
W
X
TOTAL: 1,8692"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:53:17 AMG006
MAIN GYM
SEATING
CAPACITY
- MAX USEJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 MAIN GYM SEATING CAPACITY - MAX USE OPTION 1 - THEATRICAL
A
90
B
130
C
135
D
135
E
81
F
140
H
83
G
140
L
90
K
130
J
135
I
135
M
224
N
119
O
96
P
189
Q
137
X
220
W
110
V
123
U
187
T
137
R
42
S
42
MAIN GYM
250A
R1
121
S1
122
LEFT
41
RIGHT
65
SCORER'S TABLETEAM BENCH AREATEAM BENCH AREABASKETBAL COURT
236 OCC.
47" REQ'D
72" PRVVD
236 OCC.
47" REQ'D
72" PRVVD
180 OCC.
36" REQ'D
96" PRVVD
895 OCC.
179" REQ'D
288" PRVVD
216" PRVVD
351 OCC.
70" REQ'D
96" PRVVD
351 OCC.
70" REQ'D
96" PRVVD
285 OCC.
57" REQ'D
60" PRVVD
287 OCC.
57" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
216" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
150 OCC.
30" REQ'D
60" PRVVD
SECTIONS: FLOOR, F, G, R, S
TOTAL: 1,036 1
2
3
SEATING CAPACITY
CONFIGURATIONS
3A
SMALL USE
MID USE
MAX USE
OPTION 1:
THEATRICAL
FLOOR (Removable seats):
LEFT 180
CENTER 312
RIGHT 180
ADA + COMP. 16 (Included)
TOTAL:672
LOWER BOWL (Fixed seats):
A 90
B 130
C 135
D 135
E 81
F 140
G 140
H 83
I 135
J 135
K 130
L 90
ADA + COMP. 14
TOTAL: 1,438
INDIVIDUAL SECTION CAPACITY:
MAX USE
OPTION 2:
BASKETBALL
SECTIONS: FLOOR, LOWER BOWL, R, R1, S, S1
TOTAL: 2,437
SECTIONS: FLOOR, LOWER & UPPER BOWLS
TOTAL: 3,979
SECTIONS: FLOOR 1, LOWER & UPPER BOWLS
TOTAL: 3,421
FLOOR 1 (Removable seats):
COURT SIDE L 41
COURT SIDE R 65
ADA + COMP. 8
TOTAL:114
UPPER BOWL (Marked seats):
M 224
N 119
O 96
P 189
Q 137
R 42
R1 121
S 42
S1 122
T 137
U 187
V 123
W 110
X 220
TOTAL: 1,869
FLOOR
LEFT
CENTER
RIGHT
ADA + COMP.
TOTAL:
FLOOR 1
COURT SIDE L
COURT SIDE R
ADA + COMP.
TOTAL:
LOWER BOWL
A
B
C
D
E
F
G
H
I
J
K
L
ADA + COMP.
TOTAL:
UPPER BOWL
M
N
O
P
Q
R
R1
S
S1
T
U
V
W
X
TOTAL: 1,8692"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:53:21 AMG006A
MAIN GYM
SEATING
CAPACITY -
MAX USE
(BASKETBALL
EVENT)JOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 MAIN GYM SEATING CAPACITY - MAX USE OPTION 2 - BASKETBALL
DN
DN
UP
UP
UP
2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
LAUNDRY
RM.
EQP. STOR.
RR.
WOMEN'S
RR.
MEN'S
RR.
AD101A
A3
AD102A
D1
MEN'S DRESSING
RM.
MEN'S FAC.
DRESSING RM.
EQP. STOR.
STOR.
EQP. ISSUE
RM.
VARSITY
DRESSING RM.
TRAINING RM.MECH.
AD101A
E5
CRAWL SPACE
AD410
A5
FITNESS CENTER
ALT. 1 & 2
AD101A
A5
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER FOR RELOCATION
OF ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS. FOR
ACTUAL DEMOLITION BOUNDARY AND SCOPE.
REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO.
AREA OF CONSTRUCTION
LEGEND
SCALE:1/16" = 1'-0"A1 OVERALL LEVEL 1 (71'-0") DEMO PLAN2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:48:08 AMAD101
OVERALL
LEVEL 1
(71'-0")
DEMO
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
D
E
F
G
H
J
K
H1
J1
19 20
F1
G1
C1
18
EQP. STOR.
EQP. STOR.
LAUNDRY RM.
RR.
MEN'S DRESSING RM.
02.1302.13
02.1402.20
WOMEN'S RR.
MEN'S RR.
02.13
02.13
SAUNA
02.14
02.1302.13
02.14
02.14
02.1302.13
02.0202.02
4' - 8"02.21
02.22
9' - 4"
TYP.
02.13
3' - 0"CONSTRUCTION LIMIT LINE02.13
02.14
02.14
14' - 0"
6' - 10 1/2"1' - 10"
ALTERNATE BASE BID
TRAINING ROOMMECH.
VARSITY DRESSING RM.STOR.TO NEAREST STUD3' - 4"21' - 6"6' -10" HT.7' -2" HT.02.05
02.0502.0502.05
02.02
02.02
02.05
02.02
02.02
02.14 02.14
02.19
02.14
02.1302.13
02.14 02.14
02.14
02.22
TYP.CONSTRUCTION LIMIT LINE3' - 0"3' - 4"3' - 0"3' - 1"3' - 0"2' - 8"3' - 0"2' - 8"3' - 0"2' -6" A.F.F.,4' -8" HT.02.1202.12
02.12
02.12
CONSTRUCTION LIMIT LINE02.22
TYP.
02.19
TYP.
02.1202.12
11' - 10"2' - 0"6' - 2"21 22 23
D
E
F
G
H
J
K
L
H1
J1
F1
G1
C1
02.54
02.54
02.54
02.54
17
H
J
H1
02.02
02.05
MEN'S FAC. DRESSING RM.
02.02
TYP.
7' - 2" HT.
6' - 4"
02.13
02.22
02.03
02.22
TYP.
CONCRETE SLAB DEMOLITION
DEMO LEGEND
WALL DEMOLITION
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO. 2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:12 AMAD101A
LEVEL 1
(71'-0")
AREA
DEMO
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 EXTG. EQUIP., LAUNDRY, AND DRESSING DEMO PLANS
SCALE: 1/8" = 1'-0"
A5 FITNESS CENTER DEMO PLAN
SCALE: 1/8" = 1'-0"
E5 EXTG. MEN'S FACULTY DRESSING ROOM DEMO PLAN
1 10/30/20 Addendum #1
02.02 EXISTING WALL TO REMAIN
02.03 EXISTING CONC. COLUMN
02.05 NEW WALL OPENING, REFER. TO HEIGHT & WIDTH
DIM.
02.12 REMOVE EXISTING FLOORING
02.13 REMOVE EXISTING WALL
02.14 REMOVE EXISTING DOOR & HARDWARE, SALVAGE
FOR REUSE, COORDINATE W/ OWNER
02.19 REMOVE EXISTING PLUMBING FIXTURE, SALVAGE
FOR REUSE, COORDINATE W/ OWNER
02.20 REMOVE EXISTING WINDOWS SYSTEM &
HARDWARE, SALVAGE FOR REUSE, COORDINATE W/
OWNER
02.21 REMOVE EXISTING SHELVING SYSTEM, SALVAGE
FOR REUSE, COORDINATE W/ OWNER
02.22 REMOVE EXISTING LOCKERS, SALVAGE FOR REUSE,
COORDINATE W/ OWNER
02.54 REMOVE EXISTING MECH. DUCT, RTU, ETC., RE:
MECH. DWG.
DN
DN
DN
UP
DN
UP
1
1 2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
WOMEN'S LOCKER RM.
MEN'S LOCKER RM.
AD102A
A1
AD102A
A5
AD102A
C5
AD102A
D1
AD102A
D3
MAIN GYM
PLATFORM
STOR.
STAIR
2-I
STAIR
2-F
81' - 0"
91' - 0"
TICKET TICKET
91' - 0"91' - 0"
STAIR
2-X
84' - 4"
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER FOR RELOCATION
OF ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS. FOR
ACTUAL DEMOLITION BOUNDARY AND SCOPE.
REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO.
AREA OF CONSTRUCTION
LEGEND
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 2 (91'-0") DEMO PLAN2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:48:22 AMAD102
OVERALL
LEVEL 2
(91'-0")
DEMO
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
UP
13 14 15 16 17
F
G
H
J
K
L
H1
J1
19 20
F1
G1
18
5' - 7"9' - 0"02.17 02.17
02.1302.13
02.13
02.13 02.14 02.14
02.1302.13
02.16
02.1602.16
02.16 02.16
12' - 8 1/2"12' - 8 1/2"
02.4502.25
02.14
02.45
02.17
10' - 4"10' - 4"
02.1302.13
12' 8 1/2".12' - 8 1/2"
02.16
02.16
02.16
02.1702.17
1
1
' -
5
"
02.66
02.66
02.1602.17 02.16 11' - 11"1 2
B
C
D
E
C1
MEN'S LOCKER ROOM
02.02
02.02
02.14
02.22
TYP.
02.13
02.1302.1302.14
02.13
3' - 6"CONSTRUCTION LIMIT LINE
4' - 0"CONSTRUCTION LIMIT LINE
11' - 6"
02.22
TYP.
4' - 0"1' - 3"
TEMP. CONSTRUCTION ACCESS,
OPENING EXACT LOCATION TO BE
DETERMINED BY CONTRACTOR
02.12
7
B
C
D
C1
WOMEN'S
LOCKER ROOM02.13
02.22
TYP.
02.02
02.02
02.49
02.50
TYP.
TYP.
02.02
02.13
02.14
02.49
TYP.
TEMP. CONSTRUCTION ACCESS,
OPENING EXACT LOCATION TO BE
DETERMINED BY CONTRACTOR
12' - 0"4' - 4"
02.12
21
C
D
19 20
C1
18
02.12
02.17
02.23
15' - 4"
02.14
02.14
02.18
02.16
02.05
1' - 8"
02.05
7' -6" HT.
CONSTRUCTION LIMIT LINE4' - 5"7' - 5"02.14
02.24
02.67
ABOVE
14 15
B
C
D
C1
RR.
81' - 0"
02.12 02.14
02.19
02.17
02.14
24' - 0"4' - 0"7' - 5"2' - 11"02.05
02.13
02.18
02.48
02.47
7' - 2" HT.
6' - 4"3' - 7"
84' - 4"
9' - 4"
4' - 11"
CONSTRUCTION LIMIT LINE
CONSTRUCTION
LIMIT LINE
02.18
02.14
02.14
02.16
91' - 0"3' - 0"8"STORAGE
1B
02.67 ABOVE
CONCRETE SLAB DEMOLITION
DEMO LEGEND
WALL DEMOLITION
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO. 2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:28 AMAD102A
LEVEL 2
(91'-0")
AREA
DEMO
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A1 MAIN GYM NORTH EXIT DEMO PLAN
02.02 EXISTING WALL TO REMAIN
02.05 NEW WALL OPENING, REFER. TO HEIGHT & WIDTH
DIM.
02.12 REMOVE EXISTING FLOORING
02.13 REMOVE EXISTING WALL
02.14 REMOVE EXISTING DOOR & HARDWARE, SALVAGE
FOR REUSE, COORDINATE W/ OWNER
02.16 CUT EXISTING GUARDRAIL TO THE NEAREST POST
02.17 REMOVE EXISTING CONC. STEP/BLEACHER SEATING
02.18 REMOVE EXISTING STAIR
02.19 REMOVE EXISTING PLUMBING FIXTURE, SALVAGE
FOR REUSE, COORDINATE W/ OWNER
02.22 REMOVE EXISTING LOCKERS, SALVAGE FOR REUSE,
COORDINATE W/ OWNER
02.23 REMOVE EXISTING STOREFRONT SYSTEM
02.24
02.25 EXISTING STAIR TO REMAIN
02.45 EXISTING HOLLOW METAL STRUCTURAL COLUMN
TO REMAIN
02.47 REMOVE EXISTING HEATER
02.48 REMOVE EXISTING ELEC. SERVICE BOX
02.49 REMOVE EXISTING TOILET PARTITION
02.50 REMOVE EXISTING SHOWER PARTITION
02.66 REMOVE EXISTING SEATS, PROTECT AND SALVAGE
TO OWNER
02.67 REMOVE EXISTING ORGAN BOX
SCALE: 1/8" = 1'-0"
C5 EXTG. MEN'S LOCKER ROOM DEMO PLAN
SCALE: 1/8" = 1'-0"
A5 EXTG. WOMEN'S LOCKER ROOM DEMO PLAN
SCALE: 1/8" = 1'-0"
D3 MAIN GYM NEW SOUTHWEST EXIT DEMO PLAN
SCALE: 1/8" = 1'-0"
D1 MAIN GYM NEW SOUTHEAST EXIT DEMO PLAN
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
B B
A A
C C
D D
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
AD111A
A5
AD111A
E5
AD111A
C5
AD410
A1
AD111A
A1
ALT. 1 & 2
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER FOR RELOCATION
OF ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS. FOR
ACTUAL DEMOLITION BOUNDARY AND SCOPE.
REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO.
AREA OF CONSTRUCTION
LEGEND2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:48:32 AMAD111
OVERALL
LEVEL 1
(71'-0")
DEMO
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 1 (71'-0") DEMO RCP
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
17
H
J
H1
02.5602.56
D
E
F
19 20
F1
C1
18
02.56
02.56
02.56
02.56
02.15
TYP.
02.15
TYP.
TYP.
02.15
02.56
02.56
02.57
TYP.
02.56
02.15
TYP.
02.15
TYP.
02.57
TYP.
02.09
SLOPED
H
J
K
H1
J1
19 20
G1
18
02.56
02.56 02.56
02.56
02.56
02.57
02.56
02.56
02.09
SLOPED02.09
SLOPED
02.09
SLOPED
21 22 23 24 25 26 27 28 29
D
E
F
G
H
J
K
L
H1
J1
F1
G1
C1
02.11
02.54
02.11
02.54
02.54
02.11
02.54
CEILING DEMOLITION
DEMO CEILING LEGEND
WALL DEMOLITION
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO. 2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:36 AMAD111A
LEVEL 1
AREA
DEMO
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
E5 EXTG. MEN'S FACULTY DRESSING RM DEMO RCP
SCALE: 1/8" = 1'-0"
C5 EXTG. TRAINING & STUDENT DRESSING RMS DEMO RCP
SCALE: 1/8" = 1'-0"
A5 EXTG. EQUIP., LAUNDRY & DRESSING RMS DEMO RCP
02.09 EXISTING BEAM
02.11 REMOVE EXISTING CATWALKS, MECH. SUPPORT &
PLATFORM
02.15 REMOVE EXISTING LIGHT FIXTURE, RE: ELEC. DWG.
SALVAGE FOR REUSE, COORDINATE W/ OWNER
02.54 REMOVE EXISTING MECH. DUCT, RTU, ETC., RE:
MECH. DWG.
02.56 REMOVE EXISTING CEILING
02.57 REMOVE EXISTING MECH. EQUIPMENT, SALVAGE
FOR REUSE, COOORDINATE W/ OWNER
SCALE: 1/8" = 1'-0"
A1 FITNESS CENTER DEMO RCP
2 11/05/20 Addendum #2
1
1 2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
AD112A
C5
AD112A
A5
AD112A
B1
AD112A
B3
AD112A
A1
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER FOR RELOCATION
OF ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS. FOR
ACTUAL DEMOLITION BOUNDARY AND SCOPE.
REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO.
AREA OF CONSTRUCTION
LEGEND2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:48:42 AMAD112
OVERALL
LEVEL 2
(91'-0")
DEMO
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 2 (91'-0") DEMO RCP
7
B
C
D
C1
02.15
02.57
TYP.
TYP.
02.57
TYP.
02.56
02.56
1 2
B
C
D
E
C1
02.56
02.56
02.56
02.57
02.57
02.15
TYP.
TYP.
TYP.
C
19 20
C1
18
02.31
02.31 02.31
02.31
EXISTING
STRUCTURAL BEAM,
BO. ELE. 89' -1 1/2",
VERIFY
02.60RE. FLOOR PLAN
FOR NEW WALL @
THIS LOCATION
02.6002.60
ALTERNATE #5
14 15
B
C
D
C1
02.31
02.56
02.56
02.56
EXISTING
STRUCTURAL BEAM,
BO. ELE. 89' -1 1/2",
VERIFY
CEILING DEMOLITION
DEMO CEILING LEGEND
WALL DEMOLITION
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO.
13 14 15 16 17
L
19 2018
REFER TO ELECTRICAL PLANS
02.31
02.31
02.6002.60 02.6002.6002.60 02.6002.60
REFER TO SHEETS AE112B AND AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND WOMEN'S
LOCKER ROOMS ON LEVEL 2 (91'-0"). BASE BID TO
INCLUDE FLOOR FINISH AND TRENCH DRAIN/PLUMBING
IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE HW 2-B CEILING, ELEC. FIXTURES, FIRE
SPRINKLERS, HVAC DUCTS, ETC. @ 81'-0" LEVEL. FIELD
VERIFY DESIGN, HEIGHT, LAYOUT, AND DIMENSIONS
WITH ELEC. DWGS. THIS ALTERNATE IS TO
ACCOMMODATE THE 4" CONDUITS THAT ARE
INCLUDED IN THE BASE BID.
LIST OF ALTERNATES2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:46 AMAD112A
LEVEL 2
(91'-0")
AREA
DEMO
REFLECTED
CEILING
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A5 EXTG. WOMEN'S LOCKER ROOM DEMO RCP
SCALE: 1/8" = 1'-0"
C5 EXTG. MEN'S LOCKER ROOM DEMO RCP
SCALE: 1/8" = 1'-0"
B3 MAIN GYM (NEW) SOUTHWEST EXIT DEMO RCP
SCALE: 1/8" = 1'-0"
B1 MAIN GYM (NEW) SOUTHEAST EXIT DEMO RCP
02.15 REMOVE EXISTING LIGHT FIXTURE, RE: ELEC. DWG.
SALVAGE FOR REUSE, COORDINATE W/ OWNER
02.31 EXISTING ACOUSTIC CEILING TILE
02.56 REMOVE EXISTING CEILING
02.57 REMOVE EXISTING MECH. EQUIPMENT, SALVAGE FOR
REUSE, COOORDINATE W/ OWNER
02.60 REMOVED REUIRED CEILING PANELS AND FRAMING
SYSTEM (IF REQ'D) FOR MECH., STRU., AND ARCH.
WORK, PROTECT FOR REUSE; ALSO REFER TO MECH
AND STRU. DWG.
2 11/05/20 Addendum #2
3 11/10/20 Addendum #3
SCALE: 1/8" = 1'-0"
A1 (NEW) NORTH EXIT DEMO RCP
11 12 13 14 15 16 17 21
D
E
F
G
H
J
K
L
H1
J1
19 20
F1
G1
C1
18
02.31
02.31
02.31
02.31
02.31
02.31
02.60
02.60
TYP.
RE. DEMO
NOTE #6
TYP.
RE. DEMO
NOTE #6
TYP.
RE. DEMO
NOTE #6
02.60
CEILING DEMOLITION
DEMO CEILING LEGEND
WALL DEMOLITION
GENERAL DEMO NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO. 2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:53 AMAD112B
LEVEL 2
(91'-0")
MAIN GYM
DEMO
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A2 LEVEL 2 MAIN GYM DEMO RCP
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
02.31 EXISTING ACOUSTIC CEILING TILE
02.60 REMOVED REUIRED CEILING PANELS AND FRAMING
SYSTEM (IF REQ'D) FOR MECH., STRU., AND ARCH.
WORK, PROTECT FOR REUSE; ALSO REFER TO MECH
AND STRU. DWG.
17
J
K
J1
02.02
02.1302.13
MEN'S DRESSING RM.
02.22
SIM.
02.02
8' - 4"
ALTERNATE BASE BID
17
J
K
J1
ALTERNATE
MEN'S DRESSING RM.
BASE BID
02.56 02.5602.5602.56
CEILING DEMOLITION
RCP DEMO LEGEND
DEMOLITION NOTES
A. PROTECT ALL ADJACENT SURFACES AND
EQUIPMENT DURING CONSTRUCTION.
B. SET UP A CONSTRUCTION BARRIER IN EACH
OF THE CONSTRUCTION AREAS.
C. DUST CONTAINMENT IS MANDATORY.
D. COORDINATE WITH OWNER TO RELOCATE
ANY EXISTING IT AND SURVEILLANCE
EQUIPMENT.
E. REFER TO MEP AND STRUCTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
F. MUST REFER TO STRU. AND ELEC. DWGS.
FOR ACTUAL DEMOLITION BOUNDARY AND
SCOPE. REPLACE CEILING TILES BACK TO THE
ORIGINAL STATE AFTER FINAL COMPLETIO. 2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:56 AMAD410
LEVEL 1
(71'-0")
DEMO
PLANS -
ALTERNATEJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A5 EXTG. MEN'S DRESSING ROOM DEMO PLAN (ALT. 1 & 2)
02.02 EXISTING WALL TO REMAIN
02.13 REMOVE EXISTING WALL
02.22 REMOVE EXISTING LOCKERS, SALVAGE FOR
REUSE, COORDINATE W/ OWNER
02.56 REMOVE EXISTING CEILING
SCALE: 1/2" = 1'-0"
A1 EXTG. MEN'S DRESSING ROOM DEMO RCP (ALT. 1 & 2)
1 2
B
C
D
E
C1
4' - 10"12' - 5"3' - 8"13' - 10"9' - 6"1' - 7"9' - 6"
10' - 11"11' - 1"14' - 7"TYP.
90' - 10"
T.O. SLAB 16' - 8"12' - 7"8' - 4"
22.06
5' - 3"2' - 5"
T.O. DRAIN
90'-11"
T.O. DRAIN
90'-10 3/4"
T.O. DRAIN
90'-11"
T.O. DRAIN
90'-11"13' - 9"T.O. DRAIN
90'-11"
T.O. DRAIN
90' -11"
4' - 6"
T.O. DRAIN
90'-11 1/2"
D1
AE500
TYP.9' - 0"5' - 4"5' - 2"5' - 0"8' - 10"47' - 6"10' - 0"8' - 10"5' - 5"5' - 3"6' - 0"7' - 10"6' - 5"4' - 9"4' - 0"34' - 5 1/2"38' - 10 1/2"03.04
T.O. DRAIN
90'-1 1/4"
7 10
B
C
D
E
C1
2' - 8"3' - 6"T.O.SLAB
22.06
TYP.4' - 8"5' - 0"
2' - 4"3' - 1"
3' - 0"
6' - 0"27' - 9"6' - 9"D1
AE500
33' - 2"4'- 0".34' - 9"
15' - 6"6' - 4"7' - 3"3' - 6"11' - 4"4' - 1"14' - 0"4' - 0"22.06
03.04
90' - 10"91' - 0"
EXTG. CONC.
21 22
D
E
F
G
H
J
K
H1
J1
19 20
F1
G1
C1
18
3' - 6"10' - 0"7' - 3"7' - 7"11' - 2"6' - 10"12' - 10 1/2"
7"12' - 3"3' - 9"2' - 10"17' - 6"4' - 0"6' - 6"10' - 9"
2' - 0"2' - 0"T.O.D.
71'-8"4' - 7"T.O. DRAIN
71'-0"
T.O. DRAIN
71'-0"
71' - 8"
T.O. SLAB
T.O.S.
T.O SLAB
70' -10 1/2"
D1
AE500
4' - 0"71' - 0"
EXTG. CONC.
EXTG. CONC.
71' - 0"
03.042"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:48:59 AMAE100
LEVEL 1
(71'-0") &
LEVEL 2
(91'-0")
SLAB
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A1 LEVEL 2 MEN'S LOCKER RM. SLAB PLAN
SCALE: 1/8" = 1'-0"
A3 LEVEL 2 WOMEN'S LOCKER RM. SLAB PLAN
03.04 CONC. SLAB ON GRADE
22.06 FLOOR OR TRENCH DRAIN, RE. PLUMBING DWG.
SCALE: 1/8" = 1'-0"
A5 LEVEL 1 LAUNDRY ROOM, WOMEN'S & MEN'S RESTROOM SLAB PLAN
1 10/30/20 Addendum #1
DN
UP
UP
UP
2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
B B
A A
C C
D D
E E
F F
G
H
J
K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
AE101A
A5
21' - 8"21' - 8"21' - 8"21' - 8"21' - 8"62' - 4"19' - 9"1' - 1"22' - 10"17' - 0"17' - 0"22' - 8"22' - 8"39' - 8"17' - 0"22' - 10"1' - 1"21' - 7"21' - 0"22' - 4"22' - 4"22' - 4"22' - 4"22' - 8"20' - 4"21' - 0"11' - 0"9' - 9"21' - 3"21' - 0"4"20' - 8"5' - 6"15' - 6"10' - 8"10' - 4"15' - 10"5' - 2"21' - 0"33' - 8"18
18
WOMEN'S
181
MEN'S
183
LAUNDRY
RM.
180
FITNESS
CENTER
182
ACTIVITY
STOR.
177
CUSTODIAN
176
178
EQUIP. RM.179
NEW WELLNESS CENTER
MECH.
190
ACTIVITY
STOR.
191
SPINNING
RM.
189
AE101A
A2
AE101A
A3 HW.
1-D
CRAWL SPACE
AE102B
A2
AE410
A5
71' - 0"
79' - 0"
AE411
A5
ABOVE @ MAIN GYM
CUSTODIAN
OFFICE
175
AF100
D3
AF100
D5
AF100
D6
ALT. 1
ALT. 2
AE410
A3
AE411
A3
76' - 4"
AREA OF CONSTRUCTION
LEGEND
REFER TO SHEETS AE112B AND AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND WOMEN'S
LOCKER ROOMS ON LEVEL 2 (91'-0"). BASE BID TO
INCLUDE FLOOR FINISH AND TRENCH DRAIN/PLUMBING
IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE HW 2-B CEILING, ELEC. FIXTURES, FIRE
SPRINKLERS, HVAC DUCTS, ETC. @ 81'-0" LEVEL. FIELD
VERIFY DESIGN, HEIGHT, LAYOUT, AND DIMENSIONS
WITH ELEC. DWGS. THIS ALTERNATE IS TO
ACCOMMODATE THE 4" CONDUITS THAT ARE
INCLUDED IN THE BASE BID.
LIST OF ALTERNATES
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 1 (71'-0") FLOOR PLAN2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:49:03 AMAE101
OVERALL
LEVEL 1
(71'-0")
FLOOR
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
H
J
K
H1
J1
19 20
G1
18
WOMEN'S
181
MEN'S
183
1815' - 3"4' - 7"16' - 5"13' - 5"4' - 1"5' - 0"180
P3S
P3S
P3S
P3S
P3S
P3S
P3S
9' - 8"ALIGN
180
LAUNDRY RM.D
P3S
ALIGN
179A
SORT &
ASSEMBLE
179A
WELLNESS
CTR
OFFICE
179B
WELLNESS
CTR
OFFICE
179C
WELLNESS
CTR
OFFICE
179D
P3S
P3S
P3S
P3S P3S
ALIGN
ALIGN
5' - 7"10' - 10"W
A1
AE301
C1
AE301
A1
AE302
P3S
179D
179
179C179B
176
177
178
ACTIVITY
STOR.
177
CUSTODIAN
176
EQUIP. RM.
178
183
CUSTODIAN
OFFICE
175
11' - 0"11' - 0"11' - 0"
ALIGN
1' - 6"
P6S
W
D
17503.08
P3S
P3S
C/L
AE500
E2
7' - 0"
C3
AE400
C5
7' - 6"8' - 6"
71' - 0"
71' - 8"
183A
3' - 4"6' - 9"3' - 3"8"
ALTERNATE 1
RE. AE410
ALTERNATE 2
RE. AE411
D
E
F
19 20
F1
C1
18
190
MECH.
190
ACTIVITY
STOR.
191
P3S
CMU12
P6S
ALIGN ALIGN
189
SPINNING RM.
A1
AE301
C1
AE301
190A
191
189 9' - 4"11' - 2"5' - 2"CMU12
ELEC. PANELelec panel
A
A
A
P3S
Concrete Slab on
Grade - 4"
190B
189A
P3S
STOR.
190B
11' - 6"STOR.
189A
17
H
J
H1
ACTIVITY
STOR.
177
CMU12
A1
AE302
177
OWNER PROVIDED/REPURPOSED
2-TIER LOCKER
2-TIER 'Z' LOCKER
3 TIER LOCKER
LOCKER LEGENDS
GENERAL LOCKER NOTES
A. ALL LOCKERS TO BE SET ON A CMU BASE
B. SLOPE THE FLOOR TO DRAIN
C. REFER TO MECH. DWGS FOR VENTED LOCKER
LOCATIONS2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:08 AMAE101A
LEVEL 1
(71'-0")
AREA
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A5 RESTROOMS & WELLNESS CENTER FLOOR PLANS
SCALE: 1/8" = 1'-0"
A3 ACTIVITY STORAGE 189A & SPINNING RMS. FLOOR PLANS
SCALE: 1/8" = 1'-0"
A2 ACTIVITY STORAGE 177 FLOOR PLAN
03.08 8" CONCRETE HOUSEKEEPING PAD WITH 1/2"
CHAMFER
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
UP
DN
UP
UP
DN
DN
1
1 2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
24
24
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
AE102A
C5
AE102A
C5
AE102B
A2
52' - 2"21' - 8"21' - 8"21' - 8"21' - 8"21' - 8"62' - 4"19' - 9"1' - 1"22' - 10"17' - 0"17' - 0"22' - 8"22' - 8"39' - 8"17' - 0"22' - 10"1' - 1"21' - 7"21' - 0"20' - 4"21' - 0"11' - 0"9' - 9"21' - 3"21' - 0"4"20' - 8"5' - 6"15' - 6"10' - 8"10' - 4"15' - 10"5' - 2"21' - 0"33' - 8"8' - 0"AE102A
C1
AE102A
C3
18
18
207A
MEN'S EMP. LOCKER RM.
261
WOMEN'S STUDENT
LOCKER RM.
MAIN GYM
250A
STAIR
2-Y
VEST.
2-U
STAIR
2-T
STAIR
2-S
STAIR
2-X
STORAGE
211
81' - 0"
84' - 4"
91' - 0"
91' - 0"
91' - 0"
207
MEN'S STUDENT LOCKER
RM.
261A
WOMEN'S EMPLOYEE
LOCKER RM.
AF100
A3
220
TICKET OFFICE
E003
NORTH EXIT
RR.
212
SW. EXIT
E001E002
SE. EXIT
AE102A
A1
AF100
D1
AF100
A1
AREA OF CONSTRUCTION
LEGEND
REFER TO SHEETS AE112B AND AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND WOMEN'S
LOCKER ROOMS ON LEVEL 2 (91'-0"). BASE BID TO
INCLUDE FLOOR FINISH AND TRENCH DRAIN/PLUMBING
IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE HW 2-B CEILING, ELEC. FIXTURES, FIRE
SPRINKLERS, HVAC DUCTS, ETC. @ 81'-0" LEVEL. FIELD
VERIFY DESIGN, HEIGHT, LAYOUT, AND DIMENSIONS
WITH ELEC. DWGS. THIS ALTERNATE IS TO
ACCOMMODATE THE 4" CONDUITS THAT ARE
INCLUDED IN THE BASE BID.
LIST OF ALTERNATES
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 2 FLOOR PLAN2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:49:17 AMAE102
OVERALL
LEVEL 2
(91'-0")
FLOOR
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
1 10/30/20 Addendum #1
UP
DN
DN
UP
1 2
B
C
D
E
C1
207D
207F
207B
P3
P3
P3
P3
P3S
STORAGE
207D
207A
MEN'S EMP. LOCKER RM.
207A
11' - 3"
207C
207
MEN'S STUDENT LOCKER
RM.
ALIGN
5' - 3 1/2"
P3S 7' - 10"4' - 11"14' - 8"3' - 0"P3
AE400
A35' - 6"2' - 3"5' - 6"2' - 3"5' - 6"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 9"1' - 0"6' - 3"2' - 1"5' - 8"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"1' - 3"
C3
TYP.
10.08
4' - 6"
06.02
SIM.
A4
AE500
A1
AE500
A3
AE500
C3
AE500 6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"1' - 6"1' - 4"
AE414
D6
7' - 6"1' - 5"
7' - 6"2' - 3"6' - 6"1' - 5"
P3 1' - 4"12' - 9"11' - 1"11' - 1"10' - 5"1' - 6"11.04
11.04
STEAM ROOM
ALT. 3
5' - 0 1/2"
207E
P3
P3
P3
P3
P3
C2
AE500
C2
AE500 C3S
C3S
4' - 11"1' - 5"16' - 1"4' - 3"6' - 3"3' - 5"10' - 7"10' - 0"4' - 7"6' - 4"C3C3
C2S 05.18
ABOVE
EXISTING
WALL
P3S
5' - 5 1/2"5' - 0"5' - 1"8' - 1"
7 10
B
C
D
E
C1
5' - 5"10' - 8"10' - 8"4' - 2"4' - 2"11' - 10"5' - 1"16' - 2"11' - 0"2' - 8"
261B
P3
STORAGE
261E
261
WOMEN'S STUDENT
LOCKER RM.
261A
261C
261A
WOMEN'S EMPLOYEE
LOCKER RM.
261F
NURSING
261B
P3
261D
NURSING
261D
P3
TYP. HT.
8' -0"
AE400
A5
1' - 3"7' - 6"2' - 3"5' - 7"2' - 3"6' - 6"2' - 3"6' - 6"2' - 3"6' - 6"
11.04
SIM.
3' - 0"
4' - 4"
P6
10.08
SIM.
06.02
10.09
SIM.
TYP.261EALIGN
AE414
A6
ALIGN
4' - 0"1' - 3"7' - 7"2' - 2"5' - 10"2' - 2"6' - 7"2' - 2"6' - 7"2' - 2"7' - 7"11"1' - 3"2' - 10"7' - 2"
1' - 4"
8' - 1"5' - 1"
10.10
2' - 1"
STEAM ROOM
ALT. 3
3' - 0"1' - 6"
261G
261H 1' - 6"1' - 8"
C1
C3S
C3
C3
13 14 15
B
A
C
D
C1
A1
AE300
C1
AE300
1" / 1'-0"1" / 1'-0"15' - 2 1/2"ALIGN DN.DN.
ALIGN
210
STORAGE
211
RR.
212
211
CMU12 STAIR
S003
1' - 0"4' - 7"81' - 10"
SE. EXIT
E002
81' - 0"6' - 2"84' - 4"
CMU6
E002
P3S
CMU12
ALIGN
P6S
P3S
5' - 1"
ALIGN
3' - 8"
9' - 7 1/2"
C3
03.0603.06
AE401
A3
C5
AE300
212
AE500
D2
PLATFORM
210
A1
AE401
E3
AE401
213
E3
AE600
P6S-2
03.09
TYP.
02.178"17 21
B
C
D
E
19 20
C1
18
AL1
81' - 0"
P6S-2
CHAIR
STOR.
290
A1
AE301
C1
AE301
SW. EXIT
E001 E001
81' - 0"
STAIR
S001 CMU12
200
CMU12
03.0603.06
AE401
A5
200A 200B 200C
STAIR
S002
A5
AE301 HW.
2-B
HW.
2-A
PLATFORM
210
STOR.
200
P6S-2
8' - 10"
200D
AE112A
C3
OWNER PROVIDED/REPURPOSED
2-TIER LOCKER
2-TIER 'Z' LOCKER
3 TIER LOCKER
LOCKER LEGENDS
13 14 15 16 17
L
19 2018C1
AE301
CON6 CON6
S004STAIR
S004
ALIGN ALIGN
7' - 7"7' - 0"5' - 1"5' - 1"7' - 0"7' - 7"
P6SP6S
P6S
C3
E003
NORTH EXIT
E003A E003B E003C E003D E003E
E003K
E003J
E003H
E003G
E003F
2' - 6"ALIGN ALIGN
2' - 5"AE501
A1
P6S 220A220B220
TICKET OFFICE DISPLAY
221
A5
AE502
ALIGN W/
WOOD PANELING
ABOVE
A3
AE502
C3
AE502
AE501
A1
SIM.
O.P.P.
05.16 05.16
GENERAL LOCKER NOTES
A. ALL LOCKERS TO BE SET ON A CMU BASE
B. SLOPE THE FLOOR TO DRAIN
C. REFER TO MECH. DWGS FOR VENTED LOCKER
LOCATIONS
REFER TO SHEETS AE112B AND AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND WOMEN'S
LOCKER ROOMS ON LEVEL 2 (91'-0"). BASE BID TO
INCLUDE FLOOR FINISH AND TRENCH DRAIN/PLUMBING
IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE HW 2-B CEILING, ELEC. FIXTURES, FIRE
SPRINKLERS, HVAC DUCTS, ETC. @ 81'-0" LEVEL. FIELD
VERIFY DESIGN, HEIGHT, LAYOUT, AND DIMENSIONS
WITH ELEC. DWGS. THIS ALTERNATE IS TO
ACCOMMODATE THE 4" CONDUITS THAT ARE
INCLUDED IN THE BASE BID.
LIST OF ALTERNATES2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:25 AMAE102A
LEVEL 2
(91'-0")
AREA
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
C5 MEN'S LOCKER ROOM FLOOR PLAN
SCALE: 1/8" = 1'-0"
A5 WOMEN'S LOCKER ROOM FLOOR PLAN
SCALE: 1/8" = 1'-0"
C1 MAIN GYM SOUTHEAST EXIT FLOOR PLAN
SCALE: 1/8" = 1'-0"
C3 MAIN GYM SOUTHWEST EXIT FLOOR PLAN
02.17 REMOVE EXISTING CONC. STEP/BLEACHER SEATING
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE.
STR. DWG.
03.09 CAST IN PLACE CONCRETE STEP, RE. STRU. DWG.
05.16 METAL RAILING W/ GLAZING PANEL
05.18 4" C H METAL STUD ON TOP OF EXISTING WALL TO
DECK; INSULATION, 5/8" ON BOTH SIDES. ALIGN
INSIDE FACE WITH WALL TYPE C2S BELOW
06.02 SOLID SURFACE COUNTERTOP
10.08 ADA BENCH
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT, REUSE OF
EXISTING
10.10 SOLID PLASTIC LOCKER W/ BENCH, REFER TO
AE102A FOR 2 OR 3 TIER STYLE LOCATIONS
11.04 SPIN DRYER PROVIDED BY OWNER
SCALE: 1/8" = 1'-0"
A1 MAIN GYM NORTH EXIT FLOOR PLAN
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
4 Date 4 ASI #1
UP
DN
11 12 13 14 15 16 17 21 22
C
D
E
F
G
H
J
K
L
H1
J1
19 20
F1
G1
C1
A1
AE300
C1
AE300
18
2' - 4"7' - 0 1/2"MAIN GYM
250A91' - 0"91' - 0"
91' - 0"
91' - 0"91' - 0"
P6S-2
P6S-2
A1
AE301
C1
AE301
A1
AE302
SW. EXIT
E001
05.114' - 0"81' -0"25' - 0"2' - 8"24' - 2"03.09
03.09
POUR CONC.
FLUSH WITH
GYM FLOOR
10' - 6"
REFER TO STRUCTURAL DWG. FOR
STRUCTURAL REINFORCEMENT UNDER
THE MAIN FLOOR
02.55
A6
AE302
ADA
SEATING
AREA
ADA
SEATING
AREA
05.14
7' - 0 1/2"C5
AE500
5' - 1"C5
AE500
C5
AE500
D1
AE402
D2
AE402
A1
AE401
AE402
B1
AE402
B1
A5
AE402
AE402
A1
10' - 6"2' - 4"A2
AE501
A1
AE702
03.06
E3
AE600
A5
AE501
A5
AE501
A5
AE501
A5
AE501
A5
AE501
A5
AE501
A5
AE402
A5
AE501
A5
AE501
A5
AE501
05.11
05.11
05.11
05.11
05.1105.11
05.1105.11
03.06
05.11 05.11
05.1105.11
05.1105.11
05.11
05.1105.11
05.11
AE702
D1
AE702
D1
05.1605.16
05.16 05.16
03.09
03.0903.09
D1
AE402
20' - 3"05.1605.16
05.16
POUR CONC.
FLUSH WITH
GYM FLOOR2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:30 AMAE102B
LEVEL 2
(91'-0")
AREA PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A2 MAIN GYM FLOOR PLAN
02.55 EXISTING SOUND BOOTH
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.09 CAST IN PLACE CONCRETE STEP, RE. STRU. DWG.
05.11 METAL RAILING
05.14 METAL ROOF LADDER
05.16 METAL RAILING W/ GLAZING PANEL
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
11 12 13 14 15 16 17 21
D
E
F
G
H
J
K
L
H1
J1
19 20
F1
G1
C1
18
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
BO. CATWALKS
113' -2"
BO. CATWALKS
113' -2"
BO. CATWALKS
116' -8"
12.05
02.10
12.05
02.10
12.05
02.10
12.05
02.102"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:33 AMAE103
EXISTING
CATWALK
FLOOR
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A2 EXISTING CATWALK PLAN
02.10 EXISTING CATWALKS TO REMAIN
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
AE104A
A3
AREA OF CONSTRUCTION
LEGEND2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:49:38 AMAE104
OVERALL
ROOF PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 OVERALL ROOF PLAN
21 22 23 24 25 26 27 28 29
D
E
F
G
H
J
K
L
H1
J1
F1
G1
C1
A1
AE504
07.06
07.06
1/2" PER 12"1/2" PER 12"SLO PESLOPE
1/2" PER 12"1/2" PER 12"SLOPESLOPE23.03
23.03
RIDGE
07.0407.04
A3
AE504
07.05
07.05
TYP.
TYP.
07.05
TYP.
TYP.
A3
AE504
TYP.
02.53
TYP.
02.6502.65
02.53
02.6502.65
TYP.
TYP.
08.08
B
BB
B
08.08
B
B
B
B
B
B
B
B
B
A5
AE504
A5
AE504
23.01
ROOF TRAFFIC PAD
GENERAL ROOF LEGEND
NEW CRICKET
GENERAL ROOF NOTES
A. REFER TO AE504 FOR TYPICAL ROOF
DETAILS.
2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:41 AMAE104A
ROOF
AREA PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 FITNESS CENTER ROOF PLAN
02.53 EXISTING ROOF DRAIN
02.65 REMOVE EXISTING GUARDRAIL, SALVAGE FOR
REUSE
07.04 PATCH AND REPAIR EXTG. ROOFING AS REQ'D
07.05 3' WIDE FULLY ADHERED TRAFFIC MEMBRANE,
MATERIAL TO BE COMPATIBLE WITH EXISTING ROOF
MATERIAL
07.06 1/2" PER 12" SLOPE CRICKET, SUBMIT SHOP
DRAWING FOR APPROVAL PRIOR TO DEMOLITION
08.08 DOME SKYLIGHT ON EXISTING RTU CURB
23.01 MECH. DUCT
23.03 MECH. RTU, RE. MECH. DWG. ACTUAL DIMENSION
PROTECT EXISTING ROOF
2 11/05/20 Addendum #2
2 43 5 6 7 10 11 12 13 14 15 16 17 21 22 23 24 25 26 27 28 29
B
A
C
D
E
F
G
H
J
K
L
M
H1
J1
19 20
F1
G1
C1
18
AE111A
A5
MEN'S
183
WOMEN'S
181
LAUNDRY
RM.
180
FITNESS
CENTER
182
STAIR
1-A
CUSTODIAN
176
EQUIP. RM.
178
179
NEW WELLNESS CENTER
ACTIVITY
STOR.
177
AE111A
E5
AE111A
C5
SPINNING
RM.
189
ACTIVITY
STOR.
191
MECH.
190
AE410
C5
AE411
C5
AE111A
A1
AREA OF CONSTRUCTION
LEGEND
A. REFER TO ARCHITECTURAL DRAWINGS
FOR LOCATION OF LIGHT FIXTURES AND
ELECTRICAL DRAWINGS FOR QUANTITY
AND TYPE OF FIXTURES.
B. ELECTRICAL AND MECHANICAL
SUBCONTRACTORS TO COORDINATE WORK
WITH SPRINKLER CONTRACTOR TO AVOID
CONFLICTS IN FIELD.
C. PATCH & REPAIR CEILINGS AS NEEDED FOR
NEW FINISH.
D. PROVIDE ACCESS TO ALL CLEANOUTS.
E. PROVIDE ACCESS TO ALL
CONTROLS/VALVES.
F. CONTRACTOR TO REVIEW CEILING PLANS
AND NOTIFY ARCHITECT OF ANY CONFLICTS
SUCH AS DUCTWORK, PIPE WORK,
ELECTRICAL, AND ETC. BEFORE
PROCEEDING WITH WORK.
G. FIRE RATED CEILING ASSEMBLIES TO BE
CONTINUOUS. SEE DETAILS FOR RATED
ASSEMBLIES AND DROP CEILING.
GENERAL LEGEND CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:49:45 AMAE111
OVERALL
LEVEL 1
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 1 (71'-0") REFLECTED CEILING PLAN
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
H
J
K
H1
J1
19 20
G1
18
A7'-1"
C4
A9'-0"
C4
A9'-0"
C4
A9'-0"
C4
MEN'S
183
WOMEN'S
181
LAUNDRY
RM.
180
B9'-0"
C2
B9'-0"
C2
B9'-0"
C2
B9'-0"
C2
B7'-1"
C2
B9'-0"
C3
B9'-0"
C3
B9'-0"
C3
B9'-0"
C3
B9'-0"
C3
179
NEW WELLNESS CENTER
SORT &
ASSEMBLE
179A
WELLNESS
CTR
OFFICE
179B
WELLNESS
CTR
OFFICE
179C
WELLNESS
CTR
OFFICE
179D
02.09
(SLOPED)
SIM.
CUSTODIAN
OFFICE
175
B9'-0"
C3
REFER TO ELECTRICAL PLANS
D
E
F
19 20
F1
C1
18
MECH.
190 191
ACTIVITY STOR.
189
SPINNING RM.
02.09
(SLOPED)
XTG
C5
CXTG
C5
C
XTG
C5
C
STOR.
189A
XTG
C5
C
REFER TO ELECTRICAL PLANS
STOR.
190B
9'-0"XTG C
C5
17
H
J
H1 B7'-1"
C3
ACTIVITY
STOR.
177
REFER TO ELECTRICAL PLANS
CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE
CEILING FINISH LEGEND
A -GYPSUM
C -OPEN TO STRUCTURE
B -ACOUSTIC CEILING TILE
D -PORCELAIN TILE
A. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATION OF LIGHT FIXTURES AND ELECTRICAL
DRAWINGS FOR QUANTITY AND TYPE OF FIXTURES.
B. ELECTRICAL AND MECHANICAL SUBCONTRACTORS TO
COORDINATE WORK WITH SPRINKLER CONTRACTOR
TO AVOID CONFLICTS IN FIELD.
C. PATCH & REPAIR CEILINGS AS NEEDED FOR NEW
FINISH.
D. PROVIDE ACCESS TO ALL CLEANOUTS.
E. PROVIDE ACCESS TO ALL CONTROLS/VALVES.
F. CONTRACTOR TO REVIEW CEILING PLANS AND NOTIFY
ARCHITECT OF ANY CONFLICTS SUCH AS DUCTWORK,
PIPE WORK, ELECTRICAL, AND ETC. BEFORE
PROCEEDING WITH WORK.
G. FIRE RATED CEILING ASSEMBLIES TO BE
CONTINUOUS. SEE DETAILS FOR RATED ASSEMBLIES
AND DROP CEILING.
GENERAL CEILING NOTES
2122 23 24 25 26 27 28 29
D
E
F
G
H
J
K
L
H1
J1
F1
G1
C1
FITNESS
CENTER
182
9'-0"
C5
XTG
REFER TO ELECTRICAL PLANS2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:49:49 AMAE111A
LEVEL 1
(71'-0")
AREA
REFLECTED
CEILING
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
02.09 EXISTING BEAM
SCALE: 1/8" = 1'-0"
A5 RESTROOMS, LAUNDRY ROOM & NEW WELLNESS CTR. RCP
SCALE: 1/8" = 1'-0"
C5 ACTIVITY STORAGE 189A & SPINNING CLASSROOM RCP
SCALE: 1/8" = 1'-0"
E5 ACTIVITY STORAGE 177 RCP
SCALE: 1/8" = 1'-0"
A1 FITNESS CENTER RCP
C
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
1
1 2
2
4
4
3
3
5
5
6
6
7
7
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
21
21
22
22
23
23
B B
A A
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
H1 H1
J1 J1
19
19
20
20
F1 F1
G1 G1
C1 C1
18
18
250A
MAIN GYM
MEN'S STUDENT
LOCKER RM.
207
MEN'S EMP.
LOCKER RM.
207A
WOMEN'S STUDENT
LOCKER RM.
261
WOMEN'S EMP.
LOCKER RM.
261A
AE112A
C5
AE112A
A5
AE112B
A2
AE112A
C1
AE112A
C3
NURSING
261D
NURSING
261D
AREA OF CONSTRUCTION
LEGEND
A. REFER TO ARCHITECTURAL DRAWINGS
FOR LOCATION OF LIGHT FIXTURES AND
ELECTRICAL DRAWINGS FOR QUANTITY
AND TYPE OF FIXTURES.
B. ELECTRICAL AND MECHANICAL
SUBCONTRACTORS TO COORDINATE WORK
WITH SPRINKLER CONTRACTOR TO AVOID
CONFLICTS IN FIELD.
C. PATCH & REPAIR CEILINGS AS NEEDED FOR
NEW FINISH.
D. PROVIDE ACCESS TO ALL CLEANOUTS.
E. PROVIDE ACCESS TO ALL
CONTROLS/VALVES.
F. CONTRACTOR TO REVIEW CEILING PLANS
AND NOTIFY ARCHITECT OF ANY CONFLICTS
SUCH AS DUCTWORK, PIPE WORK,
ELECTRICAL, AND ETC. BEFORE
PROCEEDING WITH WORK.
G. FIRE RATED CEILING ASSEMBLIES TO BE
CONTINUOUS. SEE DETAILS FOR RATED
ASSEMBLIES AND DROP CEILING.
GENERAL LEGEND CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:49:57 AMAE112
OVERALL
LEVEL 2
(91'-0")
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/16" = 1'-0"
A1 OVERALL LEVEL 2 (91'-0") REFLECTED CEILING PLAN
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
14 15
B
C
D
C1
NO ARCH. WORK
PERFORMED IN THE
GREY AREA,
02.31
STORAGE
211
SE. EXIT
E002
RR.
212
B8'-1"
C3
B9'-0"
C3
A11'-1"
C4
REFER TO ELECTRICAL PLANS
C
19 20
C1
18
CHAIR
STOR.
290
HW.
2-A
SW. EXIT
E001
HW.
2-B
02.31
02.31 02.31
02.31
B8'-1"
C2
REFER TO ELECTRICAL PLANS
B8'-8"
C3
AS REQ'D
02.31
2' - 11"8' - 0"8' - 0"8' - 0"3' - 1"4' - 7"ALTERNATE #5
09.28
7 10
B
C
D
C1
A9'-0"
C4
8'-0"D
C6
261
WOMEN'S STUDENT
LOCKER RM.
261A
WOMEN'S EMPLOYEE
LOCKER RM.
A9'-0"
C4
STORAGE
261E
NURSING
261B
A9'-0"
C4
NURSING
261D
A9'-0"
C4
REFER TO ELECTRICAL PLANS2' - 4"2' - 8"10' - 0"
4' - 6"8' - 0"8' - 9"8' - 9"
4' - 6"4' - 6"EQEQ3' - 6"7' - 3"3' - 0"7' - 0"7' - 0"2' - 8"10' - 0"2' - 0"EQ EQ
EQEQEQEQEQ EQ
8' - 9"8' - 3"8' - 9"8' - 9"4' - 6"7' - 0"3' - 6"8' - 0"8' - 9"8' - 9"8' - 8"
3' - 4"6' - 5"EQ EQ4' - 0"5' - 0"8' - 10"8' - 5"8' - 9"9' - 2"6' - 6"EQ EQ
EQEQEQEQEQ EQ
EQEQEQ EQ
AE414
A5
STEAM ROOM
ALT. 3
26.05
TYP.
TYP.
26.05
EQ EQ
1 2
B
C
D
E
C1
8'-0" D
C6
A9'-0"
C4
STORAGE
207D
207
MEN'S STUDENT LOCKER
RM.
207A
MEN'S EMP. LOCKER RM.
A9'-0"
C4
REFER TO ELECTRICAL PLANS
08.02
26.05
TYP.
26.05
TYP.
26.05
TYP.
AE414
D5
STEAM ROOM
ALT. 3
8' - 0"8' - 4"8' - 9"8' - 9"4' - 6"2' - 6"7' - 9"8' - 9"8' - 9"8' - 10"EQEQEQ EQ
EQ EQEQEQ
8' - 9"8' - 9"8' - 9"4' - 6"7' - 4"4' - 0"7' - 9"7' - 9"8' - 3"8' - 9"8' - 9"8' - 9"8' - 10"7' - 0"
EQ EQEQEQ2' - 8"5' - 4"
5' - 4"10' - 4"3' - 0"10' - 4"3' - 0 1/2"5' - 4"2' - 8"
3' - 8"7' - 2"7' - 2"
7' - 2"7' - 2"3' - 8"4' - 11 1/2"5' - 0"5' - 4"6' - 0"EQ EQ
5' - 4"9' - 2"5' - 10"5' - 4"9' - 2"
2' - 3"
5' - 6"2' - 10"EQEQ4' - 6"13 14 15 16 17
L
19 2018
REFER TO ELECTRICAL PLANS B8'-10"
C3
B9'-0"
C3
B9'-0"
C3
26.05 26.05
TYP.
TYP.
NORTH
EXIT
E003
DISPLAY
221
TICKET
OFFICE
220
02.31
02.31
A. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATION OF LIGHT FIXTURES AND ELECTRICAL
DRAWINGS FOR QUANTITY AND TYPE OF FIXTURES.
B. ELECTRICAL AND MECHANICAL SUBCONTRACTORS TO
COORDINATE WORK WITH SPRINKLER CONTRACTOR
TO AVOID CONFLICTS IN FIELD.
C. PATCH & REPAIR CEILINGS AS NEEDED FOR NEW
FINISH.
D. PROVIDE ACCESS TO ALL CLEANOUTS.
E. PROVIDE ACCESS TO ALL CONTROLS/VALVES.
F. CONTRACTOR TO REVIEW CEILING PLANS AND NOTIFY
ARCHITECT OF ANY CONFLICTS SUCH AS DUCTWORK,
PIPE WORK, ELECTRICAL, AND ETC. BEFORE
PROCEEDING WITH WORK.
G. FIRE RATED CEILING ASSEMBLIES TO BE
CONTINUOUS. SEE DETAILS FOR RATED ASSEMBLIES
AND DROP CEILING.
GENERAL CEILING NOTES
CEILING FINISH LEGEND
A -GYPSUM
C -OPEN TO STRUCTURE
B -ACOUSTIC CEILING TILE
D -PORCELAIN TILE
CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE
REFER TO SHEETS AE112B AND AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND WOMEN'S
LOCKER ROOMS ON LEVEL 2 (91'-0"). BASE BID TO
INCLUDE FLOOR FINISH AND TRENCH DRAIN/PLUMBING
IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE HW 2-B CEILING, ELEC. FIXTURES, FIRE
SPRINKLERS, HVAC DUCTS, ETC. @ 81'-0" LEVEL. FIELD
VERIFY DESIGN, HEIGHT, LAYOUT, AND DIMENSIONS
WITH ELEC. DWGS. THIS ALTERNATE IS TO
ACCOMMODATE THE 4" CONDUITS THAT ARE
INCLUDED IN THE BASE BID.
LIST OF ALTERNATES2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:03 AMAE112A
LEVEL 2
(91'-0")
REFLECTED
CEILING
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
C1 MAIN GYM SOUTHEAST EXIT RCP
SCALE: 1/8" = 1'-0"
C3 MAIN GYM SOUTHWEST EXIT RCP
SCALE: 1/8" = 1'-0"
A5 WOMEN'S LOCKER ROOM RCP
SCALE: 1/8" = 1'-0"
C5 MEN'S LOCKER ROOM RCP
SCALE: 1/8" = 1'-0"
A1 MAIN GYM NORTH EXIT RCP
02.31 EXISTING ACOUSTIC CEILING TILE
08.02 CEILING ACCESS PANEL
09.28 PATCH & REPAIR EXTG. CEILING AROUND THE NEW
WALL AS REQ'D
26.05
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
3 11/10/20 Addendum #3
11 12 13 14 15 16 17 21
D
E
F
G
H
J
K
L
H1
J1
19 20
F1
G1
C1
18
31' - 2"31' - 0"5' - 8"8' - 0"56' - 0"8' - 0"8' - 0"49' - 3 1/2"8' - 0"49' - 3 1/2"6' - 8 1/2"26' - 7"26' - 7"02.31
02.31
02.31
02.31
02.3102.31
12.05 12.0512.05 12.05
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
TOP CURTAIN HEAD RAIL
109' -0"
BOT. CURTAIN HEAD RAIL
109' -0"
TYP.05.15
TOP SUPPORTING PIPE
111' -10 1/2"
11.05
11.05 11.05
11.05
CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE
CEILING FINISH LEGEND
A -GYPSUM
C -OPEN TO STRUCTURE
B -ACOUSTIC CEILING TILE
D -PORCELAIN TILE
A. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATION OF LIGHT FIXTURES AND ELECTRICAL
DRAWINGS FOR QUANTITY AND TYPE OF FIXTURES.
B. ELECTRICAL AND MECHANICAL SUBCONTRACTORS TO
COORDINATE WORK WITH SPRINKLER CONTRACTOR
TO AVOID CONFLICTS IN FIELD.
C. PATCH & REPAIR CEILINGS AS NEEDED FOR NEW
FINISH.
D. PROVIDE ACCESS TO ALL CLEANOUTS.
E. PROVIDE ACCESS TO ALL CONTROLS/VALVES.
F. CONTRACTOR TO REVIEW CEILING PLANS AND NOTIFY
ARCHITECT OF ANY CONFLICTS SUCH AS DUCTWORK,
PIPE WORK, ELECTRICAL, AND ETC. BEFORE
PROCEEDING WITH WORK.
G. FIRE RATED CEILING ASSEMBLIES TO BE
CONTINUOUS. SEE DETAILS FOR RATED ASSEMBLIES
AND DROP CEILING.
GENERAL CEILING NOTES2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:10 AMAE112B
LEVEL 2
REFLECTED
CEILING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
02.31 EXISTING ACOUSTIC CEILING TILE
05.15 CONTINUOUS CROSS BEAM @ 21' O.C., RE:
STRUCTURAL SCHEDULE
11.05 AALCO. BASKETBALL BACKSTOPS, 134SF
SIDE FOLD SIDE BRACED
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC.
AND STRU. DWGS. FOR CONNECTION AND
SUPPORT
SCALE: 1/8" = 1'-0"
A2 MAIN GYM REFLECTED CEILING PLAN
2 11/05/20 Addendum #2
21 22
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 3
109' -0"
19 2018
CHAIR
STOR.
290
ACTIVITY
STOR.
191
MECH.
190
HW.
1-D
A1
AE301
C1
AE301
03.06
12.05
SW. EXIT
E001
AE501
A2
TYP.
05.11
03.07
05.11
AE501
A5SIM.MIN. 6' - 8"8' - 1"C1
AE401
B C
LEVEL 1A
76' -4"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
C1
1" / 1'-0"
12.05
SE. EXIT
E002
LANDING
6' - 8 1/2"
RAMP
30' - 0"
LANDING
9' - 9"
03.04
AE310
A5
05.11
11 12 13 14 15
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 3
109' -0"
1" / 1'-0"
SE. EXIT
E002
(MIN. 6' - 8")7' - 3"03.06
03.06
03.07
05.11
12.05
A1
AE401
AE501
A2
E3
AE600
LANDING
10' - 10"
RAMP
10' - 0"
LANDING
12' - 10"
81' - 10"
AE501
A5
SIM.
05.11
TYP.
C5
AE401
B C
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
C1
03.06
STORAGE
211
RR.
212
13 14 15
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
C1
AE300
03.06
STORAGE
211
RR.
212
03.04 03.06
E3
AE401
SE. EXIT
E002
H J K
L
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
H1 J1
LEVEL 3
109' -0"
A1
AE302
ACTIVITY
STOR.
177
CUSTODIAN
176
EQUIP. RM.
178
AE501
C1
TYP.
AE500
C5
TYP.
AREA OF REMODELING WORK
EXTG. TO REMAIN
SECTION LEGEND2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:15 AMAE300
BUILDING
SECTIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A3 SECTION @ GRID C1 & D
SCALE: 1/8" = 1'-0"
C1 SECTION @ GRID 13 & 14
SCALE: 1/8" = 1'-0"
A1 SECTIO @ GRID C1 & D
SCALE: 1/8" = 1'-0"
C3 SECTION @ GRID 14
SCALE: 1/8" = 1'-0"
C5 SECTION @ GRID B & C
03.04 CONC. SLAB ON GRADE
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.07 CONCRETE STAIRS
05.11 METAL RAILING
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
SCALE: 1/8" = 1'-0"
A5 SECTION @ GRID 17
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
D E F G H J K L
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
H1 J1
LEVEL 3
109' -0"
F1 G1C1
12.06
12.05
MECH.
190
LAUNDRY
RM.
180
SORT &
ASSEMBLE
179A
A1
AE302
03.06
STOR.
189A
SW. EXIT
E001
05.16 05.11
AE501
A5
TYP.
CURTAIN
OPENING,
RE: SPEC.
CURTAIN
OPENING,
RE: SPEC.
STOR.
190B
C D E F G H J K L
LEVEL 1
71' -0"
LEVEL 1A
76' -4"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
H1 J1
LEVEL 3
109' -0"
F1 G1C1
12.05
191
ACTIVITY STOR.
189
SPINNING RM.
MEN'S
183
WOMEN'S
181
WELLNESS
CTR
OFFICE
179C
HW.
2-B
STAIR
2-D
SW. EXIT
E001
A1
AE302
AE310
A3
03.06
05.14
03.0403.04
CURTAIN
OPENING,
RE: SPEC.
21 22
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
19 2018
C1
AE301
HW.
2-B
AE311
A5
03.0703.06
STAIR
S002
05.14
STOR.
200
D
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 3
109' -0"
C1
ACTIVITY
STOR.
191
05.11
AE310
A1
05.16
03.06
03.06
03.04
AREA OF REMODELING WORK
EXTG. TO REMAIN
SECTION LEGEND2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:22 AMAE301
BUILDING
SECTIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A1 SECTION @ GRID 18
03.04 CONC. SLAB ON GRADE
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE.
STR. DWG.
03.07 CONCRETE STAIRS
05.11 METAL RAILING
05.14 METAL ROOF LADDER
05.16 METAL RAILING W/ GLAZING PANEL
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC.
AND STRU. DWGS. FOR CONNECTION AND
SUPPORT
12.06 ALTERNATIVE CURTAIN
SCALE: 1/8" = 1'-0"
C1 SECTION @ GRID 19 & 20
SCALE: 1/8" = 1'-0"
A5 SECTION @ GRID C & C1
2 11/05/20 Addendum #2
SCALE: 1/8" = 1'-0"
C6 SECTION @ GRID 19
1112131415161721
LEVEL 1
71' -0"
LEVEL 1A
76' -4"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 3
109' -0"
1920 18
A1
AE301
C1
AE301
HW.
1-D
WOMEN'S
181
WOMEN'S
181
LAUNDRY
RM.
180
ACTIVITY STOR.
177
05.1505.15
03.06 03.0605.16 05.16 05.1105.1605.1605.11
AE501
A5
TYP.
AE500
C5
TYP.
CDEFGHJKL
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
H1J1
LEVEL 3
109' -0"
F1G1 C1
A1
AE302
HW.
1-D
HW.
2-A
HW.
2-B
AE311
A3
11 12 13 14 15
LEVEL 1A
76' -4"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 3
109' -0"
03.09
ADA
SEATING
AREA2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:27 AMAE302
BUILDING
SECTIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
A1 SECTION @ GRID J
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.09 CAST IN PLACE CONCRETE STEP, RE. STRU. DWG.
05.11 METAL RAILING
05.15 CONTINUOUS CROSS BEAM @ 21' O.C., RE:
STRUCTURAL SCHEDULE
05.16 METAL RAILING W/ GLAZING PANEL
SCALE: 1/8" = 1'-0"
C1 SECTION @ GRID 20 & 21
SCALE: 1/8" = 1'-0"
A6 BUILDING SECTION @ GRID H & H1
2 11/05/20 Addendum #2
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
C1
125' - 7"
113' - 2"
02.26
02.30
02.09
02.03
02.33
02.31
02.28
03.06
02.34
02.36
02.37
02.38
111' - 0"
FIN. CLG.
T.O. BEAM
T.O. BEAM
02.17
EXISTING
STRUCTURAL BEAM,
SLOPED, VERIFY ELE.
02.28
02.09
02.30
02.41
02.40
02.34
02.31
02.34
02.36
122' - 0"
B.O. FASCIA
ACTIVITY
STOR.
191
SW. EXIT
E001
04.04
03.06
05.16
26.05
A2
AE501
STOR.
200
08.03
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
C1
125' - 7"
T.O. BEAM
T.O. BEAM
113' - 2"
111' - 0"
T.O. CURTAIN
HEAD RAIL
02.30
02.26
02.28
02.09
02.33
02.31
12.05
02.10
02.09
02.41
02.40
02.30
02.04
02.34
02.37
02.34
02.36
02.34
FIN. CLG.
02.34
02.03
FIN. CLG.
100' - 4"
FIN. CLG.
FIN. CLG.
02.37
122' - 0"
B.O. FASCIA
ACTIVITY
STOR.
191
SW. EXIT
E001
09.07
09.02
26.05
03.06
89' - 8"
09.02
26.05
89' - 1"
26.05
ALT. 5
COORDINATE W/ NEW
ELEC. CONDUITS
LEVEL 1A
76' -4"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1B
79' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
C1
02.30
02.26
02.09
02.27
02.09
02.30
02.28
02.07
02.34
03.04 03.06
02.37
02.38
02.36
T.O. BEAM
T.O. BEAM
T.O. BEAM
T.O. BEAM
ELE. VERIFY
FIN. CLG.
FIN. CLG.
T.O. CURTAIN
HEAD RAIL
81' - 10"
B.O. FASCIA
09.02
09.02
90' - 7 1/2"
113' - 2"
02.28
7' - 3"02.09
02.41
102' - 0"
125' - 7"
122' - 0"
02.31
111' - 0"
100' - 4"
02.31
02.33
02.09
SE. EXIT
E002
AE501
A2
7' - 4"90' - 0"
FIN. CLG.
FIN. CLG.
09.07
26.05
26.05
05.1605.16
3' - 6"A2
AE501
08.03
05.11
AREA OF REMODELING WORK
EXTG. TO REMAIN
SECTION LEGEND2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:31 AMAE310
WALL
SECTIONSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A1 WALL SECTION
SCALE: 1/2" = 1'-0"
A3 WALL SECTION
SCALE: 1/2" = 1'-0"
A5 WALL SECTION
2 11/05/20 Addendum #2
02.03 EXISTING CONC. COLUMN
02.04 EXISTING METAL GUARDRAIL
02.07 EXISTING DOOR TO REMAIN
02.09 EXISTING BEAM
02.10 EXISTING CATWALKS TO REMAIN
02.17 REMOVE EXISTING CONC. STEP/BLEACHER SEATING
02.26 EXISTING PRECAST CONC. FASCIA
02.27 EXISTING BRICK VENEER
02.28 EXISTING 12" X 8" X 16" CMU WALL
02.30 EXISTING ROOF, 2" RIGID INSULATION & 1 1/2" METAL
DECK
02.31 EXISTING ACOUSTIC CEILING TILE
02.33 EXISTING REGLET
02.34 EXISTING CONC. SLAB, 4 1/2" THICK
02.36 EXISTING GRAVEL
02.37 EXISTING CONC. FOUND. WALL, 16" THICK
02.38 EXISTING CONC. FOOTING
02.40 EXISTING STUCCO FINISHED CEILING
02.41 EXISTING OPEN WEB STEEL JOIST
03.04 CONC. SLAB ON GRADE
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
04.04
05.11 METAL RAILING
05.16 METAL RAILING W/ GLAZING PANEL
08.03 SCH'D DOOR
09.02 SCH'D CEILING, RE: RCP
09.07 PAINTED WALL
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
26.05
C
LEVEL 1
71' -0"
LEVEL 2
91' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
02.26
02.30
02.09
02.41
02.40
02.34
02.31
02.37
02.38
02.34
02.36
08.01
100' - 4"
B.O. FASCIA
HW.
2-B
ALT. #5
COORDINATE W/ NEW
ELEC. CONDUITS
09.0289' - 8"
LEVEL 1
71' -0"
LEVEL 2
91' -0"
127'-0"
127' -0"
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
LEVEL 3
109' -0"
18
02.30
02.09
02.26
02.28
02.27
02.09
B.O. FASCIA
02.09
02.09
T.O. BEAM
T.O. BEAM
02.34
02.46
02.37
02.34
02.36
02.37
02.31
02.33
02.31
102' - 5 1/2"
92' - 3 1/2"
122' - 0"
02.41
02.30
02.31
C1
AE401
T.O. BEAM
T.O. BEAM
88' - 7"
104' - 7"05.02
114' - 0"
T.O. BEAM
05.02
STAIR
S002
STOR.
20003.06AE401
E1
90' - 8"
FIN. CLG.
03.07
09.07
08.03
REFER TO SHEETS AE410 TO 414.
ALTERNATE #1:
ANY WORK RELATED TO CUSTODIAN ROOM 176 ON
LEVEL 71'-0" @ GRIDS 17/J.
ALTERNATE #2:
ANY WORK RELATED TO EQUIPMENT ROOM 178 ON
LEVEL 1 (71'-0") @ GRIDS 17/K.
ALTERNATE #3:
(2) STEAM ROOMS IN BOTH THE MEN'S AND
WOMEN'S LOCKER ROOMS ON LEVEL 2 (91'-0").
BASE BID TO INCLUDE FLOOR FINISH AND TRENCH
DRAIN/PLUMBING IN THESE 2 ROOMS.
ALTERNATE #4:
REMOVAL OF THE BASKETBALL STANDARDS IN THE
FITNESS CENTER 182 ON LEVEL 1 (71'-0"), PROTECT
AND SALVAGE TO OWNER. NO DRAWINGS ARE
INCLUDED IN THE CD.
ALTERNATE #5:
REPLACE THE CEILING BETWEEN HW 2-B. FIELD
VERIFY DESIGN, LAYOUT, AND DIMENSIONS WITH
ELEC. DWGS.
LIST OF ALTERNATES
AREA OF REMODELING WORK
EXTG. TO REMAIN
SECTION LEGEND2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:34 AMAE311
WALL
SECTIONSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A3 WALL SECTION
SCALE: 1/2" = 1'-0"
A5 WALL SECTION
2 11/05/20 Addendum #2
02.09 EXISTING BEAM
02.26 EXISTING PRECAST CONC. FASCIA
02.27 EXISTING BRICK VENEER
02.28 EXISTING 12" X 8" X 16" CMU WALL
02.30 EXISTING ROOF, 2" RIGID INSULATION & 1 1/2" METAL
DECK
02.31 EXISTING ACOUSTIC CEILING TILE
02.33 EXISTING REGLET
02.34 EXISTING CONC. SLAB, 4 1/2" THICK
02.36 EXISTING GRAVEL
02.37 EXISTING CONC. FOUND. WALL, 16" THICK
02.38 EXISTING CONC. FOOTING
02.40 EXISTING STUCCO FINISHED CEILING
02.41 EXISTING OPEN WEB STEEL JOIST
02.46 EXISTING 7 1/2" CONC. SLAB BELOW 4" WOOD FINISH
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.07 CONCRETE STAIRS
05.02 STRUCTURAL BEAM, RE: STR. SCHEDULE
08.01 ALUMINUM STOREFRONT, RE: DOOR SCHEDULE
08.03 SCH'D DOOR
09.02 SCH'D CEILING, RE: RCP
09.07 PAINTED WALL
10' - 8"10' - 8"261F
NURSING
261B
C3C3
9' - 0"
1' - 8"2' - 2"1' - 6"3' - 0"5' - 0"3' - 0"3' - 1"3' - 1"5' - 0"
10.07
10.023' - 1"3' - 1"3' - 1"5' - 0"5' - 0"
22.05
06.02
10.06
1' - 0"ALIGN6' - 3"5' - 8"3' - 5"3' - 5"6' - 3"10.01
12.05
1' - 2"
1' - 8"3' - 0"2' - 4"1' - 2"
10.13 1' - 8"3' - 0"10.08
C2
AE500
TYP.
22.07
10.16
10.15
1' - 8"3' - 0"6"2' - 6"5' - 0"6"3' - 8"6"1' - 6"
C1
AE500
22.01
22.07ADA
TYP.
10.01
2' - 5"3' - 0"3' - 0"3' - 1"3' - 2"5' - 0"1' - 8"1' - 8"3' - 1"2' - 0"
22.01
10.07
10.01
10.02
10.06 06.02 22.05
10.013' - 3"3' - 3"3' - 3"3' - 4"1' - 2"1' - 2"10.03
5' - 1"3' - 1"3' - 1"3' - 1"5' - 6"2' - 2"2' - 2"5' - 6"22.02
10.08
22.07
4' - 3"6' - 4"3' - 11"3' - 1"3' - 0 1/2"3' - 3"3' - 3"3' - 3"C2
AE5003' - 1"3' - 0"6' - 4"4' - 7"3' - 4"3' - 4"4' - 3"4' - 0"2' - 0"2' - 10"1' - 7"4' - 5"TYP.
22.07
12.05
12.0712.07
ADA.
WOMEN'S
181
MEN'S
183
1' - 8"1' - 8"C3
22.0506.02
5' - 1"3' - 1"3' - 1"4' - 10"4' - 0"3' - 1"3' - 1"3' - 1"22.01
10.01
5' - 1"
5' - 1"
10.07
22.02
10.03
10.02
C3
3' - 0"3' - 0"3' - 0"EQ.EQ.3' - 1"3' - 0"3' - 1"3' - 1"3' - 1"3' - 1"3' - 1"5' - 1"1' - 9 1/2"3' - 9"3' - 0"3' - 0"4' - 10"3' - 0"3' - 0"
24' - 2"7' - 0"4' - 1"5' - 0"3' - 1"3' - 1"3' - 1"3' - 1"3' - 1"6' - 1"3' - 1"3' - 1"6' - 11"10.08
10.11
5' - 1"3' - 1"3' - 1"3' - 1"3' - 1"3' - 1"3' - 1"5' - 1"1' - 2"1' - 2"1' - 8"C2
AE500
10.01
2' - 6"6"2' - 6"6"1' - 8"3' - 8"10.15
RR.
212
1' - 6"
22.071' - 5"1' - 0"10.08
10.01
1' - 6"6"3' - 0"
22.01
10.01 2' - 6"22.05
10.072"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:40 AMAE400
RESTROOM
& SHOWER
ROOM
FLOOR
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
A5 RESTROOM - WOMEN'S LOCKERS
SCALE: 1/4" = 1'-0"
A3 RESTROOM - MEN'S LOCKERS
06.02 SOLID SURFACE COUNTERTOP
10.01 ADA COMPLIANT GRAB BAR
10.02 TOILET PARTITION
10.03 URINAL PARTITION
10.06 PAPER TOWEL DISPENSER
10.07 TOILET PAPER DISPENSER
10.08 ADA BENCH
10.11 DRESSING PARTITION W/ BENCH
10.13 WALL MOUNTED ADJUSTABLE BRACKET SHELVES,
PROVIDE BLOCKING AS REQ'D
10.15
10.16
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
12.07
22.01 WALL MOUNTED TOILET, RE PLUMBING DWG.
22.02 WALL MOUNTED URINAL, SEE PLUMBING
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
22.07 SHOWER FIXTURE, SEE PLUMBING
SCALE: 1/4" = 1'-0"
C5 MEN'S 183 & WOMEN'S 181 RESTROOMS
SCALE: 1/4" = 1'-0"
C3 RESTROOM - RR. 212
1 10/30/20 Addendum #1
DN
DN
C1
18
STAIR
S001
STAIR
S002
C1
AE401
C3
AE401
6 EQ. TREADS @ 11"5' - 6"3' - 8"3' - 8"6 EQ. TREADS @ 11"
5' - 6"
05.11
03.07
03.07
E5
AE401
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
C1
C3
AE401
03.076 EQ. RISER @ 6 1/2"3' - 4"AE401
E1
03.06 3' - 0"05.11
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
18C1
AE401
03.07
AE401
E1
6 EQ. RISER @ 6 1/2"3' - 4"03.06
6 EQ. TREADS @ 11"
5' - 6"
PRECAST
CONCRETE
METAL GUARDRAIL
EXISTING 8" CMU
WALL
36"C1
STAIR
S003
6 EQ. TREADS @ 11"5' - 6"3' - 8"
C5
AE401
A1
AE401
03.07
03.06
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
C1
6 EQ. RISERS @ 6 1/2"3' - 4"03.0703.06
AE401
E1
6 EQ. TREADS @ 11"
5' - 6"
E3
AE401
6 EQ.TREADS @ 11"
5' - 6"
GEOFAOM
FINISH MATERIAL
TO MATCH
ADJACENT
SURFACE
CAST IN PLACE
CONCRETE
EXISTING
CONCRETE SLAB
EXISTING FLOORING
LEVEL 1C
81' -0"
LEVEL 1D
84' -4"
C1
CAST IN PLACE CONCRETE,
PAINT BLACK ON
VERTICALCONCRETE
CAST IN PLACE CONCRETE
GEOFOAM
STAIR RISERS BEHIND
E3
AE401
GEOFOAM
CAST IN PLACE CONCRETEEXISTING FLOORING
EXISTING
CONCRETE SLAB2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:44 AMAE401
STAIR
PLAN,
SECTIONS
& DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A5 STAIR - S001 & S002
SCALE: 1/2" = 1'-0"
C1 STAIR SECTION - S001
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.07 CONCRETE STAIRS
05.11 METAL RAILING
SCALE: 1/2" = 1'-0"
C3 STAIR SECTION - S002
SCALE: 1 1/2" = 1'-0"
E5 STAIR STRINGER / HANDRAIL DETAIL
SCALE: 1/2" = 1'-0"
A3 STAIR - S003
SCALE: 1/2" = 1'-0"
C5 STAIR SECTION - 003
SCALE: 1" = 1'-0"
E1 PRECAST STAIR DETAIL
SCALE: 1/2" = 1'-0"
A1 STAIR SECTION - S003
SCALE: 1 1/2" = 1'-0"
E3 PLATFORM DETAIL
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
14
D
D1
AE402
D2
AE402
C5
AE402
EQ 2' - 8"2' - 8"2' - 8"2' - 8"2' - 8"2' - 8"2' - 8"EQ
24' - 0"
03.09
A2
AE501
TYP.
05.11
TYP.
05.16
05.16
1' - 4"4' - 0"14
LEVEL 2
91' -0"
LEVEL 1C
81' -0"
D1
AE402
D2
AE402
02.06 03.09 7"7"7"7"7"7"7"7"7"1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
AE501
C2
SIM.
05.16
05.16
LEVEL 2
91' -0"
LEVEL 1C
81' -0"
AE501
A4
SIM.
LEVEL 2
91' -0"
LEVEL 1C
81' -0"
2A
89' -8"
1" X 1" BRUSHED STAINLESS
STEEL U-CHANNEL TOP RAIL
W/ PROTECTIVE INSERT
1/2" CLEAR TEMPERED GLASS
GUARDRAIL WITH POLISHED EDGES
CONCRETE SLABSEALANT,
COLOR: BLACK
BRUSHED STAINLESS
STEEL BASE CLADDING
J-TRIM,
MUDDED IN
FASCIA MOUNTED BASE SHOE
GLAZING GASKET
5x5x5/16" CONTINUOUS SUPPORT ANGLE
GYPSUM BOARD SOFFIT
3-5/8" STEEL STUDS
@ 24" O.C. MAX.
16 17
K
A5
AE300
A5
AE402
2"10' - 2"2"2' - 2"2"2"10' - 2"2"2"2' - 2"C5
AE500
C5
AE50005.1605.16
03.06
03.0603.09 03.09
TYP.TYP.
05.11 05.11
1' - 4"4' - 0"1' - 4"4' - 0"
K
LEVEL 2
91' -0"
J1
TYPICAL LED
HANDRAIL AT AISLE
WITH EVEN STEPS
02.0602.06
03.09
TYP.
AE501
A5
2' - 10"SIMILAR EXCEPT TREADS AND
HANDRAIL ARE CONSISTENT
SLOPE AT NEW TREADS
7"7"7"7"7"7"7"7"7"1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
1' - 4"
05.112"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:48 AMAE402
STAIR
PLAN,
SECTIONS
& DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
B1 ENLARGED GYM STAIR
SCALE: 1/2" = 1'-0"
C5 MAIN GYM STAIR SECTION
SCALE: 1/2" = 1'-0"
D1 WALL SECTION
SCALE: 1/2" = 1'-0"
D2 WALL SECTION
SCALE: 1/2" = 1'-0"
A1 ENLARGED MAIN GYM @ NEW STAIR,ADA LOCATION
SCALE: 1/2" = 1'-0"
A5 WALL SECTION
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
02.06 EXISTING TYP. REINFORCED CONCRETE BLEACHER
SEATING
03.06 CAST IN PLACE CONCRETE OVER GEOFOAM, RE. STR.
DWG.
03.09 CAST IN PLACE CONCRETE STEP, RE. STRU. DWG.
05.11 METAL RAILING
05.16 METAL RAILING W/ GLAZING PANEL
17
J
J1
CMU12
CUSTODIAN
176
P3S
P3S
A1
AE302
A5
AE300
17616' - 1"08.06
19' - 9 1/2"
178
EQUIP. RM.
ALT. 2
17
J
J1
B7'-1"
C3
B9'-0"
C3
CUSTODIAN
176
02.09
(SLOPED)
EQUIP. RM.
178
ALT. 2
REFER TO ELECTRICAL PLANS
F5 P1B1
176
CUSTODIAN
AE410
C3
E3
E1 C1
178
EQUIP. RM.
ALT. 2
09.01
09.14
22.10
09.01
P1
P1
W2
09.10
B1
02.03
10.13
10.13
09.10
B1
P1P1
02.03
02.09
02.37 02.37
08.03
09.01
10.13
09.10
P1
B1
09.14
22.10
10.13
09.1010.13
B1
P1
P1
P1
W2
02.28
02.37
02.372"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:54 AMAE410
CUSTODIAN
ROOM 176
(ALTERNATE
1)JOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
02.03 EXISTING CONC. COLUMN
02.09 EXISTING BEAM
02.28 EXISTING 12" X 8" X 16" CMU WALL
02.37 EXISTING CONC. FOUND. WALL, 16" THICK
08.03 SCH'D DOOR
08.06 SCH'D DOOR AND PARTITION IF ALTERNATE IS
ACCEPTED BY OWNER
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.10 WALL BASE
09.14 FRP. FINISH
10.13 WALL MOUNTED ADJUSTABLE BRACKET SHELVES,
PROVIDE BLOCKING AS REQ'D
22.10 FLOOR SINK, RE. PLUMBING DWG.
SCALE: 1/2" = 1'-0"
A5 CUSTODIAN ROOM 176 FLOOR PLAN (ALT. 1)
SCALE: 1/2" = 1'-0"
C5 CUSTODIAN RM. 176 RCP (ALT. 1)
SCALE: 1/2" = 1'-0"
A3 CUSTODIAN ROOM 176 FINISH PLAN (ALT. 1)
SCALE: 1/2" = 1'-0"
C3 CUSTODIAN - NORTH (ALT. 1)
SCALE: 1/2" = 1'-0"
E3 CUSTODIAN - SOUTH (ALT. 1)
SCALE: 1/2" = 1'-0"
C1 CUSTODIAN - WEST (ALT. 1)
SCALE: 1/2" = 1'-0"
E1 CUSTODIAN - EAST (ALT. 1)
2 11/05/20 Addendum #2
17
K
J1
A5
AE300
178
EQUIP. RM.
P3S
P3S
178
STAIR
1-L
ALIGN
176
CUSTODIAN
ALT. 1
17
K
J1
EQUIP. RM.
178
STAIR
1-L
B9'-0"
C3
F3 P1B4
178
EQUIP. RM.
06.03
AE411D1
D3
C3
06.02
M2
M1
1' - 3"2' - 10"2' - 2"2' - 6"06.02
08.03
1' - 8"
P1
M2
09.10
B4
02.282' - 6"2' - 2"2' - 10"06.02
1' - 3"
1' - 8"
09.01
P1
M2
09.10
B4
08.03
09.01
P1
09.10
B4
3' - 0"3' - 0"2' - 10"2' - 2"2' - 6"06.02
3' - 0"3' - 0"3' - 0"1' - 8"
260
1'-8"
260
1'-8"
260
1'-8"
260
1'-8"
302
1'-3"
302
1'-3"
302
1'-3"
M1M1M1M1
M2
301
1'-3"
3' - 0"1' - 8"1 1/2"1"
M1M1M1M1
1"1 1/2"
P1
P1
02.28
02.372"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:50:59 AMAE411
EQUIPMENT
ROOM
(ALTERNATE
2)JOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A5 EQUIP. RM. FLOOR PLAN (ALT. 2)
SCALE: 1/2" = 1'-0"
C5 EQUIPMENT RM. 178 RCP (ALT. 2)
SCALE: 1/2" = 1'-0"
A3 ENLARGED EQUIPEMNT ROOM FINISH PLAN (ALT. 2)
02.28 EXISTING 12" X 8" X 16" CMU WALL
02.37 EXISTING CONC. FOUND. WALL, 16" THICK
06.02 SOLID SURFACE COUNTERTOP
06.03 BASE/UPPER CABINETS
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.10 WALL BASE
SCALE: 1/2" = 1'-0"
C3 EQUIPMENT ROOM - NORTH (ALT. 2)
SCALE: 1/2" = 1'-0"
D3 EQUIPMENT ROOM - SOUTH (ALT. 2)
SCALE: 1/2" = 1'-0"
C1 EQUIPMENT ROOM - WEST ((ALT. 2)
SCALE: 1/2" = 1'-0"
D1 EQUIPMENT ROOM - EAST ((ALT. 2)
1 10/30/20 Addendum #1
F6 T3-
207D
STORAGE
AE413
B5
D2
B4
D5
F7
23.02
23.046' - 6"1' - 3"
THIS STORAGE ROOM TO BE
TURNED INTO STEAM ROOM
09.12
TYP.
1/4" / 1'-0"1' - 8"EQEQEQEQEQSTEAM ROOM
207D
F6 T3-
261E
STORAGE
AE413 A2
A4
B2
A5
09.12
1' - 8"1' - 3"4' - 8"23.02
THIS STORAGE ROOM TO BE
TURNED INTO STEAM ROOM
SIM.
1/4" / 1'-0"
23.04 EQEQEQEQF7
STEAM ROOM
261E
09.15
09.12
23.04
1' - 0"23.02
1' - 0"5' - 0"1' - 6"T3
F6
26.05
TYP.
09.15
08.034' - 6"1' - 6"T3
26.05
TYP.
09.15
1' - 0"5' - 0"23.02
TYP.1' - 6"09.19
C6
T3
26.05
TYP.
09.15
09.12
1' - 0"23.04
1' - 6"T3
F6
09.19
C6
26.05
TYP.
09.15
1' - 6"4' - 6"T3
26.05
TYP.
09.15
09.12
23.04
6' - 0"23.02
1' - 6"F6
T3
5' - 0"1' - 0"26.05
TYP.
09.15
08.03
1' - 0"23.02
TYP.1' - 6"T3
09.19
C6
26.05
TYP.
09.15
09.12
23.04
1' - 6"F6
T3
09.19
C6
26.05
TYP.6' - 0"FINISH TAG LEGEND
F WB
101
ROOM NAME
SEE FINISH LEGEND ON SHEET AE610 FOR
FINISHES
X = KEEP EXISTING FINISH.
PATCH & REPAIR AS
REQUIRED
WALL FINISH
BASE FINISEFLOOR
FINISH
ROOM
NUMBER
FLOOR FINISH HATCH
LEGEND
CARPET
VCT
CONCRETE
TILE
TERAFLEX2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:04 AMAE413
STEAM
ROOM
PLAN &
ELEVATION
(ALTERNATE
3)JOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
D6 MEN'S EMPLOYEE STEAM ROOM 207D (ALT.3)
SCALE: 1/2" = 1'-0"
A6 WOMEN'S EMPLOYEE STEAM ROOM 261E (ALT.3)
SCALE: 1/2" = 1'-0"
A5 STEAM ROOM 261E - NORTH (ALT.3)
SCALE: 1/2" = 1'-0"
A4 STEAM ROOM 261E - SOUTH (ALT.3)
SCALE: 1/2" = 1'-0"
A2 STEAM ROOM 261E - WEST (ALT.3)
SCALE: 1/2" = 1'-0"
B2 STEAM ROOM 261E - EAST (ALT.3)
SCALE: 1/2" = 1'-0"
B5 STEAM ROOM 207D - NORTH (ALT.3)
SCALE: 1/2" = 1'-0"
B4 STEAM ROOM 207D - SOUTH (ALT.3)
SCALE: 1/2" = 1'-0"
D5 STEAM ROOM 207D - WEST (ALT.3)
SCALE: 1/2" = 1'-0"
D2 STEAM ROOM 207D - EAST (ALT.3)
08.03 SCH'D DOOR
09.12 SCH'D SEAT TILE
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
09.19 SCH'D CEILING TILE
23.02 STEAM HEAD
23.04 TEMPERATURE SENSOR
26.05
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
4 Date 4 ASI #1
B
LEVEL 2
91' -0"
LEVEL 3
109' -0"
02.3002.26
02.09
02.27
02.29 02.41
05.06
02.35
02.36
02.44
08.03
FIN. CLG.
09.01
09.18
09.15
09.19
05.06
09.1809.12 BULL NOSE
FRONT EDGE
1' - 6"1' - 8"
03.08
32.08
23.05
AE414
A1
D1
AE414
99' - 0"
E
LEVEL 2
91' -0"
FIN. CLG.
02.39
03.08
BULL NOSE
FRONT EDGE
23.05
08.03
05.06 1' - 6"1' - 8"
32.08
02.35
02.36
100' - 0"
05.17 09.01
09.15
09.01
05.06
02.02
AE414
B1
SIM.
D1
AE414
SIM.
08.02
99' - 0"
1
B
D2
AE414
207D
7' - 8"13' - 9"A1
AE414
SIM.
C5
AE402
SIM.
STEAM ROOM
207D
A2
AE414
261E6' - 9"4' - 9"10' - 0"B1
AE414
D1
AE414
SIM.
SIM.
STEAM ROOM
261E
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D WALL TILE
MORTAR
GROUT
3 5/8" METAL STUD
EXISTING
FACE BRICK
EXISTING
CMU
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D
CEILING TILE,
6" METAL STUD
BATT INSULATION
MORTAR
SEALED SLIP JOINT
WATERPROOF
MEMBRANE
WATERPROOF
MEMBRANE
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D WALL TILE
MORTAR
GROUT
1 5/8" METAL STUD
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D
CEILING TILE,
SLOPED
6" METAL STUD
MORTAR
SEALED SLIP JOINT
EXISTING WALL
WATERPROOF
MEMBRANE
WATERPROOF
MEMBRANE
2 " / 1 ' -0 "
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D
WALL TILE
MORTAR
GROUT
3 5/8" METAL STUD
1/2" CEMENTITIOUS
BACKER UNIT
SCH'D
CEILING TILE,
SLOPED
6" METAL STUD
MORTAR
SEALED SLIP JOINT
2 " / 1 ' -0 "
SCH'D
WALL TILE
5/8"
GYP. BOARD
MORTAR
GROUT
LOCKER
ROOM
STEAM
ROOM
WATERPROOF
MEMBRANE
WATERPROOF
MEMBRANE
1
B
8'-0" D
C6
08.02
A9'-0"
C4
8' - 9"STEAM ROOM
207D
2" / 1'-0"2" / 1'-0"
1' - 2"3' - 3"4' - 9"3' - 3"3' - 9"
08.02 A9'-0"
C4
STEAM ROOM
261E
8'-0" D
C6
2" / 1'-0"2" / 1'-0"1' - 2"3' - 8"4' - 1"CEILING FINISH LEGEND
A -GYPSUM
C -OPEN TO STRUCTURE
B -ACOUSTIC CEILING TILE
D -PORCELAIN TILE
CEILING LEGEND
SURFACE MOUNTED
FLUORESCENT
OR LED FIXTURE
MECHANICAL
FIXTURES
FIRE SPRINKLERS
RECESSED LIGHT
WALL MOUNTED
FLUORESCENT
OR LED FIXTURE
XTG
FINISH
A
CEILING
HEIGHT
CEILING TYPE
CEILING FINISH
XTG = EXISTING CEILING HEIGHT
SEE SHEET AE610 FOR FINISH LEGEND
CEILING TYPES:
A = GYPSUM BOARD
B = ACOUSTIC CEILING TILES
C = OPEN TO STRUCTURE
D = PORCELAIN TILE
X = EXISTING FINISH TO REMAIN
2X4 FLUORESCENT
OR LED FIXTURE
2X2 FLUORESCENT
OR LED FIXTURE
STRIP FLUORESCENT
OR LED FIXTURE2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:08 AMAE414
STEAM
ROOM
PLAN,
SECTION &
DETAILS
(ALTERNATE
3)JOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
D2 STEAM ROOM 207D SECTION (ALT.3)
SCALE: 1/2" = 1'-0"
A2 STEAM ROOM 261E SECTION (ALT.3)
02.02 EXISTING WALL TO REMAIN
02.09 EXISTING BEAM
02.26 EXISTING PRECAST CONC. FASCIA
02.27 EXISTING BRICK VENEER
02.29 EXISTING 8" X 8" X 16" CMU WALL
02.30 EXISTING ROOF, 2" RIGID INSULATION & 1 1/2"
METAL DECK
02.35 EXISTING CONC. SLAB ON GRAD, 4" THICK
02.36 EXISTING GRAVEL
02.39 EXISTING 4 1/2" CONC.SLAB ON 1 1/2" METAL DECK
02.41 EXISTING OPEN WEB STEEL JOIST
02.44 EXISTING CONC. FOUND. WALL 12" THICK
03.08 8" CONCRETE HOUSEKEEPING PAD WITH 1/2"
CHAMFER
05.06 3 5/8" METAL STUD
05.17 1 1/2" METAL FURRING
08.02 CEILING ACCESS PANEL
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.12 SCH'D SEAT TILE
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
09.18 CEMENTITIOUS BACKER UNIT
09.19 SCH'D CEILING TILE
23.05 STEAM GENERATOR
32.08 4" GRAVEL
SCALE: 1/2" = 1'-0"
D6 STEAM ROOM 207D FLOOR PLAN (ALT.3)
SCALE: 1/2" = 1'-0"
A6 STEAM ROOM 261E FLOOR PLAN (ALT.3)
SCALE: 1 1/2" = 1'-0"
A1 STEAM ROOM WALL ASSEMBLY
SCALE: 1 1/2" = 1'-0"
B1 STEAM ROOM WALL ASSEMBLY
SCALE: 1 1/2" = 1'-0"
D1 STEAM ROOM WALL ASSEMBLY
SCALE: 1/2" = 1'-0"
D5
STEAM ROOM 207D
REFLECTED CEILING PLAN @ 91' - 0" (ALT.3)
SCALE: 1/2" = 1'-0"
A5
STEAM ROOM 261E
REFLECTED CEILING PLAN @ LEVEL 91' - 0" (ALT.3)
2 11/05/20 Addendum #2
4 Date 4 ASI #1
4"
#4 REBARS @ 18" O.C. EACH
WAY, ALSO RE. STRU. DWG.
#4 REBARS @ 32" O.C. EPOXY
DOWEL INTO EXISTING CONC.
SLAB, ALSO RE. STRU. DWG.
GEOFOAM
EXISTING
SUSPENDED
CONCRETE TIERS
#4 REBARS @ 16" O.C. EPOXY
DOWEL INTO EXISTING CONC.
TIERS, ALSO RE. STRU. DWG.
1/2" FROSTED TEMPERED
GLASS GUARDRAIL W/ 1/2"
JOINTS EVERY 4' MAX &
POLISHED EXPOSED EDGES
EXSTING
FLOOR MOUNT SEAT
1" X 1" STAINLESS STEEL U-
CHANNEL TOP RAIL W/
PROTECTIVE INSERT
GLAZING GASKET
SEALANT,
BLACK, @ EACH SIDE2' - 2"1" X 1" STAINLESS STEEL U-
CHANNEL TOP RAIL W/
PROTECTIVE INSERT
ROUND CORNER
ALUMINUM BASE SHOE
STAINLESS STEEL
CLADDING TO MATCH
RAILINGS EACH SIDE
OF BASE SHOE
STAINLESS STEEL ENDCAPS @
EVERY BASE SHOE TERMINATION -
TO MATCH RAILING
4 1/2"1/2" X 4" STEEL PLATE
1/2" CAP SCREW
@ 12" O.C.
2"
W/ WALL BACK SUPPORT
20" TO 24"1"17" TO 19"WALL ATTACHED
ADA BENCH
EXISTING WALL
PARTITION
EXISTING CONC.
SLAB ON GRADE
INSTALL BLOCKING
IN WALL AS
REQUIRED TO
ANCHOR BENCH
EXISTING WALL
SCH'D WALL PARTITION
3 5/8" METAL STUD
MIRROR
ATTACHED TO
THE LOCKER
SOLID PLASTIC LOCKER
CONC. SLAB ON GRADE
SCH'D TILE BASE
FLOOR TILE ON
SLOPED MORTAREXISTING CONC.
SLAB ON GRADE
CMU BASE
20 GA. SLOPED CAP TOP W/
20 GA. CLOSURE @ EA. END
OF A LOCKER RUN
20 GA. GUSSET @ 4' -0" O/C
2"1' - 8"5"MECH. EXHAUST DUCT, RE. MECH. DWG.
MTL. STUD FURRING & INSULATION TO SPAN
FROM FLOOR TO FLOOR @ ALL EXTERIOR
WALL LOCATIONS
1' - 4"SOLID PLASTIC LOCKER
EXISTING WALL
CONC. SLAB ON GRAD
SCH'D WALL
EXISTING CONC.
SLAB ON GRADE
SCH'D TILE BASE
FLOOR TILE ON
SLOPED MORTAR
CMU BASE
20 GA. SLOPED CAP TOP W/
20 GA. CLOSURE @ EA. END
OF A LOCKER RUN
20 GA. GUSSET @ 4' -0" O/C5"3"1' - 3"2"1' - 4"MECH. VENTED CAVITY
1" SOLID SURFACE
SOLID PLASTIC LOCKER
CMU BASE
TILE BASE
FLOOR TILE ON
SLOPED MORTAR
CONC. SLAB
ON GRADE
1/2" PLYWOOD
ON 2X3 (2)
TREATED WOOD
20 GA. SLOPED CAP TOP W/
20 GA. CLOSURE @ EA. END
OF A LOCKER RUN
20 GA. GUSSET @ 4' -0" O/C5"1' - 0"1"1' - 4"2"1' - 3"3"1' - 3"
MECH. VENTED CAVITY
CMU BASE
LOCKER
1X4 SLEEPER
20 GA. SLOPING CAP TOP W/
20 GA. CLOSURE @ EACH
END OF LOCKER RUN
20 GA. GUSSETS @ 4' -0" O/C
SCH'D WALL
PARTITION
SCH'D TILE
SCH'D TILE BASE
THICK SET FLOOR TILE,
SLOPED TO DRAIN
CONC. SLAB
ON GRADE6"8"MECH. VENTED CAVITY
NEW CMU WALL
EXISTING BRICK WALL
7/8" HAT CHANNEL
5/8 TYPE X GYP. W/
TEXTURED PAINT
1 1/2”X 2”STAINLESS
STEEL TRIM, MATCH
EXISTING
(2) LAYER TYPE X. GYP.
PAINT, RE. FINISH SCHEDULE
2" X 2" X 4' STAINLESS STEEL
CORNER GUARD, TYP. AT ALL
EXPOSED GYP. BOARD
VERTICAL CORNERS
EXISTING COLUMN
3 5/8" METAL STUD, TYP.
NOTE: APPLY THIS DETAIL TO ALL EXPOSED/EXISTING COLUMN AND
BEAM THAT ARE RELATED TO THE PROJECT
MIN.4"DEPTH VARIESMIN.
4"
MIN.
4"
EXPANSION
JOINT
EXPANSION JOINT
CONCRETE SLAB AND/OR
RAMP SEE STRUCTURAL
GRAVEL
EARTH
STAINLESS STEEL GRATE
W/ WALL BACK SUPPORT
20" TO 24"1"17" TO 19"WALL ATTACHED ADA
FOLDING BENCH
SCH'D WALL
EXISTING CONC.
SLAB ON GRADE
INSTALL BLOCKING
IN WALL AS
REQUIRED TO
ANCHOR BENCH1' - 3"5 1/2"2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:11 AMAE500
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1 1/2" = 1'-0"
C5 ADA SEATNG PLATFORM DETAIL
SCALE: 1 1/2" = 1'-0"
C2 ADA FIXED SEATING DETAIL
SCALE: 1 1/2" = 1'-0"
A4 LOCKER SECTION
SCALE: 1 1/2" = 1'-0"
A3 LOCKER SECTION
SCALE: 1 1/2" = 1'-0"
A1 LOCKER SECTION
SCALE: 1 1/2" = 1'-0"
C3 LOCKER SECTION
SCALE: 1 1/2" = 1'-0"
D2 CMU/BRICK WALL DETAIL
SCALE: 1 1/2" = 1'-0"
E2 2 HR. RATED COLUMN WRAP DETAIL
SCALE: 1 1/2" = 1'-0"
D1 TRENCH DRAIN DETAIL
SCALE: 1 1/2" = 1'-0"
C1 ADA FOLDING SEATING DETAIL
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
1/2" CLEAR
TEMPERED
GLASS
A4
AE501
ALUMINUM
COMPOSITE PANEL
SCHEDULED BASE
1/2" WIDE ALUMINUM
COMPOSITE PANEL JOINT
1" SQUARE
STAINLESS
U TOP TRIM
STAIR RISERS
BEHIND
1/2" WIDE GLASS
OPEN JOINT -POLISHED
EDGES
1 1/2"3' - 6"1"2' - 10 1/2"6 1/2"1/2" CLEAR
TEMPERED
SAFETY GLASS
GUARDRAIL
A4
AE501
ALUMINUM
COMPOSITE PANEL
1/2" WIDE ALUMINUM
COMPOSITE PANEL
JOINT
1" SQUARE STAINLESS
U TOP TRIM
CONCRETE STAIR RISERS WITH
WOOSTER ANTI-SLIP NOSING
CAST INTO EACH RISER
1/2" WIDE GLASS OPEN
JOINT -POLISHED EDGES
1" SQUARE STAINLESS U
TOP TRIM 3' - 6"1"2' - 10 1/2"6 1/2"3' - 6"1 1/2"
C1
AE501
C2
AE501
A4
AE501
GYP. BOARD REVEAL
MITER CORNERS TYP.
2" TYP.2" TYP.2"
FASTENER.
RE: MFR. RECOMMENDATION
TAPE & JOINT COMPOUND
FRY REGLET REVEAL
SCHEDULED PARTITION
5/8" GYP. BOARD PANEL
SCHEDULED
PARTITION
5/8" GYP. BOARD PANEL
TAPE & JOINT COMPOUND
ALUMINUM TRIM GYPSUM
BOARD FLUSH BASE
4"FINISH FLOOR
NOTE: ALIGN
FINISHED SURFACES 4 1/2"1/4" CLEAT
3/4" WOOD VENEER
PLY. PANEL
1" ALUMINUM CHANNEL
BASE W/ RETURN KEY
FINISH FLOOR
5/8" GYP. BOARD
OR EXISTING
SUBSTRATE
METAL FURRING
SCHEDULED BASE SOLID WOOD BLOCKING TO
ALIGN FACE OF BASE WITH
FACE OF WOOD PANEL
SEALANT, COLOR: BLACK
PARTITION
SCH'D
1"6 1/2"1"1 1/2"1"1"
HORIZONTAL SOLID
WOOD SUPPORT,
PAINTED BALCK @ 24"
O.C. VERTICALLY
SOLID OAK,
VERTICAL SLAT GRILLE,
STAINED TO MATCH EXISTING
WOOD PANELING
1 1/2" X 3/4" VERTICAL
HARDWOOD SLATS ATTACHED
TO 3/4" THICK PLYWOOD PANEL
SCHEDULED BASE
SCHEDULED PARTITION
SOLID WOOD BLOCKING TO
ALIGN FACE OF BASE WITH
FACE OF WOOD SLATS
PREFINISHED FLAT BLACK
SHEET METAL FLASHING,
FINISH BEHIND WALL BASE
TAPER BOTTOM OF SLATS TO
ACCOMODATE FLASHING
2 1/2"PARITION
SCH'D
1 1/2" X 3/4" VERTICAL
HARDWOOD SLATS @ 1 1/2" O.C.
ATTACHED TO SOLID WOOD
FRAME. VERTICAL SLAT PANEL
SHALL HAVE REMOVABLE
PORTION FOR MAINTENANCE
SCHEDULED BASE
SOLID WOOD BLOCKING TO
ALIGN FACE OF BASE WITH
FACE OF WOOD SLATS
PAINT EXPOSED TOP OF
BLOCKING FLAT BLACK
2X4 HORIZONTAL FRAME @24"
O.C. MAX, PAINTED FLAT BLACK
ALL SIDES
2X4 VERTICAL FRAME @24"
O.C. MAX, PAINTED FLAT BLACK
ALL SIDES
SOLID WOOD BLOCKING
SUPPORTING FRAME1/2"PREFINISHED FLAT BLACK
SHEET METAL FLASHING, FINISH
BEHIND WALL BASE
ALUMINUM COMPOSITE PANEL
CLIPPED TO PLYWOOD
SUBSTRATE
3/4" FIRE RETARDANT TREATED
PLYWOOD
SCHEDULED BASE
1/2" X 4" STEEL BASE PLATE
SOLID WOOD BLOCKING TO
ALIGN FACE OF BASE WITH
FACE OF ALUMINUM PANEL
SEALANT, COLOR: BLACK
WRAP ALUMINUM FINISH
AROUND END OF PANEL
3"PARTITION
SCH'D
3' - 6"1" X 1" BRUSHED STAINLESS
STEEL U-CHANNEL TOP RAIL W/
PROTECTIVE INSERT
1/2" CLEAR TEMPERED GLASS
GUARDRAIL WITH POLISHED EDGES
CONCRETE SLAB
SEALANT,
COLOR: BLACK
BRUSHED STAINLESS
STEEL BASE CLADDING
J-TRIM, MUDDED IN
PARTITION
SCH'D
FASCIA MOUNTED
BASE SHOE
GLAZING GASKET
EXISTING STRUCTURAL BEAM,
BO. ELE. 89' -8", VERIFY
CONCRETE
STEPPED
AISLE
CORE DRILL CONCRETE
AND SET TOP AND BOTTOM
POSTS IN EPOXY GROUT
POWER SUPPLY FOR LED
LIGHT FROM BELOW AND
TRAVELS UP POST2' - 10"1 1/2" DIAMETER STAINLESS
STEEL HAND RAIL
1 1/2" DIA STAINLESS STEEL
BALUSTER POST -REFER
TO ELEVATION
1 1/2" DIAMETER STAINLESS
STEEL MID RAIL WITH LED LIGHT
STRIP, CONTINUOUS BETWEEN
HANDRAIL BRACKETS1' - 0"1' - 0"1 1/2" DIAMETER STAINLESS
STEEL MID RAIL
2' - 10"1 1/2" DIAMETER STAINLESS
STEEL HAND RAIL
EXISTING
CONCRETE
STEPPED AISLE
1 1/2" DIA STAINLESS STEEL
BALUSTER POST -REFER
TO ELEVATION
CORE DRILL CONCRETE
AND SET POST IN EPOXY
GROUT
ADA COMPLIANT STAINLESS
STEEL POST CAP WITH
ADJUSABLE RAILING BRACKET.
1 1/2" DIAMETER STAINLESS
STEEL MID RAIL WITH LED LIGHT
STRIP, CONTINUOUS BETWEEN
HANDRAIL BRACKETS1' - 0"1' - 0"1 1/2" DIAMETER STAINLESS
STEEL MID RAIL
3' - 6"1" X 1" STAINLESS STEEL
U-CHANNEL TOP RAIL W/
PROTECTIVE INSERT
1/2" CLEAR TEMPERED GLASS
GUARDRAIL WITH POLISHED EDGES
SEALANT, COLOR: BLACK
GLAZING GASKET
ALUMINUM COMPOSITE PANEL
CLIPPED TO PLYWOOD
SUBSTRATE
CONCRETE SLAB
3/4" FIRE RETARDANT TREATED
PLYWOOD
SCHEDULED BASE
6"
1/2" X 4" STEEL BASE PLATE
SEALANT,
COLOR: BLACK
SOLID WOOD BLOCKING TO
ALIGN FACE OF BASE WITH
FACE OF ALUMINUM PANEL
STRUCTURAL TAPE AND EPOXY
ALUMINUM WRAPS UP AND
OVER SILL
SOLID WOOD BLOCKING
SEALANT, COLOR: BLACK
WRAP ALUMINUM FINISH
AROUND END OF PANEL6 1/2"2"SLOPED 10"
CHANNEL,
MATCH STAIR
RISER ANGLE
CORE DRILL AND SET
RAILING POST IN EPOXY
GROUT COORDINATE
CORE LOCATION WITH
STRUCTURAL ENGINEER -
TYPICAL AT ENDS
D1
AE501
D2
AE501
POWER SUPPY FOR LED
LIGHTED HANDRAIL
TRAVELS UP THROUGH
FLOOR SLAB FROM
BELOW
POWER SUPPY FOR LED LIGHTED
HANDRAIL TRAVELS UP THROUGH
FLOOR SLAB FROM BELOW
1 1/2" DIAMETER
STAINLESS STEEL
HAND RAIL TURNED
DOWN AT ENDS TO
FORM POSTS
1 1/2" DIAMETER STAINLESS STEEL HAND
RAIL WITH LED LIGHT STRIP, CONTINUOUS
BETWEEN HANDRAIL BRACKETS
4"
4"R 6"R 6"
EXISTING BEAM BELOW
STEPPED AISLE-TYP
EXISTING STEPPED CONCRETE
SLAB FOR SEATING-TYP
EXISTING CONCRETE RISER
FOR STEPPED AISLE-TYP
HANDRAIL HEIGHT NOTE:
EXISTING STEPPED AISLES WERE CONSTRUCTED UNDER
PREVIOUS BUILDING CODE WHICH ALLOWED NON-UNIFORM
TREADS. IT IS TECHNICALLY INFEASIBLE TO REVISE THE
STEPPED AISLES TO A UNIFORM TREAD LENGTH. DUE TO THIS
NON-UNIFORM SLOPE ANGLE, THE HANDRAIL SLOPE VARIES
ABOVE THE NOSING OF THE RISER; THE HEIGHT OF THE
HANDRAIL ABOVE EACH NOSING SHALL BE WITHIN THE 34-38"
REQUIRED BY CURRENT 2018 IBC.2' - 10"3' - 1"1'
-
0"D2
AE501
91' - 0"
2 ND LEVEL
LANDING
ROW 9
ROW 8
ROW 7
ROW 6
ROW 5
ROW 4
ROW 3
ROW 2
ROW 1
80' - 9 1/2"
4"
ADA-COMPLIANT POST
CAP WITH
ADJUSTABLE
MOUNTING BRACKET
TYPICAL -SEAT ROW NUMBER
2' - 4" +/-
2' - 4"
5' - 8"2' - 4"5' - 8"2' - 4"5' - 8"2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:14 AMAE501
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
C1 GLASS GUARDRAIL
SCALE: 1/2" = 1'-0"
C2 GLASS GUARDRAIL
SCALE: 1/2" = 1'-0"
A1 ENLARGED GLASS GUARDRAIL
SCALE: 1 1/2" = 1'-0"
B6 GYPSUM BOARD REVEAL INTERSECTION
SCALE: 1 1/2" = 1'-0"
C5 TYPICAL GYPSUM BOARD REVEAL PLAN
SCALE: 1 1/2" = 1'-0"
B5 TYPICAL GYPSUM BOARD PANELING SECTION
SCALE: 1 1/2" = 1'-0"
A6 TYPICAL BASE @ PLYWOOD PANELING SECTIONSCALE: 1 1/2" = 1'-0"
C4 WOOD SLAT PLAN
SCALE: 1 1/2" = 1'-0"
D5 WOOD SLAT BASE DETAIL
SCALE: 1 1/2" = 1'-0"
D4 WOOD SLAT BASE DETAIL @ RETURN AIR
SCALE: 1 1/2" = 1'-0"
D6 ALUMINUM PANEL BASE DETAIL
SCALE: 1 1/2" = 1'-0"
A2 GLASS GUARDRAIL DETAIL @ WALKWAY
SCALE: 1 1/2" = 1'-0"
D1 STEPPED AISLE HANDRAIL DETAIL
SCALE: 1 1/2" = 1'-0"
D2 STEPPED AISLE HANDRAIL INTERMEDIATE POST DETAIL
SCALE: 1 1/2" = 1'-0"
A4 GLASS GUARDRAIL DETAIL @ BLEACHER
SCALE: 1/2" = 1'-0"
A5 TYPICAL EXISTING STEPPED AISLE LED LIGHTED HANDRAIL DETAIL
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
4 Date 4 ASI #1
LEVEL 2
91' -0"11' - 4"1' - 4"9' - 0"2' - 4"8' - 8"3"1' - 2"1' - 8"4"1' - 7"
3/4" TOE KICK
NATURAL WOOD
MILLWORK FRONT
WOOD VENEER
GLASS DISPLAY CASE
W/ SLIDING DOORS
GLASS
SHELVES
CUSTOME
WOOD GRILLE6' - 0"STAINLESS STEEL
BASEBOARD
1' - 4"
6"1' - 11 1/2"1' - 4"1' - 4"1' - 4 1/2"EXISTING
CONC. SLAB
EXISTING CONC.
TOPPING SLAB
EXISTING CMU
WALL W/ WOOD
PANEL
SPRAY APPLIED
FIREPROOFING
STEEL TUBE
3/4" FIRE
RETARDANT
TREATED
PLYWOOD
WRAP ALUMINUM
FINISH AROUND
PANEL END
3"
AE502
A2
2' - 4"99' - 8"
3"
NORTH
EXIT
E003
EXISTING
CONC. SLAB
EXISTING CONC.
TOPPING SLAB
EXISTING CMU
WALL W/ WOOD
PANEL
SCH'D CEILING
DOOR
FRAME
SCH'D
WALL
PARTITION
SPRAY APPLIED
FIREPROOFING
STEEL TUBE
3/4" FIRE
RETARDANT
TREATED
PLYWOOD
WRAP ALUMINUM
FINISH AROUND
PANEL END
1 5/8" STEEL
STUD LEDGER
CONTINUOUS
LED STRIP LIGHT
WITH DIFFUSER
SCH'D DOOR
L
NORTH
EXIT
E003
EXISTING STUD
WALL W/ WOOD
PANEL
DOOR
FRAME
SCH'D
WALL
PARTITION
SCH'D DOOR
EXISTING
CONC. SLAB
EXISTING CONC.
TOPPING SLAB
SCH'D CEILING
BASE MILLWORK
TOP MILLWORK
1/4" TEMPERED GLASS
BASE GLIDER
UPPER ROLLERS2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:16 AMAE502
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1 1/2" = 1'-0"
A5 WOOD SLAT WALL AT DISPLAY
SCALE: 1 1/2" = 1'-0"
A3 INTERIOR NORTH WALL DETAIL AT LIGHT LOCK
SCALE: 1 1/2" = 1'-0"
C3 INTERIOR SOUTH WALL DETAIL AT LIGHT LOCK
SCALE: 1 1/2" = 1'-0"
A2 DISPLAY CASE GLASS DETAIL
1 10/30/20 Addendum #1
RIM @ 10' - 0" A.F.F.3 X 2
WELDED
BRACE
FLOOR FINISH
AE503
A6
FLOOR FINISH10' - 0"JACKKNIFING
SIDE BRACE
1/4, 7 X 19
AIRCRAFT
CABLE
6-5/8" O.D.
MAIN DROP PIPE
3-1/2" O.D.
PIPE
AE503
B6
SIM.
AE503
C62"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:17 AMAE503
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1 1/2" = 1'-0"
A6 HINGE CLAMP
SCALE: 1/2" = 1'-0"
A5 BAKSETBALL BACKSTOP
SCALE: 1 1/2" = 1'-0"
B6 BEAM CLAMP
SCALE: 1 1/2" = 1'-0"
C6 BRACE CLAMP
SCALE: 1/2" = 1'-0"
A3 BASKETBALL BACKSTOP
2 11/05/20 Addendum #2
THIS ENTIRE SHEET IS FOR
REFERENCE ONLY, ALSO REFER TO
STRUCTURAL DWG. AND
MANUFACTURER PRODUCT INFO.
SINGLE PLY ROOFING
EXTG. OR NEW INSULATION
EXISTING METAL ROOF DECK 12" MIN. @ HIGHEST PT.COVER BOARD IF APPLICABLE
6" MIN.
EXTG. SINGLE PLY ROOFING
STL. TUBE, RE. STR. DWG
3 5/8" MTL. STUD BETWEEN STL. TUBES
2" RIGID INSULATION
5/8" EXT. SHEATHING
STL . CHANNEL, RE. STR. DWG.
RTU
MECH. DUCT
BLACK BUTYL
SEALANT
ALUMINUM
RETAINER CAP
POLYURETHANE
SEALANT
FASTENERS
EXISTING ROOF
CURB
ACRYLIC OUTER DOME
ACRYLIC INNER DOME
CONDENSATE PROVISION
SANTOPRENE
THERMOPLASTIC
GASKET (UL LISTED)
CONDENSATE
WEEP HOLES
SEALANT
ALUMINUM CURB FRAME
SINGLE PLY ROOFING,
MATCH EXISTING
6" WIDE LAP STRIP
EXISTING ROOFING
12" MIN.12" MIN.1"PREFINISHED METAL
FLASHING, AS
REQUIRED
EXISTING
SURFACE MODIFY ECISTING ROOF CURB IF NECESSARYBASE FLASHING
FLASHING
SEAM EDGE TREATMENT
4"9" MIN.SEALANT
VARIES
VENT STACK
1/2" GYPSUM
PROTECTION BOARD,
MATCH EXISTING, IF
REQUIRED
5/8" GLASS MAT
SINGLE PLY. ROOFING,
MATCH EXISTING
OVERLAP
1' - 0"2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:18 AMAE504
ROOF
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1 1/2" = 1'-0"
A1 TYPICAL MECH. UNIT CURB DETAIL
SCALE: 6" = 1'-0"
A3 TYPICAL SKYLIGHT DETAIL
SCALE: 1 1/2" = 1'-0"
A5 TYPICAL PIPE PENETRATION
2 11/05/20 Addendum #2
SCHEDULED TILE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED TILE
CONCRETE SLAB
TILE MOVEMENT JOINT TO BE
INSTALLED IN ACCORDANCE
WITH TCNA EJ171 STANDARD;
SEALANT TO MATCH GROUT
COLOR.
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"SCHEDULED TERAFLEX
AND BACKING.
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
VINYL COMPOSITION TILE
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"8" DIA. DRAIN
CUT-OUT
4"3/8"CENTER LINE
OF DRAIN
SCHEDULED SHEET FLOORING
EDGE "T" TO COVER MARINE-GRADE
SILICONE SEALANT AT JOINT,
1/8" AND 3/16" MATERIAL THICKNESS
T-SHAPED RUBBER
WATER STOPPER
SHOWER PAN INSERT
GYPCRETE UNDERLAYMENT
INTEGRAL LEVEL SUPPORT
SOUND MAT
3/4" FLOOR SHEATHING
CONCRETE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED VINYL
COMPOSITION TILE.
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"CONCRETE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED TILE
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"CONCRETE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED TERAFLEX
AND BACKING.
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"CONCRETE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
CONCRETE
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED CARPET
AND BACKING
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"SCHEDULED CARPET AND
BACKING.
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
VINYL COMPOSITION TILE
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"SCHEDULED CARPET AND
BACKING.
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED TILE
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"SCHEDULED CARPET AND
BACKING.
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
SCHEDULED CARPET
AND BACKING
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"2"
EQ EQ
RUBBER
TRANSITION STRIP
CONCRETE
SCHEDULED CARPET
ROUTED FLOORING
ADHESIVE
DOOR
STAINLESS STEEL FLAT
HEAD SCREWS 6 1/2" O.C.
SEALANT 1/4" MIN.
BEAD IN 3 LOCATIONS
2"
EQ EQ
RUBBER
TRANSITION STRIP
CONCRETE
MARLEY FLOORING
ROUTED FLOORING
ADHESIVE
DOOR
SEALANT 1/4" MIN.
BEAD IN 3 LOCATIONS
2"
EQ EQ
STAINLESS STEEL
TRANSITION STRIP
SCHEDULED VINYL
COMPOSITION TILE
VINYL COMPOSITION
TILE
ROUTED FLOORING
DOOR
STAINLESS STEEL FLAT
HEAD SCREWS 6 1/2" O.C.
SEALANT 1/4" MIN.
BEAD IN 3 LOCATIONS
SCHEDULED VINYL
COMPOSITION TILE.
STONE THRESHOLD,
SUBMIT PROFILE FOR
APPROVAL; WIDTHS
VARY.
VINYL COMPOSITION TILE
CONCRETE SLAB
WIDTH OF JAMB
VARIES WITH
T.O. UNRECESSED
CONC. FLOOR SLAB
DOOR PANEL
3/4"2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:21 AMAE505
FLOOR
TRANSITION
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 3" = 1'-0"
A5 TILE TO TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
A3 TERAFLEX TO VINYL COMPOSITION TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
A1 ROLL-IN SHOWER THRESHOLD
SCALE: 3" = 1'-0"
D1 CONCRETE TO VINYL COMPOSITION TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
B5 CONCRETE TO TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
B3 CONCRETE TO TERAFLEX METAL THRESHOLD
SCALE: 3" = 1'-0"
B1 CONCRETE TO CONCRETE METAL THRESHOLD
SCALE: 3" = 1'-0"
D3 CONCRETE TO CARPET METAL THRESHOLD
SCALE: 3" = 1'-0"
C5 CARPET TO VINYL COMPOSITION TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
C3 CARPET TO TILE METAL THRESHOLD
SCALE: 3" = 1'-0"
C1 CARPET TO CARPET METAL THRESHOLD
SCALE: 3" = 1'-0"
D5 CONCRETE TO CARPET TRANSITION
SCALE: 3" = 1'-0"
D6 CONCRETE TO MARLEY FLOORING TRANSITION
SCALE: 3" = 1'-0"
E1 VCT TO VCT TRANSITION
SCALE: 3" = 1'-0"
E3 VCT TO VCT METAL THRESHOLD
G2-T G2-T G2-T G2-T
G2-T
AL17' - 0"2"2' - 2"2"9' - 6"2"3' - 2"2"6' - 0"2"6' - 0"2"6' - 0"2"
22' - 0"
GLAZING TYPE
GLAZING SCHEDULE
G1
G1 1/4" GLASS
G1-T 1/4" TEMPERED GLASS
G2 1" GLASS
G2-T 1" TEMPERED GLASS
G3-T 1/4" TEMPERED & FROSTED GLASS
GENERAL DOOR NOTES
1. DOOR CALLOUTS ARE ON AE100 SERIES
KEYPLANS
2. MATCH EXISTING DOOR PANEL, FRAME COLOR
& FINISH
DOOR SCHEDULE NOTES (REFER TO DOOR
SCHEDULE "NOTES" COLUMN)
A. THIS DOOR IS INCLUDED AS AN ALTERNATE,
REFER TO ALTERNATES
B. COMBINE DOOR FRAME WITH ADJACENT
FRAME FOR 1 FRAME SYSTEM FOR ALL 4 DOORS
AS SHOWN IN PLAN.
C. REFER TO ALUMINUM STOREFRONT SYSTEMS
FOR FRAME TYPE
D. TEMPORARY CONSTRUCTION ACCESS DOOR,
CONTRACTOR'S OPTION FOR SECURITY AND
ACCESS PURPOSES.
E. VAPOR TIGHT STEAM ROOM DOOR, FRAME AND
SEAL SYSTEM.
F. FROSTED GLASS AT THIS GLASS PANEL.
PANEL & FRAME MATERIAL
HM HOLLOW METAL
WD FLUSH WOOD-THERMO FUSED DOOR
ALUM ALUMINUM STOREFRONT
FINISH
PAINT PAINT -MATCH EXISTING
STAIN THERMO FUSED TO MATCH EXISTING
DOOR SCHEDULE NOTES
WIDTH +1"PARTITION5/8" TYPE "X"
GYPSUM BOARD
TILE
(APPLIED AREA)
HM DOOR FRAME
3 5/8" METAL STUD
SEALANT @
BOTH SIDES
2"
SCHEDULED
DOOR
JAMB ANCHORS
PER JAMB MIN
FILL FRAME WITH
BATT INSULATION
TO MATCH
PARTITIONWIDTH + 1"PARTITIONHM DOOR FRAMESEALANT @
BOTH SIDES
2"PARTITIONSCH'D1/2"1/2"SCHEDULED
DOOR
FILL FRAME WITH
BATT INSULATION
TO MATCH
PARTITION
JAMB ANCHORS
3 PER JAMB MIN.8 1/2"5/8" TYPE "X"
GYPSUM BOARD
(APPLIED AREA)
HM DOOR FRAME
1" AIR GAP
8" X 8" X 16" CMU
2"
FACE BRICK DOOR
SCREW @ 24" O.C.
W/ CONDUIT SPACER
12 GA. METAL STRAP 8 1/2"5/8" TYPE "X"
GYPSUM BOARD
(APPLIED AREA)
HM DOOR FRAME
12" X 8" X 16" CMU
2"
DOOR
SCREW @ 24" O.C.
W/ CONDUIT SPACER
12 GA. METAL STRAP
SOLID SLAB W/
GLASS PANEL
P10
6"6"
NARROW HALF
GLASS PANEL
P21
WIDTH
SCH'D
3' - 6"6"VARIES6"6"6"WIDTH
SCH'D
6"VARIES 6"6"VARIES1' - 0"HEIGHTSCH'DWIDTH
SCH'D
SOLID SLAB W/
GLASS PANEL
P30 P30AHEIGHTSCH'DHEIGHTSCH'DALUMINUM
WIDE STILE
(MATCH EXIST'G)
WIDTH
SCH'D
4 1/2"4 1/2"4 1/2"10"HEIGHTSCHEDULEDFINISHED
FLOOR
P40
WIDTH
SCH'D
HEIGHTSCHEDULEDSTEAM ROOM
ALUMINUM
DOORHEIGHTSCH'D10"SOLID SLAB
P01HEIGHTSCH'DWIDTH
SCH'D
G1-T
G1-T
G1-T G2-T
G2-T
TYPICAL FRAME
F01
FRAME W/
SINGLE
SIDELIGHT
F21
NARRROW
FRAME
F10
FINISHED
FLOORHEIGHTSCH'D2"
WIDTH
SCH'D 2"HEIGHTSCH'D2"
WIDTH
SCH'D 2"4' - 0"2"1 1/2"3' - 1"1 1/2"HEIGHTSCH'D1 1/2"G1-T
8 1/2"
ALIGN
EXISTING CMU AND
BRICK WALL
STEEL ANGLE HEADER
AE702
E1
SIM
STEEL DOOR FRAME 2"2 1/2"1/4" THICK CLEAT
3/4" THICK
HARDWOOD VENEER
PANEL
ALIGN
EXISTING CMU AND
BRICK WALL
SIMSTEEL DOOR FRAME 2"1/4" THICK CLEAT
3/4" THICK
HARDWOOD VENEER
PANEL
12 GA. METAL STRAP
AE702
E1
SCHEDULED DOOR
SCREW @ 24" O.C.
W/ CONDUIT SPACER
FINISHED
FLOOR
2"2' - 8"2"2"4' - 4"2"2' - 6"A
G1
EXISTING OPENING
EXISTING OPENINGB
HOLLOW METAL WINDOW ALUMINUM SKYLIGHT2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:25 AMAE600
DOOR,
WINDOW
SCHEDULE
& DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
DOOR AND FRAME SCHEDULE
DOOR
SIZE DOOR FRAME FIRE
RATING
(MINUTES)
HW.
GROUP NOTES RV.WIDTH HEIGHT THICK
LEAF 1
TYPE
LEAF 2
TYPE MATERIAL FINISH TYPE MATERIAL FINISH
LEVEL 1
175 3' - 0" 7' - 0" 1 3/4" P21 WD STAIN F21 HM PAINT 0
176 6' - 0" 7' - 0" 1 3/4" P01 P01 HM PAINT F01 HM PAINT 0 A.
177 6' - 0" 7' - 0" 1 3/4" P01 P01 HM PAINT F01 HM PAINT 0
178 3' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0 A.
179 3' - 0" 7' - 0" 1 3/4" P30 WD STAIN F21 HM PAINT 0
179A 3' - 0" 7' - 0" 1 3/4" P21 WD STAIN F21.18 HM PAINT 0
179B 3' - 0" 7' - 0" 1 3/4" P10 WD STAIN F21 HM PAINT 0
179C 3' - 0" 7' - 0" 1 3/4" P10 WD STAIN F21 HM PAINT 0
179D 3' - 0" 7' - 0" 1 3/4" P10 WD STAIN F21.18 HM PAINT 0
180 6' - 0" 7' - 0" 1 3/4" P21 P21 WD STAIN F01 HM PAINT 0
181 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
183 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
183A 2' - 8" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
189 3' - 0" 7' - 0" 1 3/4" P21 WD STAIN F01 HM PAINT 0
189A 4' - 0" 7' - 0" 1 3/4" P01 P01 HM PAINT F01 HM PAINT 0
190 3' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
190A 3' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
190B 4' - 0" 7' - 0" 1 3/4" P01 P01 HM PAINT F01 HM PAINT 0
191 3' - 6" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
LEVEL 1C
200 7' - 0" 8' - 0" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
200A 6' - 0" 7' - 0" 1 3/4" P30A P30A AL ANODIZED * AL ANODIZED 0 C.
200B 6' - 0" 7' - 0" 1 3/4" P30A P30A AL ANODIZED * AL ANODIZED 0 C.
200C 6' - 0" 7' - 0" 1 3/4" P30A P30A AL ANODIZED * AL ANODIZED 0 C.
200D 3' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
211 6' - 0" 8' - 0" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
E001 6' - 0" 7' - 0" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
E002 6' - 0" 7' - 0" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
LEVEL 1D
210 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
212 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
213 3' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
LEVEL 2
207A 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0 F.
207B 2' - 8" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
207C 3' - 0" 7' - 0" 1 3/4" P21 WD STAIN F01 HM PAINT 0 F.
207D 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0 A,E.
207E 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0
207F 3' - 0" 7' - 0" 1 3/4" P21 WD STAIN F01 HM PAINT 0 F.
220A 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
220B 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
261A 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0 F.
261B 3' - 0" 7' - 0" 1 3/4" P21 HM PAINT F01 HM PAINT 0 F.
261C 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0 F.
261D 3' - 0" 7' - 0" 1 3/4" P21 HM PAINT F01 HM PAINT 0 F.
261E 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0 A,E.
261F 2' - 0" 7' - 0" 1 3/4" P01 HM PAINT F01 HM PAINT 0
261G 3' - 0" 7' - 0" 1 3/4" P01 WD STAIN F01 HM PAINT 0
261H 3' - 0" 7' - 0" 1 3/4" P40 AL ANODIZED F10 AL ANODIZED 0
E003A 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
E003B 3' - 0" 8' - 8" 1 3/4" P01 WD STAIN F01 HM PAINT 0 B.
E003C 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0 B.
E003D 3' - 0" 8' - 8" 1 3/4" P01 WD STAIN F01 HM PAINT 0 B.
E003E 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
E003F 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
E003G 3' - 0" 8' - 8" 1 3/4" P01 WD STAIN F01 HM PAINT 0 B.
E003H 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0 B.
E003J 3' - 0" 8' - 8" 1 3/4" P01 WD STAIN F01 HM PAINT 0 B.
E003K 6' - 0" 8' - 8" 1 3/4" P01 P01 WD STAIN F01 HM PAINT 0
S004 2' - 6" 6' - 8" 1 3/4" P01 HM PAINT F01 HM PAINT 0
FLOOR
FINISH
SCALE: 1/4" = 1'-0"
B5 ALUMINUM STOREFRONT SYSTEMS
SCALE: 1 1/2" = 1'-0"
C4 INTERIOR DOOR DETAIL
SCALE: 1 1/2" = 1'-0"
C3 INTERIOR DOOR DETAIL
SCALE: 1 1/2" = 1'-0"
C2 INTERIOR DOOR DETAIL
SCALE: 1 1/2" = 1'-0"
D2 INTERIOR DOOR DETAIL
SCALE: 1/4" = 1'-0"
DOOR PANEL TYPES
SCALE: 1/4" = 1'-0"
DOOR FRAME TYPES
SCALE: 1 1/2" = 1'-0"
E3 GYM DOOR HEAD @ WOOD
SCALE: 1 1/2" = 1'-0"
D3 GYM DOOR JAMB @ WOOD
A2 A5
SCALE: 1/4" = 1'-0"
WINDOW TYPESB2
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
SCHEDULED
CEILING
SCHEDULED
BASE
FINISH
FLOOR LINE
NOTES
PARTITION TYPE
FIRE RATING
GA FILE # WP-_ _ _
IBC 2015, TABLE 721.1 (2), 3-1.1
2 HR.
CMU6, CMU8, CMU12
8" WALL 12" WALL6" WALL
CMU6 CMU8 CMU12
CMU WALL
-FOR AREAS WITH TILE FINISH THAT ARE NOT RATED USE THE
FOLLOWING FOR TILE ASSEMBLY: TCNA CW223.
SEE INTERIOR ELEVATION & FINISH PLANS FOR AREAS W/ WALL FINISH.
SCHEDULED CEILING ; SEE
REFLECTED CEILING PLANS
(1) LAYER OF 5/8" TYPE "X"
GYPSUM BOARD
STEEL STUD
SCHEDULED BASE
ACOUSTICAL SEALANT (BOTH
SIDES TOP AND BOTTOM)
FINISH FLOOR LINE
NOTES
PARTITION TYPE
FIRE RATING
GA FILE # WP.___
3 5/8" STEEL STUD
P3
1HR (P3R & P6R)
1049, UL419
*5/8" TYPE "X" GYPSUM BOARD
APPLIED PARALLEL OR AT RIGHT
ANGLES TO STUDS W/ 6d CEMENT
COATED NAILS,
1 7/8" LONG, 0.0915" SHANK, 15/64"
HEAD, 7" O.C., WALL TYPE P3.1.1)*
P3, P3S, P6, P6S, P6S-2
STEEL DEFLECTION TRACK
P3S
3 5/8" STEEL STUD
W/ SOUND INSULATION
6" STEEL STUD 6" STEEL STUD
W/ SOUND INSULATION
P6 P6S
5"5"7 1/2"7 1/2"
2HR (P6S-2)-2 LAYERS 5/8" "X" ON BOTH SIDES
-FOR AREAS WITH TILE FINISH THAT ARE NOT RATED USE THE FOLLOWING FOR TILE ASSEMBLY:
DRY AREAS: TCNA W242-20
WET AREAS: TCNA W244C-20
SEE INTERIOR ELEVATION & FINISH PLANS FOR AREAS W/ WALL FINISH.
-'S' DENOTES INSULATION, TYPICAL
SCHEDULED CEILING ; SEE
REFLECTED CEILING PLANS
(1) LAYER OF 5/8" TYPE "X"
GYPSUM BOARD
STEEL STUD
SCHEDULED BASE
ACOUSTICAL SEALANT
(ONE SIDE TOP AND BOTTOM)
FINISH FLOOR LINE
NOTES
PARTITION TYPE
FIRE RATING
GA FILE # WP.___
C2S-2 1/2" STL. STUD
C3-3 5/8" STL. STUD
C2S/C3/C3S
N/A
1049, UL419
*5/8" TYPE "X" GYPSUM BOARD
APPLIED PARALLEL OR AT RIGHT
ANGLES TO STUDS W/ 6d CEMENT
COATED NAILS,
1 7/8" LONG, 0.0915" SHANK, 15/64"
HEAD, 7" O.C., WALL TYPE P3.1.1)*
C1, C2S, C3, C6
STEEL DEFLECTION TRACK
6" STEEL STUD
C6
7/8" HAT CHANNEL
C1
R18 BATT INSULATION TO BE
APPLIED AT ALL EXTERIOR WALL
LOCATIONS
-FOR AREAS WITH TILE FINISH THAT ARE NOT RATED USE THE
FOLLOWING FOR TILE ASSEMBLY:
DRY AREAS: TCNA W242-20
WET AREAS: TCNA W244C-20
SEE INTERIOR ELEVATION & FINISH PLANS FOR AREAS W/ WALL FINISH.
-APPLY BATT INSULATION TO ALL EXTERIOR WALL LOCATIONS.
-'S' DENOTES INSULATION, TYPICAL
CONCRETE WALL
FINISH FLOOR LINE
NOTES
PARTITION TYPE
FIRE RATING
GA FILE # WP-_ _ _
N/A
CON6
N/A
6" WALL
CON6
BOTTOM OF
STRUCTURE2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
12/17/2020 11:51:27 AMAE610
WALL,
CEILING,
FLOOR
TYPES &
FINISH
LEGENDJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
INTERIOR WALL
FINISH LEGEND
Finish Code Product Type Location Specs Note(s)
W2 FIBERGLASS
REINFORCED
PANEL
CUSTODIAN 176 MANF: ALTRO PURAGUARD
TYPE: EXTRUDED SEMI-RIGID PVCu
SHEET
STYLE/PATTERN: SMOOTH
SURFACE
COLOR: SALT W139
INSTALLATION: APPLIED TO WALL
WITH ALTRO ADHESIVE, W/ 1-PART
START & EDGE TRIM
DIMENSIONS: 4'X4', .08" THICK
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
FINISH LEGEND
Finish Code Product Type Location Specs Note(s)
M2 SOLID SURFACE TICKET BOOTH,
EQUIPMENT
ROOM
MANF: WILSONART
TYPE: SOLID SURFACE
STYLE/PATTERN:
COLOR: CASHMERE MIRAGE
9135MG
INSTALLATION:
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
M3 SOLID WOOD DISPLAY AREA MANF:
TYPE: NATURAL WOOD
STYLE/PATTERN: OAK
COLOR: WHITE OAK
INSTALLATION:
DIMENSIONS:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
M4 PLASTIC
LAMINATE
SORT &
ASSEMBLE
ROOM
MANF: FORMICA
TYPE: LAMINATE
STYLE/PATTERN:
COLOR: NEUTRAL TWILL MATTE
FINISH 8826-58
INSTALLATION: VERTICAL
SURFACE-CABINETS, DRAWERS
AND SHELVES
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
M5 SOLID SURFACE RESTROOMS,
LOCKER
ROOMS
MANF: WILSONART
TYPE: SOLID SURFACE
STYLE/PATTERN: -
COLOR: FROSTY WHITE MIRAGE
INSTALLATION: COUNTERTOP & 4"
BACKSPLASH
DIMENSIONS: 3/4" THICK (2CM)
WEIGHT:
BACKING:
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
REP:
REP PHONE:
REP EMAIL:
PAINT
P1 PAINT GENERAL WALL
PAINT
MANF: SHERWIN WILLIAMS
TYPE: PAINT
STYLE/PATTERN: COLUMBIA
(COLOR GUILD)
COLOR: SHELL WHITE SW8917
INSTALLATION: 3X COATS,
EGGSHELL FOR WALLS;
SEMI-GLOSS FOR TRIM, DOORS &
MILLWORK; FLAT FOR CEILINGS
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
P2 PAINT PLATFORM MANF: SHERWIN WILLIAMS
TYPE: PAINT
COLOR: TRICORN BLACK SW6258
INSTALLATION: 3X COATS,
EGGSHELL FOR WALLS;
SEMI-GLOSS FOR TRIM, DOORS &
MILLWORK; FLAT FOR CEILINGS
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
P3 PAINT DISPLAY AREA MANF: SHERWIN WILLIAMS
TYPE: PAINT
COLOR: NAVAL SW6244
INSTALLATION: 3X COATS,
EGGSHELL FOR WALLS;
SEMI-GLOSS FOR TRIM, DOORS &
MILLWORK; FLAT FOR CEILINGS
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
WALL
T1 TILE LOCKER
ROOMS
MANF: AMERICAN OLEAN
TYPE: GLAZED CERAMIC
STYLE/PATTERN: PERSPECTA
COLOR: CIRRUS WHITE PE09
INSTALLATION: STRAIGHT
VERTICAL STACK
DIMENSIONS: 8"X24"
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
T2 TILE LOCKER
ROOMS
SHOWERS
MANF: DALTILE
TYPE: GLAZED CERAMIC
STYLE/PATTERN: COLOR WHEEL
COLLECTION - LINEAR
COLOR: SEA BREEZE 1174
INSTALLATION: STRAIGHT
VERTICAL STACK
DIMENSIONS: 8"X24"
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
T3 TILE STEAM ROOM
WALLS
MANF: DALTILE
TYPE: PORCELAIN MOSAIC
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN
COLOR: ARCTIC WHITE D617
INSTALLATION: STRAIGHT JOINT
DIMENSIONS: 2"X2"
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONSTRACTOR
T4 TILE MEN'S 183 &
WOMEN'S 181
RESTROOMS,
RESTROOM 212
MANF: DALTILE
TYPE: COLORBODY PORCELAIN
STYLE/PATTERN: UNIFORM
CONCRETE, POLISHED
COLOR: WHITE UC10
INSTALLATION: HORIZONTAL
STRAIGHT STACK
DIMENSIONS: 12"X24"
GROUT MANF: MAPEI
GROUT COLOR: ALABASTER 01
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONSTRACTOR
W1 ACOUSTIC
WOOD GRILL
TICKET BOOTH,
DISPLAY AREA
MANF: 9 WOOD
TYPE: 3200 ACOUSTIC WOOD
GRILLE
STYLE/PATTERN: 3200 STYLE
ACOUSTIC PLANK
SPECIES: MAPLE, QUARTER SAWN,
BOOK MATCHED TO MATCH
ARCHITECTS SAMPLE
FINISH: SATIN SHEEN
INSTALLATION:
DIMENSIONS: 3/4" THICK WITH 1/16"
WIDE GROOVES SPACED 8mm O.C.;
PANEL SIZE AND JOINTS AS
DETAILED
BACKING: 1" THICK, BLACK
INSULATION BEHIND PANEL FACE
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
FINISH LEGEND
Finish Code Product Type Location Specs Note(s)
C6 PORCELAIN
TILE
STEAM ROOM MANF: DALTILE
TYPE: PORCELAIN MOSAIC
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN
COLOR: ARCTIC WHITE D617
INSTALLATION: STRAIGHT JOINT
DIMENSIONS: 2"X2"
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
FLOOR
F1 CARPET TILE TICKET BOOTH,
OFFICES
MANF: INTERFACE
TYPE: CARPET TILE
STYLE/PATTERN: FREQUENCY II
COLOR: REPETEND 9422
INSTALLATION:
DIMENSIONS:
PROVIDED BY:
OWNER
INSTALLED BY:
OWNER
REP:
REP PHONE:
REP EMAIL:
F2 CARPET TILE MANF: INTERFACE
TYPE: CARPET TILE
STYLE/PATTERN: STEP REPEAT
SR899
COLOR: SMOKE 104938
INSTALLATION:
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
OWNER
INSTALLED BY:
OWNER
REP:
REP PHONE:
REP EMAIL:
F3 VINYL
COMPOSITION
TILE
2ND FLOOR
FINISH
MANF: ARMSTRONG
TYPE: VCT
STYLE/PATTERN: IMPERIAL
TEXTURE STANDARD EXCELON
COLOR: SHELTER WHITE 51836
INSTALLATION:
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
F4 VINYL
COMPOSITION
TILE
2ND FLOOR
ACCENT FINISH
MANF: ARMSTRONG
TYPE: VCT
STYLE/PATTERN: IMPERIAL
TEXTURE STANDARD EXCELON
COLOR: GENTIAN BLUE 51946
INSTALLATION:
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
F5 CONCRETE MANF:
TYPE: POLISHED CONCRETE
STYLE/PATTERN: CLEAR
COLOR: CLEAR
INSTALLATION: LOW SHEEN, 300
GRIT
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
F6 PORCELAIN
TILE
LOCKER
ROOMS, STEAM
ROOM,
NURSING
ROOMS
MANF: DALTILE
TYPE: PORCELAIN MOSAIC
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN
COLOR: 15% SUEDE GRAY D182,
15% DESERT GRAY SPEC D200, 35%
GALAXY D023, 35% ARCTIC WHITE
D617
INSTALLATION: STRAIGHT JOINT
DIMENSIONS: 1"x1"
GROUT MANF: MAPEI
GROUT COLOR: IRON 107
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
F7 PORCELAIN
TILE
MEN'S 183 &
WOMEN'S 181
RESTROOMS
MANF: DALTILE
TYPE: PORCELAIN MOSAIC
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN
COLOR: 50% MOONSHINE D117,
25% DESERT GRAY SPEC D200, 25%
GALAXY D023
INSTALLATION: STRAIGHT JOINT
DIMENSIONS: 1"X1"
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
F8 TARAFLEX SPINNING
ROOM
MANF: GERFLOR
TYPE: TARAFLEX
STYLE/PATTERN: SPORT M PLUS
DRY-TEX
COLOR: LIGHT CHERRY DESIGN
6350
INSTALLATION: GLUE DOWN
DIMENSIONS:
BACKING: DOUBLE DENSITY CXP
HD FOAM BACKING
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
F9 CONCRETE MANF: -
TYPE: POLISHED CONCRETE
STYLE/PATTERN: STAINED BLACK
COLOR: BLACK STAIN
INSTALLATION: LOW SHEEN, 300
GRIT
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
F10 PORCELAIN
TILE
RESTROOM 212 MANF: DALTILE
TYPE: PORCELAIN MOSAIC
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN
COLOR: DESERT GRAY D014
INSTALLATION: STRAIGHT JOINT
DIMENSIONS: 2"X2"
GROUT MANF: MAPEI
GROUT COLOR: PEWTER 02
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
MILLWORK
M1 PLASTIC
LAMINATE
TICKET BOOTH,
EQUIPMENT
ROOM
MANF: WILSONART
TYPE: LAMINATE
STYLE/PATTERN:
COLOR: WHITE NEBULA 4621
INSTALLATION:
DIMENSIONS:
WEIGHT:
BACKING:
PROVIDED BY:
INSTALLED BY:
REP:
REP PHONE:
REP EMAIL:
FINISH LEGEND
Finish Code Product Type Location Specs Note(s)
BASE
B1 RUBBER BASE OFFICES,
CUSTODIAN
176, MECH,
STORAGE,
VEST. 1-G,
CORRIDOR 143,
SW EXIT E001
MANF: ROPPE
TYPE: VINYL BASED, TYPE TV
STYLE/PATTERN:
COLOR: DARK GRAY P150
INSTALLATION:
DIMENSIONS: 4"H
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B2 CARPET BASE OFFICES,
TICKET BOOTH,
NURSING
ROOMS
MANF: INTERFACE
TYPE: CARPET BASE
STYLE/PATTERN: FREQUENCY II
COLOR: REPETEND 9422
INSTALLATION: PROVIDE EDGE
BAND
DIMENSIONS: 4"H
PROVIDED BY:
OWNER
INSTALLED BY:
OWNER
B3 CARPET BASE SE EXIT MANF: INTERFACE
TYPE: CARPET BASE
STYLE/PATTERN: STEP REPEAT
SR899
COLOR: SMOKE 104938
INSTALLATION: PROVIDE EDGE
BAND
DIMENSIONS: 4"H
PROVIDED BY:
OWNER
INSTALLED BY:
OWNER
B4 RUBBER BASE ACTIVITY
STORAGE,
SPINNING
STORAGE,
LAUNDRY
MANF: ROPPE
TYPE: VINYL BASED, TYPE TV
STYLE/PATTERN:
COLOR: FLAX 632
INSTALLATION:
DIMENSIONS: 4"H
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B5 RUBBER BASE SPINNING
ROOM,
CORRIDORS
MANF: ROPPE
TYPE: VINYL BASED, TYPE TV
STYLE/PATTERN:
COLOR: BLACK 100
INSTALLATION:
DIMENSIONS: 4"H
WEIGHT:
BACKING:
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B6 (ALT.) STAINLESS
STEEL BASE
LOBBY MANF: INPRO
TYPE: STAINLESS STEEL SANI-BASE
STYLE/PATTERN: STRAIGHT BASE
COLOR: -
INSTALLATION:
DIMENSIONS: 4"H
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B7 TILE BASE MEN'S &
WOMEN'S
LOCKER
ROOMS,
NURSING
ROOMS
MANF: DALTILE
TYPE: PORCELAIN MOSAIC BASE
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN,
BUILD-UP BASE MB4C
COLOR: 15% SUEDE GRAY D182,
15% DESERT GRAY SPEC D200, 35%
GALAXY D023, 35% ARCTIC WHITE
D617
INSTALLATION: BUILD-UP BASE
DIMENSIONS: 4"H
GROUT MANF: MAPEI
GROUT COLOR: IRON 107
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B8 TILE BASE MEN'S 183 &
WOMEN'S 181
RESTROOMS
MANF: DALTILE
TYPE: PORCELAIN MOSAIC BASE
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN,
BUILD-UP BASE MB4C
COLOR: 50% MOONSHINE D117,
25% DESERT GRAY SPEC D200, 25%
GALAXY D023
INSTALLATION: BUILD-UP BASE
DIMENSIONS: 4"H
GROUT MANF: MAPEI
GROUT COLOR: SILVER 27
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
B9 TILE BASE RESTROOM 212 MANF: DALTILE
TYPE: PORCELAIN MOSAIC BASE
STYLE/PATTERN: KEYSTONES
COLORBODY PORCELAIN,
BUILD-UP BASE MB4C
COLOR: DESERT GRAY D014
INSTALLATION: BUILD-UP BASE
DIMENSIONS: 4"H
GROUT MANF: MAPEI
GROUT COLOR: PEWTER 02
GROUT SIZE: 1/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
CEILING
C3 ACOUSTIC TILE OFFICES, HW
2-B
MANF: USG CEILING SOLUTIONS
TYPE: RADAR BASIC ACOUSTICAL
PANELS
STYLE/PATTERN: DON BRAND
COLOR: WHITE
INSTALLATION: 15/16" SQUARE
LAY-IN EDGE PROFILE, ITEM#1910,
PRELUDE SUSPENSION
DIMENSIONS: 24"X24"X5/8"
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
C4 PAINT MANF: SHERWIN WILLIAMS
TYPE: PAINTED GYP
STYLE/PATTERN: COLUMBIA
(COLOR GUILD)
COLOR: SHELL WHITE SW8917
INSTALLATION: 3X COATS,
EGGSHELL FOR WALLS;
SEMI-GLOSS FOR TRIM, DOORS &
MILLWORK; FLAT FOR CEILINGS
DIMENSIONS:
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
C5 OPEN TO
STRUCTURE
ABOVE
SPINNING
ROOM,
SPINNING
STORAGE,
MECH, ACTIVITY
STORAGE
MANF: -
TYPE: DRY FALL PAINT
STYLE/PATTERN: -
COLOR: DUST GREY
INSTALLATION: SPRAY ON ALL
ITEMS ON CEILING, DECK, MECH
DUCTS, ETC.;
SPRAY 12" BELOW LOWEST
MECHANICAL DUCTWORK-FIELD
VERIFY.
PROVIDED BY:
CONTRACTOR
INSTALLED BY:
CONTRACTOR
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
4 Date 4 ASI #1
5' - 0"2' - 0"4 1/2"4' - 0"
26.04
B5
09.01
P1
26.04 26.04
6' - 4 1/2"12' - 0"12' - 0"6' - 7 1/2"
SIM.
09.10
10.05
7 1/2"
02.09
P1
08.03
09.10
B5
4' - 0"5' - 8"5' - 8"4' - 8"
08.05 08.05 08.05
02.28
08.03 08.03
02.28
02.06
09.10 09.01 02.2809.10 02.28
02.09
3' - 0"1' - 6"3' - 0"2' - 10"254
2'-0"
212
2'-0"
212
2'-0"
M4 M4 M4
06.02
M2
1"1"
06.06
M4
3' - 0"1' - 6"3' - 0"2' - 10"212
2'-0"
254
2'-0"
212
2'-0"
M4 M4 M4
06.02
M2
1"1"
06.06
M4
5' - 0"2' - 10"06.06
M4
06.02
M2
3' - 0"3' - 0"3' - 0"1' - 0"2' - 0"7' - 0"08.03
P1
09.10
B1
400
1'-8"
400
1'-8"
400
1'-8"
M4 M4 M4
09.10
B1
09.0109.01
1/2"3' - 6"3' - 9"3' - 6"1/2"1' - 8"1' - 7"
09.01
09.01
P1 P1
P1
P1
09.10
09.107' - 0"2' - 0"400
1'-4"
400
1'-4"
400
1'-4"
B1
B1
M4 M4 M4
02.28 02.28
2' - 0"7' - 0"09.01
P1
09.10
B1
400
1'-4"
400
1'-4"
400
1'-4"
M4 M4 M4
3' - 0"3' - 0"3' - 0"1' - 3"1' - 3"3' - 5"3' - 5"3' - 5"3' - 5"1' - 3 1/2"2' - 0"7' - 0"09.01
P1
400
1'-4"
400
1'-4"
400
1'-4"
400
1'-4"
M4 M4 M4 M4
08.03 08.03
09.10 09.01
08.03
09.10 09.01
09.01
08.0308.03
09.01
08.03
09.10 09.01
P1B48"03.0202.09
11.01
09.10
02.09
02.0202.27
B4 P1
09.0109.1002.27
P1B4
02.37
09.01
11.01 11.01 11.01 11.01
02.03
02.09
03.02 8"09.10
B4 P12"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:34 AMAE700
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
A2 SPINNING - SOUTH
SCALE: 1/4" = 1'-0"
A4 SPINNING - WEST
SCALE: 1/4" = 1'-0"
A1 SPINNING ROOM - EAST
SCALE: 1/4" = 1'-0"
A6 SPINNING ROOM - NORTH
SCALE: 1/4" = 1'-0"
C6 SORT & ASSEMBLE ISLAND - WEST
SCALE: 1/4" = 1'-0"
D6 SORT & ASSEMBLE ISLAND - EAST
SCALE: 1/4" = 1'-0"
B1 SORT & ASSEMBLE ISLAND - NORTH
SCALE: 1/4" = 1'-0"
B4 SORT & ASSEMBLE - WEST
SCALE: 1/4" = 1'-0"
B6 SORT & ASSEMBLE - NORTH
SCALE: 1/4" = 1'-0"
B5 SORT & ASSEMBLE - SOUTH
SCALE: 1/4" = 1'-0"
B2 SORT & ASSEMBLE - EAST
SCALE: 1/4" = 1'-0"
C5 WELLNESS CENTER - NORTH
SCALE: 1/4" = 1'-0"
C4 WELLNESS CENTER - SOUTH
SCALE: 1/4" = 1'-0"
C2 WELLSNESS CENTER - WEST
SCALE: 1/4" = 1'-0"
C1 WELLNESS CENTER - EAST
SCALE: 1/4" = 1'-0"
D5 LAUNDRY RM. - NORTH
SCALE: 1/4" = 1'-0"
D4 LAUNDRY RM. - SOUTH
SCALE: 1/4" = 1'-0"
D2 LAUNDRY RM. - WEST
SCALE: 1/4" = 1'-0"
D1 LAUNDRY RM. - EAST
1 10/30/20 Addendum #1
02.02 EXISTING WALL TO REMAIN
02.03 EXISTING CONC. COLUMN
02.06 EXISTING TYP. REINFORCED CONCRETE BLEACHER
SEATING
02.09 EXISTING BEAM
02.27 EXISTING BRICK VENEER
02.28 EXISTING 12" X 8" X 16" CMU WALL
02.37 EXISTING CONC. FOUND. WALL, 16" THICK
03.02 CONC. FLOOR
06.02 SOLID SURFACE COUNTERTOP
06.06 SIDE MILLWORK PANEL
08.03 SCH'D DOOR
08.05 SCH'D WINDOW
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.10 WALL BASE
10.05 MIRROR
11.01 WASHER / DRYER PROVIDED BY OWNER
26.04 OWNER PROVIDED TV
OPENOPEN
OPEN
OPEN OPEN
OPENOPENOPEN
09.15
22.0222.01 10.07 10.01
10.02
10.03
T4
08.03
06.0222.05
22.02
SIM.M5
09.15
T4
08.03
10.03
10.06
SIM.SIM.
10.01
10.02
22.0110.07
SIM.
09.15
T4
09.15
22.05
06.02
T4
M5
10.06
SIM.
22.02
SIM.
10.03
SIM.
09.1509.15
T4 T4
10.11
10.01
10.07
22.01
SIM.
SIM.
09.15
09.15
T4
T4
06.02
M5
22.05
10.02
08.03
22.0506.022' - 10"SIM.
09.15
T4 09.1509.15
T4 T4
M5
10.06
10.05 10.05
22.0110.07
09.15
T4
09.15
T4
10.11 10.02
09.15 10.02
T4
06.02
M5
10.06
10.0909.01 09.01
SIM.SIM.
10.09
P1P1
09.10 09.10 09.10
B5 B5 B5
09.08 09.08
09.15
06.02
SIM.M5
T4
10.11
06.02
09.15
SIM.
M5
T4
22.05
22.01 10.07
10.02
GENERAL LOCKER NOTES
A. REFER TO AE102A FOR 2TIER, 3 TIER, AND
REPURPOSED LOCKER LOCATIONS
10.0810.01
10.15
10.1110.0210.01 09.15
T42"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:40 AMAE701
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
A6 RESTROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
B6 RESTROOM (MEN) - SOUTH
SCALE: 1/4" = 1'-0"
A4 RESTROOM (MEN) - WEST 1
SCALE: 1/4" = 1'-0"
A2 RESTROOM (MEN) - WEST
SCALE: 1/4" = 1'-0"
B4 RESTROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
D6 RESTROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
C4 RESTROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
D4 RESTROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
C6 RESTROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
C1 HALLWAY LOCKERS - EAST
SCALE: 1/4" = 1'-0"
B1 RESTROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
A1 RESTROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
B2 RESTROOM (MEN) - NORTH
1 10/30/20 Addendum #1
06.02 SOLID SURFACE COUNTERTOP
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.08 SCH'D TILE BASE, RE: AE500 DETAILS
09.10 WALL BASE
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
10.01 ADA COMPLIANT GRAB BAR
10.02 TOILET PARTITION
10.03 URINAL PARTITION
10.05 MIRROR
10.06 PAPER TOWEL DISPENSER
10.07 TOILET PAPER DISPENSER
10.08 ADA BENCH
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT, REUSE
OF EXISTING
10.11 DRESSING PARTITION W/ BENCH
10.15
22.01 WALL MOUNTED TOILET, RE PLUMBING DWG.
22.02 WALL MOUNTED URINAL, SEE PLUMBING
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
3' - 0"2' - 0"
22.05 10.01
10.07
09.15
T3
22.096' - 8"22.07
09.15
08.03
T3
09.15
T3
10.08
10.01
T3
22.05
09.15
10.01
10.08
22.0709.15
6' - 8"T3
22.09
10.01
10.07
10.01 10.08
09.0109.10
B5 P1
E4
AE702
E5
AE702
E4
AE702
E5
AE702
E5
AE702
E1
AE702
E4
AE702
E5
AE702
A6
AE501
A6
AE501
AE501
A2
AE501
A2
A1
AE7025' - 3"E3
AE600
E5
AE702
E1
AE702
E4
AE702
E3
AE600
D3
AE600
D3
AE600
E4
AE702
E2
AE702
E1
AE702
C1
4' - 0"4" STEEL STUDS @
16" O.C. HANG FROM
VERTICAL TUBE
STEEL SUPPORT
5/8" TYPE X GYPSUM
BOARD EA. SIDE
1/4" CLEATS @ 24" O.C.
MAX HORIZONTALLY
3/4" HARDWOOD
VENEER PANEL
AE702
E4
AE702
E1
PAINT EXPOSED GYPSUM
BOARD ON PLATFORM
SIDE FLAT BLACK TO
MATCH OTHER
PLATFORM WALLS
4" STEEL STUD BOX
BEAM HEADER
5/8" GYPSUM BOARD
AE702
E1
STEEL TUBE SUPPORT
PLATFORM
210
EXISTING
GYM
COORDINATE HANGING
OF STEEL FRAMING WITH
SPRAY APPLIED
FIREPROOFING
FIREPROOFING
1 5/8" STEEL STUDS @ 16"
O.C. ATTACHED WITH Z
CLIPS CLIPPED TO STUDS
PRIOR TO FIREPROOFING
PAINT EXPPOSED
GYPSUM BOARD
FINISH FLAT BLACK
EXISTING
MASONRY WALL
AS SUBSTRATE
1" INSIDE CORNER CHANNEL
W/ RETURN KEYS
3/4" THICK WOOD
VENEER PANEL
1/4" CLEATS @ 24" O.C.
HORIZONTALLY
EXISTING MASONRY
OR SCH'D PARTITION
SUBSTRATE
1" ALUMINM OUTSIDE
CORNER CHANNEL W/
RETURN KEYS
3/4" THICK HARDWOOD
VENEER PANEL
1/4" THICK CLEATS @
24" O.C. HORIZONTALLY
1" ALULMINUM "L" ANGLE
CHANNEL W/ RETURN KEYS
3/4" THICK
HARDWOOD
VENEER PANEL
EXISTING MASONRY
WALL OR SCH'D
PARTITION SUBSTRATE
1/4" THICK CLEATS @
24" O.C.
HORIZONTALLY
1" ALUMINUM
CHANNEL W/
RETURN KEYS
3/4" THICK
HARDWOOD
VENEER PANEL
EXISTING MASONRY OR
SCH'D PARTITION
SUBSTRATE
1/4" THICK CLEATS @ 24"
O.C. HORIZONTALLY 1/2"JOINT2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:45 AMAE702
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
A6 RESTROOM 212 - NORTH
SCALE: 1/4" = 1'-0"
B6 RESTROOM 212 - SOUTH
SCALE: 1/4" = 1'-0"
A5 RESTROOM 212 - WEST
SCALE: 1/4" = 1'-0"
B5 RESTROOM 212 - EAST
SCALE: 1/4" = 1'-0"
A2 SOUTHWEST EXIT - NORTH
SCALE: 1/8" = 1'-0"
C6 PLATFORM - EAST
SCALE: 1/8" = 1'-0"
C5 PLATFORM - WEST
SCALE: 1/8" = 1'-0"
C1 MAIN GYM - SOUTH
SCALE: 1 1/2" = 1'-0"
A1 PLATFORM OPENING HEAD DETAIL
SCALE: 1 1/2" = 1'-0"
E2 HARDWOOD VENEER PANEL INSIDE CORNER DETAIL
SCALE: 1 1/2" = 1'-0"
E4 HARDWOOD VENEER PANEL CHANNEL OUTSIDE CORNER DETAIL
SCALE: 1 1/2" = 1'-0"
E1 HARDWOOD VENEER PANEL EDGE DETAIL
SCALE: 1 1/2" = 1'-0"
E5 HARDWOOD VENEER TYPICAL REVEAL DETAIL
SCALE: 1 1/2" = 1'-0"
D1 HARDWOOD VENEER PANEL PLAN
2 11/05/20 Addendum #2
4 Date 4 ASI #1
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.10 WALL BASE
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
10.01 ADA COMPLIANT GRAB BAR
10.07 TOILET PAPER DISPENSER
10.08 ADA BENCH
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
22.07 SHOWER FIXTURE, SEE PLUMBING
22.09 WATER CLOSET
OPEN
OPEN
10.0211.04 09.15
T1
22.05
06.02
10.06
09.15
T1
M5
22.01
10.01
10.07
09.15
T1
10.01
10.07
22.01 10.02 06.02 22.05
10.05
10.06
SIM.
09.15 09.15
SIM.SIM.
T1
M5
6' - 0"3' - 10"10.07
22.01
10.02
10.06
06.02
SIM.
SIM.
09.15 09.15
10.05
22.05
10.09
09.08
T1 T1
M58"6' - 8"SIM.
22.01
10.07
09.15
T1
10.0609.15
06.02
M5
T1
22.05
10.02 09.15 6' - 0"T16' - 8"8"05.11 09.01
B5P1
09.1005.11 09.01 05.11
P1
09.10
B5
09.10 09.10
09.01
P1
P1
B5 B5
02.28
08.03
09.10
B5
09.01
P1
09.01 02.02
P1P1
5' - 1"2' - 11"2' - 3"
08.03
09.10
P1B5
09.10
B5
E3
AE600
02.28
09.10
B5 B5
09.01
P1
17' - 1"9' - 9"
02.28
P1
09.10 22.10
09.10
B5 P1
04.0402.28
P1
22.10
11' - 11 1/2"6' - 4 1/2"
09.10
B5
09.01
P1 P1
09.10
B5
02.28
P1
09.10
B5
09.01
05.16
05.162"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:51:52 AMAE703
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
B2 EMPLOYEE'S RESTROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
A4 EMPLOYEE'S RESTROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
B4 EMPLOYEE'S RESTROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
A2 EMPLOYEE'S RESTROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
B5 STUDENT'S RESTROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
A6 STUDENT'S RESTROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
B6 STUDENT'S RESTROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
A5 STUDENT'S RESTROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
C5 SOUTHEAST EXIT - EAST
SCALE: 1/4" = 1'-0"
C2 SOUTHEAST EXIT - WEST
SCALE: 1/4" = 1'-0"
A1 PLATFORM - NORTH
SCALE: 1/4" = 1'-0"
B1 PLATFORM - EAST
SCALE: 1/4" = 1'-0"
D2 STORAGE 211 - NORTH
SCALE: 1/4" = 1'-0"
E2 STORAGE 211 - SOUTH
SCALE: 1/4" = 1'-0"
D1 STORAGE 211 - WEST
SCALE: 1/4" = 1'-0"
E1 STORAGE 211 - EAST
SCALE: 1/4" = 1'-0"
D4 SOUTHEAST EXIT - NORTH
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
4 Date 4 ASI #1
02.02 EXISTING WALL TO REMAIN
02.28 EXISTING 12" X 8" X 16" CMU WALL
04.04
05.11 METAL RAILING
05.16 METAL RAILING W/ GLAZING PANEL
06.02 SOLID SURFACE COUNTERTOP
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.08 SCH'D TILE BASE, RE: AE500 DETAILS
09.10 WALL BASE
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
10.01 ADA COMPLIANT GRAB BAR
10.02 TOILET PARTITION
10.05 MIRROR
10.06 PAPER TOWEL DISPENSER
10.07 TOILET PAPER DISPENSER
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT, REUSE
OF EXISTING
11.04 SPIN DRYER PROVIDED BY OWNER
22.01 WALL MOUNTED TOILET, RE PLUMBING DWG.
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
22.10 FLOOR SINK, RE. PLUMBING DWG.
OPEN OPENOPEN
OPEN OPENOPEN
OPEN
OPEN
10.08
10.05
SIM.
10.10 09.15
SIM.
08.03
09.08
4' - 10"3' - 10"06.02
T1
M5
09.15
08.03
11.04
T1
10.09
SIM.
09.0811.04
10.10
SIM.
10.08
09.15
10.05
SIM.
06.0209.08
T1
M5
09.15
T1
T1
T2
09.15
09.15
4' - 0"2' - 0"3' - 0"09.15
T1
09.15
T2 3' - 0"2' - 0"4' - 0"09.15
10.09
11.04
T1
09.15
T2 3' - 0"2' - 0"4' - 0"12.0510.13 22.07
08.03
09.15
09.08
10.10
SIM.
04.03
T1
10.1009.15
09.08
SIM.
04.03 04.03
10.09
T1
04.03 09.08
09.1510.10
SIM.T1
09.15
T1
09.15
T2 3' - 0"2' - 0"4' - 0"12.05
22.07
10.1610.08
10.01
GENERAL LOCKER NOTES
A. REFER TO AE102A FOR 2TIER, 3 TIER, AND
REPURPOSED LOCKER LOCATIONS
09.15
T1
08.02
10.08
10.10
SIM.
09.08
10.05
3' - 10"SIM.
2' - 9"09.15
T1
10.10
SIM.
08.03
09.01
P1
09.10
B7
08.03
06.02
22.05
M5
09.01
P1
09.10
B7
09.10
B7
P1
09.01
09.10
B7
22.05
06.02
M5
09.01
P1
09.10
B7
06.02
M5
09.01
09.10
B7
P1
22.05
06.02
M5
09.01
09.10
P1
B7
06.0222.05
M5
09.13
09.10
B7
P1
08.03
09.01
P1
09.10
B72"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:52:01 AMAE704
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
D5 EMPLOYEE'S LOCKER ROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
D3 EMPLOYEE'S LOCKER ROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
A2 STUDENT'S LOCKER ROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
B2 STUDENT'S LOCKER ROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
C6 TYP. STUDENT'S SHOWER ROOM (WOMEN) - NORTH
SCALE: 1/4" = 1'-0"
C5 TYP. STUDENT'S SHOWER ROOM (WOMEN) - SOUTH
SCALE: 1/4" = 1'-0"
C4 TYP. STUDENT'S SHOWER ROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
A1 STUDENT'S LOCKER ROOM (WOMEN) - WEST
SCALE: 1/4" = 1'-0"
B1 STUDENT'S LOCKER ROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
C1 EMPLOYEE'S LOCKER ROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
C2 TYP. STUDENT'S SHOWER ROOM (WOMEN) - EAST
SCALE: 1/4" = 1'-0"
B5 EMPLOYEE'S LOCKER ROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
A5 EMPLOYEE'S LOCKER ROOM (MEN) - SOUTH
SCALE: 1/4" = 1'-0"
D2 NURSING 261B - NORTH
SCALE: 1/4" = 1'-0"
D1 NURSING 261B - SOUTH
SCALE: 1/4" = 1'-0"
E2 NURSING 261B - WEST
SCALE: 1/4" = 1'-0"
E1 NURSING 261B - EAST
SCALE: 1/4" = 1'-0"
E6 NURSING 261D - NORTH
SCALE: 1/4" = 1'-0"
E5 NURSING 261D - SOUTH
SCALE: 1/4" = 1'-0"
E4 NURSING 261D - WEST
SCALE: 1/4" = 1'-0"
E3 NURSING 261D - EAST
1 10/30/20 Addendum #1
4 Date 4 ASI #1
04.03 CMU BASE, RE: AE500 DETAILS
06.02 SOLID SURFACE COUNTERTOP
08.02 CEILING ACCESS PANEL
08.03 SCH'D DOOR
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.08 SCH'D TILE BASE, RE: AE500 DETAILS
09.10 WALL BASE
09.13 CMU WALL
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
10.01 ADA COMPLIANT GRAB BAR
10.05 MIRROR
10.08 ADA BENCH
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT, REUSE
OF EXISTING
10.10 SOLID PLASTIC LOCKER W/ BENCH, REFER TO
AE102A FOR 2 OR 3 TIER STYLE LOCATIONS
10.13 WALL MOUNTED ADJUSTABLE BRACKET SHELVES,
PROVIDE BLOCKING AS REQ'D
10.16
11.04 SPIN DRYER PROVIDED BY OWNER
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
22.07 SHOWER FIXTURE, SEE PLUMBING
OPEN
OPEN
OPEN OPENOPEN OPEN
09.15
T1
22.01
10.01
10.07
OPEN
SIM.
09.0811.0409.08 04.03
10.10
OPEN
10.09
SIM.
SIM.
SIM.
06.02 09.08
10.10 09.15
4' - 9"
T1
10.08
M5
3' - 11 1/2"3' - 10"3' - 11"3' - 10"4' - 10"
10.05
06.02
10.02
SIM.
10.05
SIM.SIM.
10.06 22.01
10.07
10.01
22.02
10.03
6' - 8"5' - 8"22.05
M5 SIM.
SIM.
1' - 0"6' - 0"3' - 10"11.04
10.02
09.15
T1
22.05
09.15
T1
10.06
09.15
T1
09.15
T2
10.13 6' - 8"4' - 0"2' - 0"3' - 0"09.15
2' - 0"3' - 0"09.15
T2
12.05 10.13
6' - 8"T1
4' - 0"09.15 10.10
SIM.
09.083' - 0"2' - 0"T1
09.15
T2
6' - 8"10.13 12.05
09.15
T1
T23' - 0"2' - 0"22.07
6' - 8"SIM.
12.05
10.13
09.15
4' - 0"04.03 09.08
SIM.
04.0306.0209.08
10.05
09.1510.10 10.094' - 9"3' - 10"T1
M5
10.1010.09
SIM.SIM.
06.02 09.0809.08 04.0304.03
09.15
M5
T1
SIM.
04.03 04.0309.08
10.0910.10
09.15
T1
10.1010.10
SIM.
09.08 04.03
GENERAL LOCKER NOTES
A. REFER TO AE102A FOR 2TIER, 3 TIER, AND
REPURPOSED LOCKER LOCATIONS
08.03
SIM.
10.05
SIM.
10.10
09.08
10.10 2' - 9"3' - 10"09.15
T1
10.08
08.03
09.15
11.04
10.10
SIM.T1
10.10
09.082"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:52:10 AMAE705
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
C2 STUDENT RESTROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
B5 STUDENT'S LOCKER ROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
A5 STUDENT'S LOCKER ROOM (MEN) - WEST
SCALE: 1/4" = 1'-0"
C5 STUDENT'S RESTROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
D5 STUDENT'S RESTROOM (MEN) - SOUTH
SCALE: 1/4" = 1'-0"
C3 STUDENT'S RESTROOM (MEN) - WEST
SCALE: 1/4" = 1'-0"
D6 TYP. STUDENT'S SHOWER ROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
B1 TYP. STUDENT'S SHOWER ROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
B3 TYP. STUDENT'S LOCKER ROOM (MEN) - SOUTH
SCALE: 1/4" = 1'-0"
C6 TYP. STUDENT'S SHOWER ROOM (MEN) - WEST
SCALE: 1/4" = 1'-0"
A3 STUDENT'S LOCKER ROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
A1 STUDENT'S LOCKER ROOM (MEN) - SOUTH
SCALE: 1/4" = 1'-0"
B2 STUDENT'S LOCKER ROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
E1 EMPLOYEE'S LOCKER ROOM (MEN) - NORTH
SCALE: 1/4" = 1'-0"
E3 EMPLOYEE'S LOCKER ROOM (MEN) - EAST
SCALE: 1/4" = 1'-0"
D1 EMPLOYEE'S LOCKER ROOM (MEN) - WEST
1 10/30/20 Addendum #1
4 Date 4 ASI #1
04.03 CMU BASE, RE: AE500 DETAILS
06.02 SOLID SURFACE COUNTERTOP
08.03 SCH'D DOOR
09.08 SCH'D TILE BASE, RE: AE500 DETAILS
09.15 SCH'D WALL TILE FROM A.F.F. TO FIN, CLG.
10.01 ADA COMPLIANT GRAB BAR
10.02 TOILET PARTITION
10.03 URINAL PARTITION
10.05 MIRROR
10.06 PAPER TOWEL DISPENSER
10.07 TOILET PAPER DISPENSER
10.08 ADA BENCH
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT, REUSE
OF EXISTING
10.10 SOLID PLASTIC LOCKER W/ BENCH, REFER TO
AE102A FOR 2 OR 3 TIER STYLE LOCATIONS
10.13 WALL MOUNTED ADJUSTABLE BRACKET SHELVES,
PROVIDE BLOCKING AS REQ'D
11.04 SPIN DRYER PROVIDED BY OWNER
12.05 MOTORIZED CURTAIN, ALSO REFER TO ELEC. AND
STRU. DWGS. FOR CONNECTION AND SUPPORT
22.01 WALL MOUNTED TOILET, RE PLUMBING DWG.
22.02 WALL MOUNTED URINAL, SEE PLUMBING
22.05 LAVATORY & FAUCET, RE PLUMBING DWG.
22.07 SHOWER FIXTURE, SEE PLUMBING
OPEN OPEN OPEN OPEN
08.03 08.0308.03 08.03 08.03
09.01 09.01 09.01
P3 P3 P3
09.10 09.10 09.10
B4 B4 B4
A5
AE502
D5
AE501
D5
AE501
D5
AE501
D6
AE501
D6
AE501
D6
AE501
D6
AE501
08.07 08.07 08.07 08.07
09.01
P1
09.27
B6 (ALT.)
08.03 08.03
09.20
09.20
06.0706.0706.07
09.2009.20
09.20
OPEN OPEN
3' - 8 1/2"3' - 10"3' - 8 1/2"3' - 10"3' - 8 1/2"
OPENOPEN
06.10 06.10
M3 M3
06.09 06.09
06.07 06.07 06.0709.27 09.2709.278' - 4 1/2"4"B6 (ALT.)B6 (ALT.)B6 (ALT.)
09.27
B6 (ALT.)
09.27 09.27 09.27 09.27
B6 (ALT.)B6 (ALT.)B6 (ALT.)B6 (ALT.)
09.27
B6 (ALT.)
09.27
B6 (ALT.)
W1 W1 W1
W1 W1 W13' - 4"1' - 11 1/2"4' - 0 1/2"1' - 11 1/2"4' - 0 1/2"1' - 11 1/2"8' - 10"2' - 8"C5
AE501
C5
AE501
TYP.TYP.
08.03 08.03 08.03 08.03 08.03 09.0109.0109.01
P3 P3 P3
09.10 09.10 09.10
B4 B4 B4
09.10
B4
P3
09.0109.01
08.03
09.10
09.01
P3
B4
09.01
211
2'-0"
212
2'-0"
212
2'-0"
7' - 7"6' - 0"6' - 0"6' - 0"7' - 2"
09.01
P1
M1M1M1
09.10
B1
08.0308.03
08.0708.0708.07
08.07
1' - 9"1' - 9"2' - 6"3' - 6"2' - 6"3' - 6"
211
2'-0"
M1
06.02
M23' - 4"09.10
B15' - 9 1/2"2' - 8"4' - 11"06.02
M2
P1
09.10
B1
02.282' - 7"2' - 0"
09.01
P1
09.10
B1
M2
2' - 0"
09.10
P1B1
M2
02.28
A5
AE502
1' - 10"29' - 1"1' - 10"3' - 0"EQ.EQ.EQ.2' - 0"1' - 8"4"1' - 4"30' - 1"1' - 4"
06.09
06.09 06.09
06.10
06.10
M3
M3
06.10 M3
06.10 06.1006.10
M3 M3M3
1' - 4"6"11' - 0"2' - 0"6' - 0"3' - 0"3' - 0"1' - 4"1' - 4"1' - 4"2' - 0"1' - 8"4"1' - 4"6' - 4 1/2"
1' - 10"5' - 6 1/2"
1' - 4"6"
06.10
M3
06.10
M3
06.09
6' - 4 1/2"1' - 4"
5' - 6 1/2"1' - 10"3' - 0"1' - 4"1' - 4"1' - 4"2' - 0"2' - 0"2' - 0"6' - 0"3' - 0"6"1' - 4"
06.10
06.10
M3
M3
06.09
D4
AE501
C4
AE501
06.07
W12"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:52:18 AMAE706
INTERIOR
ELEVATIONJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/4" = 1'-0"
B5 NORTH EXIT - NORTH
SCALE: 1/4" = 1'-0"
A1 NORTH EXIT - SOUTH
SCALE: 1/4" = 1'-0"
D5 NORTH EXIT - SOUTH
SCALE: 1/4" = 1'-0"
B4 NORTH EXIT - WEST
SCALE: 1/4" = 1'-0"
D4 NORTH EXIT - EAST
SCALE: 1/4" = 1'-0"
B2 TICKET OFFICE - NORTH
SCALE: 1/4" = 1'-0"
D2 TICKET OFFICE - SOUTH
SCALE: 1/4" = 1'-0"
E1 TICKET OFFICE - WEST
SCALE: 1/4" = 1'-0"
D1 TICKET OFFICE - EAST
SCALE: 1/4" = 1'-0"
E5 DISPLAY - SOUTH
SCALE: 1/4" = 1'-0"
E4 DISPLAY - WEST
SCALE: 1/4" = 1'-0"
E2 DISPLAY - EAST
SCALE: 1/4" = 1'-0"
B1 TICKET OFFICE EAST SIDE - WEST
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
3 11/10/20 Addendum #3
4 Date 4 ASI #1
02.28 EXISTING 12" X 8" X 16" CMU WALL
06.02 SOLID SURFACE COUNTERTOP
06.07 CUSTOM WOOD GRILLE
06.09 GLASS DISPLAY CASE WITH SLIDING LOCKABLE DOORS
06.10 NATURAL OAK WOOD MILLWORK
08.03 SCH'D DOOR
08.07 OWNER PROVIDED COUNTER SHUTTER
09.01 5/8" TYPE 'X' GYPSUM BOARD
09.10 WALL BASE
09.20 ALUMINUM COMPOSITE MATERIAL PANEL WITH 1/2"
REVEAL, CONCEALED FASTENER. SUBMIT SHOP
DRAWING FOR THE JOINT LAYOUT
09.27 STAINLESS STEEL BASE AS ALTERNATE, RE. FINISH
SCHEDULE
F8 P1B5
189
SPINNING RM.
F3 P1B4
191
ACTIVITY STOR.
F5 P1B1
190
MECH.
AE700
A2
A4
F3 P1B4
189A
STOR.
A3
AE505 B3
AE505
B1
AE505
D1
AE505
A1
A6
09.21
TYP.
STOR.
F3 P1B4
190B
D1
AE505
AE701
A6
B6
AE701 A4B4
AE701 C6D6
AE701
D4
C4
AE700D1 D2
D4
D5
A2
AE701C1
AE700
C4
C1 C2
C5
F3 P1B4
177
ACTIVITY STOR.
WELLNESS
CTR
OFFICE
F1 P1B2
179D
WELLNESS
CTR
OFFICE
F1 P1B2
179C
WELLNESS
CTR
OFFICE
F1 P1B2
179BF1P1B2
179A
SORT & ASSEMBLE
F1 P1B2
175
CUSTODIAN OFFICE
F3 P1B4
178
EQUIP. RM.
F5 P1B1
176
CUSTODIAN
F3 P1B4
180
LAUNDRY RM.
(ALT. 1)
(ALT. 2)
B1 A1
VEST.
F5 P1B1
1-G
F1 P1B2
179
NEW WELLNESS CENTER
WOMEN'S
F7 T4T1
181
MEN'S
F7 T4T1
183
11.01
11.01
06.02
M5
10.11
10.11
06.02
M5
VEST.
F5 P1B1
1-G
10.09
10.09
D1
AE505
D1
AE505
D1
AE505
D3
AE505
D1
AE505
C1
AE505
C1
AE505
C1
AE505
C1
AE505
D3
AE505
B5
AE505
B5
AE505
09.21
TYP.
AE410
A3
AE411
A3
B2
AF101
A5
FITNESS
CENTER
X XX
182
F5 P1B1
211
STORAGE
F10 T4B9
212
RR.
STAIR
X P2B5
S003
F2 P1B3
E002
SE. EXIT
AE703
E2
AE703 C2
AE703
C5
D4
AE702
A2
AE703B1
A1
E1
D2
D1
MAIN GYM
250A
PLATFORM
X P2B5
210
SW. EXIT
X P1B1
E001A1
AE401
E3
AE401
P2
STOR.
X P2B1
200
03.07 03.07
STAIR
X P2B5
279
D3
AE505
B1
AE505
C1
AE505
B1
AE505
B1
AE505
B1
AE505
D6
AE505
D6
AE505
D5
AE505
E3
AE600
AE702C6 AE702 C5
09.21
TYP.
AF101
A3
F5 P1B1
213
HW.
F2 P1B3
214
HW.
C1
AE501
C2
AE501
AE706
D2
D1
B2
E1
AE706
E5
E2 E4
AE706
A1
AE706
B5
D4
D5
B4
F3 P1-
221
DISPLAY
F1 P1B2
220
TICKET OFFICE
F3 P3B4
E003
NORTH EXIT
AE706 B1
A5
AE502P3
P3
09.27
B6 (ALT.)
09.27
09.27
09.27
09.27
09.27
B6 (ALT.)
B6 (ALT.)
B6 (ALT.)
B6 (ALT.)
B6 (ALT.)
C5
AE505
C5
AE505
E3
AE505
E3
AE505
E3
AE505
AE704
D3
AE703B2 A2
D5
AE703 A5B5AE704
C6
C4
AE704
A2
B2
B4
A4
C5
A6
B6
A1B1
C1
C2
AE413
A6
F6 T1B7
261A
WOMEN'S EMPLOYEE
LOCKER RM.
261E
STORAGE
ALT. 31/4" / 1'-0"1/4" / 1'-0"06.02
M5
06.02
M5
10.11
10.11
10.10
A5
AE505
AE704E1
D1
D2
E2
F6 T1B7
261
WOMEN'S STUDENT
LOCKER RM.
F6 P1B7
261B
NURSING
F6 P1B7
261D
NURSING
AE704
E6
E3
E5
E4
AE705 C6
AE705
D5
C3C2
C5AE705D1
AE705 A5B5
E3
B3
B1
D6
A3
AE705
A1
B2
E1
AE704
B5
AE413
D6
F6 T1B7
207A
MEN'S EMP. LOCKER RM.
207D
STORAGE
ALT. 3 1/4" / 1'-0"1/4" / 1'-0"1/4" / 1'-0"1/4" / 1'-0"
06.02
06.02
M5
M5
10.10
10.10
10.10
A5
AE505
F6 T1B7
207
MEN'S STUDENT LOCKER
RM.
A5
10.08
FINISH TAG LEGEND
F WB
101
ROOM NAME
SEE FINISH LEGEND ON SHEET AE610 FOR
FINISHES
X = KEEP EXISTING FINISH.
PATCH & REPAIR AS
REQUIRED
WALL FINISH
BASE FINISEFLOOR
FINISH
ROOM
NUMBER
FLOOR FINISH HATCH
LEGEND
CARPET
VCT
CONCRETE
TILE
TERAFLEX2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:52:36 AMAF100
LEVEL 1 & 2
FINISH
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/8" = 1'-0"
D3 SPINNING, ACTIVITY & MECH. RMS. FINISH PLANS
SCALE: 1/8" = 1'-0"
D5 WELLNESS CTR., ACTIVITY STORAGE & LAUNDRY RMS. FINISH PLAN
SCALE: 1/8" = 1'-0"
D6 FITNESS CENTER FINISH PLAN
SCALE: 1/8" = 1'-0"
B3 PLATFORM & EXITS FINISH PLAN
SCALE: 1/8" = 1'-0"
A3 TICKET SALES & NORTH EXIT FINISH PLAN
SCALE: 1/8" = 1'-0"
D1 WOMEN'S LOCKER ROOM FINISH PLAN
SCALE: 1/8" = 1'-0"
A1 MEN'S LOCKER ROOM FINISH PLAN
03.07 CONCRETE STAIRS
06.02 SOLID SURFACE COUNTERTOP
09.21
09.27 STAINLESS STEEL BASE AS ALTERNATE, RE.
FINISH SCHEDULE
10.08 ADA BENCH
10.09 15" X 18" DOUBLE STACKED LOCKER UNIT,
REUSE OF EXISTING
10.10 SOLID PLASTIC LOCKER W/ BENCH, REFER
TO AE102A FOR 2 OR 3 TIER STYLE
LOCATIONS
10.11 DRESSING PARTITION W/ BENCH
11.01 WASHER / DRYER PROVIDED BY OWNER
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
AE700B2 AE700C6AE700D6
B5
B4
B6
AE700
B1
AE702B5
A6
A5
B6
RESTROOM
F10 B9 T4
212
A1
AE505
FINISH TAG LEGEND
F WB
101
ROOM NAME
SEE FINISH LEGEND ON SHEET AE610 FOR
FINISHES
X = KEEP EXISTING FINISH.
PATCH & REPAIR AS
REQUIRED
WALL FINISH
BASE FINISEFLOOR
FINISH
ROOM
NUMBER
FLOOR FINISH HATCH
LEGEND
CARPET
VCT
CONCRETE
TILE
TERAFLEX2"1"0"654321
654321
EDCBAREFERENCE NOTES
DATE REVISION
PROJECT NUMBER
12/17/2020 11:52:38 AMAF101
ENLARGED
FINISH
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020REXBURG ID20054
SCALE: 1/2" = 1'-0"
A5 SORT & ASSEMBLE PLAN FINISH PLAN (ALT. 2)
SCALE: 1/2" = 1'-0"
A3 RESTROOM 212 FINISH PLAN
1 10/30/20 Addendum #1
2 11/05/20 Addendum #2
STRUCTURAL GENERAL NOTES
BASIS OF DESIGN
1.GOVERNING BUILDING CODE...............................................2018 IBC
2.OCCUPANCY CATEGORY.......................................................III
3.LOAD COMBINATIONS:
ASD -GRAVITY AND LATERAL.......................................1605.3.1
LRFD -GRAVITY AND LATERAL....................................1605.2.1
4.GRAVITY DESIGN:
DEAD LOAD
ROOF................................................................................20 PSF
FLOOR..............................................................................VARIES
LIVE LOAD (UNIFORMLY DISTRIBUTED LOADS)
STAGE..............................................................................150 PSF
GYM FLOOR WITH REINF...............................................150 PSF
MECHANICAL....................................................................125 PSF
ROOF LIVE LOAD
(NOT CONCURRENT WITH ROOF SNOW LOAD)............20 PSF
ROOF SNOW LOAD
GROUND SNOW LOAD...................................................50 PSF
FLAT ROOF SNOW LOAD...............................................39 PSF
Is........................................................................................1.10
Ce......................................................................................1.00
Ct.......................................................................................1.00
DRIFTING PER ASCE 7
5.LATERAL DESIGN:
WIND DESIGN PER ASCE 7-10
ULTIMATE DESIGN WIND SPEED..................................112 MPH
EXPOSURE.....................................................................B
INTERNAL PRESSURE COEFFICIENT..........................0.18
TOPOGRAPHIC FACTOR...............................................1.00
SEISMIC DESIGN
SEISMIC DESIGN PROCEDURE.....................................EQUIVALENT
Ss CHART VALUE.............................................................37 g
S1 CHART VALUE.............................................................143 g
SITE COEFFICIENT FA....................................................1.30
SITE COEFFICIENT FV....................................................1.50
SDS....................................................................................321 g
SD1....................................................................................143 g
SITE CLASS.....................................................................C
SEISMIC DESIGN CATEGORY.......................................C
IMPORTANCE FACTOR Ie...............................................1.25
REDUNDANCY FACTOR..................................................1.00
PORTION OF SNOW LOAD INCLUDED..........................20%
GENERAL
1.THE GENERAL CONTRACTOR SHALL:
A.BECOME FAMILIAR WITH ALL PORTIONS OF THE CONTRACT DOCUMENTS AND INSURE THAT ALL
SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF
WORK. NO DEVIATIONS WILL BE ALLOWED UNLESS AGREED UPON BY ALL PARTIES IN
WRITING PRIOR TO CONSTRUCTION FABRICATION.
B.VERIFY ALL DIMENSIONS AND ELEVATIONS. COORDINATE ALL DEMOLITION, DOORS, WINDOWS, NON-
BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS,
RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFERS, KERFS, ETC.
C.COORDINATE DEMOLITION WITH ARCHITECT'S DRAWINGS. FIELD VERIFY ALL SITE CONDITIONS AND
IMMEDIATELY NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER REGARDING ACTUAL CONDITIONS
AT THE SITE WHICH ARE NOT PER THE DRAWINGS.
D.COORDINATE ALL WORK BETWEEN THE VARIOUS TRADES AND SUBCONTRACTORS. REPORT
ANY MODIFICATIONS TO THE STRUCTURAL PORTION OF THE BUILDING BY OTHER TRADES TO
THE ARCHITECT AND STRUCTURAL ENGINEER.
E.BE RESPONSIBLE FOR SAFETY AND PROTECTION IN AND AROUND THE JOB SITE AND/OR
ADJACENT PROPERTIES.
F.REPORT PROGRESS OF WORK TO ARCHITECT AND STRUCTURAL ENGINEER.
G.COORDINATE AND VERIFY LOCATIONS AND WEIGHTS OF MECHANICAL UNITS AND/OR OTHER
EQUIPMENT OR DEVICES PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY SUPPORTING
STRUCTURE. SUCH LOADS SHALL BE REPORTED TO THE ARCHITECT AND STRUCTURAL
ENGINEER FOR REVIEW. ADDITIONAL FRAMING MAY BE REQUIRED FOR THE PROPER SUPPORT
OF SUCH UNITS AND/OR EQUIPMENT. LATERAL SUPPORT FOR THE EQUIPMENT SHALL BE
PROVIDED BY EQUIPMENT INSTALLER.
H.COORDINATE AND VERIFY ROOF, FLOOR, AND WALL OPENINGS REQUIRED WITH
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND/OR OTHER DRAWINGS PRIOR TO
CONSTRUCTION. REPORT OPENINGS REQUIRED WHICH ARE NOT SPECIFICALLY SHOWN ON
THE STRUCTURAL DRAWINGS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW.
I.COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL
NOTES, OR SPECIFICATIONS WITH THE ARCHITECT AND STRUCTURAL ENGINEER.
2.CONTRACT DOCUMENTS:
A.REFER TO THE SPECIFICATIONS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES
OR THE DRAWINGS.
B.DETAILS, SECTIONS AND NOTES SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED TO
BE TYPICAL AND SHALL APPLY TO ALL SIMILAR SITUATIONS ELSEWHERE, UNLESS NOTED OR
SHOWN OTHERWISE.
C.THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS
SPECIFICALLY NOTED OTHERWISE.
D.INFORMATION ON DRAWINGS INDICATING EXISTING CONDITIONS IS BASED ON BEST PRESENT
KNOWLEDGE, BUT MAY NOT BE ENTIRELY ACCURATE AND MUST BE FIELD VERIFIED.
3.BUILDING CODE COMPLIANCE:
A.INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP AND MATERIALS SHALL CONFORM TO
THE REQUIREMENTS OF THE GOVERNING BUILDING CODE AND STANDARDS. ASTM, IBC, AND
OTHER DESIGNATIONS SHALL BE AS AMENDED TO LATEST DATE UNLESS NOTED OTHERWISE.
4.CONSTRUCTION SEQUENCE, SHORING, AND BRACING REQUIREMENTS:
A.THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE METHOD, MEANS, AND SEQUENCE OF
ALL STRUCTURAL ERECTION EXCEPT WHEN SPECIFICALLY NOTED OTHERWISE ON THE
DRAWINGS. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING TO
PROVIDE ADEQUATE VERTICAL AND LATERAL SUPPORT DURING ERECTION. THIS SHORING AND
BRACING SHALL REMAIN IN PLACE UNTIL ALL PERMANENT MEMBERS ARE PLACED AND ALL
FINAL CONNECTIONS ARE COMPLETED, INCLUDING ALL ROOF AND FLOOR ATTACHMENTS.
B.SHORING AND SUPPORTING FORM WORK FOR SUSPENDED CONCRETE OR MASONRY
MATERIAL SHALL REMAIN IN PLACE AND SHALL NOT BE REMOVED UNTIL THE STRUCTURAL
MEMBERS HAVE ACQUIRED SUFFICIENT STRENGTH TO SAFELY SUPPORT THEIR OWN WEIGHT
AND ANY ADDITIONAL CONSTRUCTION, STORAGE, AND/OR OTHER LOADS TO WHICH THE MAY
BE SUBJECTED. IN NO CASE SHALL THEY BE REMOVED PRIOR TO 7 DAYS. RE-SHORING SHALL
BE IMMEDIATELY INSTALLED UPON REMOVAL OF SUCH FORMS AND SHALL REMAIN IN PLACE
UNTIL 28 DAYS AFTER PLACING OF MATERIAL OR UNTIL MATERIAL HAS REACHED ITS 28 DAY
DESIGN STRENGTH, WHICHEVER IS LONGER. DO NOT REMOVE LARGE AREAS OF SHORING
BEFORE STARTING RE-SHORING PROCEDURES.
C.NON-BEARING INTERIOR WALLS SHALL BE ADEQUATELY BRACED TO THE STRUCTURE ABOVE
WITH ALLOWANCE FOR DEFLECTION OF THE STRUCTURE ABOVE AND/OR BELOW.
D.BUILDING WALLS WHICH RETAIN EARTH MUST BE BRACED AT THE TOP. DO NOT BACKFILL
UNLESS BRACING IS PROVIDED OR UNTIL THE COMPLETE FLOOR OR ROOF SYSTEM IS IN
PLACE, TYPICAL, UNLESS NOTED OTHERWISE.
5.OMISSIONS AND/OR CONFLICTS:
A.OMISSIONS IN AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONTRACT
DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND
STRUCTURAL ENGINEER AND SHALL BE RESOLVED BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
B.IN CASE OF CONFLICTS IN THE STRUCTURAL WORK, THE MOST STRINGENT REQUIREMENTS, AS
DIRECTED BY THE ARCHITECT AND STRUCTURAL ENGINEER, SHALL BE IMPLEMENTED AT NO
ADDITIONAL COST TO THE OWNER.
6.MISCELLANEOUS:
A.DURING AND AFTER CONSTRUCTION, THE CONTRACTOR AND/OR OWNER SHALL KEEP THE
LOADS ON THE STRUCTURE WITHIN THE LIMITS OF THE DESIGN.
B.OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ARCHITECT AND/OR
STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS INSPECTION NOR APPROVAL OF
CONSTRUCTION.
C.STAIRS ARE TO BE AS PER THE ARCHITECTURAL DRAWINGS.
D.ELEVATOR MACHINERY SUPPORT BEAMS, GUIDE RAILS, SUPPORTS, ETC., SHALL BE SUPPLIED
BY THE ELEVATOR MANUFACTURER. ALL LOADS IMPOSED BY THE ELEVATOR ONTO THE
STRUCTURE SHALL BE DETERMINED BY THE ELEVATOR MANUFACTURER AND SHALL BE
CLEARLY SHOWN ON SHOP DRAWINGS SUBMITTED FOR REVIEW. ADDITIONAL FRAMING MAY
BE REQUIRED FOR THE PROPER SUPPORT OF THESE LOADS. COORDINATE WITH THE
ARCHITECT AND STRUCTURAL ENGINEER.
E.ALL WORK SHALL BE DONE IN ACCORDANCE WITH OSHA REQUIREMENTS. ANY CONFLICTS
BETWEEN THESE DOCUMENTS AND OSHA REQUIREMENTS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH
WORK.
7.SUBMITTALS:
A.THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO FABRICATION, ERECTION, INSTALLATION, OR OTHERWISE BEING
INCORPORATED INTO THE WORK.
MATERIALS CERTIFICATION FOR ALL CONCRETE MATERIALS.
MIX DESIGNS FOR EACH TYPE OF CONCRETE.
REINFORCING STEEL SHOP DRAWINGS.
STRUCTURAL STEEL SHOP DRAWINGS.
WELDING PROCEDURES AND CERTIFICATIONS.
B.A MINIMUM OF TWO WEEKS SHALL BE ALLOWED FOR THE REVIEW OF ALL SUBMITTALS BY THE
ARCHITECT AND STRUCTURAL ENGINEER.
C.REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL
ENGINEER IN WRITING. REASON(S) FOR THE REQUEST AND COST DIFFERENTIALS SHALL BE
INCLUDED IN THE REQUESTS. SUBSTITUTIONS ARE NOT ALLOWED UNLESS APPROVED IN
WRITING BY THE ARCHITECT AND STRUCTURAL ENGINEER.
G.CONTINUOUS FOOTINGS WITHOUT CONCRETE FOUNDATION WALLS ABOVE SHALL BE
REINFORCED WITH A MINIMUM OF 2-#6 LONGITUDINAL TOP BARS IN ADDITION TO REINFORCING
SPECIFIED IN THE FOOTING SCHEDULE. AT OPENINGS, PROVIDE (1) #6 TOP BAR FOR EACH
FOOT OF FOOTING WIDTH OR PORTION THEREOF, EXTEND 24" BEYOND EDGE OF OPENING,
EACH SIDE.
H.NO PENETRATIONS SHALL BE ALLOWED THROUGH ANY CONCRETE FOOTING. WHEN CONFLICTS
ARISE BETWEEN UNDERGROUND PLUMBING, UTILITIES, ETC., THE FOOTING SHALL BE STEPPED
DOWN BELOW THE CONFLICT AND A CONCRETE WALL, PIER, COLUMN ETC., SHALL BE
EXTENDED TO THE FOOTING AS REQUIRED.
I.BEARING SURFACES FOR FOOTINGS WHICH ARE, OR BECOME, UNDERMINED DURING
CONSTRUCTION SHALL BE BACKFILLED WITH A LEAN-MIX CONCRETE (2000 PSI MIN.).
6.SLABS ON GRADE:
A.INTERIOR SLABS ON GRADE SHALL BE A MINIMUM OF 4 INCHES THICK, SHALL BEAR ON A 4
INCH MINIMUM LAYER OF FREE-DRAINING GRAVEL, AND SHALL BE REINFORCED WITH #4 BARS
AT 18" O.C. BOTH WAYS, TYPICAL UNLESS NOTED OTHERWISE. PROVIDE CHAIRS WITH SAND
PLATES FOR PROPER PLACEMENT.
B.SLABS ON GRADE SHALL BE SUBDIVIDED BY CONSTRUCTION AND/OR CONTRACTION (CONTROL)
JOINTS INTO ROUGHLY SQUARES WHOSE SIDES SHALL NOT EXCEED 15 FEET IN EITHER
DIRECTION.
C.SEE ARCHITECTURAL FOR EXTERIOR SLABS ON GRADE, TYPICAL, UNLESS NOTED OTHERWISE.
7. WALLS:
A.CONCRETE WALLS SHALL BE REINFORCED AS FOLLOWS, UNLESS NOTED OTHERWISE:
WALL VERTICAL HORIZONTAL
THICKNESS REINFORCING REINFORCING
(GRADE 60)(GF 0.0012)(GF 0.0020)
8"#4 @ 18" O.C.#4 @ 12" O.C.
10"#4 @ 16" O.C.#5 @ 14" O.C.
12"#4 @ 18" O.C.,E.F.#4 @ 16" O.C.,E.F.
14"#4 @ 18" O.C.,E.F.#4 @ 14" O.C.,E.F.
16"#4 @ 18" O.C.,E.F.#4 @ 12" O.C.,E.F.
18" #4 @ 18" O.C.,E.F.#4 @ 10" O.C.,E.F.
(SHEAR WALLS)(GF 0.0025)(GF 0.0025)
8"#5 @ 14" O.C.#5 @ 14" O.C.
10"#5 @ 12" O.C.#5 @ 12" O.C.
12"#4 @ 12" O.C.,E.F.#4 @ 12" O.C.,E.F.
14"#4 @ 10" O.C.,E.F.#4 @ 10" O.C.,E.F.
16"#5 @ 14" O.C.,E.F.#5 @ 14" O.C.,E.F.
18" #5 @ 12" O.C.,E.F.#5 @ 12" O.C.,E.F.
B.PLACE VERTICAL REINFORCING IN THE CENTER OF THE WALL (EXCEPT FOR BASEMENT WALLS,
RETAINING WALLS, OR WHEN EACH FACE IS SPECIFIED).
C.VERTICAL REINFORCING SHALL BE DOWELED TO CONCRETE FOOTING OR STRUCTURE BELOW
AND TO STRUCTURE ABOVE WITH THE SAME SIZE BAR AND SPACING, TYPICAL, UNLESS NOTED
OTHERWISE.
D.PROVIDE CORNER BARS AT ALL INTERSECTIONS AND CORNERS. USE SAME SIZE BAR AND
SPACING AS THE HORIZONTAL REINFORCING.
E.HORIZONTAL REINFORCING SHALL TERMINATE AT THE ENDS OF WALLS AND AT OPENINGS WITH
A STANDARD HOOK.
F.WHEN TWO CURTAINS OF STEEL ARE REQUIRED, THE SPLICES IN THE HORIZONTAL
REINFORCING OF EACH CURTAIN SHALL NOT OCCUR AT THE SAME LOCATION.
G.PENETRATIONS THROUGH ANY CONCRETE WALL SHALL BE BUILT INTO THE WALL AS THE WALL
IS BEING CONSTRUCTED AND SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL
ENGINEER PRIOR TO INSTALLATION.
H.PROVIDE DRAINAGE AT THE BASE OF RETAINING WALLS AND AT THE BASE OF ALL BASEMENT
WALLS.
8. SUSPENDED SLABS, SLABS ON DECK, BEAMS, AND JOISTS:
A.LARGE AREAS OF SUSPENDED SLAB SHALL BE PLACED SUCH THAT THE MAXIMUM EXTENT OF
ANY INDIVIDUAL CASTING OF SUSPENDED SLAB SHALL NOT EXCEED 65 FEET IN EITHER
DIRECTION.
B.FORMS AND SCREEDS FOR SUSPENDED CONCRETE MEMBERS SHALL BE CAMBERED 1/4" PER
10 FEET OF SPAN TO COMPENSATE FOR DEAD LOAD DEFLECTIONS.
C.CONSTRUCTION JOINTS IN SUSPENDED SLABS AND/OR BEAMS SHALL OCCUR AT OR NEAR MID
SPAN, WITHIN THE MIDDLE THIRD. COORDINATE PLACEMENT WITH THE ARCHITECT AND
STRUCTURAL ENGINEER. SEE PLANS FOR REQUIRED POUR STRIPS.
D.BRIDGING IN CONCRETE JOISTS SHALL BE 6 INCHES NOMINAL WIDTH BY FULL DEPTH OF THE
JOIST. REINFORCE WITH 1#5 BY CONTINUOUS TOP AND BOTTOM.
9. COLUMNS:
A.VERTICAL REINFORCING IN COLUMNS SHALL HAVE A MINIMUM OF 40 BAR DIAMETERS SPLICE
LENGTH. SPLICES SHALL OCCUR AT FLOOR LEVELS ONLY.
B.LATERAL TIES IN COLUMNS SHALL BE SPACED AT ONE HALF THE REGULAR SPACING BUT NOT
MORE THAN 8 INCHES ON CENTER AT THE TOP AND BOTTOM OF THE COLUMN FOR A DISTANCE
OF 1/6 THE CLEAR COLUMN HEIGHT, THE MAXIMUM COLUMN PLAN DIMENSION, OR 18 INCHES,
WHICHEVER IS GREATER.
C.WHEN CROSS SECTIONAL CHANGES OCCUR IN COLUMNS, THE LONGITUDINAL BARS SHALL BE
OFFSET IN A REGION WHERE LATERAL SUPPORT IS PROVIDED. AT THE OFFSET, THE SLOPE
OF THE INCLINED PORTION SHALL NOT BE MORE THAN 1 IN 6, AND THE LATERAL TIES SHALL BE
SPACED NOT OVER 3 INCHES ON CENTER FOR A DISTANCE OF ONE FOOT BELOW AND ABOVE
THE POINT OF OFFSET.
MASONRY
1.CODES AND STANDARDS:
A.MASONRY CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) 530.1, "SPECIFICATIONS FOR MASONRY STRUCTURES",
AND SECTIONS 2103, 2104, AND 2105 OF THE IBC.
2.MATERIALS:
A.MASONRY BLOCK SHALL BE LIGHTWEIGHT CONCRETE MASONRY UNITS AND SHALL CONFORM
TO ASTM C90, GRADE N, TYPE 1, WITH A MINIMUM COMPRESSIVE STRENGTH OF 2800 PSI AT 28
DAYS FOR NET AREA.
B.MASONRY BRICK SHALL BE CLAY MASONRY UNITS AND SHALL
CONFORM TO ASTM C62, GRADE SW, WITH A MINIMUM COMPRESSIVE
STRENGTH OF 4,000 PSI AT 28 DAYS.
C.MORTAR SHALL BE TYPE "S" AS DEFINED BY THE IBC AND SHALL CONFORM TO ASTM C270,
WITH A MINIMUM COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. IT SHALL CONSIST OF 1.0
PART PORTLAND CEMENT, 0.25 TO 0.5 PARTS HYDRATED LIME OR PUTTY LIME, AND 3.5 TO 4.5
PARTS SAND. ALL MEASUREMENTS ARE PARTS BY VOLUME. NO ADDITIVES ARE ALLOWED.
D.GROUT SHALL CONFORM TO ASTM C476 WITH A MINIMUM COMPRESSIVE STRENGTH OF
3000 FOR F'M = 2000 PSI AT 28 DAYS. IT SHALL BE OF A FLUID
CONSISTENCY AND SHALL CONSIST OF A MINIMUM OF 1.0 PART PORTLAND CEMENT, 2.25 TO 3.0
PARTS SAND, AND MAY CONTAIN AN ADDITIONAL 1 TO 2 PARTS PEA GRAVEL IF GROUT SPACES
ARE 4" OR MORE IN EVERY DIRECTION. ALL MEASUREMENTS ARE PARTS BY VOLUME. LIMIT
FLY ASH TO 15% OF THE TOTAL CEMENTITIOUS MATERIAL.
E.PRISM TESTS SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF F'M =
2000 PSI AT 28 DAYS.
F.EPOXY SHALL CONFORM TO ASTM C881, TYPES I, II, IV, AND V, GRADE 3, CLASSES B AND C.
3.CONSTRUCTION:
A.ALL MASONRY BLOCK SHALL BE STORED UNDER COVER AT THE JOB SITE.
B.FACE SHELLS SHALL BE FULLY BEDDED.
C.ALL MORTAR JOINTS SHALL BE TOOLED CONCAVE UNLESS NOTED OTHERWISE.
D.DO NOT USE MORTAR FOR GROUT.
E.DO NOT USE ANY FROZEN MATERIAL.
F.PRIOR TO PLACING MASONRY, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT OF
OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS,
ETC.
G.GROUT SHALL BE POURED IN ACCORDANCE WITH LOW LIFT PROCEDURES PER ACI 530,
TYPICAL, UNLESS NOTED OTHERWISE.
H.GROUT SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION DURING PLACING AND
RECONSOLIDATED AFTER EXCESS MOISTURE HAS BEEN ABSORBED BUT BEFORE
WORKABILITY IS LOST.
I.ALL CELLS WHICH CONTAIN REINFORCING, BOLTS, ANCHORS, ETC., AND AS OTHERWISE
SPECIFIED SHALL BE GROUTED SOLID. ALL CELLS WHICH ARE TO BE GROUTED SHALL BE
CLEAN AND FREE FROM DELETERIOUS MATERIALS.
J.GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE.
K.HOLES FOR BOLTS IN MASONRY FACE OR END SHELLS SHALL HAVE A DIAMETER TWO INCHES
LARGER THAN THE BOLT DIAMETER AND THE HOLE SHALL BE FILLED WITH GROUT.
L.NO PENETRATION SHALL BE ALLOWED THROUGH ANY MASONRY BEAM, COLUMN, PIER, OR
JAMB WITHOUT THE ARCHITECT'S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN APPROVAL.
PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS.
M.ALL BOLTS TO BE DRILLED AND EPOXIED SHALL BE INSTALLED IN SOLID MATERIAL. AT CAVITY
LOCATIONS GROUT SOLID. ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE
BRUSHED AND CLEANED WITH COMPRESSED AIR. FOLLOW MANUFACTURERS
RECOMMENDATIONS.
4.WALLS:
A.MASONRY WALLS SHALL BE CONSTRUCTED UTILIZING COMMON RUNNING BOND, TYPICAL,
UNLESS NOTED OTHERWISE.
B.MASONRY WALLS SHALL BE BUILT AS AN INTEGRAL UNIT AT CORNERS AND INTERSECTIONS.
REINFORCING SHALL BE CONTINUOUS AND BACK TO BACK END SHELLS SHALL BE REMOVED IN
EACH COURSE.
C.MASONRY WALLS SHALL BE REINFORCED AS FOLLOWS, UNLESS NOTED OTHERWISE.
WALL VERTICAL HORIZONTAL
THICKNESS REINFORCING REINFORCING
(WITH JOINT REINFORCING)
6"1-#4 AT 32" O.C.1-#4 AT 48" O.C.
8"1-#5 AT 32" O.C.2-#3 AT 48" O.C.
10"1-#5 AT 32" O.C.2-#4 AT 48" O.C.
12"1-#6 AT 32" O.C.2-#4 AT 48" O.C.
PROVIDE LADDER-TYPE JOINT REINFORCING CONSISTING OF 2-#9 WIRES (3-#9 WIRES AT
VENEER) AT 16" O.C. HORIZONTALLY IN ALL MASONRY WALLS. SEE PLANS, SCHEDULES, AND
DETAILS FOR OTHER REINFORCING REQUIREMENTS.
(WITHOUT JOINT REINFORCING)
6"1-#5 AT 32" O.C.1-#4 AT 48" O.C.
8"1-#5 AT 32" O.C.2-#4 AT 48" O.C.
10"1-#6 AT 32" O.C.2-#4 AT 48" O.C.
12"1-#7 AT 32" O.C.2-#4 AT 48" O.C.
SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER REINFORCING REQUIREMENTS.
D.PLACE VERTICAL REINFORCING IN THE CENTER OF THE WALL UNLESS EACH FACE IS
SPECIFIED OR UNLESS NOTED OTHERWISE.
E.VERTICAL REINFORCING SHALL BE DOWELED TO CONCRETE FOOTING OR FOUNDATION WALL
BELOW AND TO STRUCTURE ABOVE WITH THE SAME SIZE BAR AND SPACING, TYPICAL,
UNLESS NOTED OTHERWISE.
F.PROVIDE VERTICAL REINFORCING IN GROUTED CELL AT ALL CORNERS AND INTERSECTIONS.
G.PROVIDE CORNER BARS AT ALL INTERSECTIONS AND CORNERS. USE SAME SIZE BAR AND
SPACING AS THE HORIZONTAL REINFORCING.
H.HORIZONTAL REINFORCING SHALL TERMINATE AT THE ENDS OF WALLS AND AT OPENINGS WITH
A STANDARD HOOK.
I.HORIZONTAL REINFORCING SHALL OCCUR AT THE TOP AND BOTTOM COURSE OF ALL MASONRY
WALLS EXCEPT THE BOTTOM COURSE HORIZONTAL REINFORCING MAY BE OMITTED WHEN THE
WALL IS DOWELED TO A CONCRETE FOUNDATION WALL BELOW.
J.OPENINGS IN WALLS WHICH EXCEED 24 INCHES IN EITHER DIRECTION SHALL BE REINFORCED
WITH A MINIMUM OF 2-#5 BARS IN GROUTED SPACE ON ALL SIDES OF THE OPENING, TYPICAL,
UNLESS NOTED OTHERWISE. VERTICAL BARS SHALL EXTEND THE FULL HEIGHT OF THE WALL
BETWEEN SUPPORTS. HORIZONTAL BARS SHALL EXTEND A MINIMUM OF 24 INCHES BEYOND
THE EDGES OF THE OPENING.
K.PENETRATIONS THROUGH ANY MASONRY WALL SHALL BE BUILT INTO THE WALL AS THE WALL
IS BEING CONSTRUCTED AND SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL
ENGINEER PRIOR TO INSTALLATION.
L.CONSTRUCTION JOINTS IN REINFORCED MASONRY WALLS SHALL NOT OCCUR AT THE EDGE OF
BEAM SUPPORTS AND SHALL BE PROVIDED PER THE ARCHITECTURAL DRAWINGS.
M.WHERE HORIZONTAL REINFORCING BARS JOIN CONCRETE WALLS, COLUMNS, OR PILASTERS,
REINFORCING SHALL BE CONTINUOUS. ALSO, A KEY SHALL BE PROVIDED BETWEEN THE
MASONRY AND THE CONCRETE. FILL KEY WITH GROUT.
5.COLUMNS:
A.GROUT JAMBS SOLID FOR FULL HEIGHT OF WALL (FLOOR TO FLOOR AND/OR ROOF) AT SIDES
OF OPENINGS; ONE CELL FOR EACH 4'-0" OF SPAN OR PORTION THEREOF. REINFORCE WITH 2-
#5 VERTICAL BARS IN EACH GROUTED CELL WITH ONE BAR PLACED AT EACH FACE OF WALL,
TYPICAL UNLESS NOTED OTHERWISE. SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER
REINFORCING REQUIREMENTS.
MASONRY VENEER
1.PRODUCT:
A.LEDGERS AND LINTELS SHALL BE ASTM A36 GALVANIZED MATERIAL.
B.MASONRY VENEER ANCHOR TIES SHALL BE ONE OF THE FOLLOWING.
I.DOVETAIL ANCHORS.
II.DW-10 SEISMIC CLIP INTERLOCK SYSTEM BY HOHMANN & BARNARD.
III.ARCHITECT AND STRUCTURAL ENGINEER APPROVED TWO PIECE ADJUSTABLE HOT-DIPPED
GALVANIZED TIES.
2.INSTALLATION:
A.MASONRY VENEER SHALL BE INDEPENDENTLY SUPPORTED AT EACH STORY IN SEISMIC
DESIGN CATEGORY D, E, OR F.
B.MAXIMUM SPACING OF ANCHOR TIES SHALL BE 16" O.C. HORIZONTAL AND VERTICAL.
C.PROVIDE CONTINUOUS HORIZONTAL GALVANIZED #9 WIRE IN CENTER THIRD OF MORTAR JOINTS
AT 16" O.C.. ENGAGE #9 WIRE WITH ALL ANCHOR TIES.
D.MAXIMUM SPACING OF STUD BACKING SHALL BE 16" O.C. STUDS SHALL BE COVERED WITH
1/2" SHEATHING AND APPROVED PAPER.
E.CONSTRUCTION JOINTS IN MASONRY VENEER WALLS SHALL BE PROVIDED AS PER THE
ARCHITECTURAL DRAWINGS, AND SHALL BE SPACED AT A MAXIMUM OF 30'-0" O.C. FOR BRICK
VENEER AND A MAXIMUM OF 15'-0" O.C. FOR MASONRY BLOCK VENEER.
REINFORCING STEEL
1.CODES AND STANDARDS:
A.REINFORCING STEEL SHALL COMPLY WITH:
I.CONCRETE REINFORCING STEEL INSTITUTE "MANUAL OF STANDARD PRACTICE".
II.AMERICAN CONCRETE INSTITUTE "DETAILING MANUAL", ACI 315 (OR SP-66).
2.MATERIALS:
A.REINFORCING STEEL SHALL BE NEW STOCK DEFORMED BARS AND SHALL CONFORM TO ASTM
A615, GRADE 60, WITH A DESIGN YIELD STRENGTH OF 60,000 PSI, EXCEPT AS NOTED BELOW.
I. DOWELS TO BE BENT IN THE FIELD DURING CONSTRUCTION SHALL BE ASTM A615, GRADE
40 OR ASTM A706, GRADE 60, "LOW-ALLOY STEEL".
II. REINFORCING TO BE WELDED SHALL BE ASTM A706, GRADE 60,"LOW-ALLOY STEEL".
B.MASONRY JOINT REINFORCING SHALL CONFORM TO ASTM 951 AND SHALL BE MANUFACTURED
FROM WIRE WHICH CONFORMS TO ASTM A82.
C.MECHANICAL SPLICE COUPLERS SHALL BE CAPABLE OF DEVELOPING 125% OF THE SPECIFIED
STRENGTH OF THE BAR.
3.CONSTRUCTION:
A.REINFORCING SHALL BE DETAILED, BOLSTERED, AND SUPPORTED PER ACI 315.
B.REINFORCING STEEL SHALL BE FREE OF LOOSE FLAKY RUST, SCALE, GREASE, OIL, DIRT, AND
OTHER MATERIALS WHICH MIGHT AFFECT OR IMPAIR BOND.
C.REINFORCING SHALL BE CONTINUOUS IN WALLS, BEAMS, COLUMNS, SLABS, FOOTINGS, ETC.
D.SPLICES IN CONTINUOUS REINFORCING SHALL BE MADE IN AREAS OF COMPRESSION AND/OR
AT POINTS OF MINIMUM STRESS, TYPICAL UNLESS NOTED OTHERWISE. LAP SPLICES SHALL
BE MINIMUM OF 40 BAR DIAMETERS LONG IN CONCRETE AND 48 BAR DIAMETERS LONG IN
MASONRY, TYPICAL UNLESS NOTED OTHERWISE. MINIMUM LAP SHALL BE 24 INCHES LONG.
DOWELS SHALL HAVE A MINIMUM OF 30 BAR DIAMETERS EMBEDMENT. TENSION SPICES
SHALL BE USED IN CONCRETE WHEN SPECIFICALLY NOTED, USE A CLASS B SPLICE. SPLICES
IN TOP BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT MID SPAN. SPLICES IN
BOTTOM BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT SUPPORTS.
E.BENDS SHALL BE MADE COLD. DO NOT USE HEAT. BENDS SHALL BE DONE IN THE
FABRICATOR'S SHOP UNLESS SPECIFICALLY NOTED FOR THE FIELD. DO NOT UN-BEND OR RE-
BEND A PREVIOUSLY BENT BAR.
F.REINFORCING STEEL IN CONCRETE SHALL BE SECURELY ANCHORED AND TIED IN PLACE PRIOR
TO PLACING CONCRETE AND SHALL BE POSITIONED WITH THE FOLLOWING MINIMUM CONCRETE
COVER:
CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH................................................................3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER........................................................................2"
#5 AND SMALLER......................................................................1-1/2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS AND WALLS, #11 AND SMALLER..................................3/4"
BEAMS AND COLUMNS, MAIN REINFORCING OR TIES.........1-1/2"
SLABS ON GRADE.....................................................................CENTER OF SLAB
G.REINFORCING STEEL IN MASONRY SHALL BE PLACED PRIOR TO GROUTING AND SHALL BE
PLACED, POSITIONED, AND LOCATED ACCORDING TO THE STRUCTURAL DRAWINGS. IT SHALL
BE SECURED AGAINST DISPLACEMENT AT INTERVALS NOT TO EXCEED 200 BAR DIAMETERS OR
TEN FEET.
H.NO REINFORCING SHALL BE WELDED UNLESS SPECIFICALLY NOTED AS SUCH. USE E90XX
ELECTRODES AND ASTM A706 REINFORCING. COMPLY WITH AWS D1.4 REQUIREMENTS.
I.EPOXY COATED REINFORCING BARS SHALL BE USED WHEN SPECIFICALLY NOTED. INCREASE
LAP SPLICE LENGTHS AS REQUIRED BY THE IBC AND ACI.
8.DEFERRED SUBMITTALS:
A.THE FOLLOWING ITEMS REQUIRING DEFERRED SUBMITTALS ARE LISTED BELOW. THESE ITEMS
SHALL BE DESIGNED AND FABRICATED BY THE MANUFACTURER ACCORDING TO THE
SPECIFICATIONS GIVEN IN THE CONTRACT DOCUMENTS.
PRE-CAST CONCRETE MEMBERS
MANUFACTURED WOOD JOIST AND BEAMS
B.THESE DEFERRED SUBMITTALS SHALL FIRST BE SUBMITTED TO THE PROJECT ARCHITECT
AND/OR ENGINEER FOR REVIEW AND COORDINATION. UPON THE COMPLETION OF THE
ARCHITECT/ENGINEER REVIEW, THE ARCHITECT/ENGINEER WILL SUBMIT THE DEFERRED
SUBMITTALS TO THE BUILDING OFFICIAL FOR REVIEW AND APPROVAL. THE SUBMITTAL TO THE
BUILDING OFFICIAL SHALL INCLUDE A LETTER STATING THAT THE ARCHITECT/ENGINEER REVIEW
HAS BEEN PERFORMED AND THAT THE PLANS AND THE CALCULATIONS FOR THE DEFERRED
SUBMITTAL ITEMS ARE FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN
DRAWINGS WITH NO EXCEPTIONS.
C.THE FINAL SUBMITTAL SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
LICENSED IN THE STATE IN WHICH CONSTRUCTION WILL OCCUR AND SHALL BE AVAILABLE AT
THE JOBSITE THROUGHOUT CONSTRUCTION.
D.CONSTRUCTION RELATED TO DEFERRED SUBMITTALS SHALL NOT COMMENCE UNTIL THE
BUILDING OFFICIAL HAS APPROVED THE SUBMITTAL.
QUALITY ASSURANCE PLAN FOR STRUCTURE
1.INSPECTION:
A.THE OWNER SHALL PROVIDE SPECIAL INSPECTION BY QUALIFIED INSPECTORS FOR THE
FOLLOWING TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1704 AND 1707, THE
SPECIFICATIONS, AND THE ATTACHED TABLES INCLUDED IN THESE GENERAL NOTES.
REINFORCED CONCRETE:DURING THE CASTING OF ALL CONCRETE AND TAKING OF ALL
TEST SPECIMENS, AND SHALL VERIFY THE PLACEMENT OF ALL REINFORCING. INSPECTOR
SHALL BE ACI-II OR ICC CERTIFIED. SEE ATTACHED TABLE LABELED REQUIRED
VERIFICATION AND INSPECTION OF CONCRETE/STEEL CONSTRUCTION.
BOLTING: ALL HIGH STRENGTH BOLTS AND BOLTS EMBEDDED IN CONCRETE AND/OR
EPOXY. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF
CONCRETE/STEEL CONSTRUCTION.
WELDING: ALL SHOP AND FIELD WELDS. INSPECTOR SHALL BE AWS-QC1 CERTIFIED. SEE
ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF STEEL
CONSTRUCTION.
POST-INSTALLED ANCHORS:THE FIRST 25 POST-INSTALLED ANCHORS SHALL BE INSPECTED
AND 10 PERCENT OF THE REMAINING ANCHORS SHALL BE INSPECTED.
2.TESTING:
A.THE OWNER SHALL PROVIDE TESTING BY QUALIFIED TESTING AGENCIES FOR THE FOLLOWING
TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1708 AND THE SPECIFICATIONS.
SOILS: COMPACTION OF STRUCTURAL FILL.
CONCRETE: STRENGTH, SLUMP, AIR, AND TEMPERATURE.
MASONRY: STRENGTH OF MORTAR, GROUT, BLOCK, AND PRISMS.
BOLTING: PROPER INSTALLATION AND CORRECT TORQUE AND/OR TENSION.
WELDING:TYPE, SIZE, LENGTH, AND QUALITY OF ALL SHOP AND FIELD WELDS BY
APPROVED METHODS. ULTRASONICALLY TEST ALL COMPLETE PENETRATION WELDS.
3.STRUCTURAL OBSERVATIONS:
A.THE STRUCTURAL ENGINEER SHALL BE NOTIFIED TO PERFORM STRUCTURAL OBSERVATIONS
AT SIGNIFICANT STAGES OF CONSTRUCTION.:
B.THE STRUCTURAL ENGINEER SHALL PROVIDE A COPY OF THE OBSERVATION REPORT TO THE
ARCHITECT FOR FURTHER DISTRIBUTION.
4.THE CONTRACTOR SHALL:
A.SUBMIT A STATEMENT OF RESPONSIBILITY TO THE OWNER AND BUILDING OFFICIAL PRIOR TO
COMMENCING WORK ON STRUCTURE THAT INCLUDES AWARENESS OF THE QUALITY
ASSURANCE PLAN REQUIREMENTS, ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED
TO OBTAIN CONFORMANCE TO CONSTRUCTION DOCUMENTS, PROCEDURES FOR EXERCISING
CONTROL, METHOD AND FREQUENCY OF REPORTING, AND IDENTIFICATION AND
QUALIFICATIONS OF PERSONNEL IN CHARGE OF CONTROL.
B.CORRECT ALL WORK FOUND TO BE DEFICIENT AT NO ADDITIONAL COST TO THE OWNER.
C.COORDINATE ALL THE REQUIRED INSPECTIONS, TESTING, AND/OR STRUCTURAL
OBSERVATIONS OF THE QUALITY ASSURANCE PLAN. DO NOT PROCEED WITH SUBSEQUENT
WORK UNTIL THE REQUIRED INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATIONS HAVE
BEEN PROVIDED. NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER AT LEAST 48 HOURS
PRIOR TO ANY REQUIRED OBSERVATIONS.
D.PROVIDE COPIES OF THE DAILY INSPECTION REPORTS AND ALL TESTING RESULTS TO THE
ARCHITECT, STRUCTURAL ENGINEER, OWNER, AND BUILDING OFFICIAL.
CONCRETE
1.CODES AND STANDARDS:
A.CONCRETE CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) EDITIONS OF:
I.ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS".
II.ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", EXCEPT AS
MODIFIED BY THE IBC.
III.ACI 347, "RECOMMENDED PRACTICE FOR CONCRETE FORM WORK".
2.MATERIALS:
A.CEMENT SHALL CONFORM TO ASTM C150, PORTLAND CEMENT.
I.USE TYPE I OR II FOR EXPOSURE CLASS S0
II.USE TYPE I OR V FOR EXPOSURE CLASS S1
III.USE TYPE V FOR EXPOSURE CLASS S2 AND S3
B.HARD ROCK AGGREGATES SHALL CONFORM TO ASTM C33. LIGHTWEIGHT AGGREGATES SHALL
CONFORM TO ASTM C330.
C.WATER SHALL BE POTABLE.
D.AIR ENTRAINMENT SHALL CONFORM TO ASTM C260.
I.LIMIT AIR CONTENT TO 3% AT TROWEL FINISHED FLOOR SLABS OR FINISH PER ACI302.1R-96
"GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION" WHERE AIR CONTENT IS >3%.
E.FLY ASH, CLASS F POZZOLAN SHALL CONFORM TO ASTM C618.
F.CALCIUM CHLORIDE SHALL NOT BE USED.
G.DEFORMED BAR ANCHORS (DBA) SHALL CONFORM TO ASTM A496.
H.HEADED ANCHOR STUDS (HAS) SHALL CONFORM TO ASTM A108.
I.SILICA FUME (2% TO SUSPENDED PARKING SLABS) SHALL CONFORM TO ASTM C1240
3.MIX DESIGNS:
A.ONLY ONE TYPE OF CONCRETE SHALL BE PLACED AT THE SITE AT ANY GIVEN TIME.
B.LIMIT SLUMP TO 4" MAXIMUM PRIOR TO THE ADDITION OF PLASTICIZERS AND WATER REDUCING ADD
MIXTURES. CONCRETE SUPPLIER SHALL INDICATE FINAL SLUMP OF EACH CONCRETE MIX DESIGN.
C.CONCRETE MIXES SHALL CONFORM TO THE FOLLOWING:
D. LIMIT FLY ASH TO 25% OF THE TOTAL CEMENTITIOUS MATERIAL.
E. PEA GRAVEL AGGREGATE AND/OR PLASTICIZER MAY BE USED IN CONGESTED AREAS WHEN
REQUIRED TO PROPERLY FILL ALL VOIDS AND/OR FOR WORKABILITY. (CONTRACTORS OPTION).
4.CONSTRUCTION:
A. CONCRETE SHALL BE PROPERLY VIBRATED DURING PLACEMENT.
B. PRIOR TO PLACING CONCRETE, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT
OF OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS,
ETC. ANCHOR BOLTS AND DOWELS SHALL BE PLACED PRIOR TO CASTING CONCRETE.
C. CONSTRUCTION JOINTS AND BULKHEADS SHALL BE FORMED WITH A KEY WAY. ALL CONTACT
SURFACES, NEW OR EXISTING, AT CONSTRUCTION JOINTS SHALL BE INTENTIONALLY
ROUGHENED TO A 1/4" AMPLITUDE PRIOR TO CASTING ADJACENT POUR.
D. GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE.
E. OPENINGS IN FLOORS AND/OR WALLS SHALL HAVE ADDITIONAL REINFORCING AROUND ALL
SIDES OF THE OPENING EQUIVALENT TO THE BARS CUT BY THE OPENING WITH HALF ON EACH
SIDE OF THE OPENING OR 2-#5 BARS, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE.
BARS PARALLEL TO THE PRINCIPAL REINFORCING SHALL RUN FULL LENGTH OF THE SPAN.
BARS IN THE OTHER DIRECTION SHALL RUN 24 INCHES BEYOND THE EDGE OF THE OPENING
OR END WITH A STANDARD HOOK. ALSO PROVIDE 2-#5 X 4'-0" DIAGONAL BARS AT EACH
CORNER OF EACH OPENING.
F.NO PENETRATION SHALL BE ALLOWED THROUGH ANY CONCRETE BEAM, JOIST, COLUMN, PIER,
OR JAMB WITHOUT THE ARCHITECT?S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN
APPROVAL. PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS.
G.ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH
COMPRESSED AIR. FOLLOW MANUFACTURERS RECOMMENDATIONS.
5.FOOTINGS:
A.FOOTINGS SHALL BEAR ON PROPERLY PREPARED MATERIAL. SEE THE SITE PREPARATION
NOTES.
B.FOOTINGS SHALL BE CENTERED BELOW THE WALL AND/OR COLUMN ABOVE, TYPICAL UNLESS
NOTED OTHERWISE.
C.EXTERIOR FOOTINGS SHALL BEAR BELOW THE EFFECTS OF FROST.
D.PROVIDE A 2X4 BEVELED KEY WAY IN ALL CONTINUOUS WALL FOOTINGS.
E.STAGGER FOOTING CONSTRUCTION JOINTS FROM WALL CONSTRUCTION JOINTS ABOVE BY AT
LEAST 6 FEET.
F.REINFORCING IN CONTINUOUS FOOTINGS SHALL BE CONTINUOUS AT CORNERS AND/OR
INTERSECTIONS BY PROVIDING PROPER LAP LENGTHS AND/OR CORNER BARS.
STRUCTURAL STEEL
1.CODES AND STANDARDS:
A.STRUCTURAL STEEL DESIGN, FABRICATION, AND ERECTION SHALL COMPLY WITH:
I.THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS (AISC 360-16)", WITH "COMMENTARY".
II.AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES (AISC 303-10)"
EXCLUDING SECTIONS 1.5.1,4.4,7.5.4, AND 7.13.3.
III.AMERICAN WELDING SOCIETY (AWS-D1.1) "STRUCTURAL WELDING CODE -STEEL",
EXCLUDING ITEMS CONFLICTING WITH AISC REQUIREMENTS.
2.MATERIALS:
A.STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. OTHER
STRUCTURAL STEEL SHAPES, PLATES, ANGLES, ETC. SHALL CONFORM TO ASTM A36.
RUSSIAN STEEL IS NOT PERMITTED.
B.HOLLOW STRUCTURAL SECTIONS SHALL CONFORM TO ASTM A500, GRADE B, WITH A MINIMUM
YIELD STRENGTH Fy = 46 KSI.
C.STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, WITH A MINIMUM YIELD STRENGTH
Fy = 35 KSI.
D.HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A325 (A490). ANCHOR RODS SHALL HAVE
HEADED STUDS AND SHALL CONFORM TO ASTM F1554. ALL OTHER BOLTS SHALL CONFORM TO
ASTM A307 OR BETTER.
E.HEADED ANCHOR STUDS AND DEFORMED BAR ANCHORS SHALL CONFORM TO THE
MANUFACTURER'S SPECIFICATIONS.
F.ALL MEMBERS AND WELDS WHICH HAVE COMPLETE PENETRATION GROOVE WELDS SHALL
MEET THE CHARPY V-NOTCH TOUGHNESS IMPACT TEST OF 20 FOOT POUNDS AT 0 DEGREES
FAHRENHEIT AND 40 FOOT POUNDS AT 70 DEGREES FAHRENHEIT.
3.CONSTRUCTION:
A.FABRICATION SHALL BE DONE IN AN APPROVED FABRICATOR'S SHOP.
B.CAMBER IN BEAMS SHALL BE AS INDICATED ON PLANS.
C.PROVIDE A SHOP COAT OF PAINT ON ALL STEEL ITEMS, EXCEPT AT AREAS OF WELDING
AND/OR BOLTING.
D.USE HIGH STRENGTH (8000 PSI MINIMUM AT 28 DAY), NON-SHRINK, LIQUID EPOXY GROUT
BENEATH ALL STEEL BASE PLATES AND BEARING PLATES. MIX GROUT WITH SAND OR PEA
GRAVEL AS RECOMMENDED BY THE MANUFACTURER. PLACE GROUT AS SOON AS STEEL
MEMBER HAS BEEN PROPERLY POSITIONED AND ALIGNED.
E.WHERE STRUCTURAL STEEL WIDE FLANGE, PIPE, OR HOLLOW STRUCTURAL SECTIONS ARE
EMBEDDED IN CONCRETE OR MASONRY AND REINFORCING BARS BUTT TO IT, DEFORMED BAR
ANCHORS OR REINFORCING BARS WITH THE SAME SIZE AND SPACING AS THE ADJACENT
REINFORCING BARS, 48 BAR DIAMETERS LONG, SHALL BE WELDED TO THE STRUCTURAL
STEEL. THE MANUFACTURER?S WELDING PROCEDURES SHALL BE ADHERED TO.
4.BOLTED CONNECTIONS:
A.STEEL TO STEEL BOLTED CONNECTIONS SHALL BE MADE WITH ASTM A325 HIGH
STRENGTH BOLTS AND NUTS, UNLESS NOTED OTHERWISE. BOLTS SHALL CARRY THE
IDENTIFYING MARK OF THREE (3) RADIAL LINES.
B.ALL OTHER BOLTED CONNECTIONS SHALL BE MADE WITH BOLTS AND NUTS CONFORMING TO
ASTM A307 UNLESS NOTED OTHERWISE.
C.BOLTS SHALL BE 3/4" DIAMETER, TYPICAL, UNLESS NOTED OTHERWISE. STANDARD
SPACING SHALL BE 3" O.C. AND STANDARD EDGE DISTANCE SHALL BE 1.1/2", TYPICAL, UNLESS
NOTED OTHERWISE.
D.BOLT SHALL BE BEARING TYPE CONNECTIONS WITH THREADS EXCLUDED UNLESS NOTED
OTHERWISE.
E.BOLTED CONNECTIONS SHALL BE TIGHTENED SNUG TIGHT AND SHALL
HAVE WASHERS AS REQUIRED BY AISC UNLESS NOTED OTHERWISE.
F.ENLARGING OF HOLES SHALL BE ACCOMPLISHED BY MEANS OF REAMING. DO NOT USE A
TORCH ON ANY BOLT HOLES.
5.WELDED CONNECTIONS:
A.WELDING AND GAS CUTTING SHALL BE DONE PER AWS.
B.WELDERS SHALL BE CURRENTLY CERTIFIED ACCORDING TO AWS. ALL WELDING PROCEDURES
SHALL BE PRE-QUALIFIED. WELDERS SHALL FOLLOW WELDING PROCEDURES.
C.WELDED CONNECTIONS SHALL BE MADE USING LOW HYDROGEN MATCHING FILLER MATERIAL
ELECTRODES, UNLESS NOTED OTHERWISE.
D.WELDS SHALL HAVE THE SLAG REMOVED.
E.FULL PENETRATION WELDS, SHOP OR FIELD, SHALL HAVE BACKER BARS REMOVED, BE BACK
GOUGED, AND REWELDED PER AWS TO HAVE FULL PENETRATION WELD.
STEEL DECK
1.PRODUCT:
A.STEEL DECK SHALL BE SIZE AND GAUGE AS SPECIFIED ON PLANS.
B.STEEL DECK AND ACCESSORIES SHALL BE MANUFACTURED FROM COLD ROLLED STEEL
CONFORMING TO ASTM A-653, (GALVANIZED G-60), OR ASTM A-611, GRADE C (PAINTED), AND
SHALL CONFORM TO THE STEEL DECK INSTITUTE (SDI) AND AISC STANDARDS
2.ATTACHMENT AND HANDLING:
A.WELDING PATTERN SHALL BE AS SPECIFIED ON PLAN.
B.WELD METAL DECK TO SUPPORTING FRAMING MEMBERS WITH E60XX OR E70XX ELECTRODES.
C.PUDDLE WELDS SHALL HAVE A FUSION AREA OF NOT LESS THAN 3/4" DIAMETER AT THE
UPPER SURFACE. WELD METAL SHALL PENETRATE ALL LAYERS OF THE DECK MATERIAL AND
SHALL HAVE PROPER FUSION TO THE SUPPORTING MEMBERS.
D.CRIMP SIDE SEAMS BEFORE WELDING SIDE LAPS. TOP SEAM WELDS SHALL ENGAGE ALL
LAYERS OF THE DECK MATERIAL.
E.END LAPS SHALL OVERLAP AT LEAST 2" AND SHALL OCCUR OVER A SINGLE STEEL SUPPORT.
PUDDLE WELDS SHALL OCCUR AT LEAST 1" AWAY FROM EITHER END OF DECK.
F.PUDDLE WELDS 3/8" X 1.1/2" LONG MAY REPLACE 3/4" DIAMETER PUDDLE WELDS WHEN
ACCESS IS LIMITED.
G.INSTALL DECK WITH A MINIMUM OF 3 SPANS WHEREVER POSSIBLE.
H.PROVIDE ANGLE AND/OR OTHER SUPPORT AROUND THE PERIMETER OF ALL OPENINGS
LARGER THAN 10" IN EITHER DIRECTION THROUGH METAL DECK.
I.PROVIDE DECK SUPPORT AS REQUIRED AT COLUMNS.
J.DO NOT BEND OR MAR DECK.
K.STORE DECKING OFF THE GROUND WITH ONE END ELEVATED. COVER DECK WITH
WATERPROOF MATERIAL AND VENTILATE TO AVOID CONDENSATION.
WOOD
1.CODES AND STANDARDS:
A.WOOD CONSTRUCTION SHALL COMPLY WITH:
I.THE AMERICAN FOREST & PAPER ASSOCIATION "NATIONAL DESIGN SPECIFICATION",
AFPA-NDS.
II.THE GRADING REQUIREMENTS OF THE WESTERN WOODS PRODUCTS ASSOCIATION,
WWPA.
2.MATERIALS:
A.STRUCTURAL LUMBER SHALL BE AS FOLLOWS AND SHALL BE CLEARLY MARKED AS TO
SPECIES AND GRADE:
I.JOISTS, BEAMS OR HEADERS -DOUGLAS FIR-LARCH #2 OR BETTER.
II.POSTS AND COLUMNS -DOUGLAS FIR-LARCH #1 OR BETTER.
III.STUDS -DOUGLAS FIR-LARCH #2 OR BETTER. STUD GRADE AND STANDARD GRADE ARE
NOT ALLOWED.
B.MANUFACTURED JOISTS SHALL BE AS PER THE DRAWINGS UNLESS OTHERWISE APPROVED
BY THE ARCHITECT AND STRUCTURAL ENGINEER PRIOR TO BIDDING. ALTERNATE JOIST
MANUFACTURERS PRODUCTS ARE ACCEPTABLE PROVIDED THE SECTION PROPERTIES,
DESIGN PARAMETERS, AND LOADING CAPACITIES OF THE SPECIFIED PRODUCT ARE MET OR
EXCEEDED.
C.STRUCTURAL GLUED-LAMINATED TIMBER SHALL BE MANUFACTURED AND IDENTIFIED PER AITC
A190.1 AND ASTM D 3737. IT SHALL BE 24F-V4 FOR SIMPLE SPANS AND 24F-V8 FOR
CONTINUOUS SPANS OR CANTILEVERED BEAMS AND CLEARLY MARKED, MEETING THE GRADE
REQUIREMENTS AS DEFINED BY THE IBC.
D.STRUCTURAL LAMINATED-VENEER-LUMBER (LVL) SHALL CONFORM TO THE FOLLOWING
MINIMUM DESIGN PARAMETERS:
Fb =2,600 PSI
Fv =285 PSI
E =1,900,000 PSI
E.STRUCTURAL PARALLEL-STRAND-LUMBER (PSL) SHALL CONFORM TO THE FOLLOWING MINIMUM
DESIGN PARAMETERS:
Fb =2900 PSI
Fv =290 PSI
E =2,000,000 PSI
F.STRUCTURAL LAMINATED-STRAND-LUMBER (LSL) SHALL CONFORM TO THE FOLLOWING
MINIMUM DESIGN PARAMETERS:
Fb =2250 PSI
Fv =285 PSI
E =1,500,000 PSI
G.WOOD STRUCTURAL PANELS SHALL BE EXPOSURE 1 GRADE OR BETTER A.P.A. RATED
SHEATHING WITH EXTERIOR GLUE AND SHALL CONFORM TO STANDARD PS 1-07, OR PS 2-04.
H.WOOD CONNECTORS SHALL BE SIMPSON STRONG-TIE UNLESS OTHERWISE APPROVED BY THE
ARCHITECT AND STRUCTURAL ENGINEER PRIOR TO BIDDING.
I.WOOD JOISTS AND BEAMS SHALL BE DESIGNED AND STAMPED BY A PROFESSIONAL
ENGINEER CURRENTLY LICENSED IN THE STATE IN WHICH CONSTRUCTION WILL OCCUR.
3.CONSTRUCTION:
A.ROOF AND FLOOR JOISTS SHALL BE AS NOTED ON THE PLANS. ALL JOISTS SHALL BE
LATERALLY SUPPORTED AT THE ENDS BY SOLID BLOCKING AND/OR A METAL HANGER.
B.MANUFACTURED JOISTS SHALL BE ERECTED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS AND SHALL BE DESIGNED TO SUPPORT THE MAXIMUM LOADS INDICATED
IN THE MANUFACTURER'S PUBLISHED LOAD TABLES.
C.PROVIDE APPROVED BRIDGING AT 8'-0" O.C. MAXIMUM SPACING FOR ALL DIMENSIONAL
LUMBER, LVL, PSL, AND LSL JOISTS. PROVIDE BRIDGING IN ALL OTHER MANUFACTURED JOISTS
PER THE MANUFACTURER'S RECOMMENDATIONS UNLESS OTHERWISE SHOWN ON PLAN.
D.HOLES IN WOOD CONNECTORS (FRAMING ANCHORS, JOIST HANGERS, PURLIN ANCHORS, ETC.)
MUST BE FILLED WITH NAILS AS SPECIFIED BY THE MANUFACTURER, TYPICAL, UNLESS NOTED
OTHERWISE.
E.BOLTS THRU WOOD SHALL HAVE WASHERS UNDER NUTS. ALL BOLTS HOLES SHALL BE 1/32
TO 1/16 INCH LARGER THAN BOLTS. NUTS SHALL BE TIGHTENED SNUGLY, BUT NOT SO TIGHT
AS TO CAUSE CRUSHING OF THE WOOD. DO NOT COUNTERSINK BOLTS UNLESS SPECIFICALLY
NOTED.
F.NAILING OF MEMBERS SHALL CONFORM TO THE FASTENING SCHEDULE IN THE IBC, TABLE
2304.9.1, UNLESS NOTED OTHERWISE.
G.EDGE NAILING BETWEEN PANELS OF SHEATHING SHALL OCCUR ALONG A SINGLE COMMON
BACK UP MEMBER. SHEATHING SHALL BE EDGE NAILED TO ALL MEMBERS ATTACHED TO
DRAG STRUTS, HOLD DOWNS, FLOOR TIE ANCHORS, ETC.
H.CORNERS AND INTERSECTIONS OF SHEAR WALLS SHALL BE BUILT INTEGRALLY. THE
SHEATHING FROM EACH WALL SHALL BE EDGE NAILED TO A COMMON BACK UP MEMBER.
I.SILL PLATES FOR SHEAR WALLS SHALL BE 2X MATERIAL (3X WHEN SPECIFIED), AND ANCHOR
BOLTS SHALL HAVE A 3"X3" SIMPSON BPS 5/8-6 ANCHOR BOLT PLATE OR EQUAL WHICH SHALL
BE INSTALLED A MAXIMUM OF 1/2" FROM THE WOOD STRUCTURAL PANEL FACE OF THE WALL.
J.LAMINATED BUILT-UP BEAMS OF 2X__ MEMBERS 10" DEEP OR LESS SHALL BE NAILED
TOGETHER WITH NOT LESS THAN 16d NAILS AT 12" O.C., STAGGERED. USE (2)-20d COMMON
NAILS AT ALL SUPPORTS. 2X__ MEMBERS DEEPER THAN 10" SHALL BE BOLTED TOGETHER
WITH 1/2" BOLTS AT 16" O.C. STAGGERED WITH 2 BOLTS AT SUPPORTS.
K.SPLIT RINGS SHALL BE TECO SPLIT RINGS AS MANUFACTURED BY THE TIMBER ENGINEERING
COMPANY UNLESS OTHERWISE APPROVED BY THE ARCHITECT AND ENGINEER PRIOR TO
BIDDING. SPLIT RINGS SHALL BE MANUFACTURED FROM HOT ROLLED S.A.E.-1010 CARBON
STEEL. EACH RING SHALL FORM A CLOSED TRUE CIRCLE WITH THE PRINCIPAL AXIS OF THE
CROSS SECTION OF THE RING PARALLEL TO THE GEOMETRIC AXIS OF THE RING. THE RING
SHALL FIT SNUGLY IN THE PREPARED GROOVE. GROVES FOR SPLIT RINGS SHALL NOT BE
GREATER THEN 1/16"DEEPER THAN REQUIRED. DEPTH OF GROVE SHALL BE EQUAL ON BOTH
WOOD MEMBERS.
POST-INSTALLED ANCHORS
1.EPOXY ANCHORS:
A.THE FOLLOWING EPOXY ADHESIVES SYSTEMS SHALL BE ALLOWED:
FOR CONCRETE:
SIMPSON SET-XP
HILTI HIT-RE 500-V3
HILTI HIT-RE 100
FOR SOLID GROUTED MASONRY:
SIMPSON SET
HILTI HIT HY 200
FOR UNGROUTED MASONRY:
SIMPSON ET
HILTI HY 270
B.ANCHOR RODS SHALL BE ASTM A-307, THREADED AND GALVANIZED, AND THE DIAMETER AS
INDICATED ON PLAN.
C.SCREEN TUBES SHALL BE USED AT UNGROUTED MASONRY UNITS.
D.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
E.INSTALLATION OF ADHESIVE ANCHORS THAT ARE TO BE UNDER SUSTAINED TENSION LOADING IN
HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION SHALL BE DONE BY A CERTIFIED ADHESIVE
ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318-2014
(Section 17.8.2.2). PROOF OF CURENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR
APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
F.PER ACI 318-2014 (Section 17.1.2) ADHESIVE ANCHORS SHALL BE INSTALLLED IN CONCRETE HAVING A
MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. FOR INSTALLATIONS SOONER THAN 21
DAYS CONSULT ADHESIVE MANUFACTURER.
G.IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE INSTALLATION IS AT 45 DEGREES
(FAHRENHEIT) OR LESS, AN “ACRYLIC” (COLD WEATHER) ADHESIVE IS REQUIRED –ie DEWALT AC200+,
HILTI HY200, SIMPSON AT-XP.
2.MECHANICAL ANCHORS
A.THE FOLLOWING MECHANICAL ANCHORS SHALL BE ALLOWED:
SIMPSON TITEN HD
HILTI KWIK HUS-EZ
B.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
3.SUBSTITUTES: CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR APPROVAL TO THE
ARCHITECT AND STRUCTURAL ENGINEER.2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:00 AMSE-001
GENERAL
NOTESJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
* (LW) CONCRETE SHALL HAVE A MIN. SPLITTING TENSILE STRENGTH OF 450 PSI.
SLAB ON METAL DECK (LW)* 3000 0.50 110 3/4 - 470 F0,S0,P0,C0
SLAB ON METAL DECK (NW) 3000 0.50 145 3/4 - 470 F0,S0,P0,C0
SUSPENDED SLABS AND SLABS ON METAL DECK
SLAB ON GRADE 3000 0.48 145 1 - 470 F0,S0,P0,C0
WALLS 4000 0.45 145 3/4 - 564 F0,S0,P0,C0
FOOTINGS 4000 0.45 145 1 - 564 F0,S0,P0,C0
INTERIOR MEMBERS
SLAB ON GRADE 4500 0.45 145 3/4 6±1.5 611 F2,S0,P0,C1
OTHER SITE CONCRETE 4500 0.45 145 3/4 6±1.5 611 F2,S0,P0,C1
WALLS, PIERS, BEAMS 4500 0.45 145 3/4 6±1.5 611 F2,S0,P0,C1
FOOTINGS 4000 0.45 145 1 6±1.5 564 F0,S0,P0,C0
EXTERIOR MEMBERS
TYPE OF MEMBER
MIN.
STRENGTH
@ 28 DAYS
(PSI)
MAX.
W/C
(RATIO)
DRY
WEIGHT
(PCF)
MAX
AGGREGTE
SIZE
(INCHES)
AIR
ENTRAIN-
MENT (%)
MIN.
CEMENT
PER YARD
(LBS)
EXPOSURE
CLASS
CONCRETE MIX DESIGN TABLE
Sheet List
Sheet Number Sheet Name
SE-001 GENERAL NOTES
SE-002 INSPECTIONS
SE-003 INSPECTIONS
SE-004 SCHEDULES
SE-005 3D RENDERING
SE-110 FOUNDATION PLAN
SE-111 STAGE FRAMING PLAN
SE-121 LOW ROOF FRAMING PLAN
SE-122 CURTAIN SUPPORTS
SE-123 FITNESS CENTER ROOF FRAMING
SE-201 ENLARGED FRAMING PLANS
SE-202 ENLARGED FRAMING PLANS
SE-511 FRAMING DETAILS
SE-512 FRAMING DETAILS
11/24/2020
2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:02 AMSE-002
INSPECTIONSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
REINFORCEMENT COMPLYING WITH ASTM A
615 IN SPECIAL MOMENT FRAMES,
SPECTION STRUCTURAL WALLS, AND
COUPLING BEAMS
X VERFY THAT ASTM A 615 REINFORCING STEEL USED IN THESE
AREAS COMPLIES WITH ACI 318: 21.1.5.2 BY MEANS OF CERTIFIED
MILL TEST REPORTS. IF THIS REINFORCING STEEL IS TO BE
WELDED CHEMICAL TESTS SHALL BE PERFORMED IN ACCORDANCE
WITH ACI 318: 3.5.2.
FORMWORK X VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM TO
THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS AS
REQUIRED BY THE APPROVED CONSTRUCTION DOCUMENTS.
STRENGTH VERIFICATION X VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED PRIOR
TO THE REMOVAL OF SHORES AND FORMS OR THE STRESSING OF
POST-TENSIONED TENDONS.
ERECTION OF PRECAST CONCRETE X VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED, ASSEMBLED
AND BRACED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
PRE-STRESSED CNCRETE X
CURING TEMPERATURE AND TECHNIQUES X VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS KEPT
AT >50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT.
HIGH-EARLY-STRENGTH CONCRETE SHALL BE KEPT AT >50°F FOR
AT LEAST 3 DAYS. ACCELERATED CURING METHODS MAY BE USED
(SEE ACI 318: 5.11.3). THE AMBIENT TEMPERATURE FOR SHOTCRETE
SHALL BE >40°F FOR THE SAME PERIOD OF TIME AS NOTED FOR
CONCRETE. SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
FOR AT LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO AVOID
PLASTIC SHRINKAGE CRACKING AND THAT THE SPECIFIED
WATER/CEMENT RATIO IS NOT EXCEEDED.
CONCRETE AND SHOTCRETE PLACEMENT X
CONCRETE SAMPLING FOR STRENGTH
TESTS, SLUMP, AIR CONTENT, AND
TEMPERATURE
X
USE OF REQUIRED MIX DESIGN X VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318-11: CH. 4,5.2-5.4; AND IBC
1904.3, 1913.2, 1913.3.
POST-INSTALLED ANCHORS OR DOWELS X ALL POST-INSTALLED ANCHORS/DOWELS SHALL BE SPECIALLY
INSPECTED AS REQUIRED BY THE APPROVED ICC-ES REPORT.
CAST-IN BOLTS AND EMBEDS X INSPECTION OF ANCHORS OR EMBEDS CAST IN CONCRETE IS
REQUIRED WHEN ALLOWABLE LOADS HAVE BEEN INCREASED OR
WHERE STRENGTH DESIGN IS USED.
REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS
X VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS OF
SPECIFIED TYPE, GRADE AND SIZE; THAT IT IS FREE OF OIL, DIRT,
AND RUST; THAT IT IS LOCATED AND SPACED PROPERLY; THAT
HOOKS, BENDS, TIES, STIRRUPS, AND SUPPLEMENTAL...
CONCRETE CONSTRUCTION (IBC 1705.3)
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
CONCRETE CONSTRUCTION (IBC 1705.3 AND 1705.12.1)
REINFORCEMENT COMPLYING WITH ASTM A
615 IN SPECIAL MOMENT FRAMES,
SPECTION STRUCTURAL WALLS, AND
COUPLING BEAMS
X VERFY THAT ASTM A 615 REINFORCING STEEL USED IN THESE
AREAS COMPLIES WITH ACI 318: 21.1.5.2 BY MEANS OF CERTIFIED
MILL TEST REPORTS. IF THIS REINFORCING STEEL IS TO BE
WELDED CHEMICAL TESTS SHALL BE PERFORMED IN ACCORDANCE
WITH ACI 318: 3.5.2.
FORMWORK X VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM TO
THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS AS
REQUIRED BY THE APPROVED CONSTRUCTION DOCUMENTS.
STRENGTH VERIFICATION X VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED PRIOR
TO THE REMOVAL OF SHORES AND FORMS OR THE STRESSING OF
POST-TENSIONED TENDONS.
ERECTION OF PRECAST CONCRETE X VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED, ASSEMBLED
AND BRACED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
PRE-STRESSED CONCRETE X APPLICATION OF PRESTRESSING FORCES AND GROUTING OF
BONDED PRESTRESSING TENDONS.
CURING TEMPERATURE AND TECHNIQUES X VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS KEPT
AT >50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT.
HIGH-EARLY-STRENGTH CONCRETE SHALL BE KEPT AT >50°F FOR
AT LEAST 3 DAYS. ACCELERATED CURING METHODS MAY BE USED
(SEE ACI 318: 5.11.3). THE AMBIENT TEMPERATURE FOR SHOTCRETE
SHALL BE >40°F FOR THE SAME PERIOD OF TIME AS NOTED FOR
CONCRETE. SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
FOR AT LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO AVOID
PLASTIC SHRINKAGE CRACKING AND THAT THE SPECIFIED
WATER/CEMENT RATIO IS NOT EXCEEDED.
CONCRETE AND SHOTCRETE PLACEMENT X
CONCRETE SAMPLING FOR STRENGTH
TESTS, SLUMP, AIR CONTENT, AND
TEMPERATURE
X
USE OF REQUIRED MIX DESIGN X VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318-11: CH. 4,5.2-5.4; AND IBC
1904.3, 1913.2, 1913.3.
B. MECHANICAL ANCHORS AND ADHESIVE
ANCHORS NOT DEFINED IN 4.a.
X
A. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
X
POST-INSTALLED ANCHORS OR DOWELS. X ALL POST-INSTALLED ANCHORS/DOWELS SHALL BE SPECIALLY
INSPECTED AS REQUIRED BY THE APPROVED ICC-ES REPORT.
CAST-IN BOLTS AND EMBEDS X INSPECTION OF ANCHORS OR EMBEDS CAST IN CONCRETE IS
REQUIRED WHEN ALLOWABLE LOADS HAVE BEEN INCREASED OR
WHERE STRENGTH DESIGN IS USED.
C. INSPECT ALL OTHER WELDS X
B. INSPECT SINGLE-PASS FILLET WELDS,
MAXIMUM 5/16"
X
A. VERIFY WELDABILITY OF REINFORCING
BARS OTHER THAN ASTM A706
X
REINFORCING BAR WELDING
REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS
X VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS OF
SPECIFIED TYPE, GRADE AND SIZE; THAT IT IS FREE OF OIL, DIRT,
AND RUST; THAT IT IS LOCATED AND SPACED PROPERLY; THAT
HOOKS, BENDS, TIES, STIRRUPS, AND SUPPLEMENTAL...
CONCRETE CONSTRUCTION (IBC 1705.3)
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
CONCRETE CONSTRUCTION (IBC 2015 1705.3)
VERIFY THAT HELICAL PILES USED MATCH
THE APPROVED SUBMITTAL
X
RECORD INSTALLATION EQUIPMENT USED,
PILE DIMENSIONS, TIP ELEVATIONS, FINAL
DEPTH, AND FINAL INSTALLATION TORQUE
X
HELICAL PILE FOUNDATIONS (IBC 1705.9):
PERFORM ADDITIONAL INSPECTIONS FOR
CONCRETE ELEMENTS
CONCRETE PER IBC 1705.3.
VERIFY PLACEMENT LOCATIONS AND
PLUMBNESS, CONFIRM ELENTDIAMETERS,
LENGTHSMBENTE END-BEARING CAPACITY.
RECORD CONCRETE OR GROUT VOLUMES
X
OBSERVE DRILLING OPERATION AND
REPORTING
X
CAST-IN-PLACE DEEP FOUNDATIONS (IBC 1705.8):
PERFORM ADDITIONAL INSPECTIONS FOR
STEEL, CONCRETE OR OTHER SPECIALTY
ELEMENTS
STEEL PER IBC 1705.2, CONCRETE PER IBC 1705.3, SPECIALTY
ITEMS PER REGISTERED DESIGN PROFESSIONAL.
VERIFY PLACEMENT LOCATION AND
PLUMBNESS, CONFIRM TYPE AND SIZE OF
HAMMER, RECORD NUMBER OF BLOWS PER
FOOT, RECORD TIP AND BUTT ELEVATIONS,
AND DOCUMENT ANDY DAMAGE TO
ELEMENT
X
OBSERVE DRILLING OPERATIONS X
DETERMINE CAPACITIES AND CONDUCT
NECESSARY LOAD TESTS
X
VERIFY MATERIALS, SIZES AND LENGTHS X
DRIVEN DEEP FOUNDATIONS (IBC 1705.7):
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
FOUNDATIONS (IBC 1705.7, 1705.8, AND 1705.9)
LEGEND
INDICATES BRACE CONNECTION.
INDICATES CONCRETE FILLED STEEL
COLUMN, FILL WITH 4000psi SELF
CONSOLIDATING CONCRETE.HSS?? CFINDICATES CONCRETE SLAB ON GRADE,
SEE PLAN NOTES.
INDICATES FRAME ELEVATION VIEW.
INDICATES CHANGE IN SLAB ELEVATION
AND DEPTH FROM F.S.E.
OPEN INDICATES OPENING IN DECK, SEE
DETAIL ______.
INDICATES CONCRETE WALL, SEE
SCHEDULE.
1 Ref
SE?-??
INDICATES SPECIAL MOMENT FRAME
CONNECTION, SEE DETAIL C1/SE514.
INDICATES DRAG CONNECTION, SEE
STEEL TO STEEL CONNECTION
SCHEDULE.
INDICATES CANTILEVER MOMENT
CONNECTION, SEE DETAIL _______.
INDICATES SNOW DRIFT LOADS TO BE
APPLIED TO JOISTS, SEE DRIFT
SCHEDULE.
INDICATES RECESSED SLAB, SEE ARCH.
INDICATES FINISHED FLOOR SLAB
ELEVATION.
T.F. = ??'-??"INDICATES TOP OF FOOTING
ELEVATION.
INDICATES TOP OF WALL ELEVATION.
INDICATES TOP OF PIER ELEVATION.
T.W. = ??'-??"
T.P. = ??'-??"
INDICATES BAR GRATING SPAN
DIRECTION, SEE PLAN NOTES.
INDICATES EXPANSION JOINT.
CW-??
??"
INDICATES MOMENT FRAME BRACING.
INDICATES FOLDING PARTITION.
DR-?
INDICATES TOP OF STEEL ELEVATION.T.S. = ??'-??"
INDICATES WOOD SHEATHING SPAN
DIRECTION, SEE PLAN NOTES.
SW-X.X-Y INDICATES STEEL STUD SHEAR WALL
TYPE (X.X) AND SHEATHING (Y) IF
REQUIRED. ARROW INDICATES FACE OF
WALL SHEATHING SIDE OF STEEL STUD
SHEAR WALL, SEE STEEL STUD
SCHEDULES FOR SHEATHING AND
NAILING.
WW-X.X-Y INDICATES WOOD SHEAR WALL TYPE
(X.X) AND SHEATHING (Y) IF REQUIRED.
ARROW INDICATES FACE OF WALL
SHEATHING SIDE OF WOOD STUD
SHEAR WALL WHERE OCCURS, SEE
WOOD SCHEDULES FOR SHEATHING
AND NAILING.
INDICATES MASONRY WALL, SEE
SCHEDULE.
MW-??
INDICATES DETAIL SECTION VIEW.
?
SE?-??
?
SE?-??INDICATES DETAIL VIEW OR ENLARGED
PLAN CALLOUT.
INDICATES CONCRETE BEAM, SEE
SCHEDULE.
CB-??
INDICATES MASONRY BEAM, SEE
SCHEDULE.
MB-??
INDICATES NUMBER OF OF TRIMMER
STUDS (T) AND KINGPOSTS (K)
F.S.E. =
INDICATES CONCRETE PIER (CP), SEE
SCHEDULES
CP-?
INDICATES STEEL HSS (HSS) OR STEEL
WIDE FLANGE (W). COLUMN AND BASE
PLATE, SEE SCHEDULESBP-?BP-?HSS??W?X??INDICATES STEEL ROOF DECK SPAN
DIRECTION AND TYPE, SEE SCHEDULES
INDICATES CONCRETE ON METAL DECK
SPAN DIRECTION AND TYPE, SEE
SCHEDULES.
??-??
??-??-??
T-K
INDICATES DIFFERENT SLAB THICKNESS
INDICATES RECESS IN CONCRETE
FOUNDATION WALL
CW-??
INDICATES NON-BEARING MASONRY
WALL.
MW-??
SS INDICATES STEP IN WALL
F-????'-??"INDICATES CONCRETE FOOTING TYPE
AND TOP OF FOOTING ELEVATION.
INDICATES CONCRETE FOOTING &
FOUNDATION WALL, SEE SCHEDULES
FOR SIZE AND REINFORCING.
INDICATES ISOLATION JOINT IN SLAB ON
GRADE. SEE DETAIL
?"
INDICATESMASONRY PIER (MP) OR
COLUMN (MC), SEE SCHEDULESM?-?INDICATES MASONRY CHANNEL EMBED
PLATE, SEE MASONRY SCHEDULES.
MCE-?
INDICATES MASONRY BEARING PLATE,
SEE MASONRY SCHEDULES.
MBC-?
INDICATES CONCRETE CHANNEL
EMBED PLATE, SEE CONCRETE
SCHEDULES.
CCE-?
INDICATES CONCRETE BEARING PLATE,
SEE CONCRETE SCHEDULES.
CBP-?
INDICATES BEAM WEB OPENING WIDTH-
DEPTH-ELEVATION.
W-D-E
INDICATES OPENING FOR STRONG
POINT, SEE ARCH.
CS??
INDICATES SIZE/TYPE OF STRAP
ABOVE AND BELOW WINDOW/DOOR,
SEE TYPICAL STRAPPING OVER
WINDOWS/DOORS DETAILHDU?MST??INDICATES STRAP OR HOLD DOWN, SEE
HOLD DOWN AND STRAP SCHEDULE
ABBREVIATIONS
@ AT
AB ANCHOR BOLT
ABV ABOVE
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ACHITECT
BLDG BUILDING
BLW BELOW
BM BEAM
BOT BOTTOM
BRG BEARING
BTWN BETWEEN
CJ CONSTRUCTION
/CONTROLJOINT
CJP COMPLETE JOINT
PENETRATION
CMU CONCRETE
MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
D.B.DECK BEARING
D.B.A.DEFORMED BAR
ANCHOR
DBL DOUBLE
DET DETAIL
DIA (Ø)DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DK DECK
DN DOWN
DWG DRAWING
DWL DOWEL
E.F.EACH FACE
E.J.EXPANSION JOINT
E.W.EACH WAY
EA EACH
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
ENG ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EXIST (E)EXISTING
EXP EXPOSED/
EXPANSION
EXT EXTERIOR
F.D.FLOOR DRAIN
F.F.FINISH FLOOR
F.S.E.FINISH FLOOR
ELEVATION
F.V.FIELD VERIFY
FDTN FOUNDATION
FIN FINISH
FL FLOOR
FT FOOT
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GLB GLU-LAMINATED
BEAM
GR GRADE
G.S.N.GENERAL
STRUCTURAL
NOTES
HB HORIZONTAL
BRIDGING
HORIZ HORIZONTAL
H.S.A.HEADED STUD
ANCHORS
HSS HOLLLOW
STRUCTURAL
STEEL
HT HEIGHT
I.F.INSIDE FACE
IBC INTERNATIONAL
BUILDING CODE
ICBO INTERNATIONAL
CONFERENCE OF
BUILDING OFFICIALS
ICC INTERNATIONAL CODE
COUNCIL
IN INCHES
INSUL INSULATION
INT INTERIOR
JT JOINT
JST JOIST
K KIPS -1,000 POUNDS
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LBS POUNDS
LF LINEAR FOOT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NTS NOT TO SCALE
O OBSERVE
O.C.ON CENTER
O.F.OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
P PERFORM
PCF POUNDS PER
CUBIC FOOT
PJP PARTIAL JOINT
PENETRATION
PL PLATE
PLF POUNDS PER
LINEAR FOOT
PNL PANEL
PP PARTIAL PENETRATION
PSF POUNDS PER
SQUARE FOOT
PSI POUNDS PER SQUARE
INCH
P/T POST TENSIONED
PT POINT
REINF REINFORCING
REQ'D REQUIRED
SFRS SEISMIC FORCE
RESISTING SYSTEM
SHT SHEET
SIM SIMILAR
S.O.G.SLAB ON GRADE
SQ SQUARE
STD STANDARD
ST STEEL
STIFF STIFFENER
STRUCT STRUCTURAL
T&B TOP AND BOTTOM
T.O.TOP OF
TEMP TEMPERATURE
T.C.TOP OF CONCRETE
T.F.TOP OF FOOTING
T.S.TOP OF SLAB
T.ST.TOP OF STEEL
T.W.TOP OF WALL
TYP TYPICAL
U.N.O.UNLESSS NOTED
OTHERWISE
VERT VERTICAL
W.P.WORK POINT
W/WITH
WF WIDE FLANGE
WT WEIGHT
W.W.F.WELDED WIRE FABRIC
YD YARD
MEMBER DESIGNATION
W12X26 (25) C = 1/2"
HSS3X3X1/4
INDICATES SIZE AND TYPE OF BEAM
(HSS, WIDE FLANGE, PIPE, ETC.)
NUMBER IN PARENTHESES
INDICATES NUMBER OF EQUALLY
SPACED 3/4" Ø X 3.1/2"SHEAR STUDS
UPWARD CAMBER AT MIDSPAN OF BEAM
STANDARD STEEL CONNECTION, SEE
STEEL TO STEEL CONNECTION SCHEDULE
OR SEE PLAN FOR SPECIFIC INSTANCES
FILLED TRIANGLE INDICATES MOMENT
CONNECTION
OPEN TRIANGLE INDICATES
CANTILEVERED MOMENT CONNECTION
FILLED CIRCLE INDICATES DRAG
CONNECTION, ADDITIONAL ROW OF
BOLTS REQUIRED, SEE STEEL TO STEEL
CONNECTION SCHEDULE
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC.
SEE MOMENT CONNECTION DETAIL SHEET FOR MOMENT
CONNECTION INFORMATION.
(2) 1¾x11⅞LVL
STEEL BEAMS
WOOD
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC. SEE
STANDARD WOOD CONNECTION DETAILS FOR MORE INFORMATION.
LEADING NUMBER IN PARENTHESES
INDICATES NUMBER OF PLYS
MEMBER WIDTH
MEMBER DEPTH
MEMBER TYPE (LVL, GLULAM, LSL, ETC.)
STEEL JOISTS
18LH05
JOIST DEPTH
JOIST TYPE
DBP 88DLH 730/375
SPECIAL JOIST SHAPE OR DESIGNATION AS
REQUIRED (I.E. DPB = DOUBLE PITCH)
JOIST DEPTH
JOIST TYPE
TOTAL LOAD
LIVE/SNOW LOAD
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC. SEE
PLAN, TRUSS LOADING DIAGRAMS, AND GENERAL NOTES FOR
APPROPRIATE LOADS. SEE PLAN FOR MECHANICAL UNIT LOCATIONS
EL = 4"
BEAM ELEVATION BELOW T.S.2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:04 AMSE-003
INSPECTIONSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
COMPOSITE MEMBER SIZE X VERIFY THAT COMPOSIT MEMBER IS THE REQUIRED SIZE.
REINFORCING STEEL X VERIFY APPROPRIATE REINFORCEMENT SIZE, SPACING, AND
ORIENTATION; THAT IT HAS NOT BEEN RE-BENT IN FIELD; THAT IT IS
CORRECTLY TIED AND SUPPORTED; AND THAT REQUIRED STEEL...
DOCUMENT ACCEPTANCE OR REJECTION
OF STEEL ELEMENTS
X
PLACEMENT AND INSTALLATION OF STEEL
HEADED STUD ANCHORS
X
PLACEMENT AND INSTALLATION OF STEEL
DECK
X
STEEL ELEMENTS OF COMPOSITE CONSTRUCTION (TABLE N6.1, AISC 360-10; TABLES J9-1 THRU J9-3, AISC 341-11):
H-PILES X VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE
MADE WITHIN THE PROTECTED ZONE OF PILING (SEE TABLE J8-1 OF
AISC 341-10).
PROTECTED ZONES X VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE
MADE WITHIN THE PROTECTED ZONE (SEE TABLE J8-1 OF AISC...
REDUCED BEAM SECTIONS (RBS) X VERIFY CONTOUR AND FINISH AS WELL AS DIMENSIONAL
TOLERANCES (SEE TABLE J8-1 OF AISC 341-10).
ANCHOR RODS AND OTHER EMBEDMENTS
SUPPORTING STRUCTURAL STEEL
X SHALL BE ON THE PREMISES DURING THE PLACMENT OF ANCHOR
RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL
FOR COMPLIANCE WITH CONSTRUCTION DOCUMENTS. VERIFY TH...
STRUCTURAL STEEL DETAILS X ALL FABRICATED STEEL OR STEEL FRAMES SHALL BE INSPECTED
TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN IN THE
CONSTRUCTION DOCUMENTS, SUCH AS BRACES, STIFFENERS,...
OTHER STEEL INSPECTIONS (SECTION N5.7, AISC 360-10; TABLES J8-1 & J10-1, AISC 341-10):
DOCUMENT ACCEPTANCE OR REJECTION
OF BOLTED CONNECTIONS
X
AFTER BOLTING (TABLE N5.6, AISC 360-10):
PRETENSIONED FASTENERS X VERIFY THAT FASTENERS ARE PRTENSIONED IN ACCORDANCE
WITH RCSC SPECIFICATION, PROGRESSING SYSTEMATICALLY
FROM THE MOST RIGID POINT TOWARD THE FREE EDGES.
FASTENER COMPONENT X VERIFY THAT FASTENER COMPONENT IS NOT TURNED BY WRENCH
PREVENTED FROM ROTATING.
SNUG-TIGHT PRIOR TO PRETENSIONING X VERIFY THAT JOINTS ARE BROUGHT TO SNUG-TIGHT CONDITION
PRIOR TO PRETENSIONING OPERATION.
FASTENER ASSEMBLIES X VERIFY THAT FASTENER ASSEMBLIES AR OF SUITABLE CONDITION,
PLACED IN ALL HOLES, AND WASHERS ARE POSITIONED AS
REQUIRED.
- NOT REQUIRED FOR PRETENSIONED JOINTS USING TURN-OF-THE-NUT METHOD WITH MATCH-MARKING,
DIRECT-TENSION-INDICATORS,OR TWIST-OFF TYPE TENSION CONTROL METHOD [PER SECTION N5.6(2) OF AISC 360-10].
- NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED [PER SECTION N5.6(1) OF AISC 360-10].
DURING BOLTING (TABLE N5.6-2, AISC 360-10):
PROPER STORAGE X VERIFY PROPER STORAGE OF BOLTS, NUTS, WASHERS, AND OTHER
FASTENER COMPONENTS
PRE-INSTALLATION VERIFICATION TESTING X OBSERVE AND DOCUMENT VERIFICATION TESTING BY
INSTALLATION PERSONNEL FOR FASTENER ASSEMBLIES AND...
CONNECTING ELEMENTS X VERIFY APPROPIRATE FAYING SURFACE CONDITION AND HOLE
PREPARATION, IF SPECIFIED, MEET REQUIRMENTS.
PROPER BOLTING PROCEDURE X VERIFY PROPER PROCEDURE IS USED FOR THE JOINT DETAIL.
PROPER FATENERS FOR JOINT X VERIFY GRADE, TYPE, AND BOLT LENGTH IF THREADS ARE
EXCLUDED FROM THE SHEAR PLANE.
FASTENERS MARKED X VERIFY THAT FASTENERS HAVE BEEN MARKED IN ACCORDANCE
WITH ASTM REQUIREMENTS.
CERTIFICATIONS OF FASTENERS X
- NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED [PER SECTION N5.6(1) OF AISC 360-10]
PRIOR TO BOLTING (TABLE N5.6, AISC 360-10):
WELDED JOINTS SUBJECT TO FATIGUE X
ACCESS HOLES (FLANGE > 2") X
CJP WELDS (RISK CAT. III OR IV) X A REDUCTION IN THE RATE OF ULTRASONIC TESTING IS ALLOWED
PER SECTION N5.5E.
CJP WELDS (RISK CAT. II) X ULTRASONIC TESTIN SHALL BE PERFORMED ON 10% OF CJP
GROOVE WELDS IN BUTT, T- AND CORNER JOINTS SUBJECT TO
TRANSVERSELY APPLIED TENSION LOADING IN MATERIALS...
NONDESTRUCTIVE TESTING (SECTION N5.5,
AISC 360-10):
DOCUMENT ACCEPTANCE OR REJECTION
OF WELDED JOINT/MEMBER
X
BACKING AND WELD TABS REMOVED X
K-AREA X
ARC STRIKES X
WELDS MEET VISUAL ACCEPTANCE
CRITERIA
X
SIZE, LENGTH, AND LOCATION OF WELDS X
WELDS CLEANED X VERIFY THAT WELDS HAVE BEEN PROPERLY CLEANED.
AFTER WELDING (TABLE N5.4-3, AISC 360-10):
WELDING TECHNIQUES X VERIFY INTERPASS AND FINAL CLEANING, EACH PASS IS WITHIN
PROFILE LIMITATIONS, AND QUALITY OF EACH PASS.
WPB FOLLOWED X VERIFY ITEMS SUCH AS SETTINGS ON WELDING EQUIPMENT,
TRAVEL SPEED, WEDLING MATERIALS, SHIELDING GAS TYP/FLOW
RATE, PREHEAT APPLIED, INTERPASS TEMPERATURE MAINTAINED...
ENVIRONMENTAL CONDITIONS X VERIFY WIND SPEED IS WITHIN LIMITS AS WELL AS PRECIPITATION
AND TEMPERATURE.
CRACKED TACK WELDS X VERIFY THAT WEDLING DOES NOT OCCUR OVER CRACKED TACK
WELDS
CONTROL AND HANDLING OF WELDING
CONSUMABLES
X VERIFY PACKAGING AND EXPOSURE CONTROL.
USE OF QUALIFIED WELDERS X VERIFY THAT WELDERS ARE APROPRIATELY QUALIFIED.
DURING WEDLING (TABLE N5.4-2, AISE 360-10):
FIT-UP OF FILLET WELDS X VERIFY ALIGNMENT, GAPS AT ROOT, CLEANLINESS OF STEEL
SURFACES, AND TACK WELD QUALITY AND LOCATION.
ACCESS HOLES X VERIFY CONFIGURATION AND FINISH.
FIT-UP GROOVE WELD X VERIFY JOINT PREPARATION, DIMENSIONS, CLEANLINESS, TACKING,
AND BACKING.
WELDER IDENTIFICATION X A SYSTEM SHALL BE MAINTAINED BY WHICH A WELDER WHO HAS
WELDED A JOINT OR MEMBER CAN BE IDENTIFIED.
MATERIAL IDENTIFICATION X VERIFY TYPE AND GRADE OF MATERIAL.
VERIFY WELDING PROCEDURES (WPS) AND
CONSUMABLE CERTIFICATES
X
PRIOR TO WELDING (TABLE N5.4-1, AISC 360-10):
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
STRUCTURAL STEEL (IBC 1705.2.1,1705.11.1, & 1705.12.2)
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P
INSPECTIONS TASKS AFTER BOLTING (TABLE N5.6-3)QC QA
SYSTEMATICALLY FROM THE MOST RIGID PO9INT TOWARD THE FREE EDGES
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE TCSC SPECIFICATION, PROGRESSING
O O
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING O O
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO PRETENSIONING OPERATION O O
REQUIRED) ARE POSITIONED AS REQUIRED
FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND WASHERS (IF
O O
INSPECTION TASKS DURING BOLTING (TABLE N5.6-2)QC QA
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHER, AND OTHER FASTENER COMPONENTS O O
DOCUMENT FOR FASTENER ASSEMBLIES AND METHODS USED
PRE-INSTALLATION VERIFCATION TESTING BY INSTALLATION PERSONNEL OBSERVED AND
P O
HOLE PREPARATIOIN, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
CONNECTION ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION AND
O O
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O
THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT LENGTH IF
O O
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTNER MATERIALS O P
INSPECTION TASKS PRIOR TO BOLTING (TABLE N5.6-1) QC QA
STRUCTURAL STEEL BOLTING INSPECTIONS (AISC 360 N5.6-1,2,3)
INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES OF THE WELD.
* WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER P P
REPAIR ACTIVITIES P P
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)P P
K-AREA*P P
ARC STRIKES P P
- POROSITY
- UNDERCUT
- WELD SIZE
- WELD PROFILES
- CRATER CORSS SECTION
- WELD/BASE-METAL FUSION
- CRACK PROHIBITION
WELDS MEET VISUAL ACCEPTANCE CRITERIA
P P
SIZE, LENGTH AND LOCATION OF WELDS P P
WELDS CLEANED O O
INSPECTIONS TASKS AFTER WELDING (TABLE N5.4-3)QC QA
- EACH PASS MEETS QUAILITY REQUIREMENTS
- EACH PASS WITHIN PROFILE LIMITATIONS
- INTERPASS AND FINAL CLEANING
WELDING TECHNIQUES
O O
- PROPER POSITION (F, V, H, OH)
- INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
- PREHEAT APPLIED
- SHIELDING GAS TYPE/FLOW RATE
- SELECTED WELDING MATERIALS
- TRAVEL SPEED
- SETTINGS ON WELDING EQUIPMENT
WPS FOLLOWED
O O
- PRECIPITATION AND TEMPERATURE
- WIND SPEED WITHIN LIMITS
ENVIRNOMENTAL CONDITIONS
O O
NO WELDING OVER CRACKED TACK WELDS O O
- EXPOSURE CONTROL
- PACKAGING
CONTROL AND HANDLING OF WELDING CONSUMABLES
O O
USE OF QUALIFIED WELDERS O O
INSPECTION TASKS DURING WELDING (TABLE N5.4-2)QC QA
OR MEMBER CAN BE IDNTIFIED. STAMPS, IF USED, SHALL BE THE LOW STRESS TYPE.
* THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT
CHECK WELDING EQUIPMENT O -
- TACKING (TACK WELD QUALITY AND LOCATION)
- CLEANLINESS (CONDITION OF STEEL SURFACES)
- DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
FIT-UP OF FILLET WELDS
O O
CONFIGURATION AND FINISH OF ACCESS HOLES O O
- BACKING TYPE AND FIT (IF APPLICABLE)
- TACKING (TACK WELD QUALITY AND LOCATION)
- CLEANLINESS (CONDICATION OF STEEL SURFACES)
- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
- JOINT PREPARATION
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
O O
WELDER IDNETIFICATION SYSTEM*O O
MATERIAL IDENTIFICATION (TYPE/GRADE)O O
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILIABLE P P
WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE P P
INSPECTION TASKS PRIOR TO WELDING (TABLE N5.4-1) QC QA
STRUCTURAL STEEL WELDING INSPECTIONS (AISC 360 N5.4-1,2,3)
STRUCTURAL WOOD X IF FASTENER SPACING IS < 4" O.C.: VERIFY THAT PROPER NAILING,
BOLTING, ANCHORAING, AND OTHER FASTENING OF SHEAR WALLS,
DIAPHRAGMS, DRAG STRUTS, BRACES, AND HOLDOWNS.
PERFORMED BY CODE INSPECTION FIRM.
WOOD TRUSSES SPANNING > 60-FEET X VERIFY THAT TEMPRORAY AND PERMANENT TRUSS BRACING IS
INSTALLED IN ACCORDANCE WITH APPROVED TRUSS PACKAGE.
PERFORMED BY CODE INSPECTION FIRM.
HIGH-LOAD DIAPHRAGMS X VERIFY THICKNESS AND GRADE OF SHEATHING, SIZE OF FRAMING
MEMBERS AT PANEL EDGES, NAIL/STAPLE DIAMETERS AND
LENGTH, AND THE NUMBER OF FASTENER LINES AND FASTENER
SPACING PER APPROVED PLANS. PERFORMED BY CODE...
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
WOOD CONSTRUCTION (IBC 1705.5, 1705.10.1, AND 1705.11.2)
FULL DEPTH STIFFENER EACH
SIDE OF BEAM. MATCH SINGLE
SHEAR PLATE THICKNESS.
STEEL BEAM.
STEEL COLUMN.
SHEAR PLATE.
STEEL BEAM.
TYP
DSW
12" TYP.
STEEL BEAM.
SINGLE SHEAR STIFFENER.
ADD TABS WHERE BEAMS
OCCUR.
STEEL COLUMN.
TYP
DSW
SINGLE SHEAR PLATE.
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
BEAMS ARE SAME DEPTH.
COPE JOIST
FLANGES WHERE
REQUIRED.
3 SIDES
SSW
NOTES:
1.BOLTS SHALL BE ASTM A325 HIGH STRENGTH BOLTS
2.BOLT EDGE DISTANCE SHALL BE 1.1/2" MINIMUM AT ALL EDGES.
3.BOLT SPACING SHALL BE 3" MIN. BOLT SPACING MAY BE REDUCED TO 3X
BOLT DIAMETER IF REQUIRED FOR A SINGLE ROW OF BOLTS.
4.INDICATES DRAG CONNECTION. USE TWO ROWS OF SLIP CRITICAL BOLTS
WITH A CLASS A FAYING SURFACE.
5.EXTEND ANGLED SINGLE PLATES TO ALLOW FOR BOLT CLEARANCE.
TYP
DSW
TYP
DSW
TYP
DSW TYP
DSW
TYP
DSW
TYP
DSW
HORIZ. STIFFENER PLATES
TOP AND BOTTOM
THICKNESS TO MATCH SPT.
TYP
DSW
TYP
DSW
SSW
1/4
BEAM WEB, COLUMN
WEB, OR COLUMN
FLANGE.
SINGLE PLATE
SINGLE PLATE
SINGLE BENT PLATE.
EXTEND AS REQ'D TO
ACHIEVE BOLT CLEARANCE.0° TO 30°OVER 45°BEAM TO BEAM SINGLE PLATE CONNECTION
BEAM TO BEAM SINGLE PLATE CONNECTION
BEAM TO BEAM SINGLE PLATE CONNECTION
BEAM TO COLUMN STIFFENER PLATE CONNECTION
BEAM TO COLUMN SINGLE PLATE CONNECTION BEAM TO COLUMN SINGLE PLATE DRAG CONNECTION
BEAM TO COLUMN FLANGE SINGLE PLATE CONNECTION BEAM TO COLUMN WEB SINGLE PLATE CONNECTION
0° TO 30°30° TO 45°OVER 45°
HSS TUBE COLUMN.
HSS TUBE COLUMN.
WIDE FLANGE COLUMN.WIDE FLANGE COLUMN.
BEAM WEB, COLUMN
WEB, OR COLUMN
FLANGE.
3" TYP.
2.1/2" MAX.
SKEWED SINGLE PLATE CONNECTIONS
2.1/2" MAX.
2.1/2" MAX.2.1/2" MAX.
2.1/2" MAX.2.1/2" MAX.
COLUMN WEB.
COPE JOIST
FLANGES WHERE
REQUIRED.
KNIFE PLATE USE
THICKEST REQ'D
SPT.
3 " M A X .SPT4" TYP.S
P
T
(4) 7/8"Ø BOLTS TYP.(4) 7/8"Ø BOLTS TYP.
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
BEAMS ARE HIGHER.
COPE JOIST
FLANGES WHERE
REQUIRED.
TYP
DSW
RAISED BEAM AT SINGLE PLATE CONNECTION
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
JOIST HANGS BELOW BEAM.
COPE JOIST
FLANGES WHERE
REQUIRED.
TYP
DSW
LOWERED BEAM AT SINGLE PLATE CONNECTION
(2) ROWS OF SLIP CRITICAL
BOLTS AT DRAGS, TYP.
(2) ROWS OF SLIP CRITICAL
BOLTS AT DRAGS, TYP.
SSW6" MAX.4" AT DRAGS
SPT3 1/2" M A X .30° TO 45°3/4" CAP PLATE 3/4" CAP PLATE
3/8" CAP PLATECOLUMN ABOVE,
WHERE OCCURS
NOTE:
1. SPOT WELDS ARE 3/4" DIAMETER, TYP. U.N.O.
2. B AND N DECK WELDS AT SIDELAP SHALL BE 3/8"X1.1/2" SPOT WELDS.
3. TOP SEAM WELDS (TSW) SHALL BE 1.1/2" LONG, TYP, U.N.O.
4. SHEAR STUDS ARE 3/4"Ø, U.N.O.
5. CHAIR REINFORCING TO BE 1" FROM TOP OF CONCRETE SLAB. REINFORCING SHALL NOT REST ON TOP OF FLUTES.
6. 3-SPAN MINIMUM, U.N.O.
CONCRETE ON METAL DECK.
REINFORCING EACH WAY.
METAL DECK.
36/4
36/3
36/7
36/4
32/5
32/4SHEAR STUD.
NOTES:
1.ALL FOOTINGS SHALL BEAR ON BED ROCK
2.ALL FOOTINGS SHALL BE CENTERED BELOW THE COLUMN OR WALL ABOVE, TYP., U.N.O.
3.PROVIDE DOWELS WITH STANDARD HOOKS FROM FOOTINGS TO ANY REINFORCED
ELEMENT ABOVE WITH SIZE AND SPACING TO MATCH VERTICAL REINFORCING IN ELEMENT
ABOVE. ALTERNATE HOOK DIRECTION IN SINGLE CURTAIN REINFORCING.
4.PROVIDE MINIMUM COVER FOR ALL REINFORCING PER GENERAL NOTES.
5.ANY INCREASE IN THE SIZE OF FOOTINGS SHOWN MAY REQUIRE ADDITIONAL REINFORCING,
COORDINATE WITH THE ARCHITECT AND STRUCTURAL ENGINEER.
6.PENETRATIONS THROUGH FOOTINGS ARE NOT ALLOWED, UNLESS APPROVED BY THE
STRUCTURAL ENGINEER IN WRITING PRIOR TO CASTING FOOTING.
7.SEE GENERAL NOTES FOR ADDITIONAL INFORMATION.
COVER
3" MIN.
DOWELS TO MATCH VERTICAL
COLUMN REINFORCING,
ALTERNATE HOOK DIRECTION
ROUGHEN SURFACE 1/4"
AMPLITUDE2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:07 AMSE-004
SCHEDULESJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
W36 (11) 7/8" Ø 7/16" 5/16" 1/2"
W33 (10) 7/8" Ø 7/16" 5/16" 1/2"
W30 (9) 7/8" Ø 7/16" 5/16" 1/2"
W27 (8) 7/8" Ø 7/16" 5/16" 1/2"
W24 (7) 7/8" Ø 7/16" 5/16" 1/2"
W21 (6) 7/8" Ø 7/16" 5/16" 1/2"
W18 (5) 7/8" Ø 5/16" 1/4" 3/8"
W16 (4) 7/8" Ø 5/16" 1/4" 3/8"
W12, W14, C12 (3) 7/8" Ø 5/16" 1/4" 3/8"
W8, W10, C8, C10 (2) 7/8" Ø 5/16" 1/4" 3/8"
BEAM SIZE NO. BOLTS PER ROW SINGLE SIDED WELD (SSW) DOUBLE SIDED WELD (DSW) SHEAR PLATE THICKNESS (SPT)
STEEL TO STEEL CONNECTION SCHEDULE
7½ W3 16 W3 16 NW 7 1/2" 4 1/2" #4 24" 36/4 12" 24" 24" 12"
6¼ W3 18 W3 18 LW 6 1/4" 4 1/2" #4 24" 36/4 12" 24" 24" 12"
5¼ W2 18 W2 18 LW 5 1/4" 3 1/2" #4 24" 36/4 12" 24" 24" 12"
6¼ N 18 PLN3 18 LW 6 1/4" 4 1/2" #4 24" 32/5 12" 24" 24" 12"
4 B 20 PLB 20 NW 4" 3" #4 24" 36/7 12" 18" 18" 12"
SIZE SPACING WELD VSC2 BP
MARK TYPE GAUGE
CONCRETE
TYPE
CONCRETE
DEPTH
MIN SHEAR
STUD...
REINFORCING CROSS-PANEL
WELD...
WELD SPACING
ALONG FLUTES
SIDELAP SPACING
FLOOR DECKING SCHEDULE
C.W. = CROSSWISE E.W. = EACH WAY L.W. = LENGTHWISE
F-2.5C 2'-6" CONT. 12" #4 @ 12"O.C. C.W (2) #5 L.W. - -
F5 5'-0" 5'-0" 18" (7) - #6 E.W. - -
F3.5 3'-6" 3'-6" 12" (5) - #5 E.W. -
F-3 3'-0" 3'-0" 12" (4) - #5 E.W. - -
F-2.25 2'-3" 2'-3" 12" (3) - #5 E.W. - -
MARK WIDTH LENGTH THICK. BOTTOM REINFORCING TOP REINFORCING NOTES
CONCRETE FOOTING SCHEDULE BEARING PRESSURE = 5000 PSF
2 11/05/20
20
Addendum 2
2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:09 AMSE-005
3D
RENDERINGJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1 3D STRUCTURAL RENDERING
15 16 17 18
C
C1
D
D1
E
F
F1
G
G1
H
H1
J
141312 19 20 21
B
J1
A1
SE-201HSS6X6X1/4HSS5X5X5/16HSS5X5X5/16(E) WALL
A1
SE-512
A2
SE-512
E1
SE-511
(E) WALL
(E) WALL (E ) W A L L (E) WALL(E) WALL(E) WALLHSS6X6X1/4W21X55W8X10W8X10
3
W14X22 W14X22 W10X33(E)W10X33(E)W10X33(E)W10X33(E)W10X33(E)W10X33(E)C2
SE-512
C2
SE-512
L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4B5
SE-511
TYP.
L4X4X1/4
L4X4X1/4
L4X4X1/4
L4X4X1/4A5
SE-511
A5
SE-511
SEE ARCH.
FOR LOCATION
2HSS5X5X5/16HSS5X5X5/16HSS5X5X5/16(E) 3'-0"
FOOTING
TF=69'-0"TF=67'-0"2
A2
SE-512
SIM.
1 1 HSS5X5X5/16(E) 3'-0" FOOTING
TF=67'-0"
C1
SE-202
_______C4
SE-202
_______
(E) 3'-0"
FOOTING
NEW 8" CONCRETE WALL
ALTERNATIVE W/ 2'-6" CONT.
FOOTING BELOW WALL
TF=69'-0"TF=67'-0"
(E) 9'-0" SQ.
FOOTING
(E) 8'-6" SQ.
FOOTING
(E) 10'-0" SQ.
FOOTING(E) 9'-0" SQ.
FOOTING
(E) 8'-6" SQ.
FOOTING
(E) 10'-0" SQ.
FOOTING 12" MASONRY
INFILL AT DOOR
TF=67'-0"
A4
SE-201
_______
CW-8ACW-8ACW-8A
CW-8A84' -4"
4½"
Foundation
Slab
D1
SE-512
3
(E) 3'-0"
FOOTING
12" CONCRETE SLAB. REINFORCE
WITH #4 AT 16" O.C. BOTH WAYS,
TOP AND BOTTOM OF SLAB (2 MATS
OF REINFORCING.)CW-8ACW-8A
CW-8ACW-8A
SE-201
A5
SE-201
C5
8' - 6"7' - 6"4
4
4
L4X4X1/4
L4X4X1/4
5¼ W2 18
7½ W3 16 7½ W3 16
CW-8A CW-8AA1
SE-511
A1
SE-511
REMOVE STAIR TO UPPER LEVEL.
PROVIDE COMPACTED FILL AND 4"
SLAB ON GRADE PER ARCH.
DRAWINGS, SEE GENERAL NOTES.
E6
SE-511HSS4X4X5/16HSS4X4X5/164HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4F-2.25 F-3
F-2.25 F-3
F-2.25 F-3
F-2.25 F-3
A5
SE-110
INDICATES NOTES ARE KEYED ON PLAN.
1.6" TOTAL THICKNESS L.W. CONCRETE SLAB ON 20 GAUGE W2
GALV. FORM LOCK DECK -REINFORCE WITH #4 AT 24" O.C.
BOTH WAYS IN CENTER OF SLAB. WELD METAL DECK TO ALL
SUPPORTS WIHT 3/4"Ø PUDDLE WELDS AT 12" O.C.
2.SHIFT COLUMN TO ALLOW FOR 3'-6" FOOTING TO BE CAST.
3.7¼"± L.W. CONCRETE SLAB ON 20 GAUGE W3 FORM LOCK
GALV. METAL DECK. REINFORCE WITH #4 @ 24" O.C. BOTH
WAYS CENTER OF SLAB.
4.SEE ARCH. FOR EXTENT OF FLOOR TO BE DEMOLISHED. NEW
SLAB SHALL BE 8" MIN. THICKNESS. REINFORCE WITH #4 AT 12"
O.C. BOTH WAYS TOP AND BOTTOM OF SLAB, SEE DETAIL
A1/SE-511.
KEYED SHEET NOTES
1' - 4"EXISTING CONC. JOIST
NEW L.W. CONC. INFILL EXISTING CONC. SLAB
EXISTING
FOUNDATION WALL
EXISTING 3'-0"
CONT. FOOTING
EXISTING CONC. SLAB
HSS3X3X1/4 WITH 5/8"X5"X9"
PLATE WITH (2) 5/8"X6" TITEN
HD BOLTS AT BOTTOM
NON-SHRINK LEVELING
GROUT AS REQ'D
TYP.
3/16
3/16
NEW CONC. SLAB
5/8"X6"X9" PLATE WITH (2) 5/8"X6"
TITEN HD BOLTS. FERRO SCAN
FOR REINF. PRIOR TO DRILLING
FOR BOLTS.
FOOTING, SEE PLAN
RETURN AIR PLENUM
PRIOR TO INSTALLING TUBE COLUMNS, USE JACKS
TO RAISE JOISTS 1/64". USE (2) JACKS PLACED ON
NEW FOOTINGS, (1) EACH SIDE OF COLUMN.2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:11 AMSE-110
FOUNDATION
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1/8" = 1'-0"1 STAGE FRAMING PLAN
1 10/30/20
20
Addendum 1
2 11/05/20
20
Addendum 2
NO SCALESE-110
A5
15 16 17 18
C
C1
D
D1
E
F
F1
G
G1
H
H1
J
141312 19 20 21
B
W21X55
(E) WALL
L
2
1 1HSS4X4X5/16(E) WALL
(E) WALL (E ) W A L L (E) WALL(E) WALL(E) WALLW21X55
3
W14X22 W14X22
W14X22 W14X22 W10X33(E)W10X33(E)W10X33(E)W10X33(E)W10X33(E)W10X33
(E)
C2
SE-512
C2
SE-512
L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4L4X4X1/4B5
SE-511
TYP.
A1
SE-201
L4X4X1/4
L4X4X1/4
L4X4X1/4
L4X4X1/4A5
SE-511
A5
SE-511
W12X19 (E)W12X19 (E)W12X19 (E)
W10X12 (E)W12X19 (E)W12X19 (E)W16X26 (E)W21X55 (E) W16X26 (E)W8X17W8X17 (E)W8X17 (E)W8X17W14X30 (E)W14X30 (E) W14X30 (E)
W14X22 (E)W14X22 (E)W14X22 (E)
W14X22 (E)W24X68 (E)W24X68 (E)W24X68 (E)W8X17W16X26 (E)W12X72(E) W12X72(E) W12X72W12X72W8X24W8X24W8X24W8X24W10X15 (E)W10X15 (E)EXISTING FRAMING AT MAIN LEVEL TICKET BOOTH AREA
3 3
44
AREA OF SEATING
SLAB TO BE REMOVEDAREA OF SEATING
SLAB TO BE REMOVED
W16X26 (E)
S15X42.9 W21X55 W21X55 S15X42.9
(93'-1½")
(90'-7½")
(93'-1½")
(90'-7½")(90'-7½")
(93'-1½")
(90'-7½")
(93'-1½")
(90'-7½")
A2
SE-512
SIM.(E) 6" CONC. WALL(E) 6" CONC. WALLSE-121
A1
SE-121
A4
CJ-2 TO REMAIN CJ-2 TO REMAIN
A4
SE-201
_______
NEW 8" CONCRETE WALL
ALTERNATIVE W/ 2'-6" CONT.
FOOTING BELOW WALLHSS5X5X5/16HSS5X5X5/16HSS5X5X5/16HSS6X6X1/4W8X18HSS5X5X5/16HSS5X5X5/16HSS6X6X1/4W8X18HSS5X5X5/16SE-202
A1
SE-202
A4
REMOVE STAIR TO LOWER LEVEL.
ADD HSS6X4X3/8 BEAM
C3
SE-512
L4X4X1/4
L4X4X1/4
C3
SE-512
OPP.FOR STAIR TREADS, SEE
DETAIL C3/SE-512. SEE
ARCH. FOR LOCATION
FOR STAIR TREADS, SEE
DETAIL C3/SE-512. SEE
ARCH. FOR LOCATION
D3
SE-512
OPP.D3
SE-512 HSS4X4X5/16W14X22 (E)
W14X22 (E)
W14X22 (E)
W16X26 (E)W24X68 (E)W24X68 (E)(ALL FRAMING SHOWN IS EXISTING)
W14X22 (E)
W14X22 (E)W24X68 (E)W16X26 (E)
HSS6X4X3/8
E5
SE-511 HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4HSS3X3X1/4A5
SE-110
INDICATES NOTES ARE KEYED ON PLAN.
1.PROVIDE ADEQUATE SHORING AND REMOVE BLEACHERS AS
SHOWN. INSTALL BEAMS AND COLUMNS AS SHOWN, SEE
DETAILS B5/SE-201 AND D5/SE-201. AS AN ALTERNATE, INSTALL
CONCRETE WALLS, SEE DETAIL B1/SE-512, PROVIDE 8"
CONCRETE WALL AND F-2.5C FOOTING. SEE SHEET SE-201
FOR RAKER BEAMS.
2.5½" CONCRETE SLAB ON 20 GAUGE GALV. W2 FORM LOCK
METAL DECK. REINFORCE WITH #4 AT 24" O.C. BOTH WAYS
CENTER OF SLAB.
3.REMOVE 6" CONCRETE WALLS ABOVE W10X15 BEAMS.
REMOVE (2) W12X19 BEAMS. REMOVE BLEACHERS IN AREA
SHOWN. COORDINATE WITH ARCH. DRAWINGS FOR EXTENT
OF RISER REMOVAL. SEE SHEET SE-121 FOR NEW FRAMING.
PROVIDE ADEQUATE SHORING AS REQ'D.
4.PROVIDE ADEQUATE SHORING FOR PLATFORM CONTROL
ROOM AND REMOVE TICKET BOOTH WALLS, SEE ARCH. FOR
EXTENT OF WALL REMOVAL. SEE SHEET SE-121 FOR NEW
FRAMING OF NEW SLABS, ETC.
KEYED SHEET NOTES
3/16
3/16
NEW 3/8"X7"
BOTTOM FLANGE
1/2' PLATE EACH
SIDE OF WEB
EXISTING
MASONRY WALL
COLUMN,
SEE PLAN
CUT DOWN 6" DEPTH
AT DOOR AND
OPENING PER ARCH.
1/4"X4"X1'-0" PLATE
EACH SIDE WITH (4)
3/4"Ø A325 BOLTS
1/2" STIFFENER
BOTH SIDES
1/2" STIFFENER
BOTH SIDES
EXISTING W14X30 BEAM
COLUMN, SEE PLAN 6"1/4
3/16
AA0' - 6"
0' - 1 1/2"
VIEW A-A
2½" PLATES AS
REQUIRED
1/4
(4) 3/4" A325 BOLTS
(4) 3/4" A325
BOLTS2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:13 AMSE-111
STAGE
FRAMING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1/8" = 1'-0"SE-111
A2 STAGE FRAMING PLAN
1 10/30/20
20
Addendum 1
2 11/05/20
20
Addendum 2
NO SCALESE-111
A5
15 16 17 18
C
C1
1413 19 20
B
EXISTING FRAMINGEXISTING FRAMING
22
EXISTING ROOF JOISTS 8'-0" O.C.
C1
SE-202
_______C4
SE-202
_______
A4
SE-201
_______
HSS6X4X1/4
INDICATES NOTES ARE KEYED ON PLAN.
1.USE L4X4X1/4 SHEAR TABS WITH (3) 3/4"Ø BOLTS EACH
CHANNEL.
2.REMOVE THESE WALLS, SEE ARCH.
3.RIGGING BEAMS BELOW JOISTS. CENTER GOOD FOR 2400 LBS
ONE PLACE, ALL (3) GOOD FOR 1200 LBS. EACH THESE LOADS
MUST BE SPREAD 24' -0" O.C W8X15 BEAM CAN HAVE 600 LBS
ANYWHERE ON THE BEAM. MAX (4) W8X15, 16' -0" O.C. MIN.
4.PROVIDE ADEQUATE SHORING AS REQUIRED.
5.4½" CONCRETE SLAB ON 20 GAUGE GALVANIZED TYPE BR
COMPOSITE METAL DECK. WELD DECK TO ALL SUPPORTS
WITH 3/4" PUDDLE WELDS AT 6" O.C. FOR PERPENDICULAR
SUPPORTS AND 12" FOR PARALLEL SUPPORTS. USE 1½" SIDE
SEAM WELDS AT 16" O.C.
6.6" TOTAL THICKNESS L.W. CONCRETE SLAB ON 20 GAUGE W2
FORM LOCK METAL DECK. REINFORCE W/ #4 @ 18" O.C. BOTH
WAYS IN CENTER OF SLAB. METAL DECK SHALL BE WELDED
TO SUPPORTS W/ 3/4" PUDDLE WELDS AT 6" O.C.
7.SEE DETAIL C4/MEP-B-SE101 FOR ROOF DECK INFILL. SEE
MECHANICAL AND ARCHITECTURAL DRAWINGS FOR
SIZE AND LOCATIONS.
8.SEE DETAIL D6/SE-511 FOR INSTALLATION REQUIREMENTS
FOR HSS10X8X5/16 BEAM AT GRIDS 16 TO 17.
9.EXISTING W14X30 BEAM REVISED. SEE DETAIL B5/SE-111.
KEYED SHEET NOTES
15 16 17 18 19
L HSS4X4X5/16HSS4X4X5/16HSS4X4X5/16HSS4X4X5/16HSS10X8X5/16
C5
SE-511
C3
SE-511HSS10X8X5/16HSS10X8X5/16SE-511
D5
SE-511
D5
OPP.
HSS10X8X5/16 HSS10X8X5/16
600S162-33 LIGHT GAUGE
CHANNEL SECTION AT 24" O.C.
ABOVE AND 3500S162-33 AT 24"
O.C. BELOW, SEE ARCH.
.
HSS10X4X3/16HSS3X3X3/16HSS3X3X3/16CONTROL BOOTH
E1
SE-512
E3
SE-5118
D6
SE-511
15 16 17 1814 19
L HSS4X4X5/16HSS4X4X5/16HSS4X4X5/16H S S 4 X 4 X 5 /1 6
D3
SE-511 W10X22(E) W10X15 TO
REMAIN. REMOVE
6" CONCRETE WALL
5 5
W10X22HSS4X4X1/4B4
SE-511
B3
SE-511
A2
SE-511
B2
SE-511
B1
SE-511
C1
SE-511
C2
SE-511
W16X36 W16X36
W12X19W12X19D3
SE-511
TYP.
W16X36
TYP.
FOR ADA SEATING PLATFORM
DETAIL, SEE D2/SE-512 HSS3X3X3/16HSS3X3X3/16E3
SE-511
D3
SE-511 W8X15W8X15HSS4X4X1/4(E) W12X72(E) W12X72C2
SE-511
13 14 15
B
C
15
C
1413
BHSS4X4X5/16(E) W14X30
(E) W14X30
(E) W14X30
9
0' - 1 1/2"
TO W6X20
W14X30 MADE EQUAL
A5
SE-1112"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:16 AMSE-121
LOW ROOF
FRAMING
PLANJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1/8" = 1'-0"SE-121
B1 LOW ROOF FRAMING PLAN
NO SCALESE-121
A4 REVISED FRAMING PLATFORM CONTROL BOOTH
NO SCALESE-121
A1 REVISED FRAMING MAIN LEVEL TICKET BOOTH
1 10/30/20
20
Addendum 1
3/16" = 1'-0"SE-121
B5 LEVEL 2 FRAMING REVISIONS
1112 13 14 15 16 17 2122
D
E
F
G
H
J
K
L
H1
J1
19 20
F1
G1
C1
1815161718
C1
D
D1
E
F
F1
G
G1
H
H1
J
141312 19 20 21
L
J1
K
22
W12X26
W12X26
W12X26
W12X26
W12X26
W12X26
W12X26W12X26W12X26W12X26W12X26
W12X26W12X26
W12X26
D2
SE-511
_______T-2T-2T-2T-2T-3T-3T-1AT-1AD2
SE-511
_______
D2
SE-511
_______
D2
SE-511
_______W12X26W12X26W12X26W12X26W12X26E1
SE-201
B1
SE-201
_______
C1
SE-202
_______C4
SE-202
_______
D4
SE-512
22
2 2
22
2 2
INDICATES NOTES ARE KEYED ON PLAN.
1.SEE SHEET SE-004 FOR BEAM TO BEAM CONNECTIONS.
2.SEE ARCH. FOR EXACT LOCATION OF BASKETBALL
BACKSTOPS AND SEE THE SUPPLIER FOR THE EXACT
LOCATION OF THE SUPPORTS. ALL BACKSTOP MEMBERS AND
SUPPORTS TO BE DESIGNED, SUPPLIED, AND INSTALLED BY
THE SUPPLIER. SEE THE ARCH. FOR APPROVED SUPPLIERS.
THE FLOOR OF THE GYMNASIUM IS APPROX. 31 FEET BELOW
THE SUPPORT TRUSSES, FIELD VERIFY.
SHEET NOTES2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:18 AMSE-122
CURTAIN
SUPPORTSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1/8" = 1'-0"SE-122
A1 CURTAIN AND BASKETBALL STANDARD SUPPORTS
1 10/30/20
20
Addendum 1
2 11/05/20
20
Addendum 2
C1
D
D1
E
F
F1
G
G1
H
H1
J
21 23 24
L
J1
K
22 25 26 27 28 29
T1-AT1T1T1T1T1W16X31
W16X31 W16X31 W16X31
W16X31W16X31W12X26W12X26
W12X26W12X26W12X26W12X26W12X26W12X26W12X26W12X26W16X31 W16X31 W16X31
W16X31 W16X31 W16X31W12X26
W12X26W12X26W12X26W12X26W12X26W12X26W12X26W12X26W12X26E2
SE-511
E2
SE-511
D5
SE-512
D6
SE-512
D6
SE-512
SIM.
D5
SE-512
D6
SE-512
D6
SE-512
SIM.
SE-123
D4
SE-123
D4
E5
SE-512
E5
SE-512
E5
SE-512
E5
SE-512
INDICATES NOTES ARE KEYED ON PLAN.
1.SEE SHEET SE-004 FOR BEAM TO BEAM CONNECTIONS.
SHEET NOTES
27 28HSS3X0.250HSS3X0.250C12X25 HSS3X0.250C12X25
C12X25C12X25C12X25C12X25 C12X25 HSS3X0.250HSS3X0.250HSS3X0.250E5
SE-512
E5
SE-5122"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:19 AMSE-123
FITNESS
CENTER
ROOF
FRAMINGJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
1/8" = 1'-0"SE-123
A1 FITNESS CENTER ROOF
3/16" = 1'-0"SE-123
D4 MECHANICAL CURB SUPPORT
1 10/30/20
20
Addendum 1
23 24
F1 H1
15
C1
D
14 HSS5X5X5/16W14X22 W14X22
B5
SE-201
C2
SE-512
EXISTING RAKER BEAM FROM GRID 13 TO 15 TO
BE REMOVED. PROVIDE ADEQUATE SHORING.
W21X55 RAKER BEAM ABOVE
C1
SE-202
_______
D1EFF1
SE-511
A5
SE-511
B5SE-201
C1
0' - 0"15 14 13
W14X22W14X22W21X55
81' -0"
A4
SE-512
B4
SE-512
B3
SE-512
B2
SE-512SE-512
A6
SE-512
A5
SE-512
B5
F-3.5 FOOTING
EXISTING 3'-0" CONT. FOOTING
3/4" CAP PLATE WITH (4)
3/4"Ø A325 BOLTS
1/2" STIFFENERS
EACH SIDE
SEE DETAIL A6/SE-512
3/16
1/4
75' -4"
FIELD VERIFY
75' -4"
FIELD VERIFY
75' -4"
FIELD VERIFY
F-5 FOOTING
FOOTING ELEVATIONS ARE APPROX.
FOOTING SHALL BEAR ON BEDROCK.
APPROX. GRADE, NO
CONC. SLAB
3/4"X11"X11" BASE PLATE WITH
(4) 3/4ØX16" ANCHOR BOLTS
SE-512
C1B6
SE-512
1/4
F-3 FOOTING
W8X18
3/4" PLATE WITH (4)
3/4"Ø A325 BOLTSC4
SE-512
W18X12
HSS3X3X3/16
CJP
FLANGES
AND WEB.1" CLEAR1/2" STIFFENER
PLATE EACH SIDE
PROVIDE SHIMS
AS REQ'D
1/2"X8X"12 PLATE
WITH (2) 5/8"X5" TITEN
HD BOLTS
9X16
10X14
F-5 FOOTING
FULL PENETRATION WELD
C10X20 HANDRAIL SUPPORT,
SEE DETAIL D3/SE-512
3/4"X12"X12" BASE PLATE WITH
(4) 3/4ØX16" ANCHOR BOLTS
18
C1
19
D5
SE-201 W14X22
C2
SE-512
W21X55 RAKER BEAM ABOVE
EXISTING RAKER BEAM FROM GRID 18 TO 20 TO
BE REMOVED. PROVIDE ADEQUATE SHORING
C4
SE-202
_______
181920
W21X55
W14X22
B2
SE-512
SE-512
A6
SE-512
A5
SIM.
B4
SE-512
B3
SE-512
A4
SE-512
SE-512
B5
OPP.
EXISTING SLAB ON GRADE.
REMOVE AND REPAIR AS REQ'D
(E) FOUNDATION WALL
(E) 3'-0" CONT. FOOTING
F-3.5 FOOTING 69' -0"
FIELD VERIFY
81' -0"
70' -8"
65' -0"
FIELD VERIFY
65' -0"
FIELD VERIFY
F-5 FOOTING
ALL PIERS - 14"X16" WITH (4)
#7 VERT. #4 TIES AT 7" O.C.,
(2) #4 TIES AT TOP AT 3" O.C.
FOOTING ELEVATIONS ARE APPROX.
FOOTING SHALL BEAR ON BEDROCK.
F-3 FOOTING F-5 SQ. FOOTING
3/4" CAP PLATE WITH (4)
3/4"Ø A325 BOLTS
1/2" STIFFENERS
EACH SIDE
1/4
3/4"X12"X12" BASE PLATE WITH
(4) 3/4"Ø X 16" ANCOR BOLTS ON
ALL BASE PLATES SHOWN
SE-512
C1
OPP.
B6
SE-512
3/4" PLATE WITH (4)
3/4"Ø A325 BOLTS
E4
SE-512
OPP.
W8X12
HSS3X3X3/16
CJP
1/2" STIFFENER
PLATE EACH SIDE
1/2"X8X"12 PLATE
WITH (2) 5/8"X5" TITEN
HD BOLTS
1" CLEAR PROVIDE
SHIMS AS REQ'D.
OPP.
SEE DETAIL B1/SE5-12 FOR
CONCRETE WALL ALTERNATE.
USE F2.5C FOOTINGC10X20 HANDRAIL SUPPORT,
SEE DETAIL D3/SE-512
TYPICAL ALL WINDOWS AND DOOR, BREAK-
OUT TOP FACE SHELL AND GROUT SOLID
TO TOP OF WINDOWS OR DOOR. INSTALL
5/8" RODS SIM. TO DETAIL B5/SE-511
4½" CONC. SLAB
(3) 5/8" RODS EACH LOCATION.
TOP ROD GOES THRU WIDE
FLANGE BEAM WEB.
1/4"X4"XCONT. PLATE
EACH SIDE OF WALL
80' -7½"
SEE DETAIL B5/SE-511SEE DETAIL A5/SE-511
FILL THIS AREA WITH GROUT
1/4"X4"XCONT. PLATE EACH SIDE
OF WALL WITH (3) 5/8" RODS
4" CONC. SLAB ON GRADE12" THICKENED SLAB
71' -0"
TYP.
1/4
HSS8X4X3/16
HSS4X2X3/16
HSS8X4X3/16
HSS4X2X3/16
BOTTOM CHORD OF GYM TRUSS.
3/16
SPLICE
1/8
1/8
SPLICE
1' - 4"
22' - 8"22' - 8"22' - 8"0' - 8"0' - 2"0' - 2"
5/16
15 16 17 18
100'
100' -0"
C
TO HANDBALL
COURT BLOCK
95' -4"
LEVEL 2
91' -0"
C1CC1
LEVEL 2
91' -0"
70-8
92' -3 1/2"
70-9
102' -5 1/2"
OPEN
T.O.F. GYM
76' -8"
GYM FLOOR
81' -0"
18
STAGE BOTTOM
71' -0"
PROSCENIUM
TRUSS
112' -0"
114'
114' -0"
ROOF
126' -0"
LEVEL 2
91' -0"
LOW ROOF
100' -0"
STAGE LEVEL
84' -0"
PROSCENIUM
ROOF LEVEL
125' -9 1/2"
70-8
92' -3 1/2"
70-9
102' -5 1/2"
70-10
114' -0"8' - 0"8' - 0"HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4 1' - 9 3/4"1' - 2"
SE-511
E4
SE-511
E4
SE-511
D4
SIM.2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:22 AMSE-201
ENLARGED
FRAMING
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
NO SCALESE-201
A5 RAMP FRAMING AT EAST BLEACHERNO SCALESE-201
A1 SPINNING ROOM WALL ELEVATION
NO SCALESE-201
B5 EAST RAKER BEAM AT BLEACHER
NO SCALESE-201
C5 RAMP FRAMING AT WEST BLEACHER
NO SCALESE-201
D5 WEST RAKER BEAM AT BLEACHER
NO SCALESE-201
C1
1/4" = 1'-0"SE-201
E1
1/4" = 1'-0"SE-201
B1 ACCESS TO ROOF ABOVE RAQUETBALL COURTS
SEE DETAIL C2/MEP-B-SE-101
NO SCALESE-201
A4 CONDUIT SUPPORT FRAMING
1 10/30/20
20
Addendum 1
2 11/05/20
20
Addendum 2
13 14 15
C
D
C1
15
C
C1
D
1413
B5
SE-201 W8X15C4
SE-512 HSS3X3X3/16E4
SE-512
1
C1
SE-202
_______
SEE SE-110 FOR FRAMING
-
---
_______-
---
_______
C
D
19 20
C1
1818
C
C1
D
19 20
D5
SE-201 W8X15C4
SE-512
E4
SE-512
1
C4
SE-202
_______
SEE SE-110 FOR FRAMING
GYM FLOOR
81' -0"
18
LEVEL 2
91' -0"
19 20
STAGE LEVEL
84' -0"
70-8
92' -3 1/2"
1" MIN.
(E) 18X55
(E) 16X36
BEAM TO BE REMOVED
SEE DETAIL C1/SE-201
C5
SE-512
SEE DETAIL C1/SE-201
CUT LINE
GYM FLOOR
81' -0"
15
LEVEL 2
91' -0"
1413
STAGE LEVEL
84' -0"
70-8
92' -3 1/2"
(E) 18X55
(E) 16X36
1" MIN.
BEAM TO BE REMOVED
SEE DETAIL C1/SE-201
C5
SE-512
CUT LINE
INDICATES NOTES ARE KEYED ON PLAN.
1.5" TOTAL THICKNESS L.W. CONCRETE SLAB ON 20 GAUGE W2
FORM LOCK METAL DECK. REINFORCE W/ #4 @ 18" O.C. BOTH
WAYS IN CENTER OF SLAB. METAL DECK SHALL BE WELDED
TO SUPPORTS W/ 3/4" PUDDLE WELDS AT 6" O.C.
KEYED SHEET NOTES
6"x4"x5/16" VEENER SUPPORT
ANGLE WITH 3/4" BOLTS THRU
THE 12" MASONRY WALL
1
2
REMOVE BRICK VEENER IN
ALTERNATE AREAS (4'-0" WIDE
SECTION MAX.) INSTALL VEENER
SUPPORT ANGLES PRIOR TO
REMOVING ADJACENT AREAS.
C5
SE-512
BEAM TO BE REMOVED
AFTER VEENER SUPPORT
IS IN PLACE 1
1
1
2
2
2
13 14 15
6"x4"x5/16" VEENER SUPPORT
ANGLE WITH 3/4" BOLTS THRU
THE 12" MASONRY WALL
1
2
REMOVE BRICK VEENER IN
ALTERNATE AREAS (4'-0" WIDE
SECTION MAX.) INSTALL VEENER
SUPPORT ANGLES PRIOR TO
REMOVING ADJACENT AREAS.
C5
SE-512
BEAM TO BE REMOVED
AFTER VEENER SUPPORT
IS IN PLACE1
1
1
2
2
2
18 19 202"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:25 AMSE-202
ENLARGED
FRAMING
PLANSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
NO SCALESE-202
A1 LEVEL 2 - PARTIAL PLAN 1
NO SCALESE-202
A4 LEVEL 2 - PARTIAL PLAN 2
1/4" = 1'-0"SE-202
C4
1/4" = 1'-0"SE-202
C1
1 10/30/20
20
Addendum 1
NO SCALESE-202
D1
NO SCALESE-202
D4
DOUBLE ANGLES, SEE ANGLES
AT OPENINGS TABLE
DOUBLE ANGLE WITH 5/8"Ø
RODS AT 16" O.C., SEE ANGLES
AT OPENINGS TABLE
ELEVATION
A6
SE-511
REMOVE THIS END SHELL
AND DRY PATCH SOLID
5/8" RODS AT 12" O.C.
(7 MINIMUM)
7/8"
PLUG
WELD AND
GRIND
SMOOTH,
TYP.
ALTERNATE
REMOVE THIS WEB AND
DRY PACK MIN. OF 8"
(BOTH CELLS FULL) 7/8"
5/8" RODS AT 12" O.C.
(7 MINIMUM)
PLUG
WELD AND
GRIND
SMOOTH,
TYP.
2@12
2@12
DOUBLE ANGLES, SEE ANGLES
AT OPENINGS TABLE
DOUBLE ANGLE WITH 5/8"Ø
RODS AT 16" O.C., SEE
ANGLES AT OPENINGS TABLE
ELEVATION
A6
SE-511
EXISTING MASONRY
WALL ABOVE
EXISTING 9½" CONC. SLAB
(2) C12X30 CHANNELS WITH 3/4"
THRU BOLTS AT 16" O.C.
PROVIDE HSS4X4X5/16
COLUMNS AS PER PLAN
EXISTING STEEL
BEAM
3/16 EXISTING MASONRY WALL
SE-511
D6
BETWEEN
COLUMNS
BEAM, SEE PLAN
1/4"
3/8" PLATE EACH SIDE
OF BEAM WITH (2) 3/4"Ø
A325 THRU BOLTS
EXISTING MASONRY
WALL ABOVE
EXISTING 9½" CONC. SLAB
1½" 4" 3"AT CENTER OF BEAM, PROVIDE
7/16"X8"X12" SHIM, AT MIDSPAN -
PROVIDE 5/16"X8"X12" SHIMS AT
QUARTER POINTS. JACK ENDS OF
BEAM TO PRE LOAD BEAM FOR
DEAD LOADS. INSTALL COLUMNS
3/16 3@8
3/8"X10"X16" HIGH
PLATE AT 6'-0" O.C.
WITH (4) 1/2"X4" TITEN
HD BOLTS. MIN. OF (2)
PLATES PER BEAM.
EXISTING 8" WIDE
CONC. BEAM
COLUMN,
SEE PLAN
VIEW A-A
3/4"X8X"X14"
CAP PLATE
COLUMN,
SEE PLANAA1/2" END PLATE WITH (2)
3/4Ø A325 BOLTS ON
SOUTH SIDE OF BEAM
HSS10X8X5/16 BEAM
1/4
3/16
EACH BEAM
1/4 5"
HSS10X8X5/16
BEAM
1/2" END PLATE WITH
(2) 3/4" A325 BOLTS
END PLATE
REMOVE AND REPLACE
EXISTING WALL AS REQUIRED
EXISTING STEEL BEAM
3/4"X4½"X4½" CAP PLATE
3/4"X8"X10" BASE PLATE W/
(2) 5/8"X5" SIMPSON TITEN
HD BOLTS
EXISTING MASONRY WALL
EXISTING STEEL BEAM
EXISTING CONCRETE SLAB
1/4
1/4
93'-1½"
90'-7½"
1/2" STIFFENER, (1) SIDE1/4
ADD 1/2" PLATE WITH
(2) 3/4" A325 BOLTS
EXISTING W21X55 W16X36
NEW 6" CONCRETE INFILL
WALL. #4 AT 12" O.C. BOTH
WAYS, CENTER OF WALL
EXISTING RISER SLAB
ADD 1/2" PLATE WITH
(2) 3/4" A325 BOLTS
3/16 3/16
EXISTING 12"
MASONRY WALL
EXISTING RISER SLAB
REMOVE MASONRY AS REQ'D TO
INSTALL NEW BEAMS. DRY PACK
WITH NON-SHRINK GROUT
W10X22
91'-0"
A2
SE-511
EXISTING RISER SLAB
6" CONCRETE WALL W/ #4 @ 12" O.C.
BOTH VERTICAL AND HORIZONTAL
#4 @ 12" O.C. TOP AND BOTTOM
#4 @ 12" O.C. BOTTOM OF SLAB
STEEL BEAM, SEE PLAN
#4X2'-6" A706 REBAR. WELD
TO TOP OF BEAM(2) L3½"X2½"X1/4" CONT. ANGLES
STEEL BEAM,
SEE PLAN
4½" CONCRETE SLAB ON 1½"
TYPE 'BR' METAL DECK
(2) #4 TOP, SLOPED
#4 @ 12" O.C. EMBED 4" IN EXISTING SLAB
EXISTING 4½" CONCRETE
SLAB ON 1½" METAL DECK
(2) L2½"X2"X1/4" CONT. ANGLES
EXISTING STEEL BEAM
3/4 6" O.C.
1/4 2@12
1/4 2@12
#4X6'-0" @ 12" O.C. CENTER OVER
BEAM IN TOP OF SLAB
3/4 6" O.C.
3/4 6" O.C.
3/16 2@12
4½" CONCRETE SLAB ON 1½"
TYPE BR METAL DECK (20
GAUGE.) PROVIDE SHORING AT
MID-SPAN OF 8'-0" SPAN
1/2" PLATE WITH (3)
3/4"Ø A325 BOLTS
W12X19
1/4
EXISTING COLUMN
EXISTING
COLUMN0' - 1 1/2"3/4 12
EXISTING
CONCRETE SLAB
EXISTING W10X15
(2 LOCATIONS)EXISTING W12X19
1/4 2@12W16X36
COLUMN WEB FLANGES
NOT SHOWN FOR CLARITY
EXISTING 4½"
CONC. SLAB
(E) W12X19
(E) CONNECTION
1/4
W16X36
1/2" PLATE WITH (4)
3/4"Ø A325 BOLTS
W16X36
1/4
(E) SLAB
#4X30" AT 12" O.C. EMBED
4" IN EPOXY, EACH SIDE
#4 AT 12" O.C.
#4 AT 12" O.C. TOP AND
BOTTOM, SEE PLAN
REMOVE THIS PORTION OF
RISERS, SEE PLAN(E) BEAM
(E) SLAB
SAW CUT
2"
NEW W16X36
REMOVE THIS PORTION OF
RISERS, SEE PLAN
3/4 12
3/16 2@12
L4X4X1/4XCONT. ANGLE W/ 1/2"X4"
TITEN HD BOLTS @ 24" O.C.
(CENTER OF EXISTING SLAB)
3/4" PLATE WELD
TO 3/4"X8X"X8" CAP
PLATE ON COLUMN
(2) 3/4"Ø A325
BOLTS
1/2" END PLATE ON
EACH TUBE BEAM
HSS4X4X5/16"
COLUMN BELOW
1/4
3/16
EACH BEAM
1/4STEEL BEAM, SEE PLAN
EXISTING W16X26
STEEL BEAM
REMOVE MASONRY AS REQUIRED
AND INSTALL BEAM. DRY PACK
GROUT AROUND BEAM
1/2" PLATE W/ (2) 3/4" A325 BOLTS
1/4
1919
0' - 6"HSS4X4X1/4(3) SIDES
3/16
EXISTING STEEL BEAM
EXISTING CONC. SLAB
3/4"X4½"X10" BASE
PLATE WITH (2) 5/8"X4"
TITEN HD BOLTS3/16
EXISTING
STEEL BEAM
EXISTING ROOF
JOIST BEYOND
EXISTING 4" BRICK VEENER
EXISTING 12" MASONRY WALL.
REMOVE MASONRY AS
REQUIRED. INSTALL ANGLES, DRY
PACK WITH NON-SHRINK GROUT 5" 3/4"HSS5X4X5/16
(2) L4X3X1/4
(1 EACH SIDE)
HSS4X4X1/4
TYP. TOP &
BOTTOM 1/4
SIDES, TYP.
1/4
3/16
SHOP OR
FIELD, TYP.1/4
HSS5X4X5/16
(2) L4X3X1/4
(1 EACH SIDE)
EXISTING 12" MASONRY WALL.
REMOVE SECTION AS REQ'D.
INSTALL ANGLES, DRY PACK
WITH NON-SHRINK GROUT.
EXISTING CONRETE
ON METAL DECK
EXISTING STEEL BEAMS
92' -3½"
SHOP OR
FIELD 3/16 4"3/4" CLEAR
(2) 5/8"X3½" TITEN HD
BOLTS EACH ANGLE
EXISTING GYM
FLOOR, SEE ARCH.
EXISTING GIRDER
(2X10, 2X12, 2X10)
2X REQ'D SHIMS 8" LONG.
NEW 2X6 INFILL CENTERED
BETWEEN EXISTING JOISTS
PROVIDE CONSTRUCTION
GLUE BETWEEN TOP OF
JOIST AND PLYWOOD
(4) 16d NAILS
2X6 X 16"MIN. SPLICE
MEMBER FAR SIDE
WITH (4) 16d NAILS TO
EACH ADDED 2X6
2X6 BLOCKING,
ONE SIDE
STEEL BEAM, SEE PLAN
EXISTING STEEL
BEAM
1/2" PLATE W/ (3) 3/4"
A325 BOLTS
3/4 6
EXISTING
MASONRY WALL
REMOVE MASONRY AS REQ'D
AND INSTALL BEAM. DRY
PACK GROUT AROUND BEAM
1/4
HSS10X4X3/16
3/8" END PLATE
HSS3X3X1/4
1/8
3/16
5/8" CAP PLATE
1/4
0' - 6"12" MIN.
PER COMPACT STORAGE
SUPPLIER, RECESS FOR COMPACT
STORAGE RACK TRACKS.
2" COVER
3" COVER
#4 AT 12" O.C. TOP AND
BOTTOM NORTH-SOUTH
BARS PLACE BOTTOM BAR
FIRST, TOP BAR LAST
#4 AT 12" O.C. EAST-WEST
BARS, TOP AND BOTTOM
AT EACH END OF BEAM PROVIDE
1/2"X7"X10" PLATE WELDED TO
BEAM WITH 1/4" FILLET WELD.
ATTACH TO END WALLS WITH (2)
5/8"X5" TITEN HD BOLTS, GROUT
CELLS FULL AS REQ'D
SEE ARCH, FOR
HANDRAIL
HSS6X4X3/8 BEAM
5/8" THREADED ROD AS
REQ'D AT 24" O.C.,
EMBED 6" IN EPOXY
PLUG WELD
COLUMN, SEE PLAN 3/4"X4½"X10" BASE PLATE W/
(2) 5/8"X4" TITEN HD BOLTS
EXISTING SLAB,
SEE PLAN
EXISTING CONCRETE
WALL BELOW, SEE PLAN2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:28 AMSE-511
FRAMING
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
NO SCALESE-511
A5
NO SCALESE-511
A6
8'-0" TO 12'-0" L8X4X1/4 LLV L6X6X1/4 L6X6X1/4 L6X6X1/4
4'-0" TO 8'-0" L6X4X1/4 LLV L5X5X1/4 L5X5X1/4 L5X5X1/4
UP TO 4'-0" L3X3X1/4 L4X4X1/4 L4X4X1/4 L4X4X1/4
8" CMU 10" CMU 12" CMU
OPENING
WIDTH
DOUBLE ANGLE
LINTEL SIZE
DOUBLE ANGLE COLUMN SIZE
ANGLES AT OPENINGS
NO SCALESE-511
B5 FRAMING AROUND WINDOWS
NO SCALESE-511
C5
NO SCALESE-511
D6
NO SCALESE-511
C3
NO SCALESE-511
B4
NO SCALESE-511
B3
NO SCALESE-511
A2
NO SCALESE-511
B2
NO SCALESE-511
B1
NO SCALESE-511
C1
NO SCALESE-511
C2
NO SCALESE-511
D5
NO SCALESE-511
D1
NO SCALESE-511
D2
NO SCALESE-511
D3
NO SCALESE-511
E4
NO SCALESE-511
D4
NO SCALESE-511
E1
NO SCALESE-511
E2
1 10/30/20
20
Addendum 1
NO SCALESE-511
E3
NO SCALESE-511
A1
NO SCALESE-511
E5
NO SCALESE-511
E6
EXISTING 7½"
CONC. SLAB
EXISTING STAGE FLOOR
EXISTING BRICK
VEENER
EXISTING WALL
3/8"X4" PLATE CONT. WITH
5/8"ØX6" WELDED ANCHOR
STUDS @ 16" O.C.
(2) #3 TOP
AND BOTTOM
EXISTING
FOUNDATION WALL
EXISTING
FOUNDATION WALL
EXISTING 4"
SLAB ON GRADE
NEW MASONRY WALL
INFILL AT EXISTING DOOR
#5 @ 32" O.C. VERT. EMBED
6" IN EXISITNG FOUNDAITON
NEW STAGE FLOOR,
SEE ARCH.
81' -0"
3/4 12" O.C.
8" CMU BLOCK AT FLOOR
12" MASONRY WALL INFILL AT (E) DOOR
SLOPES
CW-8A
6" MIN. THICKNESS L.W.
CONC. STAIR SLAB ON 20
GAUGE W2 FORM LOCK
DECK WITH #4 AT 12"
O.C. EACH WAY #3 NOSE
BARS IN STAIRS
3/8"X4"XCONT. PLATE WITH
3/4"X6" WELDED ANCHOR
STUDS AT 16" O.C.
4X4X1/4 ANGLE WITH
5/8"X5" TITEN HD BOLTS
AT 16" O.C.
DRILL AND EPOXY 3½" IN
CONC. SLAB, TYP.
3/4
12
3/4 12
7¼" ± L.W. CONC. SLAB ON 22 GAUGE
GALVANIZED W3 FORM LOCK METAL DECK.
REINFORCE WITH #4 @ 24" O.C. E.W.7½"X4"X5/16 CONT. BENT PLATE
WITH #4X16" DOWELS AT 24"
O.C., WELD TO BENT PLATE
3"EXISTING STAGE FLOOR
EXISTING 7½"
CONC. SLAB
EXISTING WALL AND
BRICK VEENER
NEW STAGE
FLOOR, SEE ARCH.
4"X4"X1/4" CONT. ANGLE
WITH 5/8"X5" TITEN HD
ANCHORS AT 16" O.C.
EXISTING WALL AND
BRICK VEENER
3/4 12" O.C.
7¼" ± L.W. CONC. SLAB ON 22 GAUGE
GALVANIZED W3 FORM LOCK METAL DECK.
REINFORCE WITH #4 @ 24" O.C. E.W.
BREAK OUT FACE
SHELL AT 16" O.C. AND
GROUT SOLID
SLAB BEYOND
JOIST (RISER) BEYOND
VARIES
(1) #5X30" LONG DOWEL @
EACH JOIST. EMBED 6" IN
EPOXY. INSTALL PRIOR
TO FORMING WALL
8" CONC. WALL, #5 @ 14"
O.C. BOTH WAYS CENTER
OF WALL
STEP TOP OF WALL TO MATCH
BOTTOM OF BLEACHERS
WALL ALTERNATE
SEATING SLAB
FERROSCAN JOISTS BEFORE
DRILLING HOLES FOR DOWELS
SLAB BEYOND
JOIST (RISER) BEYOND
VARIES
SLOPES
FORM ONE SIDE AND
DRY PACK WITH 6000 PSI
NON-SHRINK GROUT W21X55
SEATING SLAB
3/4" WELDED ANCHOR
STUDS, LENGTHS VARY
A6
SE-512
(2) #5 TOP
8" CONCRETE WALL W/ #4 @ 12" O.C.
BOTH WAYS IN CENTER OF WALL
INJECT W/ EPOXY
EXISTING RISER SLAB
#4 VERTICAL @ 12" O.C.
L4X4X1/4XCONT. ANGLE
W/ 3/4"X6" TITEN HD
BOLTS @ 12" O.C.
STEEL BEAM, SEE PLAN
1/4
#4 HORIZONTAL @ 12" O.C.
#4 @ 18" O.C.18"
24"
3/4 12" O.C.
STEEL BEAM,
SEE PLAN
L4X4X5/16XCONT. ANGLE
#4X24" A706 REBAR
WELDED TO BEAM
WEB @ 18" O.C.
1/4 3@12
3/4
VARIES, SEE PLAN
6" L.W. CONC. SLAB
ON METAL DECK,
SEE PLAN
12" O.C.STEEL BEAM, SEE PLAN
1/2" BOLTS @ 16" O.C.
CAST IN DRY PACK GROUT
EXISTING RISER SLAB6" L.W. CONCRETE SLAB ON
METAL DECK, SEE PLAN
#4X30" REBAR @ 18" O.C.
EMBED 6" IN EPOXY
1/4 3@12
3/4 6" O.C.
SEE E3/SE-121
FERROSCAN JOISTS TO LOCATE
REINFORCING PRIOR TO
DRILLING HOLES FOR BOLTS
3/8" BENT PLATE AS REQUIRED. (FULL
WIDTH OF BEAM + 4") W/ (1) 5/8"X5" TITEN
HD BOLT CENTER OF JOIST (RISER)
3/4"X4" WELDED
ANCHOR STUDS
EXISTING RISER SLAB
1/4
STEEL BEAM, SEE PLANAA END OF
CONCRETE
RISER SLAB
STEEL BEAM,
SEE PLAN
VIEW A-A
BENT PLATE
WITH TITEN HD
5/8"X5" TITEN HD BOLT AT
CENTER OF JOIST EXCEPT CJ-2,
FERROSCAN JOISTS TO
DETERMINE EXACT LOCATION
OF BOLTS
STEEL BEAM, SEE PLAN
NOTE:
PROVIDE SUPPORT FOR
METAL DECK AT TRANSITION
3/4" CAP PLATE W/ (8)
3/4"Ø A325 BOLTS
STEEL BEAM, SEE PLAN
1/2" GUSSET PLATE W/ (4)
3/4"Ø A325 BOLTS
STEEL COLUMN, SEE PLAN
1/4
1/2" STIFFENER BOTH
SIDES OF BEAM
1/4
L6X4X5/16 CONT.
#4 AT 18" O.C.
#4X24" A706 REBAR
WELDED TO ANGLE
AT 18" O.C.
NOTE: WELD ANGLE TO
SUPPORT ANGLES AT EACH END
3/4
(E) THEATER GYM FLOOR
AT ELEVATION 81'-0"
PROVIDE PROTECTION FOR
WOOD FLOOR WHEN
CASTING CONCRETE FLOOR
5/8" X 5" SIMPSON TITEN
HD BOLTS AT 16" O.C.
8" CONCRETE WALL
12" O.C.
6X4X5/16"
CONT. ANGLE
1/2" STIFFENER
PLATE EACH SIDE
CONCRETE ON METAL
DECK, SEE PLAN
3/4"X6"X12" CAP PLATE
WITH (4) 3/4"Ø A325 BOLTS
STEEL COLUMN, SEE PLAN
1/4
1/4
3/16 3@12STEEL BEAM,
SEE PLAN
CONCRETE SLAB ON
METAL DECK, SEE PLAN
1/4" PLATE
CUT BOTTOM FLANGE AND WEB AND REMOVE
SECTION TO MAKE BEND IN BEAM. DO NOT CUT TOP
FLANGE, CAN BE HEATED TO BEND TOP FLANGE
BEAM, SEE PLAN
BEAM, SEE PLAN
CONCRETE ON METAL
DECK, SEE PLAN
STEEL BEAM, SEE PLAN
L6X4X5/16 ANGLE W/ 3/4"X6"
TITEN HD AT 24" O.C.
EXISTING MASONRY
WALL
BREAK-OUT FACE SHELL AND
GROUT SOLID @ 16" O.C.
TYP.
3/4 12
CONCRETE ON METAL DECK,
SEE PLAN.
BEAM,
SEE PLAN.
L5X5X1/4
1/4 3@12
EXISTING BEAM.
L3X3X1/4 WITH 3/4"Ø BY 5"
TITEN HD AT 18"O.C.
3/4 12
L5X5X1/4
5/8" CAP PLATE
WITH (4) 5/8" A325
BOLTS
COLUMN, SEE PLAN
BEAM, SEE PLAN.
3/8"X6"XREQUIRED
SHEAR TAB. REMOVE
AND REPOINT MASONRY
AS REQUIRED.
1/4
NOTCH END OF CONCRETE
SLAB AS REQ'D FOR COLUMN
L5X5X1/4
CONT. ANGLE
#4X24" DOWELS AT 18" O.C.
1/2" STIFFENER
PLATE EACH SIDE
SLOPES TO MATCH
BEAM SLOPE
3/16
3"EXISTING STAGE FLOOR
EXISTING 7½"
CONC. SLAB
EXISTING WALL AND
BRICK VEENER
3/4 12" O.C.
(2) 6X4X1/4 ANGLES
WITH (4) 5/8"X6" TITEN
HD BOLTS. (2) 3/4" A325
BOLTS TO BEAM
BEAM, SEE PLAN
NEW STAGE
FLOOR, SEE ARCH.7¼" ± L.W. CONC.
SLAB ON 22 GAUGE
GALVANIZED W3
FORM LOCK METAL
DECK. REINFORCE
WITH #4 @ 24" O.C.
E.W.
4"X4"X1/4" CONT.
ANGLE WITH
5/8"X5" TITEN HD
BOLTS AT 16" O.C.
EXISTING K-BRACE
AND PLATE
1/2"X4"X10"
SHEAR PLATE
3/8"X4"X10" SHIMS
AT 2'-6" O.C.
AT GRIDS F1 AND H1, USE
3/4" PLATES. AT ALL OTHER
LOCATIONS, USE 1/2"
PLATES.
WT12X72.5
TYP.
1/4
3" EACH
SIDE OF
SQUARE
PLATE
3/16
TYP.
1/4
1/2" PLATE WITH (3)
3/4"Ø A325 BOLTS
EAC H BEAM, TYP.
3/8"X4"X10" SHIMS
AT 2'-6" O.C.
3/16
3" EACH SIDE
EACH MEMBER
12" WELDS TOTAL
TYP.
1/4
A A
VIEW A-A
10"
EXISTING TRUSS
BOTTOM CHORD
EXISTING TRUSS
TOP CHORD
EXISTING TRUSS VERT.
3/4 6EXISTING ROOF DECK
STEEL BEAM,
SEE PLAN
6½"X6½" SHIM PLATE AS
REQ'D. (4) 3/4"Ø A325 BOLTS
STEEL BEAM, SEE PLAN
1/4"X4" PLATE AT 18" O.C.
WITH 3/8"Ø DRILL AND
EPOXY BOLTS, EMBED 3½"
HSS2X2X1/4" TUBE
3/8"X3" SQUARE PLATE
3/16
TYP.
3/16
#4X15" REABAR AT 16"
O.C. EMBED 4" INTO
EXISTING IN EPOXY.
#4X16" REBAR AT 18"
O.C. EMBED 4" IN
EXISTING IN EPOXY
GEOFOAM
EXISTING SUSPENDED
CONCRETE TIERS
#4 REBARS AT 18" O.C.
(4) #4 AS SHOWN
MOUNTING OF CHAIR AND
CHAIR BY SUPPLIER
METAL GUARD RAIL,
SEE ARCH.
SEE ARCH. FOR LOCATION AND SIZE
4"
3" 3"CONCRETE STAIR TREADS, SEE ARCH. FOR
LOCATION AND SIZE. (2) #4 LENGTHWISE, #4
BENT ANCHORS AS SHOWN, EMBED 3" IN
EPOXY AT 16" O.C.
SEE DETAIL A6/SE-512
FOR FRAMING
EXISTING RISER
MASONRY WALL BRICK VEENER
6X4X5/16" BRICK
LEDGER. ANGLE WITH
3/4" THRU BOLTS AT 16"
O.C. (MIN. 3 PER ANGLE)
BREAK OUT FACE SHELL
AND GROUT SOLID FOR
3 COURSES MIN. 2"SEE DETAIL A6/SE-512
FOR FRAMING
EXISTING RISER
C10X20
(2) 5/8"X5" SIMPSON
TITEN HD BOLTS AT
EACH RISER
0' - 2"0' - 2"600S162-33 JOISTS
AT 24" O.C.
16 GAUGE TRACK WITH (2)
1/4"X1¼" TITEN STAINLESS STEEL
MASONRY SCREWS AT 12" O.C.
600S162-33 STUD
WALL AND 16 GA.
TRACK, SEE ARCH.
HSS10X4X3/16
BEAM, SEE PLAN
300S162-33 CEILING JOISTS
AT 24" O.C., SEE ARCH.
18 GAUGE TRACK WITH #12-24 X
1" SELF DRILLING SCREWS AT 24"
O.C.
EXISTING
MASONRY WALL
18 GAUGE TRACK WITH
1/4"X1¼" TITEN STAINLESS
STEEL MASONRY SCREWS
AT 12" O.C. STAGGERED.
SEE ARCH. DRAWINGS FOR ADDED
INORMATION REGARDING SHEATHING
AND ADDITIONAL FRAMING REQ'D.
BEAM, SEE PLAN.
3/8"X7"X9" SHEAR TAB
WITH (3) 3/4"Ø BOLTS.
5/16
HSS3X0.250 COLUMN, WITH
1/2"X6"X9" BASE PLATE
WITH (4) 5/8"Ø A325 BOLTS.
WELD 1/4" INSERT IN TOP
TO KEEP WATER OUT.
STEEL BEAM, SEE PLAN
9X4X1/2" ANGLE,
11" LONG
(4) 5/8"Ø THREADED RODS.(BOTTOM
FLANGE OF TRUSS CHORD IS 1-1/16"
THICK AND 12" TO 14" WIDE)
1/4 2 @ 6
2"THIS ANGLE
ONLY BOTH
ENDS2"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
11/24/2020 8:44:32 AMSE-512
FRAMING
DETAILSJOHN W. HART BUILDING PHASE 3 REMODELCONSTRUCTION DOCUMENTS BID SET - 10/16/2020REXBURG, IDProject
Number
NO SCALESE-512
A1
NO SCALESE-512
A2
NO SCALESE-512
B1
NO SCALESE-512
B2
NO SCALESE-512
A4
NO SCALESE-512
B4
NO SCALESE-512
B3
NO SCALESE-512
A6
NO SCALESE-512
A5
NO SCALESE-512
B5
NO SCALESE-512
C1
NO SCALESE-512
B6
NO SCALESE-512
C6
NO SCALESE-512
C2
3/4" = 1'-0"SE-512
C4
3/4" = 1'-0"SE-512
E4
NO SCALESE-512
D1
NO SCALESE-512
D6
NO SCALESE-512
D5
NO SCALESE-512
D2
1 10/30/20
20
Addendum 1
2 11/05/20
20
Addendum 2
NO SCALESE-512
C3
NO SCALESE-512
C5
NO SCALESE-512
D3 HANDRAIL DETAIL
NO SCALESE-512
E1
NO SCALESE-512
E5
NO SCALESE-512
D4
`fo`rfq=_^i^k`b=s^isbppvj_li=ibdbkalrqpfab=^fo=a^jmbopobqrok=^fo=a^jmbopcfiqbo=pb`qflkp`llifkd=`lfipprmmiv=^fo=c^kp^fo=e^kaifkd=rkfqpeb^qfkd=`lfipm^`h^dba=^fo=e^kaifkd=rkfq=E^erFs^of^_ib=cobnrbk`v=aofsbpobqrok=J=obifbc=^fo=c^kobifbc=^fo=a^jmbop^focilt=jb^probjbkq=pq^qflk(E)CHWSCHWRHWRHWSFSRDFDDTSS.F.D.A.D.H.D.RISE24"x12"24"x18"HOT WATER SUPPLYCOLD WATERCHILLED WATER RETURNCHILLED WATER SUPPLYHOT WATER RETURNSOIL OR WASTEDOMESTIC HOT WATEREXISTINGLOW PRESSURE STEAMLOW PRESSURE CONDENSATEDOMESTIC HOT WATER RECIRCULATINGVENTEXHAUST GRILLECONCENTRIC REDUCERTHERMOMETERGAUGE WITH GAUGE COCKGAUGE COCKECCENTRIC REDUCERTHERMOMETER OR GAUGE WELLSAFETY OR RELIEF VALVESOLENOID VALVEGLOBE VALVEPIPE GUIDEPIPE ANCHORBLIND FLANGEPRESSURE/TEMPERATURE TEST PLUG (PETE'S PLUG)FLOW CONTROLLER OR BALANCE VALVEFLOOR DRAIN, FLOOR SINK OR ROOF DRAINPRESSURE REDUCING VALVE - (PRV)STEAM TRAPDIRT LEGDRAINSTRAINEROPPOSED BLADE DAMPERPARALLEL BLADE DAMPERBRANCH DUCT TAKE-OFFSPIN-IN FITTINGTHERMOSTATTEMPERATURE SENSORDROP IN PIPEVALVE IN RISEBALL VALVEGATE VALVECHECK VALVE2 WAY CONTROL VALVE3 WAY CONTROL VALVEBUTTERFLY VALVECONTROL VALVE (PLAN VIEW)RISE IN PIPEPLUG VALVECAPUNIONNEW CONNECTIONFLAT OVAL (CROSS SECTION)ROUND DUCT (CROSS SECTION)SUPPLY DUCT (CROSS SECTION)HAND DAMPERSUPPLY AIR DIRECTIONTURNING VANES IN DUCTACCESS DOOR FOR FIRE DAMPERACCOUSTICAL LINING IN DUCTDROP OR RISE IN SUPPLY DUCTSUPPLY DIFFUSERCOMBINATION SMOKE/FIRE DAMPERRISE OR DROP IN ROUND OVAL DUCTINSIDE CLEAR DIMENSION IN INCHESDUCT SIZE, INSIDE CLEAR DIMENSION IN INCHESRETURN AIR OR EXHAUST DUCT (CROSS SECTION)RETURN AIR OR EXHAUST DIRECTIONRETURN AIR GRILLEDUCT RISEDESCRIPTIONSYMBOLSELECTION BASED ON FLOWSETSEE SPECIFICATION SECTION 23052316 - 2510 - 156 - 91.5 - 2.53 - 51.5 - 2.5GPMRANGE.5 - 1.426 - 45CONNECTION55555555PRESSUREDROPAVERAGEIN FT1/2ASO50LAS100AS150AS125AS200ASO75LASO5OHASO75H11-1/41-1/223/43/41/2FLOWSETSIZESIZE (IN)-------REMARKS-SEE SPECIFICATION SECTION 237300AIR FLOWNOMINALCFMNOMINALFLOWAIR FLOWTOTALSEE SPECIFICATION SECTION 237300SYMBOLSYMBOLSYMBOLSYMBOLMAX FINSPER INCHTOTALPRE-FILTERHOLDINGFILTERFINAL FILTERTYPE TYPE FACE AREASQ. FT.ARRANGEMENTFRAMEENTERINGWATERDB/WB °F DB/WB °FTEMP °FCFMENTERINGAIRAIRLEAVINGAIRMBHTEMP °F MBHMIN.SENSIBLECOOLINGLEAVINGWATER COOLINGTOTALSYMBOLAPPROX.TYPEAPPROX.SYMBOLREMARKSSIZETYPESIZEMAX. AIRSQ. FT.GPMSECT. VEL.DROPIN WC.TOTALCOILPERMAX.FACEPRESS.PRESSUREROWSHxLDROP, FT.NOMINALCOIL FINSIZE EACHWATERMAX.MIN.MINIMUM OUTSIDEAIR CFMBHPPRESSURECFMIN. WCTOTALSTATICFANSQNTYOFRPMFANUNIT SIZE (LxWxH)AIR HANDLINGMAXIMUMMOTOR ELECTRICALHERTZVOLTSPHASE HPDUTYFANTOTAL AHU MAXIMUMOPERATING WEIGHT (LB)TYPEFANSIZE (IN.)WHEELDUTYREMARKSMODELREMARKSRUSKINREMARKSREMARKSEACHEATOTALBHPFPSVELOCITYWATERCLASSHPTOTALNOMINALFLOWSYMBOLMAX FINSPER INCHTOTALENTERINGWATERDB °F DB °FTEMP °FCFMENTERINGAIRAIRLEAVINGAIRMBHTEMP °FHEATINGCAPACITYLEAVINGWATERMAX. AIRSQ. FT.GPMSECT. VEL.DROPIN WC.TOTALCOILPERMAX.FACEPRESS.PRESSUREROWSHxLDROP, FT.NOMINALCOIL FINSIZE EACHWATERMAX.MIN.REMARKSFPSVELOCITYWATERMIN.SEE SPECIFICATION SECTION 237300SEE SPECIFICATION SECTION 237300SEE SPECIFICATION SECTION 237300SEE SPECIFICATION SECTION 237300MODELRUSKINREMARKSLOCATIONAIR FLOWTOTALCFMSYMBOLDUTYPHASEFAN MOTORVOLTS HERTZFAN MOTORSQUANTITY OFDRIVENHPOF VFDsVFDNUMBERSEE SPECIFICATION SECTION 237300REMARKSCOILSECTIONSCOILSECTIONSAHU-400AAHU-400B5000 22,000FIELDHOUSERACQUETBALL COURT ROOF25,00031'-9" x 10'-6" x 7'-6"SF-400A25,000AHU-500ONE VFD PER FAN23.5FAN WALL3.246 1973 208 60 3203.5 19.4221536CC-400A 78.0/62.0 56.0/54.5 45 49757 49755289.0460 0.67 35"x115"12.0 10 8 2.425,0001FS-400A60AHU-400A25,000VERTICAL/FLAT2" FARR 30/30 12" CARTRIDGE5000 22,000FIELDHOUSERACQUETBALL COURT ROOF25,00031'-9" x 10'-6" x 7'-6"SF-400B25,000AHU-600ONE VFD PER FAN23.5FAN WALL3.246 1973 208 60 3203.5 19.4221536CC-400B 78.0/62.0 56.0/54.5 45 49757 49755289.0460 0.67 35"x115"12.0 10 8 2.425,0001HC-400A25,00050.0 80.2722 38.5552 460 0.06 35"x115"7.8 1 8 3.921HC-400B25,00050.0 80.2722 38.5552 460 0.06 35"x115"7.8 1 8 3.92169"x71"OAD-400A PARALLEL CD-50 AHU-400A69"x71"OAD-400B PARALLEL CD-50 AHU-400BAHU-400AVFD-400AA208 60 3621 6AHU-400AVFD-400AB208 60 369 6TOTALFS-400B60AHU-400B25,000VERTICAL/FLAT2" FARR 30/30 12" CARTRIDGERAD-400A 54.5"x60" PARALLEL CD-50AHU-400ARAD-400B 54.5"x60" PARALLEL CD-50AHU-400BAIR FLOWTOTALSYMBOLBHPPRESSURECFMIN. WCTOTALSTATICFANSQNTYOFRPMFANMOTOR ELECTRICALHERTZVOLTSPHASE HPFANTYPEFANSIZE (IN.)WHEELDUTYREMARKSEACHEATOTALBHPCLASSHPTOTALSEE SPECIFICATION SECTION 237300RRF-400A25,000AHU-400AONE VFD PER FAN20.75FAN WALL0.946 1316 208 60 3201.5 5.659.0536RRF-400B25,000AHU-400BONE VFD PER FAN20.75FAN WALL0.946 1316 208 60 3201.5 5.659.0536SUPPLY FANSRETURN / RELIEF FANSAHU-400BVFD-400BA208 60 3621 6AHU-400BVFD-400BB208 60 369 6SUPPLY FANSRETURN / RELIEF FANSSYMBOLAPPROX.TYPESIZEREMARKSMODELRUSKINSEE SPECIFICATION SECTION 237300RED-400A 57"x71" PARALLEL CD-50AHU-400ARED-400B 57"x71" PARALLEL CD-50AHU-400B180 140180 14035% PROPYLENE GLYCOL35% PROPYLENE GLYCOL11SEE SPECIFICATION SECTION 237300135% PROPYLENE GLYCOLVELOCITYCELLFPMVELOCITYCELLFPM1 2 31 2 312UNIT WEIGHT DOES NOT INCLUDE CURB OR HOUSEKEEPING PAD.3EACH UNIT SHALL HAVE A SINGLE POWER CONNECTION4 5 64 5 64PROVIDE WITH FUSED DISCONNECTUNIT SIZE DOES NOT INCLUDE CURB HEIGHT, HOUSEKEEPING PAD,PIPE ENCLOSURE, CONTROL PANELS, ELECTRICAL GEAR, ETC.5ROOFTOP UNIT6PART OF ALTERNATE NO. 290"x74"DUCTWORK APPROX.SIZE INSIDE CLEARSEE SPECIFICATION 230516AFM-400ASYMBOLO.A. DUCTAHU-400ADUTY LOCATIONMODELGOLDPH124VOLT60HZELECTRICALEBTRONTO AHU-400A90"x74"AFM-400BO.A. DUCTAHU-400BGOLD 124 60TO AHU-400B2"1"0"654321654321EDCBADATEREVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:22:54 PMM-001MECHANICALSCHEDULES20054
dofiib=^ka=afccrpbo=p`ebaribSYMBOL FACE SIZE DESCRIPTION MANUFACTURER MODELREMARKSS-1 24"x24" CEILING DIFFUSER - LAY IN KRUEGER 1400-S-2 VARIES CEILING DIFFUSER - SURFACE KRUEGER SH-S-3 VARIES SIDEWALL KRUEGER DPL2-S-4 VARIES SIDEWALL KRUEGER 880-R-1 VARIES CEILING RETURN GRILLE KRUEGER 6490-R-2 VARIES SIDEWALL RETURN GRILLE KRUEGER S5480-R-3 VARIES CEILING RETURN GRILLE - SURFACE KRUEGER EG15-E-1 VARIES CEILING EXHAUST GRILLE - LAY IN KRUEGER EG15-E-2 VARIES CEILING EXHAUST GRILLE - SURFACE KRUEGER EG15-T-1 VARIES SIDEWALL TRANSFER GRILLE KRUEGER 6490-SEE SPECIFICATION SECTION 233713s^of^_ib=slirjb=^fo=_lubp=tfqe=obeb^q=Es^soF=pbib`qflk=`e^oqSYSTEM AIR PRESSURE COILSYMBOL TITUS CFM TITUS OPERATING DROP W/ 1 ROW DIMENSIONREMARKSSIZE RANGE MODEL STATIC IN. W.C. COIL IN. W.C. INCH.VAVR_ 6 0-349 DESV 0.75 0.30 12"x8"VAVR_ 8 350-599 DESV 0.75 0.30 12"x10"VAVR_ 9 600-749 DESV 0.75 0.30 14"x12"-1/2"VAVR_ 10 750-999 DESV 0.75 0.30 14"x12"-1/2"VAVR_ 12 1000-1349 DESV 0.75 0.30 16"x15"VAVR_ 14 1350-1899 DESV 0.75 0.30 20"x17"-1/2"VAVR_ 16 1900-2399 DESV 0.75 0.30 24"x18"VAVR_ 22 2400-4800 DESV 0.75 0.30 38"x18"s^of^_ib=slirjb=tfqe=obeb^q=Es^soFBALANCE MINIMUM MAX. HEATING COIL 35% PROPYLENE GLYCOLMIN.SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITYGPMEWT MAX. PRESSURE TITUS INLET REMARKSCLG. CFM CFM HTG. CFM BTU/HR DEG F. DROP, FT. W.C. SIZE SIZE IN.VAVR-175 110 60 100 3,599 0.5 180 0.3 6 6VAVR-178 330 60 220 8,944 0.6 180 0.4 6 6 FOR ALTERNATE 1 AND/OR 2VAVR-179A 175 60 175 7,074 0.5 180 0.4 6 6VAVR-179B 110 60 100 3,781 0.5 180 0.3 6 6VAVR-179C 110 60 100 3,848 0.5 180 0.3 6 6VAVR-179D 145 60 125 5,061 0.5 180 0.4 6 6VAVR-181 700 135 440 17,821 1.3 180 0.4 9 9VAVR-189 1965 420 665 26,889 1.9 180 0.3 16 16VAVR-189A 345 60 345 13,963 1.0 180 1.8 6 6VAVR-205 230 60 230 11,057 0.8 180 1.8 6 6VAVR-207 995 165 995 40,249 2.9 180 1.3 10 10VAVR-207A 1495 320 1495 60,479 4.3 180 2.5 14 14VAVR-210A 1900 420 1,900 80,051 5.7 180 1.4 16 16VAVR-210B 1900 420 1,900 80,051 5.7 180 1.4 16 16VAVR-261 1830 320 1830 74,015 5.3 180 3.6 14 14VAVR-261A 780 165 780 31,511 2.2 180 0.8 10 10VAVR-301 560 105 495 19,979 1.4 180 1.0 8 8VAVR-303 550 105 545 22,002 1.6 180 1.0 8 8VAVR-D207 1000 235 1,000 44,273 3.1 180 1.9 12 12LOCATION208 60 3 BELTDUTYDRIVEFAN MOTORPHASEVOLTS HERTZMAXFANPRESSURETOTAL STATICBHPINCHES WCRPMAIR FLOWCFMSYMBOLEF-1HPNOM.COOKMODELbufpqfkd=bue^rpq=c^kp=EbcF0.5 1.9 650300 CPVFACULTY LOCKER / DANCE MAIN FAN ROOMVFD11NO.208 60 3 BELTEF-20.5 1.1 760245 CPVSTUDENT LOCKER ROOM MAIN FAN ROOM12208 60 3 BELTEF-40.75 1.1 700225 CPVWEST LOCKER ROOM MAIN FAN ROOM1410,0006,0005,00021.51.5aovbo=bue^rpq=c^k=EabcFLOCATION120 60 1 DIRECT-REMARKSDUTYDRIVEFAN MOTORPHASEVOLTS HERTZMAXFANPRESSURETOTAL STATICINCHES WCRPMAIR FLOWCFMSYMBOLDEF-1HPNOM.SEE SPECIFICATION SECTION 233423ENERVEXMODEL1.6 1,600EFV-315ECDRYER EXHAUST ROOF1,000 1/2SEE SPECIFICATION SECTION 233___120 60 1 DIRECT-DEF-21.6 1,600EFV-315ECDRYER EXHAUST ROOF1,000 1/2BALANCE TO 7600 CFMREMARKSBALANCE TO 2900 CFMBALANCE TO 5200 CFM2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:22:54 PMM-002MECHANICALSCHEDULES200541 10/30/20 ADD #1
111122223333444455556666777710101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMMMH101.2MH101.2MH101.2MH101.21111MH101.3MH101.3MH101.3MH101.311112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:00 PMMD101LEVEL 1OVERALLMECHANICALDEMOLITIONPLAN20054SCALE:SCALE:SCALE:SCALE:MD101MD101MD101MD1011" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=N=lsbo^ii=jb`e^kf`^i=abjlifqflk=mi^k1111000010101010202020202020202040404040
111122223333444455556666777710101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMMMD102.1MD102.1MD102.1MD102.11111MH102.4MH102.4MH102.4MH102.42222MH102.4MH102.4MH102.4MH102.41111MD102.2MD102.2MD102.2MD102.211112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:10 PMMD102LEVEL 2OVERALLMECHANICALDEMOLITIONPLAN20054000010101010202020202020202040404040SCALE:SCALE:SCALE:SCALE:MD102MD102MD102MD1021" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=O=lsbo^ii=jb`e^kf`^i=abjlifqflk=mi^k1111
A.B.C.D.E.F.G.H.FIELD VERIFY EXACT LOCATIONS OF EXISTING PIPING,DUCTWORK, EQUIPMENT, ETC.DEMOLITION FLOOR PLANS HAVE BEEN CREATED USINGAVAILABLE RECORD DRAWINGS. CONTRACTOR SHALL BERESPONSIBLE FOR VERIFYING EXACT ROUTING OF ALLPIPING, DUCTWORK, ETC. DURING CONSTRUCTION.DEMOLITION OF EXISTING MECHANICAL AND PLUMBINGCONSTRUCTION SHALL BE TO THE EXTENT REQUIRED TOACCOMMODATE THE RENOVATION AND THE ADDITION OFNEW WORK.REFERENCE ARCHITECTURAL DEMOLITION DRAWINGS TOCOORDINATE AND VERIFY THE EXTENT OF THE DEMOLITIONWORK REQUIRED.ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BEPROTECTED THROUGHOUT THE CONSTRUCTION PERIOD.PROVIDE AND INSTALL CAPS ON EXISTING MAIN DUCTWORKAND / OR PIPING BRANCH BEING REMOVED. REFERENCEARCHITECTURAL FOR PATCHWORK.INDICATED DEMOLITION OF PIPING AND DUCTWORKINCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL OFDUCTWORK, PIPING, FITTINGS, VALVES, HANGERS,SUPPORTS, INSULATION, ETC. UNLESS NOTED OTHERWISE.INDICATED DEMOLITION OF MECHANICAL EQUIPMENTINCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL OFEQUIPMENT, PIPING, VALVES, INSULATION, SEISMICBRACING, CONTROLS, ELECTRICAL, ETC. UNLESS NOTEDOTHERWISE.FIELD VERIFY EXACT LOCATIONS OF THERMOSTATS, SENSORAND CONTROLLING UNITS.CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ANDREPAIRING ANY DAMAGE CAUSED BY HIS / HER PERSONNELTO EXISTING THAT IS TO REMAIN OR TO NEWLY INSTALLEDBUILDING COMPONENTS.EXISTING PIPING INSULATION MAY CONTAIN ASBESTOS. THEOWNER IS RESPONSIBLE FOR THE REMOVAL AND HANDLINGOF ANY SUSPECT MATERIALS. IF DURING THE COARSE OFTHE WORK ANY SUSPECT MATERIALS ARE ENCOUNTERED BYTHE CONTRACTOR, THE CONTRACTOR IS TO IMMEDIATLEYSTOP WORK IN THE AREA AND NOTIFY THE OWNER.PATCH AND SEAL ALL ABANDONED OPENINGS THROUGHWALLS AND FLOORS. MATCH EXISTING SURROUNDINGFINISH.CONTRACTOR SHALL REPLACE ANY INSULATION THAT ISDAMAGED DURING CONSTRUCTION ON PIPE OR DUCTWORKTHAT IS TO REMAIN.PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK WITHELECTRICAL CONTRACTOR AND CONTROLS CONTRACTOR TOMAKE CERTAIN POWER AND CONTROLS ARE PROPERLYDISCONNECTED AND TERMINATED.I.J.K.L.M.N.CAP ANY PNEUMATIC CONTROL PIPING THAT IS MADEOBSOLETE BACK AT MAIN. DO NOT BEND OR CRIMPPIPE, PROVIDE CAP.O.212121212222222223232323242424242525252526262626272727272828282829292929C1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL11112222333344445555666677778888999944444444222233331111555555555555111122221111111111111111111111111111111111115555555555555555333322223333222266666666dbkbo^i=klqbpabjlifqflk(APPLIES TO ALL(APPLIES TO ALL(APPLIES TO ALL(APPLIES TO ALLDEMO. DRAWINGS)DEMO. DRAWINGS)DEMO. DRAWINGS)DEMO. DRAWINGS)2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:15 PMMD102.1LEVEL 2AREA 2GMECHANICALDEMOLITIONPLAN20054ao^tfkd=klqbp00005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MD102.1MD102.1MD102.1MD102.11/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=Od=cfbia=elrpb=jb`e^kf`^iabjlifqflk=mi^k1111NOTE#DESCRIPTION1111 REMOVE EXISTING SUPPLY AIRREMOVE EXISTING SUPPLY AIRREMOVE EXISTING SUPPLY AIRREMOVE EXISTING SUPPLY AIRDUCTWORK AND DIFFUSERS.DUCTWORK AND DIFFUSERS.DUCTWORK AND DIFFUSERS.DUCTWORK AND DIFFUSERS.2222 REMOVE EXISTING AIR HANDLING UNITREMOVE EXISTING AIR HANDLING UNITREMOVE EXISTING AIR HANDLING UNITREMOVE EXISTING AIR HANDLING UNITCOMPLETE, INCLUDING ASSOCIATEDCOMPLETE, INCLUDING ASSOCIATEDCOMPLETE, INCLUDING ASSOCIATEDCOMPLETE, INCLUDING ASSOCIATEDPIPING VALVES STRAINERS,PIPING VALVES STRAINERS,PIPING VALVES STRAINERS,PIPING VALVES STRAINERS,CONTORLS, ETC.CONTORLS, ETC.CONTORLS, ETC.CONTORLS, ETC.3333 REMOVE EXISTING RETURN AIRREMOVE EXISTING RETURN AIRREMOVE EXISTING RETURN AIRREMOVE EXISTING RETURN AIRDUCTWORK. (DUCTWORK DROPSDUCTWORK. (DUCTWORK DROPSDUCTWORK. (DUCTWORK DROPSDUCTWORK. (DUCTWORK DROPSDOWN THE WALL APPROX. 20').DOWN THE WALL APPROX. 20').DOWN THE WALL APPROX. 20').DOWN THE WALL APPROX. 20').4444 REMOVE EXISTING DUCTWORK ASREMOVE EXISTING DUCTWORK ASREMOVE EXISTING DUCTWORK ASREMOVE EXISTING DUCTWORK ASSHOWN.SHOWN.SHOWN.SHOWN.5555 REMOVE EXISTING RELIEF AIRREMOVE EXISTING RELIEF AIRREMOVE EXISTING RELIEF AIRREMOVE EXISTING RELIEF AIRDUCTWORK, DAMPER AND FAN ON THEDUCTWORK, DAMPER AND FAN ON THEDUCTWORK, DAMPER AND FAN ON THEDUCTWORK, DAMPER AND FAN ON THEROOF. PATCH ROOF OPENING.ROOF. PATCH ROOF OPENING.ROOF. PATCH ROOF OPENING.ROOF. PATCH ROOF OPENING.6666 REMOVE EXISTING HWS/R PIPING.REMOVE EXISTING HWS/R PIPING.REMOVE EXISTING HWS/R PIPING.REMOVE EXISTING HWS/R PIPING.7777 REMOVE EXISTING 1-1/4" HWS/RREMOVE EXISTING 1-1/4" HWS/RREMOVE EXISTING 1-1/4" HWS/RREMOVE EXISTING 1-1/4" HWS/RPIPING DOWN WALL TO A POINTPIPING DOWN WALL TO A POINTPIPING DOWN WALL TO A POINTPIPING DOWN WALL TO A POINTWHERE NEW PIPING CAN CONNECT.WHERE NEW PIPING CAN CONNECT.WHERE NEW PIPING CAN CONNECT.WHERE NEW PIPING CAN CONNECT.8888 REMOVE EXISTING 4" HWS/R PIPINGREMOVE EXISTING 4" HWS/R PIPINGREMOVE EXISTING 4" HWS/R PIPINGREMOVE EXISTING 4" HWS/R PIPINGBACK TO WHERE NEW PIPING CANBACK TO WHERE NEW PIPING CANBACK TO WHERE NEW PIPING CANBACK TO WHERE NEW PIPING CANCONNECT.CONNECT.CONNECT.CONNECT.9999 EXISTING SECTION OF 4" HWS/R PIPINGEXISTING SECTION OF 4" HWS/R PIPINGEXISTING SECTION OF 4" HWS/R PIPINGEXISTING SECTION OF 4" HWS/R PIPINGTO REMAIN.TO REMAIN.TO REMAIN.TO REMAIN.
1111111112121212131313131414141415151515161616161717171719191919202020202121212122222222BBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL11112222333333332"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:20 PMMD102.2LEVEL 2AREA 2AMECHANICALDEMOLITIONPLAN20054ao^tfkd=klqbp00005555101010101010101020202020NOTE#DESCRIPTION1111 CAP EXHAUST DUCT. SEAL AIR TIGHT.CAP EXHAUST DUCT. SEAL AIR TIGHT.CAP EXHAUST DUCT. SEAL AIR TIGHT.CAP EXHAUST DUCT. SEAL AIR TIGHT.2222 REMOVE EXISTING EXHAUSTREMOVE EXISTING EXHAUSTREMOVE EXISTING EXHAUSTREMOVE EXISTING EXHAUSTDUCTWORK AS SHOWN.DUCTWORK AS SHOWN.DUCTWORK AS SHOWN.DUCTWORK AS SHOWN.3333 REMOVE EXISTING SENSORREMOVE EXISTING SENSORREMOVE EXISTING SENSORREMOVE EXISTING SENSORPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INSAME LOCATION.SAME LOCATION.SAME LOCATION.SAME LOCATION.SCALE:SCALE:SCALE:SCALE:MD102.2MD102.2MD102.2MD102.21/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O^=j^fk=dvj=jb`e^kf`^iabjlifqflk=mi^k11111 10/30/20 ADD #1
13131313141414141515151516161616171717171919191920202020LLLLMMMM11112222333333332"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:23 PMMD102.3AREA 2BMECHANICALDEMOLITIONPLANS20054ao^tfkd=klqbpSCALE:SCALE:SCALE:SCALE:MD102.3MD102.3MD102.3MD102.31/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O_=kloqe=e^ii=jb`e^kf`^iabjlifqflk=mi^k111100005555101010101010101020202020NOTE#DESCRIPTION1111 REMOVE EXHUAST DUCT UP THROUGH CEILINGREMOVE EXHUAST DUCT UP THROUGH CEILINGREMOVE EXHUAST DUCT UP THROUGH CEILINGREMOVE EXHUAST DUCT UP THROUGH CEILINGAND CAP, SEAL AIR TIGHT.AND CAP, SEAL AIR TIGHT.AND CAP, SEAL AIR TIGHT.AND CAP, SEAL AIR TIGHT.2222 REMOVE EXISTING RETURN AIR DUCT AS SHOWN.REMOVE EXISTING RETURN AIR DUCT AS SHOWN.REMOVE EXISTING RETURN AIR DUCT AS SHOWN.REMOVE EXISTING RETURN AIR DUCT AS SHOWN.REMOVE ONLY ENOUGH VERTICAL DUCT TOREMOVE ONLY ENOUGH VERTICAL DUCT TOREMOVE ONLY ENOUGH VERTICAL DUCT TOREMOVE ONLY ENOUGH VERTICAL DUCT TOALLOW FOR NEW CONNECTION.ALLOW FOR NEW CONNECTION.ALLOW FOR NEW CONNECTION.ALLOW FOR NEW CONNECTION.3333 REMOVE EXISTING RETURN AIR GRILLEREMOVE EXISTING RETURN AIR GRILLEREMOVE EXISTING RETURN AIR GRILLEREMOVE EXISTING RETURN AIR GRILLEPREPARATORY FOR NEW. FIELD VERIFY EXACTPREPARATORY FOR NEW. FIELD VERIFY EXACTPREPARATORY FOR NEW. FIELD VERIFY EXACTPREPARATORY FOR NEW. FIELD VERIFY EXACTSIZE.SIZE.SIZE.SIZE.
111122223333444455556666777710101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMMMH101.2MH101.2MH101.2MH101.22222MH101.3MH101.3MH101.3MH101.32222MH101.5MH101.5MH101.5MH101.53333MH101.5MH101.5MH101.5MH101.54444MH101.5MH101.5MH101.5MH101.51111MH101.5MH101.5MH101.5MH101.522222"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:23:29 PMMH101LEVEL 1OVERALLMECHANICALREMODELPLAN20054000010101010202020202020202040404040SCALE:SCALE:SCALE:SCALE:MH101MH101MH101MH1011" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=N=lsbo^ii=jb`e^kf`^i=objlabi=mi^k1111
1717171719191919202020202121212122222222C1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL151515151616161616161616161616162121212120202020202020202121212121212121252525252626262627272727282828282828282828282828282828282727272726262626272727272727272726262626272727272727272727272727272727271717171719191919202020202121212122222222C1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL1111222233334444666677778888999910101010111111111212121213131313141414146"Ø6"Ø6"Ø6"Ø6"x10"+1"AL6"x10"+1"AL6"x10"+1"AL6"x10"+1"AL179A179A179A179AVAVRVAVRVAVRVAVR10"Ø10"Ø10"Ø10"Ø6"Ø6"Ø6"Ø6"Ø8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL179B179B179B179BVAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.77776"Ø6"Ø6"Ø6"Ø8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL179C179C179C179CVAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.77776"Ø6"Ø6"Ø6"Ø8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL179D179D179D179DVAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.13131313131313131313131313131313H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø1313131377778"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø12"Ø12"Ø12"Ø12"Ø14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL181181181181VAVRVAVRVAVRVAVR10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.333310"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.333310"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.333310"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.4444H.D.H.D.H.D.H.D.12"Ø12"Ø12"Ø12"Ø10"x10"10"x10"10"x10"10"x10"H.D.H.D.H.D.H.D.111112"x10"12"x10"12"x10"12"x10"H.D.H.D.H.D.H.D.10"x10"10"x10"10"x10"10"x10"10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.111110"x10"10"x10"10"x10"10"x10"222210"x10"10"x10"10"x10"10"x10"111112"Ø12"Ø12"Ø12"Ø10"x10"10"x10"10"x10"10"x10"10"x8"10"x8"10"x8"10"x8"10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.222210"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.222222"x12"22"x12"22"x12"22"x12"H.D.H.D.H.D.H.D.189A189A189A189AVAVRVAVRVAVRVAVR6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.14"Ø14"Ø14"Ø14"Ø189189189189VAVRVAVRVAVRVAVR6"Ø6"Ø6"Ø6"Ø18"x16"+1"AL18"x16"+1"AL18"x16"+1"AL18"x16"+1"AL18"Ø18"Ø18"Ø18"Ø14"Ø14"Ø14"Ø14"Ø14"Ø14"Ø14"Ø14"Ø141414142424242414"Ø14"Ø14"Ø14"Ø1414141410"Ø10"Ø10"Ø10"Ø205205205205VAVRVAVRVAVRVAVRD207D207D207D207VAVRVAVRVAVRVAVR14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL8"x7"+1"AL8"x7"+1"AL8"x7"+1"AL8"x7"+1"AL10"Ø10"Ø10"Ø10"Ø17171717H.D.H.D.H.D.H.D.ADADADADPART OF ADD. ALT. #1PART OF ADD. ALT. #1PART OF ADD. ALT. #1PART OF ADD. ALT. #1SEE DRAWING MH101.5SEE DRAWING MH101.5SEE DRAWING MH101.5SEE DRAWING MH101.510"Ø10"Ø10"Ø10"Ø1818181819191919SSSS111111111111111111111111S19191919SS12"Ø12"Ø12"Ø12"Ø14"Ø14"Ø14"Ø14"Ø177STOR.ACTIVITY176CUSTODIAN175OFFICECUSTODIAN180RMLAUNDRY179AASSEMBLESORT &179BOFFICECTRWELLNESS179COFFICEWELLNESS CTR179DOFFICECTRWELLNESS181WOMEN'S183MEN'S189ASTOR.ACTIVITY189BMECH.189RM.SPINNING11111111191919198"Ø8"Ø8"Ø8"Ø10"Ø10"Ø10"Ø10"Ø181818181717171717171717ADADADADADADADADADADADAD8"Ø8"Ø8"Ø8"Ø131313133/4"3/4"3/4"3/4"8"Ø8"Ø8"Ø8"Ø131313133/4"3/4"3/4"3/4"22222222PART OF ADD. ALT. #2PART OF ADD. ALT. #2PART OF ADD. ALT. #2PART OF ADD. ALT. #2SEE DRAWING MH101.5SEE DRAWING MH101.5SEE DRAWING MH101.5SEE DRAWING MH101.566666"Ø6"Ø6"Ø6"Ø175175175175VAVRVAVRVAVRVAVRH.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø77778"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"ALS111111112929292929292929dbkbo^i=klqbpA.A.A.A.HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE 3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:10 PMMH101.2LEVEL 1MECHANICALPLANS20054ao^tfkd=klqbp00005555101010101010101020202020NOTE#DIFFUSERCALLOUT DESCRIPTION1111 E-2E-2E-2E-2 250 CFM, 10"x10" EXHAUST AIR250 CFM, 10"x10" EXHAUST AIR250 CFM, 10"x10" EXHAUST AIR250 CFM, 10"x10" EXHAUST AIRGRILLEGRILLEGRILLEGRILLE2222 E-2E-2E-2E-2 260 CFM, 10"x10" EXHAUST AIR260 CFM, 10"x10" EXHAUST AIR260 CFM, 10"x10" EXHAUST AIR260 CFM, 10"x10" EXHAUST AIRGRILLEGRILLEGRILLEGRILLE3333 S-2S-2S-2S-2 250 CFM, 10"Ø NK, S.A. DIFFUSER250 CFM, 10"Ø NK, S.A. DIFFUSER250 CFM, 10"Ø NK, S.A. DIFFUSER250 CFM, 10"Ø NK, S.A. DIFFUSER4444 S-2S-2S-2S-2 350 CFM, 12"Ø NK, S.A. DIFFUSER350 CFM, 12"Ø NK, S.A. DIFFUSER350 CFM, 12"Ø NK, S.A. DIFFUSER350 CFM, 12"Ø NK, S.A. DIFFUSER6666 S-1S-1S-1S-1 130 CFM, 10"Ø NK, S.A. DIFFUSER130 CFM, 10"Ø NK, S.A. DIFFUSER130 CFM, 10"Ø NK, S.A. DIFFUSER130 CFM, 10"Ø NK, S.A. DIFFUSER7777 S-1S-1S-1S-1 110 CFM, 8"Ø NK, S.A. DIFFUSER110 CFM, 8"Ø NK, S.A. DIFFUSER110 CFM, 8"Ø NK, S.A. DIFFUSER110 CFM, 8"Ø NK, S.A. DIFFUSER8888 S-2S-2S-2S-2 100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER9999 S-1S-1S-1S-1 135 CFM, 8"Ø NK, S.A. DIFFUSER135 CFM, 8"Ø NK, S.A. DIFFUSER135 CFM, 8"Ø NK, S.A. DIFFUSER135 CFM, 8"Ø NK, S.A. DIFFUSER10101010 BALANCE EXISTING EXHAUST GRILLEBALANCE EXISTING EXHAUST GRILLEBALANCE EXISTING EXHAUST GRILLEBALANCE EXISTING EXHAUST GRILLETO 135 CFM.TO 135 CFM.TO 135 CFM.TO 135 CFM.11111111 12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENINGIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDBOOT.BOOT.BOOT.BOOT.12121212 E-1E-1E-1E-1 1000 CFM, 22"x22" EXHAUST AIR1000 CFM, 22"x22" EXHAUST AIR1000 CFM, 22"x22" EXHAUST AIR1000 CFM, 22"x22" EXHAUST AIRGRILLEGRILLEGRILLEGRILLE13131313 R-1R-1R-1R-1 22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUNDBOOTBOOTBOOTBOOT14141414 S-4S-4S-4S-4 370 CFM, 12"x10" NK, S.A. DIFFUSER370 CFM, 12"x10" NK, S.A. DIFFUSER370 CFM, 12"x10" NK, S.A. DIFFUSER370 CFM, 12"x10" NK, S.A. DIFFUSER15151515 EXISTING DUCTWORK TO REMAIN.EXISTING DUCTWORK TO REMAIN.EXISTING DUCTWORK TO REMAIN.EXISTING DUCTWORK TO REMAIN.16161616 CAP EXISTING EXHAUST DUCT INCAP EXISTING EXHAUST DUCT INCAP EXISTING EXHAUST DUCT INCAP EXISTING EXHAUST DUCT INCEILING.CEILING.CEILING.CEILING.17171717 PROVIDE ACCESS DOORS ASPROVIDE ACCESS DOORS ASPROVIDE ACCESS DOORS ASPROVIDE ACCESS DOORS ASREQUIRED BY CODE FOR THE DRYERREQUIRED BY CODE FOR THE DRYERREQUIRED BY CODE FOR THE DRYERREQUIRED BY CODE FOR THE DRYEREXHAUST DUCT.EXHAUST DUCT.EXHAUST DUCT.EXHAUST DUCT.18181818 RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.SEE SHEET MH102.1 FORSEE SHEET MH102.1 FORSEE SHEET MH102.1 FORSEE SHEET MH102.1 FORCONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.19191919 R-1R-1R-1R-1 24"x24" FACE R.A. GRILLE W/ SOUND24"x24" FACE R.A. GRILLE W/ SOUND24"x24" FACE R.A. GRILLE W/ SOUND24"x24" FACE R.A. GRILLE W/ SOUNDBOOTBOOTBOOTBOOT20202020 REMOVE PORTION OF HEATING WATERREMOVE PORTION OF HEATING WATERREMOVE PORTION OF HEATING WATERREMOVE PORTION OF HEATING WATERPIPING AS REQUIRED FOR NEW FLOORPIPING AS REQUIRED FOR NEW FLOORPIPING AS REQUIRED FOR NEW FLOORPIPING AS REQUIRED FOR NEW FLOORINSTALLATION ABOVE. TEMPORARILYINSTALLATION ABOVE. TEMPORARILYINSTALLATION ABOVE. TEMPORARILYINSTALLATION ABOVE. TEMPORARILYCAP RUNOUTS.CAP RUNOUTS.CAP RUNOUTS.CAP RUNOUTS.21212121 REMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGSUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,CONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCEVALVE, ETC.VALVE, ETC.VALVE, ETC.VALVE, ETC.22222222 DRYER EXHAUST CONTROL PANELDRYER EXHAUST CONTROL PANELDRYER EXHAUST CONTROL PANELDRYER EXHAUST CONTROL PANEL24242424 S-4S-4S-4S-4 150 CFM, 10"x8" NK, S.A. DIFFUSER150 CFM, 10"x8" NK, S.A. DIFFUSER150 CFM, 10"x8" NK, S.A. DIFFUSER150 CFM, 10"x8" NK, S.A. DIFFUSER25252525 RELOCATE EXISTING SENSOR FORRELOCATE EXISTING SENSOR FORRELOCATE EXISTING SENSOR FORRELOCATE EXISTING SENSOR FORTHIS VAV BOX TO EQUIPMENT ROOMTHIS VAV BOX TO EQUIPMENT ROOMTHIS VAV BOX TO EQUIPMENT ROOMTHIS VAV BOX TO EQUIPMENT ROOM178 AS PART OF BASE BID.178 AS PART OF BASE BID.178 AS PART OF BASE BID.178 AS PART OF BASE BID.26262626 CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.27272727 REMOVE SECTION OF DUCTWORK ANDREMOVE SECTION OF DUCTWORK ANDREMOVE SECTION OF DUCTWORK ANDREMOVE SECTION OF DUCTWORK ANDASSOCIATED GRILLES AND DIFFUSERSASSOCIATED GRILLES AND DIFFUSERSASSOCIATED GRILLES AND DIFFUSERSASSOCIATED GRILLES AND DIFFUSERSAS SHOWN.AS SHOWN.AS SHOWN.AS SHOWN.28282828 REMOVE VAVR BOX.REMOVE VAVR BOX.REMOVE VAVR BOX.REMOVE VAVR BOX.29292929 SEE SHEET MH101.4 FORSEE SHEET MH101.4 FORSEE SHEET MH101.4 FORSEE SHEET MH101.4 FORCONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.SCALE:SCALE:SCALE:SCALE:MH101.2MH101.2MH101.2MH101.21/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"ibsbi=N=jb`e^kf`^i=abjlifqflkmi^k1111SCALE:SCALE:SCALE:SCALE:MH101.2MH101.2MH101.2MH101.21/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"ibsbi=N=jb`e^kf`^i=objlabi=mi^k2222000055551010101010101010202020201 10/30/20 ADD #1
1111111112121212131313131414141415151515BBBBCCCCC1C1C1C1DDDD22221111111112121212131313131414141415151515BBBBCCCCC1C1C1C1DDDD16"Ø16"Ø16"Ø16"Ø16"Ø16"Ø16"Ø16"Ø20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL20"x18"+1"AL22"x24"+1"AL22"x24"+1"AL22"x24"+1"AL22"x24"+1"AL210A210A210A210AVAVRVAVRVAVRVAVR210B210B210B210BVAVRVAVRVAVRVAVR16"Ø16"Ø16"Ø16"Ø12"Ø12"Ø12"Ø12"Ø301301301301VAVRVAVRVAVRVAVR303303303303VAVRVAVRVAVRVAVR(BELOW)(BELOW)(BELOW)(BELOW)14"x11"+1"AL14"x11"+1"AL14"x11"+1"AL14"x11"+1"AL14"x11"14"x11"14"x11"14"x11"+1"AL (BELOW)+1"AL (BELOW)+1"AL (BELOW)+1"AL (BELOW)12"Ø12"Ø12"Ø12"Ø(BELOW)(BELOW)(BELOW)(BELOW)RAISE DUCT UPRAISE DUCT UPRAISE DUCT UPRAISE DUCT UPAND CONNECTAND CONNECTAND CONNECTAND CONNECT11111111----1/4"1/4"1/4"1/4"3/4"3/4"3/4"3/4"1"1"1"1"1"1"1"1"1111----1/4"1/4"1/4"1/4"2"2"2"2"SEE SHEET MH102.2SEE SHEET MH102.2SEE SHEET MH102.2SEE SHEET MH102.2FOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONSEE SHEET MH101.4SEE SHEET MH101.4SEE SHEET MH101.4SEE SHEET MH101.4FOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONdbkbo^i=klqbpA.A.A.A.HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE 3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:14 PMMH101.3LEVEL 1MECHANICALPLANS20054ao^tfkd=klqbp00005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH101.3MH101.3MH101.3MH101.31/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"qrkkbi=jb`e^kf`^i=abjlifqflkmi^k1111SCALE:SCALE:SCALE:SCALE:MH101.3MH101.3MH101.3MH101.31/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"qrkkbi=jb`e^kf`^i=objlabi=mi^k222200005555101010101010101020202020NOTE#DESCRIPTION1111 CONTRACTOR TO DETERMINE ACTUAL LOCATIONCONTRACTOR TO DETERMINE ACTUAL LOCATIONCONTRACTOR TO DETERMINE ACTUAL LOCATIONCONTRACTOR TO DETERMINE ACTUAL LOCATIONOF UNDERGROUND DUCT. SAW CUT FLOOR ANDOF UNDERGROUND DUCT. SAW CUT FLOOR ANDOF UNDERGROUND DUCT. SAW CUT FLOOR ANDOF UNDERGROUND DUCT. SAW CUT FLOOR ANDCONNECT AND RAISE A 8"x6"+1"AL DUCT UP. SEECONNECT AND RAISE A 8"x6"+1"AL DUCT UP. SEECONNECT AND RAISE A 8"x6"+1"AL DUCT UP. SEECONNECT AND RAISE A 8"x6"+1"AL DUCT UP. SEESHEET MH101.4 FOR CONTINUATION.SHEET MH101.4 FOR CONTINUATION.SHEET MH101.4 FOR CONTINUATION.SHEET MH101.4 FOR CONTINUATION.2222 REMOVE PORTION OF HEATING WATER PIPING ASREMOVE PORTION OF HEATING WATER PIPING ASREMOVE PORTION OF HEATING WATER PIPING ASREMOVE PORTION OF HEATING WATER PIPING ASREQUIRED FOR NEW FLOOR INSTALLATION ABOVE.REQUIRED FOR NEW FLOOR INSTALLATION ABOVE.REQUIRED FOR NEW FLOOR INSTALLATION ABOVE.REQUIRED FOR NEW FLOOR INSTALLATION ABOVE.TEMPORARILY CAP RUNOUTS.TEMPORARILY CAP RUNOUTS.TEMPORARILY CAP RUNOUTS.TEMPORARILY CAP RUNOUTS.1 10/30/20 ADD #1
131313131414141415151515161616161717171719191919202020202121212122222222AAAABBBBCCCCC1C1C1C16666777788888888888866666666999910101010131313131414141415151515161616161717171719191919202020202121212122222222AAAABBBBCCCCC1C1C1C111112222333310"x10" EXH.10"x10" EXH.10"x10" EXH.10"x10" EXH.10"x10" EXH.10"x10" EXH.10"x10" EXH.10"x10" EXH.33332-BHW.212RR211STOR.210PLATFORM8"x6" S.A.8"x6" S.A.8"x6" S.A.8"x6" S.A.DUCT BELOWDUCT BELOWDUCT BELOWDUCT BELOWR.R. FLOORR.R. FLOORR.R. FLOORR.R. FLOOR44445555SSS5555TO VAVRTO VAVRTO VAVRTO VAVR----210A210A210A210A& VAVR& VAVR& VAVR& VAVR----210B210B210B210BTO VAVRTO VAVRTO VAVRTO VAVR----205205205205TO VAVRTO VAVRTO VAVRTO VAVR----D207D207D207D2071212121211111111(TYP. OF 11)(TYP. OF 11)(TYP. OF 11)(TYP. OF 11)2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:18 PMMH101.4MAINLEVELMECHANICALPLANS20054ao^tfkd=klqbp00005555101010101010101020202020NOTE#DIFFUSERCALLOUTDESCRIPTION1111 E-3E-3E-3E-3 150 CFM, 10"x10" NK, EXHAUST AIR150 CFM, 10"x10" NK, EXHAUST AIR150 CFM, 10"x10" NK, EXHAUST AIR150 CFM, 10"x10" NK, EXHAUST AIRGRILLE.GRILLE.GRILLE.GRILLE.2222 S-3S-3S-3S-3 100 CFM, 8"x6" NK, S.A. DIFFUSER,100 CFM, 8"x6" NK, S.A. DIFFUSER,100 CFM, 8"x6" NK, S.A. DIFFUSER,100 CFM, 8"x6" NK, S.A. DIFFUSER,RAISE 8"x6" DUCT UP THROUGH WALLRAISE 8"x6" DUCT UP THROUGH WALLRAISE 8"x6" DUCT UP THROUGH WALLRAISE 8"x6" DUCT UP THROUGH WALLWITH SIDEWALL DIFFUSER HIGH ONWITH SIDEWALL DIFFUSER HIGH ONWITH SIDEWALL DIFFUSER HIGH ONWITH SIDEWALL DIFFUSER HIGH ONWALL.WALL.WALL.WALL.3333 E-1E-1E-1E-1 175 CFM, 10"x10" NK, EXHAUST AIR175 CFM, 10"x10" NK, EXHAUST AIR175 CFM, 10"x10" NK, EXHAUST AIR175 CFM, 10"x10" NK, EXHAUST AIRGRILLE.GRILLE.GRILLE.GRILLE.4444 REPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWAND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.SEE SHEET MH101.3 FORSEE SHEET MH101.3 FORSEE SHEET MH101.3 FORSEE SHEET MH101.3 FORCONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.5555 REPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWREPLACE EXISTING SENSOR WITH NEWAND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.AND CONNECT TO ASSOCIATED VAVR.SEE SHEET MH101.2 FORSEE SHEET MH101.2 FORSEE SHEET MH101.2 FORSEE SHEET MH101.2 FORCONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.6666 REMOVE SECTION OF DUCT ASREMOVE SECTION OF DUCT ASREMOVE SECTION OF DUCT ASREMOVE SECTION OF DUCT ASSHOWN, INCLUDING GRILLES.SHOWN, INCLUDING GRILLES.SHOWN, INCLUDING GRILLES.SHOWN, INCLUDING GRILLES.7777 CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.CAP DUCT AND SEAL AIR TIGHT.8888 REMOVE EXISTING SENSORREMOVE EXISTING SENSORREMOVE EXISTING SENSORREMOVE EXISTING SENSORPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INPREPARATORY FOR NEW SENSOR INSAME LOCATION.SAME LOCATION.SAME LOCATION.SAME LOCATION.9999 REMOVE EXISTING R.A. GRILLES.REMOVE EXISTING R.A. GRILLES.REMOVE EXISTING R.A. GRILLES.REMOVE EXISTING R.A. GRILLES.10101010 REMOVE EXISTING S.A. DIFFUSER ANDREMOVE EXISTING S.A. DIFFUSER ANDREMOVE EXISTING S.A. DIFFUSER ANDREMOVE EXISTING S.A. DIFFUSER ANDASSOCIATED DUCT AS SHOWNASSOCIATED DUCT AS SHOWNASSOCIATED DUCT AS SHOWNASSOCIATED DUCT AS SHOWN11111111 R-1R-1R-1R-1 24"x24" R.A. GRILLE24"x24" R.A. GRILLE24"x24" R.A. GRILLE24"x24" R.A. GRILLE12121212 S-4S-4S-4S-4 1000 CFM, 36"x18" NK, S.A.1000 CFM, 36"x18" NK, S.A.1000 CFM, 36"x18" NK, S.A.1000 CFM, 36"x18" NK, S.A.DIFFUSER. S.A. DIFFUSER TO BEDIFFUSER. S.A. DIFFUSER TO BEDIFFUSER. S.A. DIFFUSER TO BEDIFFUSER. S.A. DIFFUSER TO BELOCATED 4" LOWER THAN THE OLDLOCATED 4" LOWER THAN THE OLDLOCATED 4" LOWER THAN THE OLDLOCATED 4" LOWER THAN THE OLDS.A. DIFFUSERS.A. DIFFUSERS.A. DIFFUSERS.A. DIFFUSERSCALE:SCALE:SCALE:SCALE:MH101.4MH101.4MH101.4MH101.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"j^fk=ibsbi=jb`e^kf`^i=abjlifqflkmi^k1111SCALE:SCALE:SCALE:SCALE:MH101.4MH101.4MH101.4MH101.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"j^fk=ibsbi=jb`e^kf`^i=objlabimi^k2222000055551010101010101010202020201 10/30/20 ADD #12 11/05/20 ADD #2
17171717JJJJJ1J1J1J1KKKK176CUSTODIAN178EQUIP. RM175OFFICECUSTODIAN6"Ø6"Ø6"Ø6"Ø10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL178178178178VAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"Ø555588886666S1010101017171717J1J1J1J1KKKKH.D.H.D.H.D.H.D.176CUSTODIAN178EQUIP. RM175OFFICECUSTODIAN7777888899998"Ø8"Ø8"Ø8"Ø10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL178178178178VAVRVAVRVAVRVAVR6"Ø6"Ø6"Ø6"ØS101010101111BBBB207DSTORAGESTEAM UNITSTEAM UNITSTEAM UNITSTEAM UNITEEEE261ESTORAGESTEAM UNITSTEAM UNITSTEAM UNITSTEAM UNIT17171717JJJJJ1J1J1J1KKKK11112222222211111111222217171717J1J1J1J1KKKKH.D.H.D.H.D.H.D.S11112222222211111111444433332"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:26 PMMH101.5MECHANICALREMODELPLANS -ADD.ALTERNATES20054SCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=ibsbi=N=jb`e^kf`^i=objlabimi^k=J^iqbok^qb=@N3333SCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=ibsbi=N=jb`e^kf`^i=objlabimi^k=J^iqbok^qb=@O4444SCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=^ob^=O`=jbkp=bjmilvbbpil`hbo=jb`e^kf`^i=objlabi=mi^k=J^iqbok^qb=@P5555SCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=^ob^=O`=pqrabkq=il`hbopjb`e^kf`^i=objlabi=mi^k=J^iqbok^qb=@P666600002.52.52.52.5555555551010101000002.52.52.52.5555555551010101000002.52.52.52.5555555551010101000002.52.52.52.55555555510101010SCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=ibsbi=N=jb`e^kf`^iabjlifqflk=mi^k=J^iqbok^qb=@N1111ao^tfkd=klqbpSCALE:SCALE:SCALE:SCALE:MH101.5MH101.5MH101.5MH101.51/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=ibsbi=N=jb`e^kf`^iabjlifqflk=mi^k=J^iqbok^qb=@O222200002.52.52.52.5555555551010101000002.52.52.52.55555555510101010NOTE#DIFFUSERCALLOUTDESCRIPTION1111 CAP EXISTING DUCT AND SEAL AIRCAP EXISTING DUCT AND SEAL AIRCAP EXISTING DUCT AND SEAL AIRCAP EXISTING DUCT AND SEAL AIRTIGHT.TIGHT.TIGHT.TIGHT.2222 REMOVE SECTION OF EXISTING DUCTREMOVE SECTION OF EXISTING DUCTREMOVE SECTION OF EXISTING DUCTREMOVE SECTION OF EXISTING DUCTAND ASSOCIATED GRILLES ASAND ASSOCIATED GRILLES ASAND ASSOCIATED GRILLES ASAND ASSOCIATED GRILLES ASSHOWN.SHOWN.SHOWN.SHOWN.3333 REMOVE EXISTING EXHAUST DUCTREMOVE EXISTING EXHAUST DUCTREMOVE EXISTING EXHAUST DUCTREMOVE EXISTING EXHAUST DUCTDROP AND CAP.DROP AND CAP.DROP AND CAP.DROP AND CAP.4444 REMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDASSOCIATED DUCT WORK AND PIPING.ASSOCIATED DUCT WORK AND PIPING.ASSOCIATED DUCT WORK AND PIPING.ASSOCIATED DUCT WORK AND PIPING.CAP PIPING AT MAIN.CAP PIPING AT MAIN.CAP PIPING AT MAIN.CAP PIPING AT MAIN.5555 S-1S-1S-1S-1 180 CFM, 8"Ø NK, S.A. DIFFUSER180 CFM, 8"Ø NK, S.A. DIFFUSER180 CFM, 8"Ø NK, S.A. DIFFUSER180 CFM, 8"Ø NK, S.A. DIFFUSER6666 E-1E-1E-1E-1 200 CFM, 10"x10" NK, EXHAUST AIR200 CFM, 10"x10" NK, EXHAUST AIR200 CFM, 10"x10" NK, EXHAUST AIR200 CFM, 10"x10" NK, EXHAUST AIRGRILLEGRILLEGRILLEGRILLE7777 S-1S-1S-1S-1 150 CFM, 8"Ø NK, S.A. DIFFUSER150 CFM, 8"Ø NK, S.A. DIFFUSER150 CFM, 8"Ø NK, S.A. DIFFUSER150 CFM, 8"Ø NK, S.A. DIFFUSER8888 12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENING12"x14"+1"AL TRANSFER AIR OPENINGIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDBOOT.BOOT.BOOT.BOOT.9999 R-1R-1R-1R-1 22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUND22"x10" NK, R.A. GRILLE W/ SOUNDBOOTBOOTBOOTBOOT10101010 IF BOTH ALTERNATES AREIF BOTH ALTERNATES AREIF BOTH ALTERNATES AREIF BOTH ALTERNATES ARECONSTRUCTED, SENSOR WILL BECONSTRUCTED, SENSOR WILL BECONSTRUCTED, SENSOR WILL BECONSTRUCTED, SENSOR WILL BELOCATED IN ROOM 178 AS SHOWN.LOCATED IN ROOM 178 AS SHOWN.LOCATED IN ROOM 178 AS SHOWN.LOCATED IN ROOM 178 AS SHOWN.1 10/30/20 ADD #1
111122223333444455556666777710101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMMMH102.1MH102.1MH102.1MH102.11111MH102.2MH102.2MH102.2MH102.21111MH102.3MH102.3MH102.3MH102.31111MH102.4MH102.4MH102.4MH102.44444MH102.4MH102.4MH102.4MH102.43333MH101.5MH101.5MH101.5MH101.55555MH101.5MH101.5MH101.5MH101.566662"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:38 PMMH102LEVEL 2OVERALLMECHANICALREMODELPLAN20054000010101010202020202020202040404040SCALE:SCALE:SCALE:SCALE:MH102MH102MH102MH1021" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=O=lsbo^ii=jb`e^kf`^i=objlabi=mi^k1111
212121212222222223232323242424242525252526262626272727272828282829292929BBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL77778888101010101111DEFDEFDEFDEF(ON ROOF)(ON ROOF)(ON ROOF)(ON ROOF)2-ABALCONY182AUPPER EQUIP. ST.2222DEFDEFDEFDEF10"Ø10"Ø10"Ø10"Ø(ON ROOF)(ON ROOF)(ON ROOF)(ON ROOF)SS2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:44 PMMH102.1LEVEL 2AREA 2GMECHANICALREMODELPLAN20054ao^tfkd=klqbp00005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH102.1MH102.1MH102.1MH102.11/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=Od=cfbia=elrpb=jb`e^kf`^iobjlabi=mi^k1111NOTE#DIFFUSERCALLOUT DESCRIPTION1111 S-3S-3S-3S-3 925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSERWITH HORIZONTAL DISCHARGE BOOT.WITH HORIZONTAL DISCHARGE BOOT.WITH HORIZONTAL DISCHARGE BOOT.WITH HORIZONTAL DISCHARGE BOOT.SEE DETAIL 12/MH502.SEE DETAIL 12/MH502.SEE DETAIL 12/MH502.SEE DETAIL 12/MH502.2222 S-3S-3S-3S-3 925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSER925 CFM, 30"x6" NK, S.A. DIFFUSERWITH VERTICAL DISCHARGE BOOT. SEEWITH VERTICAL DISCHARGE BOOT. SEEWITH VERTICAL DISCHARGE BOOT. SEEWITH VERTICAL DISCHARGE BOOT. SEEDETAIL 12/MH502.DETAIL 12/MH502.DETAIL 12/MH502.DETAIL 12/MH502.3333 R-2R-2R-2R-2 12,500 CFM, 56"x34" NK, R.A. GRILLE12,500 CFM, 56"x34" NK, R.A. GRILLE12,500 CFM, 56"x34" NK, R.A. GRILLE12,500 CFM, 56"x34" NK, R.A. GRILLE4444 FACTORY MANUFACTURED CURB. SEEFACTORY MANUFACTURED CURB. SEEFACTORY MANUFACTURED CURB. SEEFACTORY MANUFACTURED CURB. SEEDETAIL 11/MH502. ALL CURBS SHALLDETAIL 11/MH502. ALL CURBS SHALLDETAIL 11/MH502. ALL CURBS SHALLDETAIL 11/MH502. ALL CURBS SHALLBE MINIMUM OF 18" HIGH. INSULATEBE MINIMUM OF 18" HIGH. INSULATEBE MINIMUM OF 18" HIGH. INSULATEBE MINIMUM OF 18" HIGH. INSULATECURB TO CREATE AN R-20.CURB TO CREATE AN R-20.CURB TO CREATE AN R-20.CURB TO CREATE AN R-20.5555 RISE 2-1/2" HWS/R TO CONNECT TORISE 2-1/2" HWS/R TO CONNECT TORISE 2-1/2" HWS/R TO CONNECT TORISE 2-1/2" HWS/R TO CONNECT TOAIR HANDLING UNIT ABOVE.AIR HANDLING UNIT ABOVE.AIR HANDLING UNIT ABOVE.AIR HANDLING UNIT ABOVE.6666 RISE 4" CHWS/R TO CONNECT TO AIRRISE 4" CHWS/R TO CONNECT TO AIRRISE 4" CHWS/R TO CONNECT TO AIRRISE 4" CHWS/R TO CONNECT TO AIRHANDLING UNIT ABOVE.HANDLING UNIT ABOVE.HANDLING UNIT ABOVE.HANDLING UNIT ABOVE.7777 EXISTING 4" HWS/REXISTING 4" HWS/REXISTING 4" HWS/REXISTING 4" HWS/R8888 EXISTING 6" CHWS/REXISTING 6" CHWS/REXISTING 6" CHWS/REXISTING 6" CHWS/R9999 EXISTING OVERHEAD VENTILATION FANEXISTING OVERHEAD VENTILATION FANEXISTING OVERHEAD VENTILATION FANEXISTING OVERHEAD VENTILATION FANTO REMAIN.TO REMAIN.TO REMAIN.TO REMAIN.10101010 RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.RISE 10"Ø DRYER EXHAUST DUCT UP.TRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TODRYER EXHAUST FAN ON ROOF.DRYER EXHAUST FAN ON ROOF.DRYER EXHAUST FAN ON ROOF.DRYER EXHAUST FAN ON ROOF.2 11/05/20 ADD #2
1111111112121212131313131414141415151515161616161717171719191919202020202121212122222222BBBBCCCCC1C1C1C1DDDDEEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLL250GELEC2-DSTAIR264AOFFICE264BOFFICE2-CCHW.2-MHW.250AMAIN GYM111122221111SSTO VAVRTO VAVRTO VAVRTO VAVR----30130130130133333333TO VAVRTO VAVRTO VAVRTO VAVR----3033033033032"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:50 PMMH102.2LEVEL 2AREA 2AMECHANICALREMODELPLAN20054ao^tfkd=klqbp00005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH102.2MH102.2MH102.2MH102.21/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O^=j^fk=dvj=jb`e^kf`^iobjlabi=mi^k1111NOTE# DESCRIPTION1111 REBALANCE EXISTING S.A. DIFFUSER TO 275 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 275 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 275 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 275 CFM.2222 REBALANCE EXISTING S.A. DIFFUSER TO 460 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 460 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 460 CFM.REBALANCE EXISTING S.A. DIFFUSER TO 460 CFM.3333 REPLACE EXISTING SENSOR WITH NEW ANDREPLACE EXISTING SENSOR WITH NEW ANDREPLACE EXISTING SENSOR WITH NEW ANDREPLACE EXISTING SENSOR WITH NEW ANDCONNECT TO ASSOCIATED VAVR. SEE SHEETCONNECT TO ASSOCIATED VAVR. SEE SHEETCONNECT TO ASSOCIATED VAVR. SEE SHEETCONNECT TO ASSOCIATED VAVR. SEE SHEETMH101.3 FOR CONTINUATION.MH101.3 FOR CONTINUATION.MH101.3 FOR CONTINUATION.MH101.3 FOR CONTINUATION.1 10/30/20 ADD #1
10101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323LLLLMMMM261CELEV. EQP.11112222333336"x48"+1"AL36"x48"+1"AL36"x48"+1"AL36"x48"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL1111H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL555555551111111112121212131313131414141415151515161616161717171719191919202020202121212122222222LLLL380SOUND/LIGHT CONTROL44442"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:24:55 PMMH102.3AREA 2BMECHANICALREMODELPLANS20054ao^tfkd=klqbp00005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH102.3MH102.3MH102.3MH102.31/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O_=kloqe=e^ii=jb`e^kf`^iobjlabi=mi^k1111NOTE#DIFFUSERCALLOUT DESCRIPTION1111 R-1R-1R-1R-1 150 CFM, 10"x10" NK, R.A. GRILLE150 CFM, 10"x10" NK, R.A. GRILLE150 CFM, 10"x10" NK, R.A. GRILLE150 CFM, 10"x10" NK, R.A. GRILLE2222 TRANSITION DUCT IN RISE ANDTRANSITION DUCT IN RISE ANDTRANSITION DUCT IN RISE ANDTRANSITION DUCT IN RISE ANDCONNECT TO EXISTING DUCTWORK.CONNECT TO EXISTING DUCTWORK.CONNECT TO EXISTING DUCTWORK.CONNECT TO EXISTING DUCTWORK.3333 DROP DUCT DOWN THROUGH CEILING.DROP DUCT DOWN THROUGH CEILING.DROP DUCT DOWN THROUGH CEILING.DROP DUCT DOWN THROUGH CEILING.PROVIDE SHEETMETAL ANGLE ATPROVIDE SHEETMETAL ANGLE ATPROVIDE SHEETMETAL ANGLE ATPROVIDE SHEETMETAL ANGLE ATCEILING PENETRATION AND SEAL.CEILING PENETRATION AND SEAL.CEILING PENETRATION AND SEAL.CEILING PENETRATION AND SEAL.DUCT TO HANG DOWN PAST CEILINGDUCT TO HANG DOWN PAST CEILINGDUCT TO HANG DOWN PAST CEILINGDUCT TO HANG DOWN PAST CEILINGAPPROX. 3"APPROX. 3"APPROX. 3"APPROX. 3"4444 T-1T-1T-1T-1 22"x22" NK, TRANSFER AIR GRILLE22"x22" NK, TRANSFER AIR GRILLE22"x22" NK, TRANSFER AIR GRILLE22"x22" NK, TRANSFER AIR GRILLE5555 R-3R-3R-3R-3 9200 CFM, 48"x36" NK, R.A. GRILLE.9200 CFM, 48"x36" NK, R.A. GRILLE.9200 CFM, 48"x36" NK, R.A. GRILLE.9200 CFM, 48"x36" NK, R.A. GRILLE.FIELD VERIFY EXACT SIZE.FIELD VERIFY EXACT SIZE.FIELD VERIFY EXACT SIZE.FIELD VERIFY EXACT SIZE.SCALE:SCALE:SCALE:SCALE:MH102.3MH102.3MH102.3MH102.31/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"ibsbi=P=jb`e^kf`^i=objlabi=mi^k222200005555101010101010101020202020
LOCKEREXHAUST 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"Ø12"Ø12"Ø12"Ø16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"Ø12"Ø12"Ø12"Ø16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL20"x16" EXH.20"x16" EXH.20"x16" EXH.20"x16" EXH.207207207207VAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.88888"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.88888"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.88888"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø8888H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø8888H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø8888H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø9999H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø9999H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø9999H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.8"x6"8"x6"8"x6"8"x6"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.8"x3"8"x3"8"x3"8"x3"23232323H.D.H.D.H.D.H.D.8"x3"8"x3"8"x3"8"x3"8"x3"8"x3"8"x3"8"x3"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.8"x3"8"x3"8"x3"8"x3"H.D.H.D.H.D.H.D.8"x3"8"x3"8"x3"8"x3"10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.10"x8"10"x8"10"x8"10"x8"111110"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.1111111110"x8"10"x8"10"x8"10"x8"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.222222228"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.22222-PSTAIR206CLOSET-SWIMMING POOL DECKPART OFPART OFPART OFPART OFADD. ALT. #3ADD. ALT. #3ADD. ALT. #3ADD. ALT. #3207DSTORAGE207ALOCKER RMEMP.MEN'S207LOCKER RMMEN'S STUDENT12"x10" EXH.12"x10" EXH.12"x10" EXH.12"x10" EXH.6"x6"6"x6"6"x6"6"x6"8"x8"8"x8"8"x8"8"x8"H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø17171717H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø14141414H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø18181818H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø18181818H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø14141414191919196"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.161616166"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.151515156"Ø6"Ø6"Ø6"Ø6"Ø6"Ø6"Ø6"Ø13131313H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.141414146"Ø6"Ø6"Ø6"Ø13131313H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø13131313H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø13131313H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø12121212151515156"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.212121218"x3"8"x3"8"x3"8"x3"55558"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.24242424252525251"1"1"1"HWS/RHWS/RHWS/RHWS/R10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL34343434SEE TYPICAL LOCKERSEE TYPICAL LOCKERSEE TYPICAL LOCKERSEE TYPICAL LOCKEREXHAUST CONNECTIONEXHAUST CONNECTIONEXHAUST CONNECTIONEXHAUST CONNECTION5/MH102.45/MH102.45/MH102.45/MH102.4SS777710101010BBBBCCCCC1C1C1C1DDDDEEEE111122227777101010101111111116"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL261A261A261A261AVAVRVAVRVAVRVAVR12"Ø12"Ø12"Ø12"ØH.D.H.D.H.D.H.D.3333H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.6666666616"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL261261261261VAVRVAVRVAVRVAVR12"Ø12"Ø12"Ø12"ØH.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø10101010H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø10101010H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.1111111110"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.111111118"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.2222H.D.H.D.H.D.H.D.10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"8"x6"H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.22222222H.D.H.D.H.D.H.D.10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.10"x8"10"x8"10"x8"10"x8"111111111111261ALAUNDRY RM.257EQP. ISSUE265OFFICE266FAC. OFFICEPART OFPART OFPART OFPART OFADD. ALT. #3ADD. ALT. #3ADD. ALT. #3ADD. ALT. #3261LOCKER RM.STUDENTWOMEN'S261BNURSING261ALOCKER RM.EMPLOYEEWOMEN'S261ESTORAGE261DNURSING6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"H.D.H.D.H.D.H.D.33331010101010"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.20202020222222224444H.D.H.D.H.D.H.D.6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"6"x3"8"x6"8"x6"8"x6"8"x6"6"x6"6"x6"6"x6"6"x6"H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø121212126"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.121212126"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.18181818191919196"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.121212126"Ø6"Ø6"Ø6"Ø10"x8"10"x8"10"x8"10"x8"H.D.H.D.H.D.H.D.44448"x8"8"x8"8"x8"8"x8" 8"x8"8"x8"8"x8"8"x8"4444H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø24242424252525251" 1" 1" 1" HWS/RHWS/RHWS/RHWS/R3434343410"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"ALSSdbkbo^i=klqbpA.A.A.A.HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE HWS & HWR PIPING RUNOUTS TO VAV BOXES ARE 3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.3/4" UNLESS OTHERWISE NOTED.353535353636363635353535353535352"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:06 PMMH102.4LEVEL 2AREA 2CMECHANICALPLANS20054ao^tfkd=klqbp00005555101010101010101020202020NOTE#DIFFUSERCALLOUTDESCRIPTION1111 E-1E-1E-1E-1 215 CFM, 10"x10" NK, EXHAUST AIR215 CFM, 10"x10" NK, EXHAUST AIR215 CFM, 10"x10" NK, EXHAUST AIR215 CFM, 10"x10" NK, EXHAUST AIRGRILLEGRILLEGRILLEGRILLE2222 E-1E-1E-1E-1 75 CFM, 8"x8" NK, EXHAUST AIR75 CFM, 8"x8" NK, EXHAUST AIR75 CFM, 8"x8" NK, EXHAUST AIR75 CFM, 8"x8" NK, EXHAUST AIRGRILLEGRILLEGRILLEGRILLE3333 DROP 6"x3" EXHAUST DUCT DOWNDROP 6"x3" EXHAUST DUCT DOWNDROP 6"x3" EXHAUST DUCT DOWNDROP 6"x3" EXHAUST DUCT DOWNTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKERS 4'-6" A.F.F. BALANCE TO 50LOCKERS 4'-6" A.F.F. BALANCE TO 50LOCKERS 4'-6" A.F.F. BALANCE TO 50LOCKERS 4'-6" A.F.F. BALANCE TO 50CFM.CFM.CFM.CFM.4444 E-1E-1E-1E-1 125 CFM, 8"x8" NK, EXHAUST AIR125 CFM, 8"x8" NK, EXHAUST AIR125 CFM, 8"x8" NK, EXHAUST AIR125 CFM, 8"x8" NK, EXHAUST AIRGRILLEGRILLEGRILLEGRILLE5555 DROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKERS 4'-6" A.F.F. BALANCE TO 90LOCKERS 4'-6" A.F.F. BALANCE TO 90LOCKERS 4'-6" A.F.F. BALANCE TO 90LOCKERS 4'-6" A.F.F. BALANCE TO 90CFM.CFM.CFM.CFM.6666 DROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKERS 4'-6" A.F.F. BALANCE TO 80LOCKERS 4'-6" A.F.F. BALANCE TO 80LOCKERS 4'-6" A.F.F. BALANCE TO 80LOCKERS 4'-6" A.F.F. BALANCE TO 80CFM.CFM.CFM.CFM.7777 DROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKERS 4'-6" A.F.F. BALANCE TO 70LOCKERS 4'-6" A.F.F. BALANCE TO 70LOCKERS 4'-6" A.F.F. BALANCE TO 70LOCKERS 4'-6" A.F.F. BALANCE TO 70CFM.CFM.CFM.CFM.8888 S-2S-2S-2S-2 175 CFM, 8"Ø NK, S.A. DIFFUSER175 CFM, 8"Ø NK, S.A. DIFFUSER175 CFM, 8"Ø NK, S.A. DIFFUSER175 CFM, 8"Ø NK, S.A. DIFFUSER9999 S-2S-2S-2S-2 225 CFM, 10"Ø NK, S.A. DIFFUSER225 CFM, 10"Ø NK, S.A. DIFFUSER225 CFM, 10"Ø NK, S.A. DIFFUSER225 CFM, 10"Ø NK, S.A. DIFFUSER10101010 S-2S-2S-2S-2 215 CFM, 10"Ø NK, S.A. DIFFUSER215 CFM, 10"Ø NK, S.A. DIFFUSER215 CFM, 10"Ø NK, S.A. DIFFUSER215 CFM, 10"Ø NK, S.A. DIFFUSER11111111 S-2S-2S-2S-2 290 CFM, 10"Ø NK, S.A. DIFFUSER290 CFM, 10"Ø NK, S.A. DIFFUSER290 CFM, 10"Ø NK, S.A. DIFFUSER290 CFM, 10"Ø NK, S.A. DIFFUSER12121212 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 50 CFM.PLENUM. BALANCE TO 50 CFM.PLENUM. BALANCE TO 50 CFM.PLENUM. BALANCE TO 50 CFM.13131313 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 75 CFM.PLENUM. BALANCE TO 75 CFM.PLENUM. BALANCE TO 75 CFM.PLENUM. BALANCE TO 75 CFM.14141414 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 70 CFM.PLENUM. BALANCE TO 70 CFM.PLENUM. BALANCE TO 70 CFM.PLENUM. BALANCE TO 70 CFM.15151515 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 60 CFM.PLENUM. BALANCE TO 60 CFM.PLENUM. BALANCE TO 60 CFM.PLENUM. BALANCE TO 60 CFM.16161616 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 45 CFM.PLENUM. BALANCE TO 45 CFM.PLENUM. BALANCE TO 45 CFM.PLENUM. BALANCE TO 45 CFM.17171717 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 35 CFM.PLENUM. BALANCE TO 35 CFM.PLENUM. BALANCE TO 35 CFM.PLENUM. BALANCE TO 35 CFM.18181818 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 65 CFM.PLENUM. BALANCE TO 65 CFM.PLENUM. BALANCE TO 65 CFM.PLENUM. BALANCE TO 65 CFM.19191919 DROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHDROP 6"Ø EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 55 CFM.PLENUM. BALANCE TO 55 CFM.PLENUM. BALANCE TO 55 CFM.PLENUM. BALANCE TO 55 CFM.20202020 DROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 30 CFM.PLENUM. BALANCE TO 30 CFM.PLENUM. BALANCE TO 30 CFM.PLENUM. BALANCE TO 30 CFM.21212121 E-1E-1E-1E-1 170 CFM, 8"x8" NK, EXHAUST AIR170 CFM, 8"x8" NK, EXHAUST AIR170 CFM, 8"x8" NK, EXHAUST AIR170 CFM, 8"x8" NK, EXHAUST AIRGRILLEGRILLEGRILLEGRILLE22222222 DROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHDROP 6"x3" EXHAUST DUCT THROUGHCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERCEILING AND CONNECT TO LOCKERPLENUM. BALANCE TO 20 CFM.PLENUM. BALANCE TO 20 CFM.PLENUM. BALANCE TO 20 CFM.PLENUM. BALANCE TO 20 CFM.23232323 DROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNDROP 8"x3" EXHAUST DUCT DOWNTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOTHROUGH WALL AND CONNECT TOLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKER PLENUM AT CENTER OFLOCKERS 4'-6" A.F.F. BALANCE TO 55LOCKERS 4'-6" A.F.F. BALANCE TO 55LOCKERS 4'-6" A.F.F. BALANCE TO 55LOCKERS 4'-6" A.F.F. BALANCE TO 55CFM.CFM.CFM.CFM.24242424 S-2S-2S-2S-2 100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER100 CFM, 8"Ø NK, S.A. DIFFUSER25252525 R-1R-1R-1R-1 22"x10" NK, R.A. GRILLE WITH SOUND22"x10" NK, R.A. GRILLE WITH SOUND22"x10" NK, R.A. GRILLE WITH SOUND22"x10" NK, R.A. GRILLE WITH SOUNDBOOTBOOTBOOTBOOT26262626 REMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOREMOVE EXISTING PIPING RUNOUT TOEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGEXISTING VAVR BOX, INCLUDINGSUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,SUPPLY AND RETURN PIPING,CONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCECONTROL VALVE, STRAINER, BALANCEVALVE, ETC.VALVE, ETC.VALVE, ETC.VALVE, ETC.27272727 TEMPORARILY CAP FOR NEWTEMPORARILY CAP FOR NEWTEMPORARILY CAP FOR NEWTEMPORARILY CAP FOR NEWCONNECTION.CONNECTION.CONNECTION.CONNECTION.28282828 CAP AT MAIN.CAP AT MAIN.CAP AT MAIN.CAP AT MAIN.29292929 REMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDREMOVE EXISTING VAV BOX ANDASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.30303030 REMOVE EXISTING S.A. GRILLE ANDREMOVE EXISTING S.A. GRILLE ANDREMOVE EXISTING S.A. GRILLE ANDREMOVE EXISTING S.A. GRILLE ANDASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.ASSOCIATED DUCTWORK AS SHOWN.31313131 REMOVE EXISTING EXHAUST GRILLEREMOVE EXISTING EXHAUST GRILLEREMOVE EXISTING EXHAUST GRILLEREMOVE EXISTING EXHAUST GRILLEAND ASSOCIATED DUCTWORK ASAND ASSOCIATED DUCTWORK ASAND ASSOCIATED DUCTWORK ASAND ASSOCIATED DUCTWORK ASSHOWN.SHOWN.SHOWN.SHOWN.32323232 REMOVE PORTION OF EXHAUST DUCTREMOVE PORTION OF EXHAUST DUCTREMOVE PORTION OF EXHAUST DUCTREMOVE PORTION OF EXHAUST DUCTAND DROPS TO LOCKERS.AND DROPS TO LOCKERS.AND DROPS TO LOCKERS.AND DROPS TO LOCKERS.33333333 REMOVE EXHAUST DUCT UP THROUGHREMOVE EXHAUST DUCT UP THROUGHREMOVE EXHAUST DUCT UP THROUGHREMOVE EXHAUST DUCT UP THROUGHROOF AND REMOVE EXHAUST FAN ONROOF AND REMOVE EXHAUST FAN ONROOF AND REMOVE EXHAUST FAN ONROOF AND REMOVE EXHAUST FAN ONROOF. PATCH HOLE IN ROOF. REF.ROOF. PATCH HOLE IN ROOF. REF.ROOF. PATCH HOLE IN ROOF. REF.ROOF. PATCH HOLE IN ROOF. REF.ARCHITECTURAL DRAWINGS.ARCHITECTURAL DRAWINGS.ARCHITECTURAL DRAWINGS.ARCHITECTURAL DRAWINGS.34343434 T-1T-1T-1T-1 12"x12" NK, TRANSFER AIR GRILLE12"x12" NK, TRANSFER AIR GRILLE12"x12" NK, TRANSFER AIR GRILLE12"x12" NK, TRANSFER AIR GRILLE35353535 3"x12" OPENING IN LOCKER EXHAUST3"x12" OPENING IN LOCKER EXHAUST3"x12" OPENING IN LOCKER EXHAUST3"x12" OPENING IN LOCKER EXHAUSTPLENUM. LOCATE CENTER OFPLENUM. LOCATE CENTER OFPLENUM. LOCATE CENTER OFPLENUM. LOCATE CENTER OFOPENING 4'-6" A.F.F.OPENING 4'-6" A.F.F.OPENING 4'-6" A.F.F.OPENING 4'-6" A.F.F.36363636 SEAL DUCT PENETRATION INTOSEAL DUCT PENETRATION INTOSEAL DUCT PENETRATION INTOSEAL DUCT PENETRATION INTOLOCKER EXHAUST PLENUM AIR TIGHT.LOCKER EXHAUST PLENUM AIR TIGHT.LOCKER EXHAUST PLENUM AIR TIGHT.LOCKER EXHAUST PLENUM AIR TIGHT.SCALE:SCALE:SCALE:SCALE:MH102.4MH102.4MH102.4MH102.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O`=EjbkpF=bjmilvbbp=il`hbopjb`e^kf`^i=abjlifqflk=mi^k1111SCALE:SCALE:SCALE:SCALE:MH102.4MH102.4MH102.4MH102.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O`=pqrabkq=il`hbopjb`e^kf`^i=abjlifqflk=mi^k222200005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH102.4MH102.4MH102.4MH102.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O`=EjbkpF=bjmilvbbp=il`hbopjb`e^kf`^i=objlabi=mi^k333300005555101010101010101020202020SCALE:SCALE:SCALE:SCALE:MH102.4MH102.4MH102.4MH102.41/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"^ob^=O`=pqrabkq=il`hbopjb`e^kf`^i=objlabi=mi^k4444000055551010101010101010202020201 10/30/20 ADD #1SCALE:SCALE:SCALE:SCALE:MH102.4MH102.4MH102.4MH102.41/2" = 1'1/2" = 1'1/2" = 1'1/2" = 1'----0"0"0"0"qvmf`^i=il`hbo=bue^rpq=`lkkb`qflk555500002.52.52.52.52.52.52.52.55555SIMILAR FOR OTHER SIMILAR FOR OTHER SIMILAR FOR OTHER SIMILAR FOR OTHER PLENUM CONFIGURATIONSPLENUM CONFIGURATIONSPLENUM CONFIGURATIONSPLENUM CONFIGURATIONS
22222222242424242727272728282828292929292323232321212121jb`e^kf`^i=pb`qflkjb`e^kf`^i=pb`qflkSCALE: 1/4"=1'-0"5010NOTE:ALL DOUBLE WALL DUCT HAS2" ACOUSTICAL INSULATIONWITH PERFORATED METAL LINER.AMH301AHU400AROOFTOP UNIT34"x56"+1"AL34"Ø O.D.DOUBLE WALLRRF400ARETURN / RELIEFFANSRED400ARELIEF AIRDAMPERCC400ACOOLINGCOILHC400AHEATINGCOILFS400AFILTERSECTIONSF400ASUPPLYAIR FANSPIPE HANGER, SEE SPECS2-1/2" HWS/R4" CHWS/RCCV-400AHCV-400A18" MIN. ROOFCURB, SEE DETAIL11/MH502.VFD CONTROL CABINETVFD CONTROL CABINETAHU400BROOFTOP UNITRRF400BRETURN / RELIEFFANSRED400BRELIEF AIRDAMPERCC400BCOOLINGCOILHC400BHEATINGCOILFS400BFILTERSECTIONSF400BSUPPLYAIR FANS2-1/2" HWS/R4" CHWS/RCCV-400BHCV-400B18" MIN. ROOFCURB, SEE DETAIL11/MH502.VFD CONTROL CABINETVFD CONTROL CABINETSCALE: 1/4"=1'-0"5010BMH301R-234"x56"+1"AL48"Ø O.D.DOUBLE WALLR-210"Ø DRYEREXHAUSTDEF2DRYEREXHAUST FAN2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:06 PMMH301MECHANICALSECTIONS20054
BAR SLIPHTRANSVERSE REINFORCING SIZE IS DETERMINED BY DIMENSION OF SIDE TO WHICH ANGLE IS APPLIED.*43-5455-6061-842220201-1/2 x 1-1/2 x 1/8 @60in. 1-1/21-1/21-1/2-------22-31-4219-3013-18242224UP THRU 1224(ALLSIDE,(INCHES)SIDES)FOUROFDIMENSIONLONGESTSHEETMETALGAGEMENDEDRECOM-NONE REQUIRED1 x 1 x 1/8 @60in.1 x 1 x 1/8 @60in.111NONE REQUIRED12424---24222424RECOM-MENDED26GAGEGAGE26MENDEDRECOM-24GAGESPACINGBETWEENREINFORCINGINTERMEDIATEJOINTS &/ORTRANSVERSEMINH, IN.& MAXIMUMANGLE SIZEREINFORCINGLONGITUDINALMINIMUMHEMMEDS SLIPS SLIPPLAIN ALT.SLIPDRIVE222222222222NOT REQUIREDNOT REQUIRED222222POCKET LOCKMENDEDRECOM-POCKET LOCKANGLE REINFORCEDGAGEANGLENOT REQUIREDSIZEREINFORCED222424222424RECOM-MENDEDGAGEMENDEDRECOM-24GAGE24NOT REQUIREDNOT REQUIREDNOT REQUIRED222424REINFORCEDANGLENOT REQUIREDSIZE24REIN-FORCEDBAR SLIPANGLE SLIPHHBAR SLIPANGLESTD. SEAMREINFORCEDSTD. SEAMREINFORCEDANGLESIZEHAT JOINTSTRANSVERSE REINFORCING*HH1-1/2 x 1-1/2 x 1/81-1/2 x 1-1/2 x 1/81-1/2 x 1-1/2 x 1/8NOT REQUIREDNOT REQUIREDNOT REQUIRED1-1/2 x 1-1/2 x 1/8NOT REQUIREDNOT REQUIREDNOT REQUIREDNOT REQUIREDNOT REQUIREDNOT REQUIRED1-1/2 x 1-1/2 x 1/81-1/2 x 1-1/2 x 1/8 @60in.1-1/2 x 1-1/2 x 1/8 @60in.45 DEG. ELBOWTURNINGVANESSINGLEBLADEELBOWS NOT ALLOWED.ALL DUCTS (SUPPLY, RETURNVANES IN SQUARE ELBOW.INSIDE SQUARE, OUTSIDE RADIUSAND EXHAUST) TO HAVE TURNINGSQUARE ELBOW2.1.NOTES:RADIUS ELBOWWBOTH SIDESTURNING VANES15° MAX.ONE SIDE1/2 W30° MAX.CL45° LATERAL TEECONICAL 90° TEEY-BRANCH 90°BRANCH TAKE-OFFDIMENSIONSFABRICATED ELBOWDRADD ONE PIECE FOREACH ADDITIONAL 18°R = 1.5DD = DUCT SIZE0-35° ---- 2 PIECE72-90° ----5 PIECE36-71° ----3 PIECELDMITERED 90° ELBOWREDUCEROFFSET1A MAX.2"1-1/4"A2ATURNINGVANESA1-1/4"D45°D = DUCT SIZEDIMENSIONSL = D/2+1"D2"DUCT SIDE. PROVIDE 1" TRAILINGTO START AND STOP PARALLEL WITHANGLE OF DIRECTION CHANGE. VANESEXHAUST) TO HAVE TURNING VANESALL DUCTS (SUPPLY, RETURN ANDWITH SQUARE TYPE ELBOWS AT ANYEDGE.NOTE:DUCT SIZESEE PLANS FOR12"x12" MINIMUMACCESS DOOR,VAV BOX, SEE PLANS FORSIZING AND LOCATIONON PLANSTRANSITION FROM DISCHARGE ENDAS REQUIRED TO SIZE INDICATEDBRANCH DUCT TO DIFFUSERS,SEE PLANS FOR SIZINGBOX AS REQUIREDREHEAT COIL WHEREINDICATEDTRANSITION TOINLET OF VAVMAIN SUPPLY DUCT1'-0"SEE PLANS FOR SIZEpb`qflk=^J^mi^k=sfbt12"x12" MINIMUMACCESS DOOR,2'-0" MIN. CLEARANCEAA2'-0" MIN. CLEARANCEVAV BOXVAV BOX, SEE PLANSFOR SIZING ANDLOCATIONWALLCEILINGCABLETRAYPIPINGMAINTAIN CLEARANCEBELOW VAV BOXMAINTAIN CLEARANCEIN FRONT OF VAV BOXSUPPLY DUCTVERIFY REQUIRED SLEEVELENGTH PRIOR TO ORDERINGPROVIDE ACCESS DOOR TO FIREDAMPER LINKAGE AND SMOKEDAMPER ACTUATOR LARGE ENOUGHTO SERVICE AND RESET DAMPER.12"x12" MINIMUM.RETURN OR SUPPLYAIR DUCT, SEE PLANSFOR SIZESDAMPER ACTUATORMINIMUM AND MAXIMUM CLEARANCEAS REQUIRED BY MANUFACTURERFIREWALLSLIP CONNECTION (TYP.)RETURN OR SUPPLYAIR DUCTFIRE/SMOKE DAMPER. LOCATEIN WALL AS REQUIRED BYMANUFACTURERSLEEVE GAUGE AS REQUIRED BYMANUFACTURER16 GA. MIN. OR AS REQUIRED BYMANUFACTURER ALL AROUNDYOUNG REGULATORNO. 5020-CCDUCTDAMPERYOUNG REGULATORNO. 270-301-EZADJUSTMENT WRENCHYOUNG REGULATORNO. 030REMOVABLE COVERPLATEPAINT TO MATCH CEILINGCEILINGBRACKET MOUNTEDTO CEILING STRUCTURECABLEMAXIMUM SINGLE DAMPER 12" SQUARE. FOR MULTIBLADE DAMPER, SEE DETAILREGULATOR HARDWARE BASED ON YOUNG OR VENTFABRICSROUND DUCT DAMPER REMOTE REGULATOR INSTALLATION SIMILAR.FOR DAMPERS ABOVE LAY-IN CEILING, DELETE REGULATORHARDWARE MANUFACTURERS.AND USE LOCKING QUADRANT.GENERAL NOTES:4.3.1.2.ANCHOR REGULATORCOUPLINGCOVER PLATETO CEILING SYSTEM3/8" SQUARE "CDS" RODOR RIVET TO BLADESTRAP, TACK WELDBEARING (TYP. OF 2)ACOUSTICAL LINING16 GAUGE PLATECEILING SUPPORT CHANNELCONCEALED REGULATORTOP AND BOTTOMCEILING(WHERE REQUIRED)22 GAUGE DAMPER, 1/4"1-1/4" LONG INSULATION SLEEVECLEARANCESHEET METAL DUCTWORK(12"MIN.*)SINGLE THICKNESS3/4(L)SLEEVE AND ACCESS DOOR.PROVIDE FIRE DAMPER WITHTHROUGH FIRE RATED WALLWHERE SOUND TRAP PASSESACOUSTICALNOTE:OPENINGLINES OF WALLLENGTHSEE SPECIFICATIONSWITH SHEET METAL STRAPSSUPPORT FROM STRUCTUREDUCTWORK, PIPING ETC. FIELDOBSTRUCTION. I.E. JOIST, BEAM,AS REQUIRED TO EXTEND PASTCOORDINATEWIDTHDIMENSION TO BE INCREASEDLL*1" INTERIORLINING, 1LBDENSITYTURNING VANES(TYPICAL)2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:07 PMMH501MECHANICALDETAILS20054SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501ar`q=`lkpqor`qflk=abq^fi1111SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501ob`q^kdri^o=ar`q=cfqqfkdp=abq^fi2222SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501jbafrj=sbil`fqv=ar`q=cfqqfkdpabq^fi3333SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501s^so=_lu=abq^fi4444SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501s^s=_lu=`ib^o^k`b=abq^fi5555SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501cfob=L=pjlhb=a^jmbo=EcKpKaKF=abq^fi6666SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501objlqb=a^jmbo=^agrpqjbkq=abq^fi7777SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501objlqb=a^jmbo=obdri^qlo=abq^fi8888SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501qo^kpcbo=L=obqrok=^fo=plrka=qo^mabq^fi9999
1"kl=mlm=ofsbqp=^iiltbaTO BE TIGHT AGAINST DUCT.HEAD SHEET METAL SCREWS. STRAPSSELF TAPPING CADMIUM PLATED HEXHANGER STRAPSe^kdbo=pfwbp=clo=ob`q^kdri^oar`q=mbo=pj^`k^=es^`=ar`q`lkpqor`qflk=pq^ka^oapkl=mlm=ofsbqp=^iiltbaHANGERSTRAPS`lkpqor`qflk=pq^ka^oapar`q=mbo=pj^`k^=es^`=ar`qe^kdbo=pfwbp=clo=olrkaSELF TAPPING HEX HEAD SHEETMETAL SCREWS. STRAPS TO BETIGHT AGAINST DUCTANGLE IRONROUND/OVAL DUCTANGLE IRONHANGER STRAPSe^kdbo=pfwbp=clo=olrka=L=ls^iar`q=mbo=pj^`k^=es^`=ar`q`lkpqor`qflk=pq^ka^oap(MIRACLE PF96)12" C.C. MAX.METAL FASTENERS:OR GRIP NAILS. GRIP NAILS SHALL BEINSTALLED BY "GRIP NAIL AIR HAMMER" ORBY "AUTOMATIC FASTENER EQUIPMENT".OMARK INSUL-PINS, DURA DYNE FASTENERSNOT MORE THAN 2"FROM EDGE OF LINER2"(TYP.)THE SIDESOF LINER SHALL OVERLAPTOP AND BOTTOM SECTIONWITH 100% ADHESIVEBE ADHERED TO DUCTDUCT LINER. LINER TOGALVANIZED IRON DUCTDUCT LINERALL ENDS OF LINER TO BE COATED WITHADHESIVE (MIRACLE PF96). ENDS OF LINERSHALL BE BUTTED FIRMLY TOGETHERFASTEN WITHUNDER 2" ANDACOUSTICAL(12" MIN.)2 WWSHEET METAL SCREW,RETURN AIR GRILLETYPICAL1/2 WMETAL SKIN22 GA. SHEETLENGTHGRILLE1" INTERIORLINING, 1# PCFDENSITYTURN HANGERSHEET METALSCREW1" WIDE HANGINGSTRAPSHEET METAL DUCTDUCT SECTIONLOCKING QUADRANTSTRAP 1/2" ROD45° DUCT CONNECTIONBLADE WITH V-GROOVEBLADE SECTION1/2" RODBRANCH DUCT OR RUNOUTTO DIFFUSER, SEE PLANSFOR SIZINGRECTANGULAR DUCT, SEEPLANS FOR SIZINGLOCKING QUADRANT(ONE PER BLADE)STRAP, RIVET TO BLADE(TACK WELD RODSECURELY TO BLADE)22 GA. BLADE 1/2"SPRING LOADED ENDTACK WELD OR RIVETTO BLADE (BLADE MUSTCLEAR LINER OR DUCTAPPROX. 1/4" ON ALL SIDES)BLADE MULTIPLESDUCT DEPTHUP TO 12" - 1 BLADEUP TO 20" - 2 BLADESUP TO 30 " - 3 BLADESNOTE:EQUAL CROSS SECTION AREA OFAREA OF AxC SHALL BE EQUALMINIMUM AREA OF AxB SHALLTO 1.5xAREA OF AxB.BRANCH DUCT.CHAND DAMPER WITHLOCKING QUADRANTAPLANS FOR SIZINGRECTANGULAR DUCT, SEEROUND DUCT RUNOUTTO DIFFUSER, SEEPLANS FOR SIZINGB45°BINDING STRAP5/8" SCREW TIGHTENINGFACTORY MADE DUCT WITHWOVEN FIBERGLASS FABRICMASTICMETAL DUCTROUND SHEET2"METAL SCREW (TYP. 3) THROUGHFACTORY DUCT INTO ROUNDFACTORY DUCT IN PLACESHEET METAL DUCT TO HOLDHIGH PRESSURE RATED SHEETIMPREGNATED WITH VINYL ORNEOPRENE CLAMPED IN A CONTINUALHELIX OF ALUMINUM OR COLDROLLED STEEL, 3'-0" MAX. LENGTHFLEXMASTER TYPE 4 ORTHERMAFLEX M-KCFOR SIZINGROUND DUCT, SEE PLANSMADE DUCT. MAX. LENGTH 6'-0".FASTEN WITH MASTIC AND BINDINGHIGH PRESSURE RATED FACTORYSUPPLY DIFFUSER, SEEPLANS FOR SIZINGCEILINGSTRAP. SEE DETAIL THIS SHEET.BINDING STRAPFLASH & COUNTERFLASHAIR DUCTSUPPLY OR RETURNBUILT UP ROOF1/8 AA30°1/4 ABIRDSCREEN,1/2"x1/2" MESHA+1/4AROOF INSULATIONMETAL ROOF DECKCURB INSULATIONROOF DECK WITH 5/8"SECURE CURB TOBOLTSNUMBER AND LOCATION AS5/8"Ø BOLTS, MIN. 2 PER SIDE ORRECOMMENDED BY MANUFACTURERSECURE FLASHING APPROXIMATELYCLOSED CELL NEOPRENE GASKETPREFABRICATED STEEL CURB8" O.C. WITH APPROVED FASTENERSWITH CURBNAILER STRIP FURNISHEDUNIT BASE FRAMEFURNISHED WITH UNIT.CANT STRIPSHEET METALROOFING, SEEARCHITECTURALCOUNTERUNIT CASINGUNIT FRAMEUNIT INSULATIONDRAWINGSFLASHINGDRUM LOUVER45° LOW LOSSWITH ROOF STRUCTURAL SYSTEM.AND ATTACHMENT REQUIREMENTSCOORDINATE SUPPORT LOCATIONSSECTION45°DRUM LOUVEROBDWASHERNUT AND LOCKFASTENER BOOT,LOAD RATEDHORIZONTALREQUIREMENTSPER SMACNAHANGER STRAPNOTE:WITH OBDTAKE-OFFAIR FLOWMIN. 16"MIN. 16"MIN. 16"MIN. 16"CURB HEIGHTCURB HEIGHTCURB HEIGHTCURB HEIGHT2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:07 PMMH502MECHANICALDETAILS20054SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ar`q=pqo^m=e^kdbo=abq^fi1111SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502olrka=ar`q=e^kdbo=abq^fi2222SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ls^i=ar`q=e^kdbo=abq^fi3333SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ar`q=ifkbo=abq^fi4444SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502plrka=qo^m=abq^fi5555SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502_o^k`e=ar`q=^ka=a^jmbo=abq^fi6666SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ar`q=`lkkb`qflk=abq^fi7777SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502c^`qlov=ar`q=abq^fi8888SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ar`q=`lkkb`qflk=ql=afccrpboabq^fi9999SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502dllpbkb`h=abq^fi10101010SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502ollcqlm=bnrfmjbkq=`ro_=abq^fi11111111SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502aorj=ilrsbo=q^hblcc=abq^fi12121212
SSSSCONTROL VALVE SCHEDULESYMBOL VALVE TYPE OPERATOR TYPE GPMPRESSURE DIFF.PSICIRCULATING FLUID DUTY REMARKSCCV-400A 2-WAY ELECTRIC MODULATING 89 3 CHILLED WATER AHU-400A COOLING COILCCV-400B 2-WAY ELECTRIC MODULATING 89 3 CHILLED WATER AHU-400B COOLING COILHCV-400A 3-WAY ELECTRIC MODULATING 38.5 335% PROPYLENE GLYCOL HEATINGWATERAHU-400A HEATING COILBALANCE BYPASSFOR 19 GPM.HCV-400B 3-WAY ELECTRIC MODULATING 38.5 335% PROPYLENE GLYCOL HEATINGWATERAHU-400B HEATING COILBALANCE BYPASSFOR 19 GPM.VHCV-175 2-WAY ELECTRIC MODULATING 0.5 335% PROPYLENE GLYCOL HEATINGWATERVAVR-175 HEATING COILVHCV-178 2-WAY ELECTRIC MODULATING 0.6 335% PROPYLENE GLYCOL HEATINGWATERVAVR-178 HEATING COILVHCV-179A 2-WAY ELECTRIC MODULATING 0.5 335% PROPYLENE GLYCOL HEATINGWATERVAVR-179A HEATING COILVHCV-179B 2-WAY ELECTRIC MODULATING 0.5 335% PROPYLENE GLYCOL HEATINGWATERVAVR-179B HEATING COILVHCV-179C 2-WAY ELECTRIC MODULATING 0.5 335% PROPYLENE GLYCOL HEATINGWATERVAVR-179C HEATING COILVHCV-179D 2-WAY ELECTRIC MODULATING 0.5 335% PROPYLENE GLYCOL HEATINGWATERVAVR-179D HEATING COILVHCV-181 2-WAY ELECTRIC MODULATING 1.3 335% PROPYLENE GLYCOL HEATINGWATERVAVR-181 HEATING COILVHCV-189 2-WAY ELECTRIC MODULATING 1.9 335% PROPYLENE GLYCOL HEATINGWATERVAVR-189 HEATING COILVHCV-189A 2-WAY ELECTRIC MODULATING 1.0 335% PROPYLENE GLYCOL HEATINGWATERVAVR-189A HEATING COILVHCV-205 2-WAY ELECTRIC MODULATING 0.8 335% PROPYLENE GLYCOL HEATINGWATERVAVR-205 HEATING COILVHCV-207 2-WAY ELECTRIC MODULATING 2.9 335% PROPYLENE GLYCOL HEATINGWATERVAVR-207 HEATING COILVHCV-D207 2-WAY ELECTRIC MODULATING 3.1 335% PROPYLENE GLYCOL HEATINGWATERVAVR-D207 HEATING COILVHCV-207A 2-WAY ELECTRIC MODULATING 4.3 335% PROPYLENE GLYCOL HEATINGWATERVAVR-207A HEATING COILVHCV-210A 2-WAY ELECTRIC MODULATING 5.7 335% PROPYLENE GLYCOL HEATINGWATERVAVR-210A HEATING COILVHCV-210B 2-WAY ELECTRIC MODULATING 5.7 335% PROPYLENE GLYCOL HEATINGWATERVAVR-210B HEATING COILVHCV-261 2-WAY ELECTRIC MODULATING 5.3 335% PROPYLENE GLYCOL HEATINGWATERVAVR-261 HEATING COILVHCV-261A 2-WAY ELECTRIC MODULATING 2.2 335% PROPYLENE GLYCOL HEATINGWATERVAVR-261A HEATING COILVHCV-301 2-WAY ELECTRIC MODULATING 1.4 335% PROPYLENE GLYCOL HEATINGWATERVAVR-301 HEATING COILVHCV-303 2-WAY ELECTRIC MODULATING 1.6 335% PROPYLENE GLYCOL HEATINGWATERVAVR-303 HEATING COILSee Section 230900GENERAL NOTES FOR MECHANICAL CONTROLSTYPICAL ATC PANELSENSOR MOUNTING DETAILTYPICAL DAMPER MOTOR DIAGRAMTYPICAL CONTROL VALVE DETAILLOW VOLTAGE TRANSFORMER PANEL LVTPBUILDING HVAC CONTROL SYSTEMS ONE- LINE DIAGRAMVAV COOLING WITH TERMINALREHEAT CONTROL DIAGRAMEXISTINGAHU-300SYSTEM ATCPANELEXISTING BUILDINGAUTOMATION SYSTEMCV-XXPRESSURE SWITCHES, ELECTRIC OPERATED VALVES, ETC. ARE THE RESPONSIBILITY OF DIVISION 23.ATC PANELS, SENSORS, ETC, AS INDICATED ON THE PLANS ALL IN ACCORDANCE WITH DIVISION 26.ANY QUESTION OF RESPONSIBILITY SHALL BE CLARIFIED BY THE GENERAL CONTRACTORTHE CONTROLS CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR CONTROL SYSTEMS CIRCUITS.THE CONTROLS CONTRACTOR SHALL ROUTE ALL CONDUIT FOR MECHANICAL CONTROLS, PULL WIRING REQUIREDFOR MECHANICAL CONTROLS THROUGH THE CONDUITS AND MAKE CONNECTIONS TO MECHANICAL EQUIPMENT,THROUGH THE CONTROL DEVICE AND BACK TO THE JUNCTION BOX.CONTROLS CONTRACTOR SHALL INTERRUPT THE CIRCUIT IN THE MECHANICAL EQUIPMENT JUNCTION BOX, WIRETHE ELECTRICIAN SHALL RUN AND CONNECT ALL WIRING AND DEVICES 120 VOLTS AND ABOVE WHICH POWERAUXILIARY RELAYS, LOW VOLTAGE TRANSFORMERS, CONTROL PANEL SWITCHES AND DEVICES, THERMOSTATS,ALL WIRING SHALL TERMINATE AT LABELED TERMINAL STRIPS.10.9.8.CONTROLS CONTRACTOR (DIV 23).PRODUCTS AND PRACTICES SHALL BE SIMILAR FOR ALL INSTALLATIONS.RESPONSIBILITY OF DIVISION 26.BREAKERS AND DISCONNECTS, AUXILIARY CONTACTS, STANDARD PILOT LIGHTS AND MAGNETIC STARTERS ARE THEGENERAL CONTRACT. OF SPECIFIC CONCERN ARE THE CONTROL SYSTEMS RELATED TO MECHANICAL EQUIPMENT.RESPONSIBILITY FOR THE CONTROL WORK IS DIVIDED BETWEEN THE PROJECT ELECTRICIAN (DIV. 26) AND A SPECIALTYALL ELECTRICAL INSTALLATION, BE IT POWER DISTRIBUTION OR SPECIAL SYSTEMS, IS INCLUDED IN THE SCOPE OF THETHE ELECTRICIAN SHALL PROVIDE ALL POWER TO AND THROUGHOUT THE BUILDING, TO INCLUDE MOTOR CONTROLALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH DIVISION 26 AND TO THE FULLEST EXTENT POSSIBLE,CENTERS, BREAKER PANELS AND ALL OTHER SYSTEMS DESIGNATED TO THE ELECTRICIANS.MOTORS AND OTHER MECHANICAL DEVICES. WHERE CONTROL DEVICES ARE LOCATED IN POWER CIRCUIT, THE7.6.5.4.3.2.1.CONTACTTRANSFORMERRCR120/60/1 POWERFUSESURGEOUTLETSUPPRESSORON/OFFSWITCHHNHCONTROLLERS,DIRECT DIGITALFOR QUANTITYFIRE ALARMSEE DRAWINGSLIGHTPILOTDDCR CDDCINDDCDDCDDCDDCOUTCTQUANTITY AS REQUIREDCOMMUNICATIONS CABLINGSCALE NONE:BY DIV. 26FLOORUP WITH LIGHT SWITCHSENSOR SHALL LINECONCRETE BLOCK OR STUD WALLSTUD SPACE FIELD COORDINATE WITHCONCRETE WALL OR CONCEALED WITHINCONTROL CONDUIT EMBEDDED WITHINELBOWRADIUS ELBOWNOMINAL 2"x4"x2Ð" DEEPROOM SENSOR OR SWITCH48"„J-BOXNOTE:WALL CONSTRUCTIONSCALE NONE:90 SHORT2 POSITION ORDAMPER MOTORDMCONTROL SIGNALFROM DDC PANELMODULATING AS SHOWNSCALE NONE:FROM DDC PANELCONTROL SIGNALCONTROL VALVE2 OR 3-WAY AS SHOWN2 POSITION OR MODULATING AS SHOWNSCALE: NONE120/60/1 POWERTRUNKCOMMUNICATIONDDC CONTROLLERCTHRFIRE ALARM CONTACTTRANSFORMER,QUANTITY ASREQUIREDBY DIV. 26NSCALE NONE:SCALE NONE:LEVEL 2ROOF LEVELBY DIV. 26120V POWER(TYP)LEVEL 1CONTROLLERVAVRCONTROLLERVAVREXTEND TO ADD.CONTROLLERS ASREQUIREDSCALE NONE:24 VOLT WIRINGTO TRANSFORMERIN LVTPWALL SENSORCONTROLLER(TYPICAL)DDCCONTROL VALVE HWS HWRTEMPERATUREVELOCITY SENSORTEMPERATURE/MAIN COMMUNICATION TRUNKVSDMCTDAMPER MOTORAIR SENSORDISCHARGEAI AIAI AOAOSEE SCHEDULE.2-WAYDUAL COMMUNICATIONFOR LOCATIONDUAL THERMISTOR WALLSENSOR, SEE DRAWINGSDORSMART IIDVAVRCONTROLLERRS-485 BACNETCOMMUNICATION TRUNKLOW VOLTAGE CONTROLWIRING FROM LVTP, TYP.AHU-400A SYSTEM ATC PANELAHU-400B SYSTEM ATC PANELRS-485 BACNETCOMMUNICATIONTRUNKEXTEND TO EXISTING BUILDINGAUTOMATION SYSTEMVHCV-EXTEND TO EXISTING BUILDINGAUTOMATION SYSTEM CURRENTLYEXTENDED TO AHU-3002"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:08 PMMI601MECHANICALCONTROLDIAGRAMS200541 10/30/20 ADD #1
^fo=e^kaifkd=pvpqbj=^erJQMM^=`lkqoli=af^do^j^fo=e^kaifkd=pvpqbj=^erJQMM^pb`qflk=^J^R GR RR GR RFREQUENCY INPUT FROM SF-400A CONTROLLER SCP-400AAFAULT ALARM FROM SF-400A CONTROLLER SCP-400AACC-400A CHILLED WATER RETURN TEMPERATUREAHU-400A SUPPLY AIR TEMPERATUREAHU-400A MIXED AIR TEMPERATUREAID10AIAIDIDIDITRANSFORMERIN ATCAIAIDI24 VOLTAID4AOOUTPUT TO SF-400A CONTROLLER SCP-400AAD5D6MAIN COMMUNICATIONSTART/STOP SF-400A CONTROLLER SCP-400AATRUNK CABLEDOD1AOAOD3D2CTMODULATE HEATING WATER VALVE HCV-400AMODULATE CHILLED WATER VALVE CCV-400AMOUNTED INSIDE UNIT CONTROL PANELDIRECT DIGITAL CONTROLLER(S)QUANTITY AS REQUIRED--AI AODO-- SPARE DIGITAL OUTPUT (2 SUCH)SPARE ANALOG OUTPUTSPARE DIGITAL INPUT (3 SUCH)SPARE ANALOG INPUT (2 SUCH)AOAORRF-400A INLET LOW DUCT STATIC PRESSURE 1AHU-400A CO LEVELAHU-400A RETURN AIR TEMPERATUREMODULATE RETURN AIR DAMPER RAD-400AMODULATE OUTSIDE AIR DAMPER OAD-400AD11D12AIAIAHU-400A VOC LEVELD13AISCALE: NONED14D15D16D172SF-400A FAN NO. 1 STATUSSF-400A FAN NO. 2 STATUSDID21D22DID20D19D18DIOUTPUT TO RRF-400A CONTROLLER SCP-400ABSTART/STOP RRF-400A CONTROLLER SCP-400ABDOD7AOAOD9D8MODULATE RELIEF AIR DAMPER RED-400AEAST FIELD HOUSE SPACE TEMPERATUREAIDIDIVFD ALARMCONTACT CLOSURERSUPPLY FAN VFD ENABLESSPEEDRSEE DIV. 26208/60/3POWERRSMOKE DETECTORSHANDLING SYSTEM AND BUILDING ZONESMOKE DETECTORS SERVING THE AIRPANEL BASED ON SIGNAL FROM DUCTFIRE ALARM FROM BUILDING FIRE ALARMDISCONNECTCONTACTSTART/STOPRELAYSINTERLOCKRELAYSSAFETYSR4A-2FED THROUGH FAN WALLAND SPEED OUTPUTS FROM/TOSUPPLY FAN VFD'S (TYP. OF 6)SPEED AND ALARM STATUS INPUTSCONTROLLER (TYP. OF 6)D7D8D20D21208/60/3 POWER TO VFDSSEE DIVISION 26(TYPICAL OF 6)HANDOFFAUTOPOWERON ENABLEVFDEXTERNALFAULTVFDFAULTRETURN/RELIEF FAN VFD'S(TYP. OF 6)FAN WALL CONTROLLERFAN VFD STATUS TOFAN WALL CONTROLLERSPEED CONTROL FROMCONTACT CLOSURERRRF400AMOTORS (TYP. OF 6)SEE DIV. 26208/60/3POWERDISCONNECTRCONTACTSTART/STOPVFD ALARM TO FANWALL CONTROLLERRETURN/RELIEF FAN WALLSR-4A SAFETIES CIRCUITSRSAFETIES RELAY4ALOW DUCT STATIC 1FREEZE STATSR4A-1 SR4A-3D30VFD ALARMCONTACT CLOSURERSPEEDRSEE DIV. 26208/60/3POWERRSMOKE DETECTORSHANDLING SYSTEM AND BUILDING ZONESMOKE DETECTORS SERVING THE AIRPANEL BASED ON SIGNAL FROM DUCTFIRE ALARM FROM BUILDING FIRE ALARMDISCONNECTCONTACTSTART/STOPSUPPLY FAN WALL SF-400A CONTROLLER SCP-400AARELAYSINTERLOCKRELAYSSAFETYSR4A-1D1D2D1D2HANDOFFAUTOPOWERON ENABLEVFDEXTERNALFAULTVFDFAULTSUPPLY FAN VFD'S(TYP. OF 6)FAN WALL CONTROLLERFAN VFD STATUS TOFAN WALL CONTROLLERSPEED CONTROL FROMCONTACT CLOSURERSF400ASEE DIV. 26208/60/3POWERDISCONNECTRCONTACTSTART/STOPVFD ALARM TO FANWALL CONTROLLERCHWRCHWSSD3D3D1C.S.D19(TYP. OF 3)OUTSIDERED400AFS400ACC400ASF400ALDSD8D18SR4A-2LOW DUCT STATIC 2HIGH DUCT STATICRELAY CIRCUITSUPPLY FAN WALLMOTORS (TYP. OF 6)SPEED AND ALARM STATUS INPUTSAND SPEED OUTPUTS FROM/TORETURN/RELIEF FAN VFD'S (TYP. OF 6)RETURN/RELIEF FAN VFDENABLES FED THROUGH FANWALL CONTROLLER (TYP. OF 6)208/60/3 POWER TO VFDSSEE DIVISION 26 (TYP. OF 6)EAST FIELD HOUSES D29SPACE TEMPERATURED28INSIDEOUTSIDEDWYER 602-2EAST FIELD HOUSE SPACE DIFFERENTIAL PRESSURELOCATE AS DIRECTED IN FIELDBY MECHANICAL ENGINEERNOTE:WIRING BETWEEN RESPECTIVE FAN WALLCONTROLLER AND RELATED SUPPLY FAN VFDS ISFACTORY WIRED.EAST FIELD HOUSE SPACE STATICSR 4A-3 STATUSFREQUENCY INPUT FROM RRF-400A CONTROLLER SCP-400ABFAULT ALARM FROM RRF-400A CONTROLLER SCP-400ABREF-400A FAN NO.1 STATUS C.S.REF-400A FAN NO.2 STATUS C.S.DPD13FZDPD12HDSD6LDSD7HC400ARRF400AAACCV-400ASD5DMD5RAD400AD4D5D6D1D3D2D7D9D8D24DIDID25D26DIDID27DID28D29D30DIAIAID23RRF-400A OUTLET HIGH DUCT STATIC PRESSURESF-400A LOW DUCT STATIC PRESSURE 2RRF-400A DISCHARGE PLENUM D.P.FILTER FS-400A DIFFERENTIAL PRESSURESF-400A FAN NO. 3 STATUSSF-400A FAN NO. 4 STATUSSF-400A FAN NO. 5 STATUSSF-400A FAN NO. 6 STATUSDIDIDIDIREF-400A FAN NO.3 STATUS C.S.REF-400A FAN NO.4 STATUS C.S.REF-400A FAN NO.5 STATUS C.S.REF-400A FAN NO.6 STATUS C.S.RETURN/RELIEF FAN WALL RRF-400ACONTROLLER SCP-400ABDMD9HWRHWSD4HCV-400AD17D1C.S.D16(TYP. OF 3)D15D14SD5D7C.S.D24(TYP. OF 3)D23D22D7C.S.D27(TYP. OF 3)D26D25RAOAD400AAIR DAMPERRETURNAIR DAMPERRELIEFAIR DAMPERRETURN/RELIEFFAN WALLFILTERSECTIONHEATINGCOILCOOLINGCOILSUPPLYFAN WALLAHU-400A OUTSIDE AIRFLOW VOLUMEAID31DMD6AFMD31AFM400AAIR FLOWMETERSAAQD10 D11SDSD4SD9SD2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:08 PMMI602MECHANICALCONTROLDIAGRAMS20054
^fo=e^kaifkd=pvpqbj=^erJQMM_=`lkqoli=af^do^j^fo=e^kaifkd=pvpqbj=^erJQMM^pb`qflk=^J^aovbo=bue^rpq=c^k=`lkqoli=af^do^jR GR RR GR RFREQUENCY INPUT FROM SF-400B CONTROLLER SCP-400BAFAULT ALARM FROM SF-400B CONTROLLER SCP-400BACC-400B CHILLED WATER RETURN TEMPERATUREAHU-400B SUPPLY AIR TEMPERATUREAHU-400B MIXED AIR TEMPERATUREAIE10AIAIDIDIDITRANSFORMERIN ATCAIAIDI24 VOLTAIAOOUTPUT TO SF-400B CONTROLLER SCP-400BAMAIN COMMUNICATIONSTART/STOP SF-400B CONTROLLER SCP-400BATRUNK CABLEDOAOAOCTMODULATE HEATING WATER VALVE HCV-400BMODULATE CHILLED WATER VALVE CCV-400BMOUNTED INSIDE UNIT CONTROL PANELDIRECT DIGITAL CONTROLLER(S)QUANTITY AS REQUIRED--AI AODO-- SPARE DIGITAL OUTPUT (2 SUCH)SPARE ANALOG OUTPUTSPARE DIGITAL INPUT (3 SUCH)SPARE ANALOG INPUT (2 SUCH)AOAORRF-400B INLET LOW DUCT STATIC PRESSURE 1AHU-400B CO LEVELAHU-400B RETURN AIR TEMPERATUREMODULATE RETURN AIR DAMPER RAD-400BMODULATE OUTSIDE AIR DAMPER OAD-400BE11E12AIAIAHU-400B VOC LEVELE13AISCALE: NONEE14E15E16D172SF-400B FAN NO. 1 STATUSSF-400B FAN NO. 2 STATUSDIE21E22DIE20E19E18DIOUTPUT TO RRF-400B CONTROLLER SCP-400BBSTART/STOP RRF-400B CONTROLLER SCP-400BBDOAOAOMODULATE RELIEF AIR DAMPER RED-400BWEST FIELD HOUSE SPACE TEMPERATUREAIDIDIVFD ALARMCONTACT CLOSURERSUPPLY FAN VFD ENABLESSPEEDRSEE DIV. 26208/60/3POWERRSMOKE DETECTORSHANDLING SYSTEM AND BUILDING ZONESMOKE DETECTORS SERVING THE AIRPANEL BASED ON SIGNAL FROM DUCTFIRE ALARM FROM BUILDING FIRE ALARMDISCONNECTCONTACTSTART/STOPRELAYSINTERLOCKRELAYSSAFETYSR4B-2FED THROUGH FAN WALLAND SPEED OUTPUTS FROM/TOSUPPLY FAN VFD'S (TYP. OF 6)SPEED AND ALARM STATUS INPUTSCONTROLLER (TYP. OF 6)E7E8E20E21208/60/3 POWER TO VFDSSEE DIVISION 26(TYPICAL OF 6)HANDOFFAUTOPOWERON ENABLEVFDEXTERNALFAULTVFDFAULTRETURN/RELIEF FAN VFD'S(TYP. OF 6)FAN WALL CONTROLLERFAN VFD STATUS TOFAN WALL CONTROLLERSPEED CONTROL FROMCONTACT CLOSURERRRF400BMOTORS (TYP. OF 6)SEE DIV. 26208/60/3POWERDISCONNECTRCONTACTSTART/STOPVFD ALARM TO FANWALL CONTROLLERRETURN/RELIEF FAN WALLSR-4B SAFETIES CIRCUITSRSAFETIES RELAY4BLOW DUCT STATIC 1FREEZE STATSR4B-1 SR4B-3E30VFD ALARMCONTACT CLOSURERSPEEDRSEE DIV. 26208/60/3POWERRSMOKE DETECTORSHANDLING SYSTEM AND BUILDING ZONESMOKE DETECTORS SERVING THE AIRPANEL BASED ON SIGNAL FROM DUCTFIRE ALARM FROM BUILDING FIRE ALARMDISCONNECTCONTACTSTART/STOPSUPPLY FAN WALL SF-400B CONTROLLER SCP-400BARELAYSINTERLOCKRELAYSSAFETYSR4B-1E1E2E1E2HANDOFFAUTOPOWERON ENABLEVFDEXTERNALFAULTVFDFAULTSUPPLY FAN VFD'S(TYP. OF 6)FAN WALL CONTROLLERFAN VFD STATUS TOFAN WALL CONTROLLERSPEED CONTROL FROMCONTACT CLOSURERSF400BSEE DIV. 26208/60/3POWERDISCONNECTRCONTACTSTART/STOPVFD ALARM TO FANWALL CONTROLLERCHWRCHWSSE3E3E1C.S.E17(TYP. OF 3)DME6RED400BRELIEFAIR DAMPERFS400BFILTERSECTIONCC400BCOOLINGCOILSF400BSUPPLY AIRFAN WALLLDSE8E18SR4B-2LOW DUCT STATIC 2HIGH DUCT STATICRELAY CIRCUITSUPPLY FAN WALLMOTORS (TYP. OF 6)208/60/3 POWER TO VFDSSEE DIVISION 26 (TYP. OF 6)RETURN/RELIEF FAN VFDENABLES FED THROUGH FANWALL CONTROLLER (TYP. OF 6)SPEED AND ALARM STATUS INPUTSAND SPEED OUTPUTS FROM/TORETURN/RELIEF FAN VFD'S (TYP. OF 6)WEST FIELD HOUSES E29SPACE TEMPERATUREE28INSIDEOUTSIDEDWYER 602-2WEST FIELD HOUSE SPACE DIFFERENTIAL PRESSURELOCATE AS DIRECTED IN FIELDBY MECHANICAL ENGINEERNOTE:WIRING BETWEEN RESPECTIVE FAN WALLCONTROLLER AND RELATED SUPPLY FAN VFDS ISFACTORY WIRED.WEST FIELD HOUSE SPACE STATICSR 4B-3 STATUSFREQUENCY INPUT FROM RRF-400B CONTROLLER SCP-400BBFAULT ALARM FROM RRF-400B CONTROLLER SCP-400BBREF-400B FAN NO.1 STATUS C.S.REF-400B FAN NO.2 STATUS C.S.DPE13FZDPE12HDSE6LDSE7HC400BHEATINGCOILRRF400BRETURN/RELIEFAIR FAN WALLAACCV-400BSE5DME5RAD400BRETURNAIR DAMPERE4E5E6E1E3E2E7E9E8E24DIDIE25E26DIDIE27DIE28E29E30DIAIAIE23RRF-400B OUTLET HIGH DUCT STATIC PRESSURESF-400B LOW DUCT STATIC PRESSURE 2RRF-400B DISCHARGE PLENUM D.P.FILTER FS-400B DIFFERENTIAL PRESSURESF-400B FAN NO. 3 STATUSSF-400B FAN NO. 4 STATUSSF-400B FAN NO. 5 STATUSSF-400B FAN NO. 6 STATUSDIDIDIDIREF-400B FAN NO.3 STATUS C.S.REF-400B FAN NO.4 STATUS C.S.REF-400B FAN NO.5 STATUS C.S.REF-400B FAN NO.6 STATUS C.S.RETURN/RELIEF FAN WALL RRF-400BCONTROLLER SCP-400BBDME9HWRHWSE4HCV-400BE19E1C.S.E14(TYP. OF 3)E15 E16SE4E7C.S.E22(TYP. OF 3)E23 E24E7C.S.E25(TYP. OF 3)E26 E27E4E5E6E1E3E2E7E9E8AHU-400B OUTSIDE AIRFLOW VOLUMEAIE31OUTSIDEOAD400BAIR DAMPERAFME31AFM400BAIR FLOWMETERRASAAQE10E7SDSE4SE9SDDRYER NO. 1 STATUS C.S.E32DIDRYER NO. 2 STATUS C.S.DIE33DRYER NO. 1 DUCT PRESSUREE34AIDRYER NO. 2 DUCT PRESSUREAIE35DEF-1 STATUS C.S.E36DIDEF-2 STATUS C.S.DIE37START / STOP DEF-1DODOSTART / STOP DEF-2E11E10SCALE: NONEDRYER NO. 2C.S.E33POWER FEEDPE35C.S.E37SEE DIV. 26120/60/1POWERRE11DEF2DRYER NO. 2C.S.E32POWER FEEDPE34C.S.E36SEE DIV. 26120/60/1POWERRE10DEF12"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:08 PMMI603MECHANICALCONTROLDIAGRAMS20054
INSTALL VALVES AS CLOSE TO COIL AS POSSIBLESHALL BE INSTALLED WITHIN 2'-0" OF VALVENOTES:VALVES2.1.BCOPPER PIPECOPPER TEE W/ THREADEDINSERT & P/T PLUG, (TYP.)ASUPPLY WATER TO BECONNECTED TO AIRLEAVING SIDE OF COILRETURN WATER TO BEENTERING SIDE OF COILCONNECTED TO AIRVENT HEADER1/2" BALL VALVE FOR EACHMANUAL AIR VENT, PROVIDEUNION (TYPICAL)VALVE WITH UNION ENDS2-WAY MODULATING CONTROLA(REFRIGERATION FLARE CONN.AT RATED FLOWVENTURI FOR 20" TO 50" W.G. ƒPWILL NOT BE ACCEPTED). SELECTVENTURI W/ SCHRADER VALVESW/ MEMORY STOP & INDICATOR,FLOWSET ACCUSETTER VALVEHOSE END & CAP1/2" BALL VALVE WITHBALL VALVE (TYPICAL)THREADED TO SWEAT CONN.(TYPICAL)BCOPPER PIPEAIR FLOWHWSMIN. 5 PIPE DIAMETERSREDUCERHWRTHREADED TO SWEAT CONN.COPPER TEE W/ THREADED3-WAY MODULATING CONTROLSHALL BE INSTALLED WITHIN 2'-0" OF VALVEINSTALL VALVES AS CLOSE TO COIL AS POSSIBLELEAVING SIDE OF COILSUPPLY WATER TO BECONNECTED TO AIRNOTES:VALVES1.2.B C&VALVE WITH UNION ENDS1/2" BALL VALVE FOR EACHMANUAL AIR VENT, PROVIDERETURN WATER TO BEENTERING SIDE OF COILVENT HEADERCONNECTED TO AIRUNION (TYPICAL)(TYPICAL)INSERT & P/T PLUG, (TYP.)COPPER PIPEHOSE END & CAP1/2" BALL VALVE WITHBALL VALVE (TYPICAL)COPPER PIPEBAHWSCOPPER PIPEINDICATORMEMORY STOP ANDBALL VALVE WITHCAIR FLOWW/ MEMORY STOP & INDICATOR,AT RATED FLOW(REFRIGERATION FLARE CONN.VENTURI W/ SCHRADER VALVESFLOWSET ACCUSETTER VALVEMIN. 5 PIPE DIAMETERSAHWRREFER TO DRAWING MI601 FOR CONTROL VALVE SCHEDULE.3.SYSTEMSIDEEQUIPMENTSIDEREDUCER, TYPICALBOTH SIDESUNIONMETER CONNECTIONPOINTSCIRCUIT BALANCEVALVEWALLS, USE ASG ACOUSTICAL SEALANT.FOR PENETRATIONS THROUGH SOUNDNOTE:STANDARD WEIGHT STEEL PIPESLEEVE OF SIZE TO PASS PIPEFINISHED ESCUTCHEON PLATEFLUSH AGAINST WALL AND OFSIZE TO COMPLETELY COVEROPENINGFINISHED WALL SURFACEPIPING EXPOSED TO VIEWCONCEALED PIPINGTERMINATE SLEEVE FLUSH WITHFINISHED WALL SURFACESSEAL OR CAULK SLEEVES THRUFIRE WALLS IN A SMOKE TIGHTMANNERPIPE AND INSULATION TO BECENTERED IN SLEEVE-DO NOTSUPPORT PIPE FROM SLEEVEINTERIOR WALLS~~~MAPLE OR CALCIUMINSULATIONPIPEDOUBLE NUT HANGERROD. TYPICAL"UNISTRUT" 1-5/8"CONCRETETO PIPE TRAPEZE OR SPLITSTRUCTURE TYPECONCRETERING HANGER, EQUIP, ORFASTEN CHANNEL2-HILTI DS POWER ACUATED2-1/2" DIA. HILTI KWIK BOLT IIFASTENERS W/ 3/4" PENETRATIONUNISTRUT 1-5/8" CHANNEL FOR LOADING UP TO2000 LBS. USE P-1001. MIN. LENGTH IS 8"700LBS. USE P-1000 FOR LOADING UP TOUP TO 400 LBS.400-4000 LBS.FASTENER REQUIREMENTSOVAL DUCTWORKLOADINGSTRUCTURECONCRETEFASTENERSEE SCHEDULEW/ 3-1/2" EMBED.TO STRUCTURE12" LONG SHEETMETAL PROTECTIONSILICATE SADDLE,1" AND SMALLERLOADING IS NOT EXCEEDED. SUPPORT FROM STRUCTURE PANEL POINTS.FOR TRAPEZE HANGERS SHALL NOT EXCEED THE TOTAL LOADING INDICATED.IF SMALLER ROD SIZE IS USED, DECREASE MAXIMUN SPACING SO THAT TOTALHANGERS SIZES AND SPACING ARE FOR SINGLE PIPES. HANGER ROD LOADINGNOTE:14"5" - 8"10" - 12"1-1/4" - 2"2-1/2" - 4"PIPE SIZESLEEVEWEIGHT/FT. TOTAL16202081012100/2000126/252250/8002.5/2020/2406/60TRAPEZE HANGERMAX. SPACINGPIPE LOADUP TO 2000 LBS. USEP-1000, FOR LOADINGUP TO 700 LBS. USECHANNEL-FOR LOADINGP-1001.7/8"7/8"3/8"3/8"5/8"7/8"SPLIT RING HANGERROD SIZECINCH ANCHORSTHRU-BOLTCINCH ANCHORSANGLEADJUSTABLEPIPE STANDRODSTEEL PLATEBLOCK WALLWELDED STEELWALL BRACKETU-BOLTSTEEL STRAPTURNBUCKLEEYE BOLTSOR BEAM/TRUSSU-BOLTSWALL BRACKETSTEEL OFFSETEYE BOLTPIPE CLAMPTURNBUCKLERODCONNECTIONINSERTSCLAMPSI-BEAMANGLEOR BEAM/TRUSSCONNECTIONRODU-BOLTSINSERTSNOTE:WHERE PIPES ARE INSULATED, THE INSULATIONIS TO PASS THROUGH THE CLAMP WITH EITHERCALCIUM SILICATE BLOCKERS OR INSULATIONSHIELDS AS REQUIRED.2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:09 PMMP501MECHANICALPIPINGDETAILS20054SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501OJt^v=eb^qfkd=`lfi=mfmfkdp`ebj^qf`1111SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501PJt^v=eb^qfkd=`lfi=mfmfkdp`ebj^qf`2222SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501`fo`rfq=_^i^k`fkd=s^isb=abq^fi3333SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501mfmb=mbkbqo^qfkd=abq^fi4444SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501mfmb=e^kdbo=abq^fi5555SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501qvmf`^i=mfmb=prmmloqp=abq^fi6666
EXISTING BUILTUP FAN SYSTEMEXISTING BUILTUP FAN SYSTEM70 GPM70 GPM70 GPM70 GPM70 GPM70 GPMSSSSSSSSSSSSSSSSUNDER GROUND FROM(E) 8" CHWSTANK(E) EXPANSION(E) 8" CHWR(E) AIR ELIMINATOR(E) 6" CHWS(E) 6" CHWS(E) COOLING COIL(E) 3"(E) 8" CHWREXISTINGBTU METERBY DIV. 1600120/60/1(E) COOLING COIL6"8"(E) CHILLED WATER PIPINGCENTRAL ENERGY FACILITYVIA I-CENTER(E) 8" CHWS(E) 6" CHWR(E) 1"(E) 1"(E) 6"(E) 6"(E) 4"(E) 3"210 GPM210 GPM3"90.5 GPM90.5 GPM4"4"3"90.5 GPM90.5 GPM4"4"(E) 8" CHWS(E) 4" CHWR(E) 6" CHWR(E) 6" CHWS(E) 6" CHWS(E) 6" CHWR2-1/2"43 GPM2-1/2"(E) 6"(E) 6" CHWS/R(E) COOLING COILEXISTING PACKAGED AIR HANDLING UNIT AHU-200(E) COOLING COILEXISTING PACKAGED AIR HANDLING UNIT AHU-100(E) COOLING COILEXISTING PACKAGED AIR HANDLING UNIT AHU-3004" CHWR4" CHWS(E) 4" CHWS/R TOEXISTING AIRHANDLER ON LOWERLEVEL (56 GPM)4" CHWR4" CHWS2-1/2"44.5 GPM44.5 GPM4"CC400BCOOLING COIL89 GPMAHU400BPACKAGED AIRHANDLING UNIT4"CCV-400BBALANCE AT 89 GPM2-1/2"44.5 GPM44.5 GPM4"CC400ACOOLING COIL89 GPMAHU400APACKAGED AIRHANDLING UNIT4"CCV-400ABALANCE AT 89 GPM6" CHWR6" CHWS(ROOFTOP)(ROOFTOP)CORE DRILL, SLEEVE ANDSEAL ROOF STRUCTURE.COORDINATE WITH GENERALCONTRACTOR FOR ROOFWORK.CORE DRILL, SLEEVE ANDSEAL ROOF STRUCTURE.COORDINATE WITH GENERALCONTRACTOR FOR ROOFWORK.GENERAL NOTE:SEE MI6xx SHEETS FOR CONTROL INTERFACE2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:09 PMMP601CHILLEDWATERFLOWDIAGRAM20054SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP601MP601MP601MP601`efiiba=t^qbo=cilt=af^do^j1111
63 GPM47 GPM23.5 GPM23.5 GPM(E) HEATING COIL(E)2-1/2"EXISTING BUILTUP FAN SYSTEMEXISTING BUILTUP FAN SYSTEM(E)PIPING ANDVALVES(E)COIL CONTROLVALVE(E)4"HWS(E)4"HWR(E)PRESSURECONTROL VALVE(E)HEATING WATERCIRCULATING PUMPS S20MPP47 GPM(E) HEATING COIL23.5 GPM23.5 GPM(E)2-1/2"(E)3"(E)3"(E)4"(E)4"(E)4"(E)4"(E)4"(E)4"(E)6"HWS(E)6"HWR3"3"3"(E)4"HWS(E)4"HWR(E)6"HWS(E)6"HWR(E)4"HWS(E)4"HWR(E)4"HWS(E)4"HWR18.0 GPM(E) 2"(E) 2"(E) 1"(E) 1"(E) HEATING COIL(E)COIL CONTROLVALVEEXISTING PACKAGED AIR HANDLING UNIT AHU-100(E) 4"1" HWS/R TO CABINET HEATERIN HANDBALL STAIRWAYEXISTING BUILTUP FAN SYSTEM AHU-300(E) HEATING COIL(E)4"HWS(E)4"HWRAHU400BHC400BHEATING COILSET AT 39.0 GPM2-1/2" HWR2-1/2" HWSHCV-400B38.5 GPMPACKAGED AIRHANDLING UNIT(ROOFTOP)19.25 GPM2-1/2"19.25 GPM2"AHU400AHC400AHEATING COILSET AT 39.0 GPMHCV-400A38.5 GPMPACKAGED AIRHANDLING UNIT(ROOFTOP)19.25 GPM2-1/2"19.25 GPM2"2-1/2"2-1/2"4" HWR4" HWSEXISTING HEATING WATER PIPINGRUNS ACROSS MAIN GYM INCEILING SPACECORD DRILL, SLEEVE ANDSEAL ROOF STRUCTURE.COORDINATE WITHGENERAL CONTRACTORFOR ROOF WORK.CORD DRILL, SLEEVE ANDSEAL ROOF STRUCTURE.COORDINATE WITHGENERAL CONTRACTORFOR ROOF WORK.GENERAL NOTE:SEE MI6xx SHEETS FOR CONTROL INTERFACE2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.comwww.ffkr.comwww.ffkr.comwww.ffkr.com05/16/2016 JWS PROJECT NUMBER11/30/2020 1:25:09 PMMP602HEATINGWATERFLOWDIAGRAM20054SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP602MP602MP602MP602eb^qfkd=t^qbo=cilt=af^do^j1111
_^`hcilt=mobsbkqbo=p`ebaribt^qbo=e^jjbo=^oobpqbo=p`ebaribWHA4.5.6.3.2.1.GVTRCOWCORDFCOFSFDNICCWV(E)mirj_fkd=^__obsf^qflkpqebojlpq^qf`=jfufkd=s^isbmirj_fkd=cfuqrob=p`ebaribmirj_fkd=pvj_li=ibdbkadbkbo^i=mirj_fkd=klqbpDIRECT WASTEDESCRIPTIONWALL CLEAN OUTSOIL / WASTECLEAN OUTDOMESTIC COLD WATERDOMESTIC HOT WATERDESCRIPTIONVENT THROUGH ROOFVTRDHWSYMBOLDCWCOSYMBOLWCOVWVENTDW10(PSI)DIFFERENTIALPRESSUREALLOWABLEMANUFACTURERAND MODEL NO.SYMBOLMV-1 MECHANICAL ROOMLOCATIONPOWERS - MM432FLOW24(GPM)RATEREMARKSINLET/OUTLETHOT WATERTEMP. ( F)40/110SIZEOUTLETINLETSIZE-LAVATORY - COUNTER MOUNT - ADA COMPLIANTFLOOR DRAIN - 6" SQUARE STAINLESS STEEL STRAINERWALL CLEAN OUTCLEAN OUT TO FLOORCOTFWCOFD-1DESCRIPTIONP-3ASYMBOLP-1A2"HOTCOLD1"WASTE3"2"VENT2"WATER CLOSET - WALL MOUNTED - ADA COMPLIANT3/4"3" 2"2"TRAPINTINTURINAL - WALL MOUNTED - STANDARDP-2A1/2"1/2" 1-1/2" 2"1-1/2"P-1B3" 2"WATER CLOSET - WALL MOUNTED STANDARDINT3/4"3" 2"INTURINAL - WALL MOUNTED - ADA COMPLIANTP-2BREMARKSHOSE BIBB - COLD, WITH VACUUM BREAKERHOSE BIBB - HOT, WITH VACUUM BREAKERFLOOR CLEAN OUT, NICKEL BRONZE SCORIATED TOPWALL CLEAN OUT, STAINLESS STEEL ROUND COVERWCOFCOHB-2HB-11/2"LAVATORY - WALL MOUNT - ADA COMPLIANTP-3B1/2"1/2" 1-1/2" 2"1-1/2"TRENCH DRAIN - 6" WIDETD-1-1"SHOWER VALVEP-5A1/2" -SHOWER VALVE, ADA COMPLIANTP-5B1/2" -WASHER BOX CONNECTIONP-61/2" INT1/2"- -3/4"---------------------------------3/4"-------------- - -- - -- 2"-----SWIM SUIT SPIN DRYERP-7- 1-1/4"--2"1-1/4"FIXTURE COUNTFC#TRENCH DRAIN - 6" WIDETD-22"-- - 2" 2"HAND SINK - COUNTER MOUNTEDP-4A1/2" 1/2"2"1-1/2"1-1/2" -LAUNDRY SINK - FLOOR MOUNTEDP-4B1/2" 1/2"2"1-1/2"1-1/2" -FLOOR DRAIN, FLOOR SINK OR ROOF DRAINGAS (NATURAL GAS)DOMESTIC HOT WATERSEWER OR WASTEVENT THROUGH ROOFVENTCOLD WATERTHERMOMETERPRESSURE REDUCING VALVE - (PRV)SAFETY OR RELIEF VALVEFLOOR CLEAN OUTWALL CLEAN OUTCLEAN OUTGAS SHUT OFF VALVE (GAS COCK)DROP IN PIPERISE IN PIPEVALVE IN RISEGAS TYPE WATER HAMMER ARRESTORCAPBALL VALVESYMBOLUNIONDESCRIPTIONALL PLUMBING SHALL BE DONE IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OFVALVE WITH HAND WHEEL. VALVE SHALL BE BALL TYPE, QUARTER TURN AS APPROVEDALL WALL-HUNG PLUMBING FIXTURES SHALL BE SECURELY ATTACHED TO AND SUPPORTEDTHE CONTRACTOR SHALL VERIFY ALL PLUMBING FIXTURES, EQUIPMENT REQUIREMENTS ANDLOCATIONS, AND ALL RELATED UTILITIES WITH THE MECHANICAL AND ARCHITECTURALPLANS AND SPECIFICATIONS AND SHALL PROVIDE ALL SERVICES AS REQUIRED.BY FLOOR-MOUNTED CARRIERS OF ALL-METAL CONSTRUCTION. FIXTURE HANGERS OR ARMSSHALL BE SUPPORTED FREE OF THE FINISHED WALL. HANGERS SHALL BE BY WADE,EACH INDIVIDUAL FIXTURE SUPPLY SHALL BE PROVIDED WITH A CHROME-PLATED STOPBY ENGINEER. STOPS SHALL BE ON BOTH HOT AND COLD WATER LINES.FIXTURES AND ACCESSORIES SHALL BE AS SPECIFIED. EACH ITEM SHALL BE COMPLETEWITH CHROME-PLATED BRASS TRIM. SEE PLUMBING FIXTURE SCHEDULE.CAULK WITH SILICONE COMPOUND AROUND ALL FIXTURES AT INTERFACE WITH WALLSTHE IDAHO PLUMBING CODE AND/OR LOCAL ORDINANCES.SMITH, JOSAM, OR ZURN.AND/OR FLOOR.NEW CONNECTION SYMBOLNOT IN CONTRACTCOMBINATION WASTE VENTEXISTINGMANUFACTURER/MODEL #WHA-AWHA-BWHA-CPPP SC-500PPP SC-750PPP SC-1000MARKPER PDI STANDARD PDI-WH 201PER PDI STANDARD PDI-WH 201PER PDI STANDARD PDI-WH 2011-1112-3233-601/2"3/4"1"FIXTURE UNITS INLET SIZEREMARKSSEE SPECIFICATION 224200WATER CLOSET - FLOOR MOUNTED, TANK TYPEP-1C3" 2"INT1/2"--SHOWER DRAIN - 6" SQUARE STAINLESS STEEL STRAINERSD2" 2"2" -- -SERVICE SINK - FLOOR MOUNTEDP-83/4" 3"3/4"-2"3"LAUNDRY1-1/4"SERIVCE SIZELF009SNUMBER'WATT'S' MANUFACTURERSYMBOLBFP-1QTY.2SEE SPECIFICATION 230523HUB DRAINHD--- 2" 2" 2"5MV-2 BELOW HAND SINKSBRADLEY - S59-400 .05-2.0 105°ASSE 10701/2" 1/2"TEPID---1/2"1/2"--------------------SHOWER VALVE, ADA COMPLIANTP-5C1/2" 1/2"WITH REMOTE SHOWER----FLOOR SINKFS-13" 2"3" -- - -HEAD. SEE PLAN2"1"0"654321654321EDCBADATEREVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:12:20 AMP-001PLUMBINGSCHEDULESANDDETAILSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200541 10.30.20 Addendum 12 11.06.20 Addendum 2
11112222333344445555666677778888999910101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMM18181818PD401PD401PD401PD4011111PD401PD401PD401PD4013333SCALE:SCALE:SCALE:SCALE:PD101PD101PD101PD1011" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=N=lsbo^ii=mirj_fkd=abjlifqflk=mi^k11112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:12:24 AMPD101LEVEL 1OVERALLPLUMBINGDEMOLITIONPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054000010101010202020202020202040404040
11112222333344445555666677778888999910101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMM18181818PD402PD402PD402PD4023333PD402PD402PD402PD4024444PD403PD403PD403PD4033333SCALE:SCALE:SCALE:SCALE:PD102PD102PD102PD1021" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=O=lsbo^ii=mirj_fkd=abjlifqflk=mi^k11112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:12:34 AMPD102LEVEL 2OVERALLPLUMBINGDEMOLITIONPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054000010101010202020202020202040404040
19191919202020202121212122222222G1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKK18181818111122223333777711112222222222223333333333333333CAPCAPCAPCAPCAPCAPCAPCAPCAPCAPCAPCAP33334444444444441919191920202020C1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F118181818111122223333444455553333333333333333333311111111222222222222333355555555333333334444444444444444ao^tfkd=klqbp2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:12:48 AMPD401ENLARGEDPLUMBINGDEMOLITIONPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PD401PD401PD401PD4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=abjlifqflk=mi^k111100002.52.52.52.55555555510101010SCALE:SCALE:SCALE:SCALE:PD401PD401PD401PD4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=abjlifqflk=mi^k333300002.52.52.52.55555555510101010NOTE# DESCRIPTION1111 REMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORHAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,WASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGSPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.2222 REMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETAND/OR URINAL CAP ASSOCIATEDAND/OR URINAL CAP ASSOCIATEDAND/OR URINAL CAP ASSOCIATEDAND/OR URINAL CAP ASSOCIATEDWATER, WASTE AND VENT PIPING INWATER, WASTE AND VENT PIPING INWATER, WASTE AND VENT PIPING INWATER, WASTE AND VENT PIPING INCEILING SPACE AND BELOW FLOOR.CEILING SPACE AND BELOW FLOOR.CEILING SPACE AND BELOW FLOOR.CEILING SPACE AND BELOW FLOOR.3333 REMOVE EXISTING FLOOR DRAINREMOVE EXISTING FLOOR DRAINREMOVE EXISTING FLOOR DRAINREMOVE EXISTING FLOOR DRAINAND/OR SHOWER DRAIN AND CAPAND/OR SHOWER DRAIN AND CAPAND/OR SHOWER DRAIN AND CAPAND/OR SHOWER DRAIN AND CAPASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGBELOW FLOOR.BELOW FLOOR.BELOW FLOOR.BELOW FLOOR.4444 NO PLUMBING WORK IN THIS AREANO PLUMBING WORK IN THIS AREANO PLUMBING WORK IN THIS AREANO PLUMBING WORK IN THIS AREAPROTECT DURING CONSTRUCTION.PROTECT DURING CONSTRUCTION.PROTECT DURING CONSTRUCTION.PROTECT DURING CONSTRUCTION.5555 REMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDWATER PIPING BACK TO MAIN ANDWATER PIPING BACK TO MAIN ANDWATER PIPING BACK TO MAIN ANDWATER PIPING BACK TO MAIN ANDCAP IN CEILING SPACE. CAPCAP IN CEILING SPACE. CAPCAP IN CEILING SPACE. CAPCAP IN CEILING SPACE. CAPASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGIN CEILING SPACE AND BELOW FLOOR.IN CEILING SPACE AND BELOW FLOOR.IN CEILING SPACE AND BELOW FLOOR.IN CEILING SPACE AND BELOW FLOOR.6666 NOT USEDNOT USEDNOT USEDNOT USED7777 MOVE EXISTING MIXING VALVE BOXMOVE EXISTING MIXING VALVE BOXMOVE EXISTING MIXING VALVE BOXMOVE EXISTING MIXING VALVE BOXFROM WALL TO NEW LOCATION. SEEFROM WALL TO NEW LOCATION. SEEFROM WALL TO NEW LOCATION. SEEFROM WALL TO NEW LOCATION. SEEREMODEL PLAN 2/PL401. CAPREMODEL PLAN 2/PL401. CAPREMODEL PLAN 2/PL401. CAPREMODEL PLAN 2/PL401. CAPASSOCIATED WATER PREPARATORYASSOCIATED WATER PREPARATORYASSOCIATED WATER PREPARATORYASSOCIATED WATER PREPARATORYFOR NEW CONNECTION ON REMODELFOR NEW CONNECTION ON REMODELFOR NEW CONNECTION ON REMODELFOR NEW CONNECTION ON REMODELPLAN.PLAN.PLAN.PLAN.1 10.30.20 Addendum 1
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^tfkd=klqbp2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:01 AMPD402ENLARGEDPLUMBINGDEMOLITIONPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PD402PD402PD402PD4021/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=abjlifqflk=mi^k3333SCALE:SCALE:SCALE:SCALE:PD402PD402PD402PD4021/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=abjlifqflk=mi^k444400002.52.52.52.5555555551010101000002.52.52.52.55555555510101010NOTE# DESCRIPTION1111 REMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORHAND SINK AND ASSOCIATED WATER,HAND SINK AND ASSOCIATED WATER,HAND SINK AND ASSOCIATED WATER,HAND SINK AND ASSOCIATED WATER,WASTE AND VENT PIPING COMPLETE.WASTE AND VENT PIPING COMPLETE.WASTE AND VENT PIPING COMPLETE.WASTE AND VENT PIPING COMPLETE.2222 REMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETREMOVE EXISTING WATER CLOSETAND/OR URINAL AND ASSOCIATEDAND/OR URINAL AND ASSOCIATEDAND/OR URINAL AND ASSOCIATEDAND/OR URINAL AND ASSOCIATEDWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGCOMPLETE.COMPLETE.COMPLETE.COMPLETE.3333 REMOVE EXISTING FLOOR DRAIN ANDREMOVE EXISTING FLOOR DRAIN ANDREMOVE EXISTING FLOOR DRAIN ANDREMOVE EXISTING FLOOR DRAIN ANDASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGASSOCIATED WASTE AND VENT PIPINGCOMPLETE.COMPLETE.COMPLETE.COMPLETE.4444 CAP EXISTING 4" WASTE PIPING BELOWCAP EXISTING 4" WASTE PIPING BELOWCAP EXISTING 4" WASTE PIPING BELOWCAP EXISTING 4" WASTE PIPING BELOWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANPL402.PL402.PL402.PL402.5555 REMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTREMOVE EXISTING SHOWER POSTCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDCOMPLETE. REMOVE ASSOCIATEDWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGWATER, WASTE AND VENT PIPINGWHERE SHOWN HATCHED.WHERE SHOWN HATCHED.WHERE SHOWN HATCHED.WHERE SHOWN HATCHED.6666 REMOVE EXISTING WASTE, WATER,REMOVE EXISTING WASTE, WATER,REMOVE EXISTING WASTE, WATER,REMOVE EXISTING WASTE, WATER,AND VENT PIPING WHERE SHOWNAND VENT PIPING WHERE SHOWNAND VENT PIPING WHERE SHOWNAND VENT PIPING WHERE SHOWNHATCHED.HATCHED.HATCHED.HATCHED.7777 PROTECT EXISTING 6" WASTE DROP INPROTECT EXISTING 6" WASTE DROP INPROTECT EXISTING 6" WASTE DROP INPROTECT EXISTING 6" WASTE DROP INFLOOR TO LEVEL BELOW.FLOOR TO LEVEL BELOW.FLOOR TO LEVEL BELOW.FLOOR TO LEVEL BELOW.PREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.8888 CAP EXISTING WATER PIPING ATCAP EXISTING WATER PIPING ATCAP EXISTING WATER PIPING ATCAP EXISTING WATER PIPING ATAPPROXIMATELY THIS LOCATIONAPPROXIMATELY THIS LOCATIONAPPROXIMATELY THIS LOCATIONAPPROXIMATELY THIS LOCATIONPREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.PREPARATORY FOR NEW CONNECTION.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.SEE REMODEL PLAN PL402.9999 CAP EXISTING 6" WASTE PIPING BELOWCAP EXISTING 6" WASTE PIPING BELOWCAP EXISTING 6" WASTE PIPING BELOWCAP EXISTING 6" WASTE PIPING BELOWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWFLOOR PREPARATORY FOR NEWCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANCONNECTION. SEE REMODEL PLANPL402.PL402.PL402.PL402.10101010 REMOVE EXISTING MIXING VALVE ANDREMOVE EXISTING MIXING VALVE ANDREMOVE EXISTING MIXING VALVE ANDREMOVE EXISTING MIXING VALVE ANDASSOCIATED PIPING IN WALL.ASSOCIATED PIPING IN WALL.ASSOCIATED PIPING IN WALL.ASSOCIATED PIPING IN WALL.11111111 REMOVE EXISTING DRINKINGREMOVE EXISTING DRINKINGREMOVE EXISTING DRINKINGREMOVE EXISTING DRINKINGFOUNTAIN AND ASSOCIATED PIPINGFOUNTAIN AND ASSOCIATED PIPINGFOUNTAIN AND ASSOCIATED PIPINGFOUNTAIN AND ASSOCIATED PIPINGCOMPLETE.COMPLETE.COMPLETE.COMPLETE.12121212 PROTECT EXISTING WALL HYDRANT INPROTECT EXISTING WALL HYDRANT INPROTECT EXISTING WALL HYDRANT INPROTECT EXISTING WALL HYDRANT INWALL. REMOVE ASSOCIATED WATERWALL. REMOVE ASSOCIATED WATERWALL. REMOVE ASSOCIATED WATERWALL. REMOVE ASSOCIATED WATERSUPPLY IN CEILING SPACESUPPLY IN CEILING SPACESUPPLY IN CEILING SPACESUPPLY IN CEILING SPACEPREPARATORY FOR NEW SUPPLYPREPARATORY FOR NEW SUPPLYPREPARATORY FOR NEW SUPPLYPREPARATORY FOR NEW SUPPLYPIPING. SEE REMODEL PLAN PL402.PIPING. SEE REMODEL PLAN PL402.PIPING. SEE REMODEL PLAN PL402.PIPING. SEE REMODEL PLAN PL402.1 10.30.20 Addendum 12 11.06.20 Addendum 2
131313131414141415151515BBBBCCCCC1C1C1C1DDDD111122223333ao^tfkd=klqbp2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:03 AMPD403ENLARGEDPLUMBINGDEMOLITIONPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PD403PD403PD403PD4031/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=abjlifqflk=mi^k333300002.52.52.52.55555555510101010NOTE# DESCRIPTION1111 REMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORREMOVE EXISTING LAVATORY AND/ORHAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,HAND SINK. CAP ASSOCIATED WATER,WASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGWASTE AND VENT PIPING IN CEILINGSPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.SPACE AND BELOW FLOOR.2222 REMOVE EXISTING WATER CLOSET ANDREMOVE EXISTING WATER CLOSET ANDREMOVE EXISTING WATER CLOSET ANDREMOVE EXISTING WATER CLOSET ANDCAP ASSOCIATED WATER, WASTE ANDCAP ASSOCIATED WATER, WASTE ANDCAP ASSOCIATED WATER, WASTE ANDCAP ASSOCIATED WATER, WASTE ANDVENT PIPING IN CEILING SPACE ANDVENT PIPING IN CEILING SPACE ANDVENT PIPING IN CEILING SPACE ANDVENT PIPING IN CEILING SPACE ANDBELOW FLOOR.BELOW FLOOR.BELOW FLOOR.BELOW FLOOR.3333 REMOVE EXISTING SINK. CAPREMOVE EXISTING SINK. CAPREMOVE EXISTING SINK. CAPREMOVE EXISTING SINK. CAPASSOCIATED WATER, WASTE ANDASSOCIATED WATER, WASTE ANDASSOCIATED WATER, WASTE ANDASSOCIATED WATER, WASTE ANDVENT PIPING IN WALL.VENT PIPING IN WALL.VENT PIPING IN WALL.VENT PIPING IN WALL.2 11.06.20 Addendum 2
11112222333344445555666677778888999910101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMM18181818PL401PL401PL401PL4011111PL401PL401PL401PL4012222PL401PL401PL401PL4013333PL401PL401PL401PL4014444SCALE:SCALE:SCALE:SCALE:PL101PL101PL101PL1011" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=N=lsbo^ii=mirj_fkd=objlabi=mi^k11112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:06 AMPL101LEVEL 1OVERALLPLUMBINGREMODELPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054000010101010202020202020202040404040
11112222333344445555666677778888999910101010111111111212121213131313141414141515151516161616171717171919191920202020212121212222222223232323242424242525252526262626272727272828282829292929AAAABBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1GGGGG1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKKLLLLMMMM18181818PL402PL402PL402PL4021111PL403PL403PL403PL4031111PL405PL405PL405PL4051111PL404PL404PL404PL4041111PL402PL402PL402PL4022222PL405PL405PL405PL4052222PL406PL406PL406PL4062222PL406PL406PL406PL4061111SCALE:SCALE:SCALE:SCALE:PL102PL102PL102PL1021" = 20'1" = 20'1" = 20'1" = 20'----0"0"0"0"ibsbi=O=lsbo^ii=mirj_fkd=objlabi=mi^k11112"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:16 AMPL102LEVEL 2OVERALLPLUMBINGREMODELPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054000010101010202020202020202040404040
19191919202020202121212122222222G1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKK1818181811112222PPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3A2"2"2"2"2"2"2"2"2"2"2"2"55554"4"4"4"4"4"4"4"COCOCOCOCOCOCOCO2"2"2"2"4"4"4"4"2"2"2"2"2"2"2"2"4"4"4"4"2"2"2"2"2"2"2"2"PPPP----3A3A3A3A PPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3A3333PPPP----1B1B1B1BPPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1B1B1B1BPPPP----2A2A2A2APPPP----2A2A2A2APPPP----2A2A2A2APPPP----2B2B2B2B3"3"3"3"2"2"2"2"2"2"2"2"183MEN'S181WOMEN'S180LAUNDRY RM179DOFFICECTRWELLNESS179COFFICECTRWELLNESS179BOFFICECTRWELLNESS179AASSEMBLESORT &175OFFICECUSTODIAN4"4"4"4"2"2"2"2"4"4"4"4"2"2"2"2"3"3"3"3"FDFDFDFD----22222"2"2"2"4444555544444444FDFDFDFD----1111FDFDFDFD----111133332" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWVFDFDFDFD----1111FDFDFDFD----1111PPPP----4B4B4B4B14141414FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----11111919191920202020G1G1G1G1HHHHH1H1H1H1JJJJJ1J1J1J1KKKK18181818PPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3A PPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3A PPPP----3A3A3A3A PPPP----3A3A3A3APPPP----1B1B1B1BPPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1B1B1B1BPPPP----2A2A2A2APPPP----2A2A2A2APPPP----2A2A2A2APPPP----2B2B2B2B183MEN'S181WOMEN'S180LAUNDRY RM179DOFFICECTRWELLNESS179COFFICECTRWELLNESS179BOFFICECTRWELLNESS179AASSEMBLESORT &175OFFICECUSTODIANWHAWHAWHAWHAWHAWHAWHAWHA2 1/2"2 1/2"2 1/2"2 1/2"2"2"2"2"2 1/2"2 1/2"2 1/2"2 1/2"1 1/4"1 1/4"1 1/4"1 1/4"2"2"2"2"2 1/2"2 1/2"2 1/2"2 1/2"2"2"2"2"2"2"2"2"7777777788882"2"2"2"2"2"2"2"2"2"2"2"666677777777WHAWHAWHAWHA2"2"2"2"2"2"2"2"2"2"2"2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"BDPBDPBDPBDP----1111(TWO) SUCH)(TWO) SUCH)(TWO) SUCH)(TWO) SUCH)9999101010101"1"1"1"1"1"1"1"131313131212121211111111PPPP----4B4B4B4BFDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111FDFDFDFD----1111777715151515TPTPTPTP----111115151515TPTPTPTP----11111/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"17171717JJJJJ1J1J1J12"2"2"2"3"3"3"3"PPPP----888817171717JJJJJ1J1J1J11/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"PPPP----88882"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:49 AMPL401ENLARGEDPLUMBINGREMODELPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^pqb=C=sbkq111100002.52.52.52.55555555510101010SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^qbo222200002.52.52.52.55555555510101010NOTE# DESCRIPTION8888 CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"DHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TOEXISTING 3" DCW AT APPROXIMATELYEXISTING 3" DCW AT APPROXIMATELYEXISTING 3" DCW AT APPROXIMATELYEXISTING 3" DCW AT APPROXIMATELYTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASSHOWN.SHOWN.SHOWN.SHOWN.9999 RISE 3/4" DHW AND 3/4" DCW UP ONRISE 3/4" DHW AND 3/4" DCW UP ONRISE 3/4" DHW AND 3/4" DCW UP ONRISE 3/4" DHW AND 3/4" DCW UP ONWALL AND CONNECT TO ECOLABWALL AND CONNECT TO ECOLABWALL AND CONNECT TO ECOLABWALL AND CONNECT TO ECOLABMANIFOLDS PER MANUFACTURER'SMANIFOLDS PER MANUFACTURER'SMANIFOLDS PER MANUFACTURER'SMANIFOLDS PER MANUFACTURER'SWRITTEN INSTRUCTIONS.WRITTEN INSTRUCTIONS.WRITTEN INSTRUCTIONS.WRITTEN INSTRUCTIONS.10101010 CONNECT 3/4" DHW AND 3/4" DCW TOCONNECT 3/4" DHW AND 3/4" DCW TOCONNECT 3/4" DHW AND 3/4" DCW TOCONNECT 3/4" DHW AND 3/4" DCW TOWASHER PER DETAIL 4/PL501 ANDWASHER PER DETAIL 4/PL501 ANDWASHER PER DETAIL 4/PL501 ANDWASHER PER DETAIL 4/PL501 ANDMANUFACTURERS WRITTENMANUFACTURERS WRITTENMANUFACTURERS WRITTENMANUFACTURERS WRITTENINSTRUCTIONS.INSTRUCTIONS.INSTRUCTIONS.INSTRUCTIONS.11111111 RELOCATE EXISTING MIXING VALVE TORELOCATE EXISTING MIXING VALVE TORELOCATE EXISTING MIXING VALVE TORELOCATE EXISTING MIXING VALVE TOABOVE CEILING AT APPROXIMATELYABOVE CEILING AT APPROXIMATELYABOVE CEILING AT APPROXIMATELYABOVE CEILING AT APPROXIMATELYTHIS LOCATION.THIS LOCATION.THIS LOCATION.THIS LOCATION.12121212 CONNECT NEW 2" DCW AND 2" DHWCONNECT NEW 2" DCW AND 2" DHWCONNECT NEW 2" DCW AND 2" DHWCONNECT NEW 2" DCW AND 2" DHWTO EXISTING DCW AND DHW ATTO EXISTING DCW AND DHW ATTO EXISTING DCW AND DHW ATTO EXISTING DCW AND DHW ATAPPROXIMATELY THIS LOCATION.APPROXIMATELY THIS LOCATION.APPROXIMATELY THIS LOCATION.APPROXIMATELY THIS LOCATION.13131313 CONNECT NEW TEPID WATER TOCONNECT NEW TEPID WATER TOCONNECT NEW TEPID WATER TOCONNECT NEW TEPID WATER TOEXISTING TEPID WATER. FTIELD VERIFYEXISTING TEPID WATER. FTIELD VERIFYEXISTING TEPID WATER. FTIELD VERIFYEXISTING TEPID WATER. FTIELD VERIFYEXACT SIZE AND LOCATION.EXACT SIZE AND LOCATION.EXACT SIZE AND LOCATION.EXACT SIZE AND LOCATION.14141414 DROP 2" WASTE DOWN IN WALL ANDDROP 2" WASTE DOWN IN WALL ANDDROP 2" WASTE DOWN IN WALL ANDDROP 2" WASTE DOWN IN WALL ANDCONNECT INTO 4" WASTE BELOWCONNECT INTO 4" WASTE BELOWCONNECT INTO 4" WASTE BELOWCONNECT INTO 4" WASTE BELOWFLOOR.FLOOR.FLOOR.FLOOR.15151515 LOCATED TRAP PRIMER UNDERLOCATED TRAP PRIMER UNDERLOCATED TRAP PRIMER UNDERLOCATED TRAP PRIMER UNDERLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWFLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.NOTE# DESCRIPTION1111 ROUTE 3" WASTE FROM URINALS INROUTE 3" WASTE FROM URINALS INROUTE 3" WASTE FROM URINALS INROUTE 3" WASTE FROM URINALS INWALL AND DROP BELOW FLOORWALL AND DROP BELOW FLOORWALL AND DROP BELOW FLOORWALL AND DROP BELOW FLOORWHERE SHOWN.WHERE SHOWN.WHERE SHOWN.WHERE SHOWN.2222 DROP 3" WASTE BELOW FLOOR INDROP 3" WASTE BELOW FLOOR INDROP 3" WASTE BELOW FLOOR INDROP 3" WASTE BELOW FLOOR INWALL AND CONNECT INTO EXISTING 3"WALL AND CONNECT INTO EXISTING 3"WALL AND CONNECT INTO EXISTING 3"WALL AND CONNECT INTO EXISTING 3"WASTE. FIELD VERIFY EXACT LOCATIONWASTE. FIELD VERIFY EXACT LOCATIONWASTE. FIELD VERIFY EXACT LOCATIONWASTE. FIELD VERIFY EXACT LOCATIONOF EXISTING WASTE PIPING.OF EXISTING WASTE PIPING.OF EXISTING WASTE PIPING.OF EXISTING WASTE PIPING.3333 CONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTING3" WASTE AT APPROXIMATELY THIS3" WASTE AT APPROXIMATELY THIS3" WASTE AT APPROXIMATELY THIS3" WASTE AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION OF EXISTING WASTE PIPING.LOCATION OF EXISTING WASTE PIPING.LOCATION OF EXISTING WASTE PIPING.LOCATION OF EXISTING WASTE PIPING.4444 CONNECT NEW 2" VENT TO EXISTINGCONNECT NEW 2" VENT TO EXISTINGCONNECT NEW 2" VENT TO EXISTINGCONNECT NEW 2" VENT TO EXISTINGVENT PIPING AT APPROXIMATELY THISVENT PIPING AT APPROXIMATELY THISVENT PIPING AT APPROXIMATELY THISVENT PIPING AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACT SIZELOCATION. FIELD VERIFY EXACT SIZELOCATION. FIELD VERIFY EXACT SIZELOCATION. FIELD VERIFY EXACT SIZEAND LOCATION.AND LOCATION.AND LOCATION.AND LOCATION.5555 CONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTING4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION OF EXISTING PIPING.LOCATION OF EXISTING PIPING.LOCATION OF EXISTING PIPING.LOCATION OF EXISTING PIPING.6666 CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"DHW. CONNECT NEW 2" DCW TODHW. CONNECT NEW 2" DCW TODHW. CONNECT NEW 2" DCW TODHW. CONNECT NEW 2" DCW TOEXISTING 2-1/2" DCW ATEXISTING 2-1/2" DCW ATEXISTING 2-1/2" DCW ATEXISTING 2-1/2" DCW ATAPPROXIMATELY THIS LOCATION ANDAPPROXIMATELY THIS LOCATION ANDAPPROXIMATELY THIS LOCATION ANDAPPROXIMATELY THIS LOCATION ANDROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.7777 DROP 2" DHW LOOP DOWN IN WALL TODROP 2" DHW LOOP DOWN IN WALL TODROP 2" DHW LOOP DOWN IN WALL TODROP 2" DHW LOOP DOWN IN WALL TOWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISE2" DHW LOOP UP IN WALL TO ROUTE2" DHW LOOP UP IN WALL TO ROUTE2" DHW LOOP UP IN WALL TO ROUTE2" DHW LOOP UP IN WALL TO ROUTEAS SHOWN.AS SHOWN.AS SHOWN.AS SHOWN.SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^pqb=C=sbkq3333SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL4011/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^qbo444400002.52.52.52.55555555510101010ao^tfkd=klqbp00002.52.52.52.555555555101010101 10.30.20 Addendum 12 11.06.20 Addendum 2
11112222BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1111122223333FCOFCOFCOFCOFDFDFDFD----1111FDFDFDFD----1111PPPP----1A1A1A1A PPPP----1B1B1B1BPPPP----1B1B1B1BPPPP----1A1A1A1APPPP----3A3A3A3A PPPP----3A3A3A3APPPP----3A3A3A3A PPPP----3A3A3A3A4"4"4"4"1111(E)6" WASTE4"4"4"4"4"4"4"4"(E)6" WASTEWCOWCOWCOWCOFCOFCOFCOFCOTDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111WCOWCOWCOWCOTDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----11114"4"4"4"3" CWV3" CWV3" CWV3" CWV(E) 6"VTR(E) 6"VTR(E) 6"VTR(E) 6"VTR2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV(E)2" VENT(E)2" VENT33333333(E)2" VENT(E)2" VENT(E)2" VENT2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV3"3"3"3"207DSTORAGE207ALOCKER RMMEN'S EMPLOYEE207LOCKER RMMEN'S STUDENT3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV2" CWV2" CWV2" CWV2" CWV3" CWV3" CWV3" CWV3" CWV3"3"3"3"3" CWV3" CWV3" CWV3" CWV2" CWV2" CWV2" CWV2" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV2" CWV2" CWV2" CWV2" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWVSEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----11113" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWVTDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----11113" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3333TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----11112" CWV2" CWV2" CWV2" CWV2" CVW2" CVW2" CVW2" CVWPPPP----2A2A2A2A PPPP----2B2B2B2BPPPP----2A2A2A2APPPP----2B2B2B2BPPPP----77772"2"2"2"2"2"2"2"PPPP----77772"2"2"2"2"2"2"2"11112222BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1PPPP----1A1A1A1A PPPP----1B1B1B1BPPPP----1B1B1B1BPPPP----1A1A1A1APPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3A PPPP----3A3A3A3A207DSTORAGE207ALOCKER RMMEN'S EMPLOYEE207LOCKER RMMEN'S STUDENTPPPP----5A5A5A5A1" TEPID1" TEPID1" TEPID1" TEPID1" TEPID1" TEPID1" TEPID1" TEPID1 1/4" TEPID1 1/4" TEPID1 1/4" TEPID1 1/4" TEPID1" TEPID1" TEPID1" TEPID1" TEPID1 1/2" TEPID1 1/2" TEPID1 1/2" TEPID1 1/2" TEPID3/4"3/4"3/4"3/4"444444441010101010101010WHAWHAWHAWHAMVMVMVMV11115555HBHBHBHB----1,1,1,1,HBHBHBHB----2222HBHBHBHB----1,1,1,1,HBHBHBHB----2222SEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406SEE ALTERNATE 1/PL406PPPP----2A2A2A2APPPP----2B2B2B2BPPPP----2A2A2A2APPPP----2B2B2B2B6666777788882"2"2"2"3"3"3"3"3/4"3/4"3/4"3/4"2"2"2"2"3"3"3"3"3/4"3/4"3/4"3/4"2"2"2"2"3"3"3"3"66663"3"3"3"3"3"3"3"FDFDFDFD----1111FDFDFDFD----1111TDTDTDTD----1111TPTPTPTP----1111TPTPTPTP----1111999999991/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"PPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5A PPPP----5B5B5B5BPPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5B5B5B5BPPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----7777PPPP----77771" DCW1" DCW1" DCW1" DCW(ALTERNATE #3)(ALTERNATE #3)(ALTERNATE #3)(ALTERNATE #3)1" TEPID1" TEPID1" TEPID1" TEPID1"1"1"1"1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1" DCW1 1/2" DCW1 1/2" DCW1 1/2" DCW1 1/2" DCW1"1"1"1"2"2"2"2"1" DCW1" DCW1" DCW1" DCW1 1/4" DCW1 1/4" DCW1 1/4" DCW1 1/4" DCW1" DCW1" DCW1" DCW1" DCW3/4"3/4"3/4"3/4"1" DCW1" DCW1" DCW1" DCW1" TEPID1" TEPID1" TEPID1" TEPID111111111 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW2"2"2"2"2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:13:57 AMPL402ENLARGEDPLUMBINGREMODELPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PL402PL402PL402PL4021/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^pqb=C=sbkq111100002.52.52.52.55555555510101010ao^tfkd=klqbpSCALE:SCALE:SCALE:SCALE:PL402PL402PL402PL4021/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^qbo222200002.52.52.52.55555555510101010NOTE#DESCRIPTION1111 CONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTING6" WASTE AT APPROXIMATELY THIS6" WASTE AT APPROXIMATELY THIS6" WASTE AT APPROXIMATELY THIS6" WASTE AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION.LOCATION.LOCATION.LOCATION.2222 CONNECT NEW 3" VENT TO EXISTING 6"CONNECT NEW 3" VENT TO EXISTING 6"CONNECT NEW 3" VENT TO EXISTING 6"CONNECT NEW 3" VENT TO EXISTING 6"VTR AT APPROXIMATELY THISVTR AT APPROXIMATELY THISVTR AT APPROXIMATELY THISVTR AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION.LOCATION.LOCATION.LOCATION.3333 CONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDVERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.4444 DROP 1" DHW LOOP DOWN IN WALL TODROP 1" DHW LOOP DOWN IN WALL TODROP 1" DHW LOOP DOWN IN WALL TODROP 1" DHW LOOP DOWN IN WALL TOWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISEWITHIN 2 FEET OF LAVATORY AND RISE1" DHW LOOP UP IN WALL TO ROUTE1" DHW LOOP UP IN WALL TO ROUTE1" DHW LOOP UP IN WALL TO ROUTE1" DHW LOOP UP IN WALL TO ROUTEAS SHOWN.AS SHOWN.AS SHOWN.AS SHOWN.5555 PROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPON 1" DCW PIPING IN CHASE.ON 1" DCW PIPING IN CHASE.ON 1" DCW PIPING IN CHASE.ON 1" DCW PIPING IN CHASE.PREPARATORY FOR FUTUREPREPARATORY FOR FUTUREPREPARATORY FOR FUTUREPREPARATORY FOR FUTURECONNECTION TO ALTERNATE STEAMCONNECTION TO ALTERNATE STEAMCONNECTION TO ALTERNATE STEAMCONNECTION TO ALTERNATE STEAMROOM EQUIPMENT.ROOM EQUIPMENT.ROOM EQUIPMENT.ROOM EQUIPMENT.6666 CONNECT NEW 3/4" DCW TO EXISTINGCONNECT NEW 3/4" DCW TO EXISTINGCONNECT NEW 3/4" DCW TO EXISTINGCONNECT NEW 3/4" DCW TO EXISTINGWALL HYDRANT AT APPROXIMATELYWALL HYDRANT AT APPROXIMATELYWALL HYDRANT AT APPROXIMATELYWALL HYDRANT AT APPROXIMATELYTHIS LOCATION.THIS LOCATION.THIS LOCATION.THIS LOCATION.7777 CONNECT NEW 2" DHW AND 3/4" DHWRCONNECT NEW 2" DHW AND 3/4" DHWRCONNECT NEW 2" DHW AND 3/4" DHWRCONNECT NEW 2" DHW AND 3/4" DHWRTO EXISTING 2" DHW AND 3/4" DHWRTO EXISTING 2" DHW AND 3/4" DHWRTO EXISTING 2" DHW AND 3/4" DHWRTO EXISTING 2" DHW AND 3/4" DHWRAT APPROXIMATELY THIS LOCATION.AT APPROXIMATELY THIS LOCATION.AT APPROXIMATELY THIS LOCATION.AT APPROXIMATELY THIS LOCATION.8888 EXTEND NEW 3" DCW DOWN HALL ANDEXTEND NEW 3" DCW DOWN HALL ANDEXTEND NEW 3" DCW DOWN HALL ANDEXTEND NEW 3" DCW DOWN HALL ANDCONNECT INTO EXISTING 3" DCW.CONNECT INTO EXISTING 3" DCW.CONNECT INTO EXISTING 3" DCW.CONNECT INTO EXISTING 3" DCW.FIELD VERIFY EXACT LOCATION OFFIELD VERIFY EXACT LOCATION OFFIELD VERIFY EXACT LOCATION OFFIELD VERIFY EXACT LOCATION OFEXISTING 3" DCW.EXISTING 3" DCW.EXISTING 3" DCW.EXISTING 3" DCW.9999 LOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWFLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.10101010 DROP 3/4" DHW LOOP DOWN IN WALLDROP 3/4" DHW LOOP DOWN IN WALLDROP 3/4" DHW LOOP DOWN IN WALLDROP 3/4" DHW LOOP DOWN IN WALLTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDRISE 3/4" DHW LOOP UP IN WALL TORISE 3/4" DHW LOOP UP IN WALL TORISE 3/4" DHW LOOP UP IN WALL TORISE 3/4" DHW LOOP UP IN WALL TOROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.11111111 PROVIDE 1-1/2" ISOLATION VALVEPROVIDE 1-1/2" ISOLATION VALVEPROVIDE 1-1/2" ISOLATION VALVEPROVIDE 1-1/2" ISOLATION VALVEJUST ABOVE CEILING. INCREASE PIPEJUST ABOVE CEILING. INCREASE PIPEJUST ABOVE CEILING. INCREASE PIPEJUST ABOVE CEILING. INCREASE PIPETO 2" PRIOR TO DROPPING TO BELOWTO 2" PRIOR TO DROPPING TO BELOWTO 2" PRIOR TO DROPPING TO BELOWTO 2" PRIOR TO DROPPING TO BELOWTHE CEILING. TERMINATE PIPE 2"THE CEILING. TERMINATE PIPE 2"THE CEILING. TERMINATE PIPE 2"THE CEILING. TERMINATE PIPE 2"BELOW CEILING AND RE-INSTALL HOSEBELOW CEILING AND RE-INSTALL HOSEBELOW CEILING AND RE-INSTALL HOSEBELOW CEILING AND RE-INSTALL HOSECONNECTION. PROVIDE ANGLE BRACECONNECTION. PROVIDE ANGLE BRACECONNECTION. PROVIDE ANGLE BRACECONNECTION. PROVIDE ANGLE BRACEABOVE CEILING TO SECURE PIPE INABOVE CEILING TO SECURE PIPE INABOVE CEILING TO SECURE PIPE INABOVE CEILING TO SECURE PIPE INPLACE.PLACE.PLACE.PLACE.1 10.30.20 Addendum 12 11.06.20 Addendum 23 11.10.20 Addendum 33333333333333333
77778888999910101010BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F11111222233334444WCOWCOWCOWCOWCOWCOWCOWCOTDTDTDTD----1111 TDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111 TDTDTDTD----1111WCOWCOWCOWCOFCOFCOFCOFCOWCOWCOWCOWCOFDFDFDFD----1111FDFDFDFD----1111COCOCOCOCOCOCOCO2"2"2"2"3"3"3"3"2" VENT2" VENT2" VENT2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENT2 1/2" VENTPPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3APPPP----1B1B1B1BPPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1B1B1B1B(E)4"2"2"2"2"(E)4" WASTE DROP3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV44445555(E)4" VENT2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CVW2" CVW2" CVW2" CVW2" CVW2" CVW2" CVW2" CVW2 1/2"2 1/2"2 1/2"2 1/2"2"2"2"2"2" CVW2" CVW2" CVW2" CVW261DNURSING261LOCKER RMWOMEN'S STUDENT261ALOCKER RMWOMEN'S EMPLOYEE261ESTORAGE261BNURSINGPPPP----4A4A4A4A2" CVW2" CVW2" CVW2" CVWPPPP----4A4A4A4ATDTDTDTD----1111TDTDTDTD----1111SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406PPPP----77772"2"2"2"2"2"2"2"2"2"2"2"PPPP----77773" CWV3" CWV3" CWV3" CWV4" CWV4" CWV4" CWV4" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV3" CWV4" CWV4" CWV4" CWV4" CWV3" CWV3" CWV3" CWV3" CWVSCALE:SCALE:SCALE:SCALE:PL403PL403PL403PL4031/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^pqb=C=sbkq1111ao^tfkd=klqbp00002.52.52.52.55555555510101010NOTE# DESCRIPTION1111 CONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTINGCONNECT NEW 4" WASTE TO EXISTING4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION.LOCATION.LOCATION.LOCATION.2222 CONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTINGCONNECT NEW 2" WASTE TO EXISTING4" WASTE DROP AT APPROXIMATELY4" WASTE DROP AT APPROXIMATELY4" WASTE DROP AT APPROXIMATELY4" WASTE DROP AT APPROXIMATELYTHIS LOCATION. FIELD VERIFY EXACTTHIS LOCATION. FIELD VERIFY EXACTTHIS LOCATION. FIELD VERIFY EXACTTHIS LOCATION. FIELD VERIFY EXACTLOCATION.LOCATION.LOCATION.LOCATION.3333 CONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATWASTE VENT TO EXISTING 2" VENT ATAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDVERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.4444 CONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONCONNECT NEW 2" COMBINATIONWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDVERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.5555 CONNECT NEW 2-1/2" COMBINATIONCONNECT NEW 2-1/2" COMBINATIONCONNECT NEW 2-1/2" COMBINATIONCONNECT NEW 2-1/2" COMBINATIONWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATWASTE VENT TO EXISTING 4" VENT ATAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDAPPROXIMATELY THIS LOCATION. FIELDVERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:03 AMPL403ENLARGEDPLUMBINGREMODELPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200541 10.30.20 Addendum 12 11.06.20 Addendum 2
77778888999910101010BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEEFFFFF1F1F1F1PPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3APPPP----3A3A3A3APPPP----1B1B1B1BPPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1A1A1A1APPPP----1B1B1B1B261DNURSING261LOCKER RMWOMEN'S STUDENT261ALOCKER RMWOMEN'S EMPLOYEE261ESTORAGE261BNURSINGMVMVMVMV1111WHAWHAWHAWHA2 1/2"2 1/2"2 1/2"2 1/2"2"2"2"2"2"2"2"2"2 1/2"2 1/2"2 1/2"2 1/2"1 1/4" TEPID1 1/4" TEPID1 1/4" TEPID1 1/4" TEPIDPPPP----4A4A4A4APPPP----4A4A4A4AHBHBHBHB----1,1,1,1,HBHBHBHB----2222HBHBHBHB----1,1,1,1,HBHBHBHB----2222111133332222222222222222SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406SEE ALTERNATE 2/PL406TPTPTPTP----11114444TPTPTPTP----111144441/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"PPPP----5B5B5B5BPPPP----5B5B5B5BPPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5A5A5A5APPPP----5B5B5B5BPPPP----5B5B5B5BPPPP----7777PPPP----7777FDFDFDFD----1111FDFDFDFD----11111" DCW1" DCW1" DCW1" DCW(ALTERNATE #3)(ALTERNATE #3)(ALTERNATE #3)(ALTERNATE #3)1 1/4"1 1/4"1 1/4"1 1/4"1"1"1"1"1" TEPID1" TEPID1" TEPID1" TEPIDao^tfkd=klqbpSCALE:SCALE:SCALE:SCALE:PL404PL404PL404PL4041/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^qbo111100002.52.52.52.55555555510101010NOTE# DESCRIPTION1111 CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"CONNECT NEW 2" DHW TO EXISTING 2"DHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TODHW. CONNECT NEW 2-1/2" DCW TOEXISTING 4" DCW AT APPROXIMATELYEXISTING 4" DCW AT APPROXIMATELYEXISTING 4" DCW AT APPROXIMATELYEXISTING 4" DCW AT APPROXIMATELYTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASTHIS LOCATION AND ROUTE ASSHOWN.SHOWN.SHOWN.SHOWN.2222 DROP 2" DHW LOOP DOWN IN WALLDROP 2" DHW LOOP DOWN IN WALLDROP 2" DHW LOOP DOWN IN WALLDROP 2" DHW LOOP DOWN IN WALLTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDTO WITHIN 2 FEET OF LAVATORY ANDRISE 2" DHW LOOP UP IN WALL TORISE 2" DHW LOOP UP IN WALL TORISE 2" DHW LOOP UP IN WALL TORISE 2" DHW LOOP UP IN WALL TOROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.3333 PROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPPROVIDE ISOLATION VALVE AND CAPON 1" DCW PIPING IN CHASEON 1" DCW PIPING IN CHASEON 1" DCW PIPING IN CHASEON 1" DCW PIPING IN CHASEPREPARATORY FOR FUTUREPREPARATORY FOR FUTUREPREPARATORY FOR FUTUREPREPARATORY FOR FUTURECONNECTION TO STEAM ROOMCONNECTION TO STEAM ROOMCONNECTION TO STEAM ROOMCONNECTION TO STEAM ROOMEQUIPMENT.EQUIPMENT.EQUIPMENT.EQUIPMENT.4444 LOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWFLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:08 AMPL404ENLARGEDPLUMBINGREMODELPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200541 10.30.20 Addendum 12 11.06.20 Addendum 23 11.10.20 Addendum 33333
131313131414141415151515BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEE33334444WCOWCOWCOWCOFDFDFDFD----1111PPPP----1C1C1C1C3"3"3"3"2"2"2"2"2"2"2"2"PPPP----3B3B3B3B212RR211STOR.S003STAIRE002SE. EXIT210PLATFORMFSFSFSFS----1111SDSDSDSD33333"3"3"3"3"3"3"3"7777131313131414141415151515BBBBCCCCC1C1C1C1DDDDD1D1D1D1EEEE11112222PPPP----1C1C1C1CPPPP----3B3B3B3B212RR211STOR.S003STAIRE002SE. EXIT210PLATFORM55551/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"PPPP----5C5C5C5CFDFDFDFD----11111/2"1/2"1/2"1/2"TPTPTPTP----111166662"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:13 AMPL405ENLARGEDPLUMBINGREMODELPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO20054SCALE:SCALE:SCALE:SCALE:PL405PL405PL405PL4051/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^pqb=C=sbkq111100002.52.52.52.55555555510101010ao^tfkd=klqbpSCALE:SCALE:SCALE:SCALE:PL405PL405PL405PL4051/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"bki^odba=mirj_fkd=objlabi=mi^k=Jt^qbo222200002.52.52.52.55555555510101010NOTE#DESCRIPTION1111 CONNECT NEW 1/2" DHW TO EXISTINGCONNECT NEW 1/2" DHW TO EXISTINGCONNECT NEW 1/2" DHW TO EXISTINGCONNECT NEW 1/2" DHW TO EXISTING3/4" DHW AT APPROXIMATELY THIS3/4" DHW AT APPROXIMATELY THIS3/4" DHW AT APPROXIMATELY THIS3/4" DHW AT APPROXIMATELY THISLOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.2222 CONNECT NEW 1/2" DCW TO EXISTINGCONNECT NEW 1/2" DCW TO EXISTINGCONNECT NEW 1/2" DCW TO EXISTINGCONNECT NEW 1/2" DCW TO EXISTING1/2" DCW AT APPROXIMATELY THIS1/2" DCW AT APPROXIMATELY THIS1/2" DCW AT APPROXIMATELY THIS1/2" DCW AT APPROXIMATELY THISLOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.LOCATION AND ROUTE AS SHOWN.3333 CONNECT NEW 2" VENT TO EXISTING 2"CONNECT NEW 2" VENT TO EXISTING 2"CONNECT NEW 2" VENT TO EXISTING 2"CONNECT NEW 2" VENT TO EXISTING 2"VENT AT APPROXIMATELY THISVENT AT APPROXIMATELY THISVENT AT APPROXIMATELY THISVENT AT APPROXIMATELY THISLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION. FIELD VERIFY EXACTLOCATION.LOCATION.LOCATION.LOCATION.4444 CONNECT NEW 3" WASTE TO EXISTINGCONNECT NEW 3" WASTE TO EXISTINGCONNECT NEW 3" WASTE TO EXISTINGCONNECT NEW 3" WASTE TO EXISTING4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THIS4" WASTE AT APPROXIMATELY THISLOCATION.LOCATION.LOCATION.LOCATION.5555 LOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWFLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.6666 LOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLOCATE TRAP PRIMER UNDERLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWLAVATORY. ROUTE 1/2" DCW BELOWFLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.FLOOR TO FLOOR DRAIN.7777 LOCATE MIXING VALVE ON SIDE WALL,LOCATE MIXING VALVE ON SIDE WALL,LOCATE MIXING VALVE ON SIDE WALL,LOCATE MIXING VALVE ON SIDE WALL,SEE ARCHITECTURAL FOR LOCATION.SEE ARCHITECTURAL FOR LOCATION.SEE ARCHITECTURAL FOR LOCATION.SEE ARCHITECTURAL FOR LOCATION.ROUTE SUPPLY TO REMOTE SHOWERROUTE SUPPLY TO REMOTE SHOWERROUTE SUPPLY TO REMOTE SHOWERROUTE SUPPLY TO REMOTE SHOWERHEAD AS SHOWN. VERIFY ACTUALHEAD AS SHOWN. VERIFY ACTUALHEAD AS SHOWN. VERIFY ACTUALHEAD AS SHOWN. VERIFY ACTUALLOCATION WITH ARCHITECTURALLOCATION WITH ARCHITECTURALLOCATION WITH ARCHITECTURALLOCATION WITH ARCHITECTURALDETAIL.DETAIL.DETAIL.DETAIL.2 11.06.20 Addendum 2
D1D1D1D1EEEE1111333344445555HDHDHDHD2" CVW2" CVW2" CVW2" CVW1"1"1"1"3"3"3"3"BBBBSTEAM UNITSTEAM UNITSTEAM UNITSTEAM UNIT2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWV2" CWVHDHDHDHD11112222444455551" DCW1" DCW1" DCW1" DCW4444SCALE:SCALE:SCALE:SCALE:PL406PL406PL406PL4061/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=^ob^=O`=pqrabkq=il`hbopmirj_fkd=mi^k=J^iqbok^qb=@P2222SCALE:SCALE:SCALE:SCALE:PL406PL406PL406PL4061/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"m^oqf^i=^ob^=O`=jbkp=bjmilvbbp=il`hbopmirj_fkd=mi^k=J^iqbok^qb=@P1111NOTE# DESCRIPTION1111 CONNECT 3/4" DCW TO STHE STEAMCONNECT 3/4" DCW TO STHE STEAMCONNECT 3/4" DCW TO STHE STEAMCONNECT 3/4" DCW TO STHE STEAMUNITS PER MANUFACTURER'S WRITTENUNITS PER MANUFACTURER'S WRITTENUNITS PER MANUFACTURER'S WRITTENUNITS PER MANUFACTURER'S WRITTENINSTRUCTIONS.INSTRUCTIONS.INSTRUCTIONS.INSTRUCTIONS.2222 SEE 2/PL402 FOR CONTINUATION.SEE 2/PL402 FOR CONTINUATION.SEE 2/PL402 FOR CONTINUATION.SEE 2/PL402 FOR CONTINUATION.3333 SEE 1/PL404 FOR CONTINUATION.SEE 1/PL404 FOR CONTINUATION.SEE 1/PL404 FOR CONTINUATION.SEE 1/PL404 FOR CONTINUATION.4444 PROVIDE DRAIN PAN UNDER STEAMPROVIDE DRAIN PAN UNDER STEAMPROVIDE DRAIN PAN UNDER STEAMPROVIDE DRAIN PAN UNDER STEAMUNITS IN CEILING SPACE. ROUTE 1"UNITS IN CEILING SPACE. ROUTE 1"UNITS IN CEILING SPACE. ROUTE 1"UNITS IN CEILING SPACE. ROUTE 1"DRAIN FROM DRAIN PAN TO HUBDRAIN FROM DRAIN PAN TO HUBDRAIN FROM DRAIN PAN TO HUBDRAIN FROM DRAIN PAN TO HUBDRAIN IN CIELING SPACE.DRAIN IN CIELING SPACE.DRAIN IN CIELING SPACE.DRAIN IN CIELING SPACE.5555 DROP 2" WASTE FROM HUB DRAINDROP 2" WASTE FROM HUB DRAINDROP 2" WASTE FROM HUB DRAINDROP 2" WASTE FROM HUB DRAINDOWN IN WALL AND CONNECT INTO 2"DOWN IN WALL AND CONNECT INTO 2"DOWN IN WALL AND CONNECT INTO 2"DOWN IN WALL AND CONNECT INTO 2"WASTE BELOW FLOOR.WASTE BELOW FLOOR.WASTE BELOW FLOOR.WASTE BELOW FLOOR.ao^tfkd=klqbp2"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:16 AMPL406ENLARGEDPLUMBINGREMODELPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200541 10.30.20 Addendum 100002.52.52.52.5555555551010101000002.52.52.52.55555555510101010
pbosf`b=pfkh=abq^fiqvmf`^i=mfmb=prmmloqp=abq^fiqo^m=mofjbo=abq^fit^ii=`ib^klrq=abq^firkabodolrka=mfmb=abq^ficillo=ao^fk=fk=bufpqfkd=cillo=abq^fi`ib^klrq=abq^fip`ljjbo`f^i=t^pebo=`lkkb`qflk=abq^fii^rkaov=ao^fk=EiaJNF=abq^fiFULL GRATE WITHREMOVABLE SECTIONSFOR SERVICING DRAINSSET DRAIN 1/4" BELOW CONCRETEFINISH ELEVATION TO ENSUREPOSITIVE DRAINAGEFD-2POURED-IN-PLACECONCRETE TRENCHSEWERGASESRWAETR TPA3'-0"5'-0"6'-0"(P-5) SERVICE SINKSERVICE SINK FAUCETHB, CONSISTING OF A 1/2"BALL VALVE, AND 3/4" HOSECONNECTION FOR SUPPLYTO "CUSTODIAL SOLUTIONSTATION (N.I.C.)".3/4" DHW AND DCWFLOORPRV SET @ 35PSI AND 5 GPM.1/2" REDUCED PRESSUREPRINCIPLE BACKFLOWPREVENTER.3/4"1/2"1/2" SUPPLY BRANCH,TYPICAL EACH FLOOR.PRESSURE GUAGE.SCALE: NONE1PL501CLAMPSWELDED STEELWALL BRACKETRODCINCH ANCHORSTHRU-BOLTADJUSTABLEPIPE STANDANGLETURNBUCKLEU-BOLTSTRAPSTEELEYEBOLTSSTEEL PLATEBLOCK WALLCLAMPSTEELCLEVISLOCKNUTC-WALL BRACKETSTEEL OFFSETU-BOLTSCINCH ANCHORS1/8"x1" RESTRAINING STRAPRODPIPE CLAMPI-BEAMEYEBOLTTURNBUCKLEANCHORRODANGLEU-BOLTSANCHORLAG BOLTS ORSCALE: NONE2PL501TRAP PRIMERVACUUM BREATHERPORTS.1/2"VALVE (TP-1)COLD WATER MAIN.1/2"FIN. FLOORFLOOR DRAINSCALE: NONE3PL501TEST TEECLFINISHED WALL SURFACEPLUGCLEANOUTTHREADEDCOVER PLATE WITHSECURING SCREWCENTERLINEMOUNTING HEIGHT CHARTDESCRIPTIONURINALSINKLAVATORYGENERAL WALLLOCATIONNOTE:12"12"48"HEIGHT12"COORDINATE WITH ARCHITECT PRIOR TOINSTALLING AT A HEIGHT OTHER THANTHAT LISTED ABOVE.SCALE: NONE4PL501WATER PIPINGGRAVELHOT OR COLDALL AROUND)SAND (3" MIN.CONCRETE FLOOR"THERMA-CEL"COMPACTEDPIPE INSULATIONDIRT FILLSCALE: NONE5PL50130"x30"BODYSLOPENOTE:GROUT1-1/4" MIN.ALSO TYPICAL FORFLOOR SINKS.FLOOR DRAINSCHEDULE FOR SIZEDRAIN), SEE PLUMBING(THREADS INTO FLOORDRAINAGE PIPINGFLOOR SLABEXISTING30"x30" 40 MIL. PVCSHOWER PAN LINER.TURN DOWN UNDERDRAIN CLAMPSTRAINERFLOOR DRAINCOLLARCLAMPINGTHAN FIXTURE TOPOF HOLE 6" LARGERFINISHED FLOOR. TOPSLOPESLOPESLOPESCALE: NONE6PL501`ib^klrq=ql=do^ab=E`lqdFcillo=`ib^klrq=Ec`lF1/8" BEND IF CLEANOUTOCCURS AT END OF LINELENGTH TO SUITCAST IRON WASTE LINE,1/8" CAST IRON BENDWASTE LINECAST IRON WASTE LINE,LENGTH TO SUIT1/8" CAST IRON BENDOCCURS AT END OF LINE1/8" BEND IF CLEANOUTWASTE LINECOVER. TOP OF COVERCLEANOUT AND ACCESSTO BE FLUSH W/ TOPOF FLOORFLOOR LINEFINISH GRADEBRASS CLEANOUT PLUGW/ COUNTER SUNK HEAD.TROWEL SMOOTH AND EDGE.16" SQUARE CONCRETE PADSCALE: NONE7PL501CLOTHES WASHER CONNECTION(SEE DRAWINGS)FROM BACKFLOW PREVENTERWHA3/4"(WM-1)CLOTHES WASHERSCALE: NONE8PL501P-TRAPSLOPE1" AIR GAPPROVIDE WATERPROOFINGMEMBRANE PERMANUFACTURER'SRECOMMENDED DETAILS.4"Ø OUTLETDRAIN PIPE6" WASHER TRENCHRECEIVING PIPEDRAIN PIPE FROM WASHER(TYPICAL OF 5)SUPPORT AND PIPE STRAPSTAINLESS STEEL UNISTRUTLINT SCREEN, 14 GAUGE 316 STAINLESS WITH 3/8"HOLES ON 3/4" SPACING, SIZE TO SLIDE DOWN INTOTRENCH TO COVER FULL WIDTH OF TRENCH WITH1/4" CLEARANCE BELOW BOTTOM OF GRATING.1" 316 STAINLESS STEEL ANGLE SECUREDTO TRENCH WALL WITH 1/4" CONCRETEANCHORS AT 8" SPACING. INSTALL ONBOTH SIDES OF TRENCH TO ACCEPT LINTSCREEN.NOTE:SEE DRAWINGS FOR SIZES OF TRENCHAND ARCHITECTURAL DETAILS FORCONSTRUCTION REQUIREMENTS.SCALE: NONE9PL50133332"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:16 AMPL501PLUMBINGDETAILSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200543 11.10.20 Addendum 3
MEN'S EMPLOYEELOCKER RM207AMEN'S STUDENTLOCKER RM207A(FC 3)P-5A(FC 5)P-2B(FC 10)P-1AP-1B(FC 10)HB-1HB-2HB-1HB-2P-3A(FC 1.5)P-3A(FC 1.5)FUTURE STEAMROOM CONNECTIONWHA-C3"(FC 10)P-1B1"(FC 5)P-2A(FC 5)P-2A(FC 10)P-1A(FC 5)P-2BP-3A(FC 1.5)P-3A(FC 1.5)2"2"3"3/4"1-1/2"WH-12"2"3"3"(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(FC 3)(E) WH1" TEPID 1" TEPID1" TEPID1"1-1/2" TEPIDP-5AP-5BP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5AP-5BP-5AP-5AP-5A(FC 3)P-5A1-1/4"1" 1"1"MV11-1/4"3/4"1"(E) WHCEILINGCEILINGESCUTCHEONHOSECONNECTION2"(E)2"(E)4"(E)2"(E)4"NURSING261DNURSING261BWOMEN'SSTUDENTLOCKER RM261WOMEN'SEMPLOYEELOCKER RM261A2"2-1/2"P-1BHB-1HB-2P-4AP-3AP-3A2"MV1HB-1HB-2P-3AP-3A2"2"2-1/2"WHA-CP-1BFUTURESTEAM ROOMCONNECTION1"1"1-1/4" TEPID(FC 3)P-5A(FC 3)P-5A(FC 3)P-5A(FC 3)P-5A(FC 3)P-5A(FC 3)P-5A(FC 3)P-5B(FC 3)P-5B(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 1.5)P-4A(FC 10)P-1A(FC 1.5) (FC 1.5) (FC 10) (FC 1.5)(FC 1.5)(FC 10) (FC 1.5)1-1/4" DCW1-1/4" 1-1/4"ao^tfkd=klqbp(E)2-1/2"(E)2"(E)2-1/2"(E)2"MENS183LAUNDRY RM180WOMEN'S181P-3A(FC 1.5)2"2"2"2"P-3A(FC 1.5)P-3A(FC 1.5)P-3A(FC 1.5)2"(FC 10)P-1A(FC 10)P-1A(FC 10)P-1BWHA-C(FC 10)P-1A2"(FC 5)P-2A(FC 5)P-2A(FC 5)P-2BWHA-B(FC 5)P-2A2" 2"P-3A(FC 1.5)2"2"2"P-3A(FC 1.5)P-3A(FC 1.5)P-3A(FC 1.5)P-3A(FC 1.5)P-3A(FC 1.5)2"1-1/4"2-1/2"(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1A(FC 10)P-1BWHA-C2-1/2"2-1/2"2-1/2"1"P-4B(FC 1.5)P-8(FC 2.25)1"BFP-2WM-1(FC3)BFP-2WM-1(FC3)MV3BALL VALVE, TYP.STRAINER, TYP.PRESSURE REDUCING VALVE,SET FOR 20 PSISOLID CHEMICAL DISPENSERLIQUID CHEMICAL DISPENSERPRESSUREGAUGE, TYP.3/4" SCW1"3/4"TEMPERATUREGAUGE321131CONNECT 3/4" DHW AND 3/4" DCW TO WASHERS PER DETAIL8/PL501 AND MANUFACTURERS WRITTEN INSTRUCTION.THERMOSTATIC MIXING VALVE SET FOR 115° F (ADJUSTABLE).3/4" THREADED CONNECTION WITH CAP FOR CONNECTION TOCHEMICAL DISPENSER TO BE INSTALLED BY PROVIDER.232"1"0"654321654321EDCBADATE REVISIONwww.ffkr.c omwww.ffkr.c omwww.ffkr.c omwww.ffkr.c om0 5/1 6 /2 01 6 JWSPROJECT NUMBER12/22/2020 10:14:17 AMPL601WATERFLOWDIAGRAMSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020BRIGHAM YOUNG UNIVERSITY - IDAHO200542 11.06.20 Addendum 23 11.10.20 Addendum 3SCALE:SCALE:SCALE:SCALE:PL601PL601PL601PL6011/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"t^qbo=cilt=af^do^j1111SCALE:SCALE:SCALE:SCALE:PL601PL601PL601PL6011/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"t^qbo=cilt=af^do^j2222SCALE:SCALE:SCALE:SCALE:PL601PL601PL601PL6011/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"t^qbo=cilt=af^do^j33333333333333333333
N
DN
UP
UP
UP
1/16" = 1’-0"
1 FIRE PROTECTION PLAN - LEVEL 1
FP-101
FIRE PROT.
PLAN
LEVEL 1JOHN W. HART BUILDING PHASE 3 REMODELREXBURG ID200542"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
www.ffkr.com
www.ffkr.com
www.ffkr.com
www.ffkr.com
05/16/2016 JWS
11/23/2020 CONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202011 12 13 14 15 16 17 21 22 23 24 25 26 27 28 29
L
M
H1
J1
19 20
F1
G1
C1
18
FIRE SPRINKLER KEY NOTES
1
2
3
RE: SHEETS FP101 & FP102
4
SUPPLY NEW FIRE SPRINKLERS INSTALLED AS PART OF THIS PHASE.
VERIFY LOCATION AND SIZE. CONNECT TO EXISTING FEED OR CROSS MAIN TO
EXISTING FIRE SPRINKLER SYSTEM FEED OR CROSS MAIN. CONTRACTOR TO FIELD
5
SUPPLYING FIRE SPRINKLERS IN ADJACENT AREAS TO PROVIDE WATER SUPPLY.
TABLE 2). CONNECT TO EXISTING FIRE SPRINKLER FEED AND/OR CROSS MAINS
DISCHARGE DENSITY OF 0.20 GPM/SQ FT OVER 2,500 SQ FT (FM GLOBAL 3-26
HEIGHT (IN EXCESS OF 30 FEET) DESIGN FIRE SPRINKLER SYSTEM FOR A MINIMUM
CLASSIFICATION OF LIGHT HAZARD (FM GLOBAL HC-1). DUE TO EXCESSIVE CEILING
SYSTEM EXPANSION SHALL BE HYDRAULICALLY DESIGNED TO PROTECT A HAZARD
FM GLOBAL DATA SHEETS AND SPECIFICATION SECTION 211313. FIRE SPRINKLER
FIRE SPRINKLERS IN ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 13,
PROTECT THROUGHOUT AREAS INDICATED ON PLAN. DESIGN, INSTALL AND TEST
AREAS AS A PART OF THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO
FIRE SPRINKLER SYSTEM TO PROTECT FITNESS CENTER 182 (AND ASSOCIATED
FITNESS CENTER 182 IS NOT PROTECTED BY FIRE SPRINKLERS. EXTEND EXISTING
PROVIDE WATER SUPPLY.
AND/OR CROSS MAINS SUPPLYING FIRE SPRINKLERS IN ADJACENT AREAS TO
PRESENT WITHIN EACH ROOM/AREA. CONNECT TO EXISTING FIRE SPRINKLER FEED
HC-2) OR LIGHT HAZARD (FM GLOBAL HC-1) AS APPROPRIATE FOR HAZARD
DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY (FM GLOBAL
SECTION 211313. FIRE SPRINKLER SYSTEM EXPANSION SHALL BE HYDRAULICALLY
APPLICABLE PROVISIONS OF NFPA 13, FM GLOBAL DATA SHEETS AND SPECIFICATION
INDICATED. DESIGN, INSTALL AND TEST FIRE SPRINKLERS IN ACCORDANCE WITH ALL
REMODEL IN THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO PROTECT AREA
AREA INDICATED IS NOT PROTECTED BY FIRE SPRINKLERS AND WILL UNDERGO
REMODEL.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
THROUGHOUT AREA IN ACCORDANCE WITH NFPA 13 AND FM GLOBAL DATA SHEETS.
REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE SPRINKLER PROTECTION
REMODEL. DEMO, MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS AND PIPING AS
AREA INDICATED IS PROTECTED BY EXISTING FIRE SPRINKLERS AND WILL UNDERGO
SPRINKLERS IN ADJACENT AREAS TO PROVIDE WATER SUPPLY.
EXISTING FIRE SPRINKLER FEED AND/OR CROSS MAINS SUPPLYING FIRE
APPROPRIATE FOR HAZARD PRESENT WITHIN EACH ROOM/AREA. CONNECT TO
ORDINARY (FM GLOBAL HC-2) OR LIGHT HAZARD (FM GLOBAL HC-1) AS
SHALL BE HYDRAULICALLY DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF
SHEETS AND SPECIFICATION SECTION 211313. FIRE SPRINKLER SYSTEM EXPANSION
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 13, FM GLOBAL DATA
PROTECT AREA INDICATED. DESIGN, INSTALL AND TEST FIRE SPRINKLERS IN
WILL UNDERGO REMODEL IN THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO
BID ALTERNATE - AREA INDICATED IS NOT PROTECTED BY FIRE SPRINKLERS AND
6
FACILITATE CEILING REPLACEMENT.
MAY REMAIN BUT REMOVE AND RE-INSTALL COVER PLATES AS REQUIRED TO
CEILING WORK TO OCCUR IN RACQUETBALL COURTS. EXISTING FIRE SPRINKLERS
1
1
1
4
4
4
4
1
1
1
3
3
3
2
2
2
6 6 6 6 6
5 5
55
55
5
5
5
N
UP
DN
UP
UP
DN
DN
1/16" = 1’-0"
1
FP-102
FIRE PROT.
PLAN
LEVEL 2
FIRE PROTECTION PLAN - LEVEL 2 JOHN W. HART BUILDING PHASE 3 REMODELREXBURG ID200542"1"0"654321
654321
EDCBADATE REVISION
PROJECT NUMBER
www.ffkr.com
www.ffkr.com
www.ffkr.com
www.ffkr.com
05/16/2016 JWS
11/23/2020 CONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/20201
2 43 5 6 7 10 11 12 13 14 15 16 17 21 22 23192018
FIRE SPRINKLER KEY NOTES
1
2
3
RE: SHEETS FP101 & FP102
4
SUPPLY NEW FIRE SPRINKLERS INSTALLED AS PART OF THIS PHASE.
VERIFY LOCATION AND SIZE. CONNECT TO EXISTING FEED OR CROSS MAIN TO
EXISTING FIRE SPRINKLER SYSTEM FEED OR CROSS MAIN. CONTRACTOR TO FIELD
5
SUPPLYING FIRE SPRINKLERS IN ADJACENT AREAS TO PROVIDE WATER SUPPLY.
TABLE 2). CONNECT TO EXISTING FIRE SPRINKLER FEED AND/OR CROSS MAINS
DISCHARGE DENSITY OF 0.20 GPM/SQ FT OVER 2,500 SQ FT (FM GLOBAL 3-26
HEIGHT (IN EXCESS OF 30 FEET) DESIGN FIRE SPRINKLER SYSTEM FOR A MINIMUM
CLASSIFICATION OF LIGHT HAZARD (FM GLOBAL HC-1). DUE TO EXCESSIVE CEILING
SYSTEM EXPANSION SHALL BE HYDRAULICALLY DESIGNED TO PROTECT A HAZARD
FM GLOBAL DATA SHEETS AND SPECIFICATION SECTION 211313. FIRE SPRINKLER
FIRE SPRINKLERS IN ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 13,
PROTECT THROUGHOUT AREAS INDICATED ON PLAN. DESIGN, INSTALL AND TEST
AREAS AS A PART OF THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO
FIRE SPRINKLER SYSTEM TO PROTECT FITNESS CENTER 182 (AND ASSOCIATED
FITNESS CENTER 182 IS NOT PROTECTED BY FIRE SPRINKLERS. EXTEND EXISTING
PROVIDE WATER SUPPLY.
AND/OR CROSS MAINS SUPPLYING FIRE SPRINKLERS IN ADJACENT AREAS TO
PRESENT WITHIN EACH ROOM/AREA. CONNECT TO EXISTING FIRE SPRINKLER FEED
HC-2) OR LIGHT HAZARD (FM GLOBAL HC-1) AS APPROPRIATE FOR HAZARD
DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY (FM GLOBAL
SECTION 211313. FIRE SPRINKLER SYSTEM EXPANSION SHALL BE HYDRAULICALLY
APPLICABLE PROVISIONS OF NFPA 13, FM GLOBAL DATA SHEETS AND SPECIFICATION
INDICATED. DESIGN, INSTALL AND TEST FIRE SPRINKLERS IN ACCORDANCE WITH ALL
REMODEL IN THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO PROTECT AREA
AREA INDICATED IS NOT PROTECTED BY FIRE SPRINKLERS AND WILL UNDERGO
REMODEL.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
THROUGHOUT AREA IN ACCORDANCE WITH NFPA 13 AND FM GLOBAL DATA SHEETS.
REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE SPRINKLER PROTECTION
REMODEL. DEMO, MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS AND PIPING AS
AREA INDICATED IS PROTECTED BY EXISTING FIRE SPRINKLERS AND WILL UNDERGO
SPRINKLERS IN ADJACENT AREAS TO PROVIDE WATER SUPPLY.
EXISTING FIRE SPRINKLER FEED AND/OR CROSS MAINS SUPPLYING FIRE
APPROPRIATE FOR HAZARD PRESENT WITHIN EACH ROOM/AREA. CONNECT TO
ORDINARY (FM GLOBAL HC-2) OR LIGHT HAZARD (FM GLOBAL HC-1) AS
SHALL BE HYDRAULICALLY DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF
SHEETS AND SPECIFICATION SECTION 211313. FIRE SPRINKLER SYSTEM EXPANSION
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 13, FM GLOBAL DATA
PROTECT AREA INDICATED. DESIGN, INSTALL AND TEST FIRE SPRINKLERS IN
WILL UNDERGO REMODEL IN THIS PROJECT PHASE. INSTALL FIRE SPRINKLERS TO
BID ALTERNATE - AREA INDICATED IS NOT PROTECTED BY FIRE SPRINKLERS AND
6
FACILITATE CEILING REPLACEMENT.
MAY REMAIN BUT REMOVE AND RE-INSTALL COVER PLATES AS REQUIRED TO
CEILING WORK TO OCCUR IN RACQUETBALL COURTS. EXISTING FIRE SPRINKLERS
2
2
2
2
1
1
1
1
4
4
4
4
1
1
1
1
2 2
2
CIRCUITING & GENERAL SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONKEYED NOTE REFERENCE1BRANCH CIRCUIT HOME-RUN TO PANEL INDICATEDA-1,3,53/4"C.-6#12,1#12GQTY & SIZE OF EQUIPMENT GROUND CONDUCTORQTY & SIZE OF NEUTRAL AND PHASE CONDUCTOR(S)SIZE OF CONDUITA-1,3,53/4"C.-6#12,1#12GPANEL AND CIRCUIT DESIGNATIONSEQUIPMENT GROUNDING CONDUCTORTICK MARKSNEUTRAL CONDUCTOR(S)PHASE AND/OR SWITCH-LEG CONDUCTOR(S)BRANCH CIRCUIT/FEEDER CONCEALED IN CEILING OR WALLBRANCH CIRCUIT/FEEDER CONCEALED UNDERGROUND OR FLOORNEW EQUIPMENT, DEVICES, ETC.EXISTING EQUIPMENT, DEVICES, ETC. DEMOLITION EQUIPMENT, DEVICES, ETC. DETAIL # / SHEET REFERENCE1 / ES101*25,000ACALCULATED AVAILABLE FAULT CURRENT AT EQUIPMENT(SEE POWER RISER)FIRE ALARM SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONDETECTOR SUBSCRIPTSP PHOTOELECTRIC SMOKE DETECTOR D DUCT SMOKE DETECTORID IN-DUCT SMOKE DETECTOR H HEAT DETECTORM MULTI-STATION SMOKE DETECTOR (120V W/BATTERY BACKUP)FIRE ALARM CONTROL PANEL (WALL MOUNTED, TOP AT 6'-0' AFF)FFACPNOTIFICATION DEVICE EXTENDER PANEL. PROVIDE QTY AS REQUIRED BASED ON DEVICE VOLTAGE DROP CALC'S PER NFPA 72 REQUIREMENTS. (WALL MOUNTED, TOP AT 5'-0' AFF)REMOTE ANNUCIATOR PANEL (FLUSH MOUNTED IN WALL AT 5'-0' AFF)NACRAMANUAL PULL STATION (MOUNTING HEIGHT PER ADA & NFPA 72)MAGNETIC DOOR HOLD OPEN ADDRESSABLE CONTROL/RELAY MODULEMMCMADDRESSABLE MONITORING MODULEFIRE ALARM FLOW SWITCHFIRE ALARM TAMPER SWITCHFSTSWALL MOUNTED FIRE ALARM HORN ONLYWALL MOUNTED FIRE ALARM STROBE ONLY(CANDELA RATING AS INDICATED)#ADDRESSABLE DETECTOR WITH BASE####CEILING MOUNTED FIRE ALARM STROBE ONLY(CANDELA RATING AS INDICATED)####WALL MOUNTED FIRE ALARM SPEAKER STROBE(CANDELA RATING AS INDICATED)CEILING MOUNTED FIRE ALARM SPEAKER STROBE(CANDELA RATING AS INDICATED)EXTERIOR 120V FIRE BELL, INSTALL NEXT TO FDC.FIRE/SMOKE DAMPER; COORDINATE LOCATIONS WITH MECH. DRAWINGSSDA. DO NOT INSTALL MORE THAN (10) NOTIFICATION APPLIANCES ON ANY SINGLE CLASS "A" SIGNAL CIRCUIT. DO NOT EXCEED 400 FT. OF NO. 14 WIRE IN THE TOTAL LOOP.B. NFPA ALLOWS NOTIFICATION APPLIANCES TO BE MOUNTED AT A HEIGHT RANGE BETWEEN 80" TO 96" ABOVE FINISH FLOOR. THE PREFERRED HEIGHT IS 80". IF THIS CONFLICTS WITH OTHER TRADES OR ROOM FURNISHINGS, LOCATE AS CLOSE TO 80" AS POSSIBLE, NOT EXCEEDING 96". ALL NOTIFICATION APPLIANCES IN A COMMON ROOM OR LINE OF SIGHT SHALL BE LOCATED AT A COMMON HEIGHT.C. MOUNT PULL STATIONS AT 46-48" A.F.F. TO THE OPERATING HANDLE TO MEET ADA REQUIREMENTS.D. DO NOT CONNECT THE FIRE ALARM SYSTEM TO ANY DEVICE WHICH HAS A POWER HELD CONTACTS.(FLOW, TAMPER, HOOD SYSTEM, DUCT DETECTOR, ETC..FALSE ALARM WILL OCCUR.E. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL CONDUCTOR QUANTITIES PER FIRE ALARM SYSTEM SUPPLIER, AND AS PER NFPA AND NEC REQUIREMENTS.F. DO NOT INSTALL ANY SMOKE OR HEAT DETECTORS WITHIN 3 FEET OF ANY AIR DIFFUSER.G. DO NOT EXCEED 2500 FEET ON ANY ADDRESSABLE DEVICE RUN. DO NOT EXCEED 120 DEVICES ON ANY ONE ADDRESSABLE DEVICE RUN.H. ALL AIR HANDLING EQUIPMENT 2000 CFM OR MORE MUST BE SHUT DOWN UPON FIRE ALARM AS PER LIFE SAFETY CODES.I. ALL CLASS "B" INITIATING CIRCUITS WITH ADDRESSABLE DEVICES NEED EOLR. (END OF LINE RESISTORS).J. IN CORRIDORS, NOTIFICATION APPLIANCES MUST BE LOCATED WITHIN 15' FROM ENDS OF CORRIDORS AND A MAXIMUM OF 100' SPACING.K. NOTIFICATION APPLIANCES TO BE SYNCHRONIZED TO PROVIDE A 3-3-3 TEMPORAL PATTERN.L. ALL WIRING AND CONDUIT ROUTING TO BE AS DESCRIBED ON SUPPLIED SHOP DRAWINGS. FIRE ALARM PLAN IS SHOWN FOR GENERAL LOCATION AND LAYOUT ONLY.M. THE FIRE ALARM SYSTEM TO BE IN COMPLIANCE WITH ALL APPLICABLE LOCAL, STATE AND ADA REQUIREMENTS.N. ELECT. CONTR. TO CONNECT SPRINKLER SYSTEM TAMPER SWITCHES AND FLOW VALVES TO FIRE ALARM SYSTEM AS REQUIRED. SEE FIRE SPRINKLER SYSTEM DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.GENERAL FIRE ALARM SYSTEM NOTESLIGHTING SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONPARKING AREA POLE LIGHT, SINGLE OR DOUBLE HEAD AS INDICATED ONDRAWINGS. REFER TO LIGHT POLE DETAIL FOR POLE INFORMATION.2X4 FLUORESCENT OR LED FIXTURE2X2 FLUORESCENT OR LED FIXTURESURFACE MOUNTED FLUORESCENT OR LED FIXTURESTRIP FLUORESCENT OR LED FIXTUREWALL MOUNTED FLUORESCENT OR LED FIXTUREEXTERIOR WALL MOUNTED FIXTUREROUND RECESSED FIXTURESURFACE OR PENDANT FIXTURELIGHT FIXTURE SUBSCRIPTSNL NIGHT-LIGHT(CONNECT TO UNSWITCHED LEG OF CIRCUIT)EXIT SIGN, WALL OR CEILING MOUNTING AS REQUIRED (SINGLE OR DOUBLE FACE)DIRECTIONAL CHEVRONS AS INDICATED; CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS THE EXIT SIGNS.SHADED FIXTURE INDICATES AN EMERGENCY FIXTURE. PROVIDE WITH EMERG. BATTERY PACK OR CONNECT TO EMERGENCY POWER SYSTEM (WHERE APPLICABLE). CONNECT BATTERY PACK TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT SERVES THE SAME AREA AS THE EMERGENCY FIXTURE. PROVIDE WITH TEST LIGHT AND SWITCH. CEILING MOUNTED OCCUPANCY SENSOR, REFER TO OCCUPANCY SENSOR/SWITCHSCHEDULE FOR SENSOR TYPE AND ADDITIONAL INFORMATION.SWITCH MOUNTED OCCUPANCY SENSOR OR LOW VOLTAGE SWITCHPOD, REFER TO OCCUPANCY SENSOR/SWITCH SCHEDULE FOR TYPE AND ADDITIONAL INFORMATION.SINGLE-POLE SWITCH (SEE SUB-SCRIPTS BELOW FOR ADDITIONAL INFORMATION)SWITCH SUBSCRIPTS3 3-WAY SWITCH4 4-WAY SWITCHD DIMMER SWITCH (COMPATIBLE W/ LOAD & LTG TYPES)ELV DIMMER: ACUITY P/N: ISD 400 ELV 120 **0-10V DIMMER: ACUITY P/N: ISD BC 120/277 **K KEYED SWITCHF TIMER SWITCH (INTERMATIC MODEL EI400 SERIES)P PILOT LIGHTED SWITCHF1LIGHT FIXTURE TYPE DESIGNATIONS###WALL OR CEILING MOUNTED EMERGENCY LIGHTING UNIT W/BATTERY PACKCONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS THE EMERGENCY LIGHT.LV LOW-VOLTAGE SWITCH (PER DWG'S)T THERMAL-OVERLOAD SWITCHM SWITCH SUPPLIED WITH EQUIPMENT, INSTALLED BY E.C.WP WEATHERPROOF2P DOUBLE POLE, SINGLE THROW SWITCHGENERAL LIGHTING NOTES:A. SYMBOLS SHOWN ABOVE MAY NOT REPRESENT ALL LIGHT FIXTURES USED ON PROJECT, REFER TO LIGHT FIXTURE SCHEDULE FOR ACTUAL FIXTURE INFORMATION INCLUDING FIXTURE TYPE, LAMPING, MOUNTING AND ETC.B. JUNCTION BOXES FOR LIGHTING CIRCUITING ARE NOT SHOWN FOR CLARITY. THE E.C. IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL JUNCTION BOXES REQUIRED FOR CIRCUITING OF ALL LIGHT FIXTURES THAT ARE NOT LISTED FOR "THROUGH-BRANCH CIRCUIT WIRING".C. IN GENERAL ALL SWITCH-LEG CONDUCTORS MAY NOT BE SHOWN ON DRAWINGS; E.C. SHALL PROVIDE AND INSTALL CONDUCTORS AS REQUIRED TO ACHIEVE CONTROL SCHEMES INDICATED AND DESCRIBED ON DRAWINGS. INCLUDING ALL 0 - 10V DIMMING CONTROLS BETWEEN SWITCH AND FIXTURES.D. ALL BATTERY EXIT SIGNS AND EMERGENCY LIGHTING TO BE CONNECTED TO THE UNSWITCHED LEG OF THE LIGHTING CIRCUIT IN THE AREA.###FMPOWER SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONELECTRICAL SWITCHBOARD EQUIPMENT, (SEE POWER RISER AND PANEL SCHEDULES FOR ADDITIONAL INFORMATION)'MSB''T##'DRY-TYPE TRANSFORMER, (SEE POWER RISER FOR ADDITIONAL INFORMATION)'LA'ELECTRICAL PANELBOARD, (SEE POWER RISER AND PANEL SCHEDULESFOR ADDITIONAL INFORMATION)DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATEDTYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3RFUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATEDTYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R(30A FUSES)COMBINATION STARTER & FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED. TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4XJJUNCTION BOXCR = CORD REEL; SEE DRAWINGS FOR INFORMATIONCD = CORD DROP; SEE DRAWINGS FOR INFORMATIONEQUIPMENT CONNECTION; COORDINATE CONNECTION WITH EQUIPMENTPRIOR TO ROUGH-INMOTOR CONNECTIONPOWER AND/OR DATA SERVICE POLEFLOORBOX WITH POWER ONLY (SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION) PUSHBUTTON STATIONFLOORBOX WITH POWER AND DATA(SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION) FB#FB#SPECIAL RECEPTACLE (COORDINATE NEMA TYPE WITH EQUIP.) (REFER TO PANEL SCHEDULES FOR AMPS)CEILING MOUNTED DUPLEX RECEPTACLE (COORDINATE PLACEMENT WITH CEILING EQUIPMENT PRIOR TO ROUGH-IN)DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FTGFCI-TYPE DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FTDOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FTGFCI-TYPE DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT.RECEPTACLE AND EQUIPMENT SUBSCRIPTSACABOVE COUNTERWPWEATHERPROOF (UL LISTED WEATHER-RESISTANT)42"MOUNTING HEIGHT AFF OR AFGIGISOLATED GROUNDSSURGE-PROTECTION TYPEREFREFRIGERATORWWASHING MACHINEDDRYER (30A-240V RATED RECPT.)MMICROWAVE HVAC THERMOSTAT OR SENSOR; PROVIDE & INSTALL BACKBOX,3/4" CONDUIT AND CONDUCTORS TO ASSOCIATED HVAC UNIT. COORDINATE EXACT LOCATION & SIZE AND NUMBER OF CONDUCTORS WITH M.C. TSOR30A/3P/3RSIZE 1(30A FUSES)SMALL EXHAUST FAN CONNECTIONTV120V RECEPT. FOR TV; VERIFY HEIGHT WITH ARCH. DRAWINGS & ELEVATIONSUSB120V RECPT. WITH USB CHARGING PORTSEWCELECTRIC WATER COOLER; (SEE DETAIL. RECPT. SHALL BE ACCESSIBLE, DO NOT MOUNT BEHIND HOUSING.)DISPGARBAGE DISP. (UNDER SINK)DWDISHWASHER (COORDINATE W/ MILLWORK, INSTALL PER NEC 422.16(B)(2)).M/RMICROWAVE/RANGE HOOD (COORDINATE W/ MILLWORK)RELECTRIC RANGE (50A-240V RATED RECPT.)GENERAL SPECIAL SYSTEM NOTES:A. ALL DEVICES SHOWN AT OR NEAR MILLWORK/CASEWORK SHALL BE COORDINATED WITH THE ARCHITECTURAL ELEVATION DRAWINGS AND MILLWORK INSTALLER TO INSURE PROPER MOUNTING HEIGHTS. CONTRACTOR SHALL ADJUST DEVICES AS NECESSARY IN ORDER TO POSITION DEVICES SUCH THAT THEY WILL NOT FALL BEHIND MILLWORK, CABINETS OR BE DIRECTLY ABOVE SINKS OR MIDWAY BETWEEN TILEWORK/WALL OR WAINSCOATING, ETC. B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A GFCI TYPE RECEPTACLE FOR ALL RECPTACLES SHOWN IN TOILET RMS, BATHROOMS, KITCHENS/SERVING AREAS, ROOFTOP, OUTDOORS OR WITHIN 6FT OF ANY SINK, BASIN, TUB OR FLOOR SINK AND ALL OTHER AREAS DEFINED BY THE NEC.SPECIAL SYSTEMS SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONDATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-XTELEPHONE OUTLET; _= # OF TELEPHONE CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_T-XTELEPHONE/DATA OUTLET; _= # OF TELEPHONE/DATA CABLES, X=CONDUIT SIZE(SEE NOTES 1,2,3 BELOW)_T/_D-XCEILING MOUNTED DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-XA. COMMUNICATIONS CABLES SHALL HAVE BENDS NO GREATER THAN 90 DEG.B. CONDUITS FOR COMMUNICATIONS CABLING SHALL HAVE A MAXIMUM BEND RADIUS NOT MORE THAN 10X THE DIAMETER OF THE CONDUIT.C. ALL COMMUNICATIONS CONDUITS SHALL BE TERMINATED WITH AN INSULATED NON-METALLIC BUSHING AT BOTH ENDS.D. COMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN (2) 90'S WITHOUT A PULLBOX. PULL BOXES SHALL BE LOCATED IN ACCESSIBLE LOCATIONS AND SHALL BE SIZED AT LEASED 12X THE LARGEST CONDUIT DIAMETER IN LENGTH AND MIN, 4" DEEP AND 8" WIDE.E. IT SHALL BE THE RESPONSIBILITY OF THE E.C. TO INSURE THAT THE PATHWAY FOR THE DATA CABLING DOES NOT CREATE CABLE LENGTHS TO EXCEEDS THE LENGTH OF 295FT FROM OUTLET TO PATCH PANEL, THIS INCLUDES SERVICE LOOPS AND PATCH CORDS. F. WHERE CABLE TRAY IS UTILIZED IN THE PROJECT. COMMUNICATION CONDUITS ENDING AT THE CABLE TRAY SHALL EXTEND 1" OVER THE SIDE INTO THE TRAY. GENERAL SPECIAL SYSTEM NOTES:RECESSED WALL MOUNTED AV OUTLETHUBBELL ENCLOSURE #NSV62M(1) POWERKIT HBL#NSOKPS, (1) 4-PORT DATA PLATE HBL#NSP14WMOUNT BEHIND TV HEIGHT PER ARCHITECHE.C. SHALL INSTALL 1" C., FROM DATA COMPARTMENT TO IT ROOM, INSTALL (1) COAX CABLE AND (1) CAT 6A CABLE TO DATA RACK, MAKE ALL TERMINATIONS.LARGE CAPACITY 3-GANG AV BOX W/ RECEPTACLE, (SEE NOTE 2 BELOW)HUBBELL# HBL263 WITH 3-GANG MUDRING & LV DIVIDER HBL981; PROVIDE 3-GANG DECORA COVER PLATE WITH THE FOLLOWING:(1) 20A DUPLEX RECEPTACLE(1) DATA INSERT (LEVITON P/N: 4164x-xxx) OR EQUAL(1) BRUSH PASSTHROUGH INSERT (LEVITON P/N: 41075-DBx).INSTALL 1 1/2" CONDUIT FROM BOX TO ABOVE ACCESSIBLE CEILING W/DATA CABLING/ TERMINATIONS AS INDICATED ON DRAWINGS. TVAV_D-XSPECIAL SYSTEMS NOTES:1. UTILIZE 4 11/16" DEEP BOX WITH REQUIRED MUDRING AND CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING OR DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING. PROVIDE QTY OF CABLES INDICATED FROM OUTLET TO NEAREST TELE/DATA ROOM. SEE DWGS FOR ADDITIONAL INFORMATION. UTILIZE J-HOOKS 3FT ON CENTER FOR SUPPORT OF CABLING WHERE CABLE TRAY IS NOT INSTALLED/SPECIFIED.2. CONDUIT SIZE ('X' FROM ABOVE); 2=1/2", 3=3/4", 4=1", 5=1-1/4", 6=1-1/2"3. BLANK (NO LABEL) = 4-11/16" DEEP BOX WITH REQUIRED MUDRING AND 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING/CABLE TRAY, TERMINATE WITH INSULATEDTHROAT BUSHING, PROVIDE PULL STRING. (UNLESS OTHERWISE NOTED)4. USE A MINIMUM OF 1" CONDUIT FOR ALL DATA CABLING WALL PATHWAY SYSTEM; STI FIRESTOP EZ-PATH SERIES INSTALL THROUGH WALL ABOVE ACCESSIBLE CEILING, FIELD VERIFY EXACT LOCATION TO AVOID CONFLICT WITH OTHER TRADES AND UTILITIES. PROVIDE ALL REQUIRE MOUNTING HARDWARE AND ETC. FOR COMPLETE INSTALLATION.EPF2 = FIRE RATED, EZ-PATH SERIES 22EPF3 = FIRE RATED, EZ-PATH SERIES 33EPF4 = FIRE RATED, EZ-PATH SERIES 44EP3 = NON-FIRE RATED, EZ-PATH 33NEZ SERIES###FB#_D-XMULTI-SERVICE FLOORBOX; SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION._= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)P1PH2/C3/C3P3PH3W4WACADAAFFAFGAICALA or AMPANNAPATSAVAWGBFG CCATVCBCCTVCKTCCPCTCUDSEAE.C.EMEMTENTEPOEQUIPEXFAFACPFLAFMCGNDG.C.GENGFIGFPHDHIDHOAHPHPSHVHZIGIMCJ-BOXABBREVIATIONSSINGLE POLESINGLE-PHASETWO-CONDUCTORTHREE-CONDUCTORTHREE POLETHREE-PHASETHREE-WIREFOUR-WIREABOVE COUNTERAMERICANS WITH DISABILITIES ACTABOVE FINISHED FLOORABOVE FINISHED GRADEAMPERE INTERRUPTING CAPACITYALUMINUMAMPEREANNUNCIATORACCESS POINT(WIRELESS DATA)AUTOMATIC TRANSFER SWITCHAUDIO VISUALAMERICAN WIRE GAGEBELOW FINISHED GRADECEILING MOUNTEDCABLE TELEVISIONCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCIRCUITCONDUITCONTROL PANELCURRENT TRANSFORMERCOPPERDISCONNECT SWITCHEACHELECTRICAL CONTRACTOREMERGENCYELECTRICAL METALLIC TUBINGELECTRICAL NONMETALLIC TUBINGEMERGENCY POWER OFFEQUIPMENTEXISTINGFIRE ALARMFIRE ALARM CONTROL PANELFULL LOAD AMPSFLEXIBLE METAL CONDUITGROUNDGENERAL CONTRACTORGENERATORGROUND FAULT CIRCUIT INTERRUPTERGROUND FAULT PROTECTIONHEAVY DUTYHIGH INTENSITY DISCHARGEHAND-OFF-AUTOMATICHORSE POWERHIGH PRESSURE SODIUMHIGH VOLTAGEHERTZISOLATED GROUNDINTERMEDIATE METAL CONDUITJUNCTION BOXVKVAkWkWhLEDLFMCLFNCLTGLVMAXM.C.MCAMCBMCCMDPMHMINMLOMOCPNANCNECNEMANFPANICNLNONTSOCOH DROLPBPPNLPTPTZQTYRCPRMCRNCSCASCBASFSPDSPECSWBDSWGRTLTPTTBTVTYPUGUPSVVAV.I.F.VFDW/W/OWPXFMRKILOVOLTKILOVOLT AMPEREKILOWATTKILOWATT HOURLIGHT EMITTING DIODELIQUID TIGHT FLEXIBLE METAL CONDUITLIQUID TIGHT FLEXIBLE NONMETALLIC CONDUITLIGHTINGLOW VOLTAGEMAXIMUMMECH. CONTRACTORMINIMUM CIRCUIT AMPSMAIN CIRCUIT BREAKERMOTOR CONTROL CENTERMAIN DISTRIBUTION PANELMANHOLEMINIMUMMAIN LUGS ONLYMAXIMUM OVERCURRENT PROTECTIONNOT APPLICABLENORMALLY CLOSEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNATIONAL FIRE PROTECTION ASSOCIATIONNOT IN CONTRACTNIGHT LIGHTNORMALLY OPENNOT TO SCALEON CENTEROVERHEAD DOOROVERLOADPUSHBUTTONPHASEPANELPOTENTIAL TRANSFORMERPAN/TILT/ZOOMQUANTITYREFLECTED CEILING PLANRIGID METAL CONDUITRIGID NONMETALLIC CONDUITSHORT CIRCUIT AMPSSTANDARD COLOR BY ARCHITECTSQUARE FOOT (FEET)SURGE PROTECTION DEVICESPECIFICATIONSWITCHBOARDSWITCHGEARTWIST LOCKTWISTED PAIRTELEPHONE TERMINAL BOARDTELEVISIONTYPICALUNDERGROUNDUNINTERRUPTIBLE POWER SUPPLYVOLTSVOLT AMPEREVERIFY IN FIELDVARIABLE FREQUENCY DRIVEWITHWITHOUTWEATHERPROOFTRANSFORMERA. E.C. SHALL REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT AND ELECTRICAL CONNECTIONS.B. E.C. SHALL PROVIDE MINIMUM WORKING CLEARANCE AS PER NEC BEFORE INSTALLING ANY ELECTRICAL PANELS OR CABINETS. SEE ELECTRICAL EQUIPMENT CLEARANCE DETAIL.C. INSTALL ALL LIGHT FIXTURES IN MECHANICAL ROOM AFTER THE MECHANICAL EQUIPMENT IS IN PLACE. ADJUST AS NECESSARY. PROVIDE CHAIN SUSPENSION KITS AS REQUIRED.D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN(S) FOR EXACT FIXTURE LOCATIONS, CEILING TYPES, ETC.E. E.C. SHALL PROVIDE ALL CONCRETE PADS AS REQUIRED FOR ALL ELECTRICAL EQUIPMENT.F. CONFIRM EXACT LOCATIONS OF ALL TELEPHONE/DATA OUTLETS WITH OWNER PRIOR TO ROUGH-IN.G. LOCATE SWITCHES, OUTLETS, ETC., SHOWN AT ROOM ENTRY DOORWAYS, AS CLOSE TO DOOR FRAME AS POSSIBLE, SO AS NOT RO INTERFERE WITH ROOM CABINETS, ETC.H. SUPPORT ALL LIGHT FIXTURES INDEPENDENT OF CEILING.I. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL APPLICABLE PERMITS FOR WORK AND PAY ASSOCIATED FEES.J. MAINTAIN 24" MIN. CLEARANCE FROM ALL COMMUNICATIONS CABLING AND ELECTRONIC BALLASTS.K. UNLESS SPECIFICALLY INDICATED OTHERWISE, E.C. SHALL COORDINATE WITH ANY SPECIAL SYSTEMS SUPPLIER/SHOP DRAWINGS; DENTAL, MEDICAL, KITCHEN, SPECIALIZED EQUIPMENT, ETC. FOR THE EXACT ROUGH-IN REQUIREMENTS FOR THEIR EQUIPMENT. ALSO UNLESS INDICATED OTHERWISE, THE E.C. TO BE RESPONSIBLE FOR FINAL ELECTRICAL CONNECTIONS TO ALL SPECIAL EQUIPMENT.L. ALL CONDUIT/RACEWAY/CABLES TO BE CONCEALED IN WALLS OR ABOVE CEILINGS. IF ANY SURFACE WORK IS NECESSARY, IT SHALL BE APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.M. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY INVESTIGATE THE EXISTING CONDITIONS, AS THEY RELATE TO THE SCOPE OF WORK DESCRIBED. MAKE NECESSARY PROVISIONS IN THE BASE BID TO ADEQUATELY ACCOMMODATE THESE CONDITIONS. N. DATA CABLING SYSTEM PRE-INSTALLATION CONFERENCE:1. E.C. SHALL SCHEDULE A MEETING A MINIMUM OF FIVE CALENDAR DAYS PRIOR TO BEGINNING DATA CABLING INSTALLATION . ATTENDEES SHOULD INCLUDE OWNER’S REP., ENGINEER, GC, EC AND CABLING SUB. REFER TO SECTION 26 6210(1.4)(E) FOR ADDITIONAL INFORMATION.PROJECT GENERAL NOTES:CONTACT: Jarom Taylor Nexant(801) 746-1623for assistanceUTILITY LIGHTING REBATES & INCENTIVES:IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PREPARE ALL REQUIRED APPLICATIONS AND INFORMATION REQUIRED TO PROVIDE THE OWNER WITH THE MAXIMUM AMOUNT OF REBATE DOLLARS FROM THE LOCAL UTILITY COMPANY. THE ELECTRICAL CONTRACTOR SHALL SUBMIT VERIFICATION OF THE UTILITY COMPANY PRE-APPLICATION APPROVAL PRIOR TO ORDERING ANY MATERIALS.TYPICAL DEVICE MOUNTING HEIGHTS:GENERAL COORDINATION NOTE:GENERAL DETAIL NOTES:FINISH FLOOR1' - 6''THERMOSTAT OR SENSORVERIFY WITH M.C. PRIOR TOLIGHT SW.(OR AS NOTED)* 4' - 0''* 3' - 6''(OR AS NOTED)RECEPTACLE@ MILLWORKBACKSPLASHCAB. DIMENSIONSPER ARCH. DETAIL6"CABINET* E.C. SHALL COORDINATE ALL DEVICEMOUNTING HGTS. AND EXACT LOCATIONWITH ARCHITECTURAL INTERIORELEVATIONS REPORT CONFLICTS TOARCHITECT **PRIOR TO ROUGH-IN**ROUGH-IN.TYPICAL FOR ALL DEVICESMOUNTED ABOVE COUNTER(ie C.O.'S, DATA, PHONE etc.)A.B.C.D.ALL MOUNTING HEIGHTS TYPICAL UNLESSNOTED OTHERWISE.COORDINATE OUTLET HEIGHTS WITHARCHITECTS MILLWORK DWGS. TO INSURETHAT OUTLETS WILL NOT FALL BEHINDCABINETS, BACKSPLASHES, OR INTERFEREWITH WAINSCOTING, ETC.ALL SWITCHES AND THERMOSTATS TO BEMOUNTED AS CLOSE TO DOOR JAMS ASPOSSIBLE. COORDINATE ALL DEVICES WITHARCHITECTURAL PLANS AND DETAILS.COORDINATE LIGHT SWITCH & OUTLETHEIGHTS WITHARCHITECTURALWAINSCOTING AND OR TILE WORK SO ASNOT TO FALL MIDWAY IN THESE FINISHES.FIRE6' - 8''FIRE ALARM NOTIFICATIONDEVICEFIREMANUAL PULL STATIONHANDLE SHALL BEBETWEEN 42" & 48" AFFCABINETRECEPT.TELE/DATAOUTLETTVOUTLETELECTRICAL EQUIP. CLEARANCEELECTRICALEQUIPMENTNOTE #1NOTE#4NOTE#3NOTE#2NOTES:1. THE MINIMUM HEADROOM OF WORKING SPACE SHALL BE 6 1/2FT.2. THE WIDTH OF THE WORKING SPACE SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS GREATER. THE PANEL DOOR SHALL OPEN AT LEAST 90 DEGREES.3. ALL CIRCUIT BREAKERS, WHEN IN THIER HIGHEST POSITION, SHALL NOT BE MORE THAN 6FT 7 IN. ABOVE THE FINISHED FLOOR.4. 3FT CLEARANCE IF 0-150V TO GROUND, 3.5FT CLEARANCE IF 151-600V TO GROUND. 4FT IF EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING SPACE.GENERAL NOTES:A. ALL WORKING SPACE CLEARANCES ARE FROM THE FACE OF THE EQUIPMENT.8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:13 AMEG100ELECTRICALSYMBOLS &DETAILSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054SECURITY & ACCESS CONTROL SYMBOL SCHEDULENOTE: ALL SYMBOLS MAY NOT BE USEDSYMBOLDESCRIPTIONCARD READER/KEYPAD: UTILIZE 4SQ. BOX W/ 1-GANG MUDRING, 3/4" C., TO ABOVE NEAREST ACCESSIBLE CEILING AND PULL STRINGCRCAMSECURITY CAMERA: PROVIDE AND INSTALL A 4SQ. BOX W/ 3/4" C., 1-CAT6A CABLE TO NEAREST I.T. ROOM. TERMINATE JACK ON THE CABLE FOR THE CAMERA, CAMERA TO BE MOUNTED OVER BOX. COORDINATE EXACT ROUGH-IN W/ OWNER'S CAMERA SPEC.CONNECTION TO DOOR FRAME FOR ACCESS CONTROL PROVIDE (1) 3/4" C,. FROM DOOR FRAME TO ABOVE NEAREST ACCESSIBLE CEILING, WITH PULL STRING• E.C. SHALL PROVIDE AND INSTALL CCTV CAMERA AS INDICATED ON DRAWINGS. PROVIDE ALL REQUIRED CABLING, TERMINATIONS AND MOUNTING HARDWARE. COORDINATE INSTALLATION WITH BYU-I SECURITY DEPARTMENT.• E.C. SHALL COORDINATE ALL ACCESS CONTROL ROUGH-IN AND INSTALLATIONS WITH BYU-I PRIOR TO ANY INSTALLATIONS.GENERAL SECURITY & ACCESS CONTROL NOTES:Contact:Braden Howard - System Integrator / Technical Services801-871-5483bhoward@barbizon.comwww.barbizon.comBARBIZON CONTACT INFORMATION:1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
24356789101112131415161718212223242526272829BACDEFGHJKLMH1J11920F1G1C1D1(1/EE100)(2/ED100)(3/EE100)(2/EE100)WORK AREA -ACTIVITY STORAGE & ALTERNATEWORK AREA -ACTIVITY STORAGE & ALTERNATE(4/EE100)(6/EE100)(5/EE100)(3/ED100)WORK AREA -SPINNING ROOM & ACTIVITY STORAGE(1/EE101)(3/EE101)(2/EE101)(2/ED100)'NL'MAIN PANEL PROVIDE AND INSTALL NEW 225A 3P BREAKER FOR NEW PANEL 'NL'2 1/2' C., 4-4/0+GNDDISCONNECT AND REMOVE EXISTING MCC IN FIELD HOUSE. REMOVE ALL EXISTING CONDUIT AND FEEDER BACK TO SOURCE.A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:15 AMEG101FIRSTFLOOROVERALLPLANSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/20202005440'20'0"NORTHSCALE: 1" = 20'-0"1LEVEL 1 - OVERALL1 10/30/2020 Addendum #1
124356789101112131415161718212223242526272829BACDEFGHJKLMH1J11920F1G1C1D1(1/EE104)AREA OF WORK -MAIN GYM(5/ED100)(5/EE103)(4/EE103)AREA OF WORK -SOUTHWEST EXIT(4/ED100)(1/EE103)(3/EE103)AREA OF WORK -SOUTHEAST EXIT(6/EE103)(2/EE103)(2/ED101)(6/EE102)(5/EE102)AREA OF WORK -WOMEN'S LOCKERROOM(1/ED101)(1/EE102)(3/EE102)(2/EE102)AREA OF WORK -MEN'S LOCKERROOM'P3M'PANELLOCATED IN LEVEL (3) MECH ROOM 333 AREA OF WORK -HVAC UPGRADE(1/EE105)AREA OF WORK -NORTH HALLWAY(3/ED101)(5/EE101)(4/EE101)(4/EE102)A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:SCALE: 1" = 20'-0"1LEVEL 2 - OVERALL40'20'0"NORTH8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:18 AMEG102SECONDFLOOROVERALLPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #1
TEE BAR GRIDPOWER SUPPLY CONDUIT FOR CEILING OR WALL "J" BOX.SUPPORT WIRE BY ELECTRICAL CONTRACTOR INDEPENDENT OF CEILING SYSTEM. (TYPICAL)ACOUSTIC CEILINGTILESUPPORT CLIPSALL SIDESENTRANCECONDUIT(S)4" SQUAREBOXRAISED RINGTO SUIT WALLRECEPTACLE - 20AMPRATED - SEE SPECIFICATIONS.NORMAL POWER COLOR - (SEE SPEC'S)COVER PLATE - STYLE & COLORTO BE AS PER SPECIFICATIONS.CIRCUIT NUMBER TO BE WRITTEN ONBACK OF COVER W/FELT-TIP MARKERGREEN INSULATEDGROUND CONDUCTORLEVEL 291' -0"1617F16 RECESSED LIGHT FIXTURECIRCUIT TO PANEL L, CIRCUIT THROUGH LIGHTING CONTACTOR LOCATED NEXT TO PANEL L.LIGHTING CONTROL (nLIGHT) SYSTEM SCHEDULETYPE MFGR. CATALOG # DESCRIPTIONNOTESCEILING SENSORSnD1 SENSOR SWITCH nCM-PDT-9-RJB-ADCXDUAL-TECHNOLOGY, SMALL MOTION, CEILINGOCCUPANCY SENSOR W/ AUTO DIMMING CONTROLPHOTOCELLnD2 SENSOR SWITCH nCM-PDT-10-RJB-ADCXDUAL-TECHNOLOGY, LARGE MOTION, CEILINGOCCUPANCY SENSOR W/ AUTO DIMMING CONTROLPHOTOCELLWALL SWITCHESSENSOR SWITCH nLIGHT ON/OFF PUSHBUTTONn1 SENSOR SWITCH nPODM nLIGHT ON/OFF PUSHBUTTON 3nD SENSOR SWITCH nPODM-DX nLIGHT ON/OFF PUSHBUTTON W/DIMMING 3nDC SENSOR SWITCH nPODM-DX-CCT nLIGHT ON/OFF PUSHBUTTON W/DIMMING, COLORCORRECTION3LIGHTING FIXTURE SCHEDULETYPE DESCRIPTION MOUNTING VOLTAGE LUMENSCOLORTEMP.(K) MFGR. CATALOG # NOTESF1 EDGE LITE EXIT SIGN W/90 MIN. BATTERY,GREEN LED, SINGLE FACE/DOUBL FACEWALL ORCEILING120-277 N/A N/A MULE LTG PVT-U-B-G-S/R-SCBAF2 2X2 LAY-IN LED, 0-10V DIMMING FLAT PANEL RECESSED 120-277 4000 4000 LITHONIA EPANL-2X2-400LM-80CRI-40K-MIN1-NLIGHT-MVOLTF2A 2X2 LAY-IN LED, 0-10V DIMMING FLAT PANELSURFACE MOUNTCEILING 120-277 4000 4000 LITHONIA EPANL-2X2-400LM-80CRI-40K-MIN1-NLIGHT-MVOLT-2X2SMKSHF2E 2X2 FLAT PANEL- 0-10 DIMMING W/ INTEGRALEMERGENCY TRANSFER DEVICERECESSED 120-277 4000 4000 LITHONIA SAME AS F2 BUT WITH INTEGRAL EMERGENCYTRANSFER DEVICEF2S 2X2 LAY-IN LED, 0-10V DIMMING FLAT PANEL SUSPENDED 120-277 4000 4000 LITHONIA EPANL-2X2-400LM-80CRI-40K-MIN1-NLIGHT-MVOLT- 2X2PANLACG36F3 2X2 LAY-IN LED, 0-10V DIMMING RECESSED 120-277 4000 4000 LITHONIA 2BLT2-TUWH-PROP-40L-SDP-MVOLT-NLTF4 6" ROUND RECESSED LED CAN, 0-10VDIMMINGRECESSED 120-277 1500 4000 LITHONIA LDN6-40/15-LO6AR-LSS-MVOLT-EZ10F4S 6" ROUND RECESSED LED CAN WETLOCATIONRECESSED 120-277 1500 4000 LITHONIA LDN6-40/15-LO6AR-LSS-MVOLT-EZ10-WLF5 1X4 SURFACE FIXTURE - LOCKER ROOMS SURFACE 120-277 4000 4000 KENALL MLHA5-48-F-CBA-PP-45L-40K-DCC-DVF5E 1X4 SURFACE FIXTURE - LOCKER ROOMS W/INTEGRAL EMERGENCY TRANSFER DEVICESURFACE 120-277 4000 4000 KENALL SAME AS F5 BUT WITH INTEGRAL EMERGENCYTRANSFER DEVICE6F6 2FT LINEAR WALL FIXTURE WALL ABOVEMIRROR120-277 2200 4000 LITHONIA WL2-22L-EZ1-LP840-N100F7 4FT LED STRIP, 0-10V DIMMING SURFACE/SUSPENDED120-277 4000 4000 LITHONIA CLX-L48-4000LM-SEF-RDL-MVOLT-GZ10-40K-80CRIF8 4FT LINEAR WALL FIXTURE WALL 120-277 3000 4000 LITHONIA WL4-30L-MVOLT-EZ1-LP840-N100F9 1X4 SURFACE FIXTURE - LOCKER ROOMS SURFACE 120-277 4000 4000 LITHONIA BLWP4-40L-ADP-EZ1-LP840-N100F10 2FT LED STRIP, 0-10V DIMMING SURFACE/SUSPENDED120-277LITHONIA CLX-L24-2000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI-F13 VAPOR TIGHT WALL LIGHT - STEAM ROOM WALL 120 N/A N/ALITHONIA VW150I M12PROVIDE WITH 75W. INC.F14 8FT LED STRIP, 0-10V DIMMING SURFACE/SUSPENDED120-277 8000 4000 LITHONIA CLX-L96-8000LM-SEF-RDL-MVOLT-GZ10-40K-80CRIF15 DISPLAY CASE LIGHTING RECESSED 120 4000 LITHONIA SL2L-QS-LOP-XX-FLP-GB-80CRI-40K-1000LMF-MIN1-120-NLIGHT8F16 RECESSED ARCHITECTURAL LIGHTING RECESSED 120 4000 LITHONIA FSM4L-FL-275LF-40K-1C-UNV-LD1-XFN-WH-XX 7,8F17 HANDRAIL LIGHTING IN HANDRAILFIXTURE FURNISHED W/ HANDRAIL 9SCALE: NONE1RECESSED LIGHT FIXTURE DETAILSCALE: NONE2RECEPTACLE MOUNTING DETAIL1. REFER TO DRAWINGS FOR FIXTURES REQUIRED TO HAVE 0-10V OR STEP-LEVEL DIMMING CONTROL. PROVIDE FIXTURE(S) WITH LED DRIVER(S) AND REQUIRED DIMMING/SWITCH-LEG CONDUCTORS BETWEEN SWITCH(ES) AND FIXTURE(S) TO PROVIDE CONTROL AS INDICATED ON DRAWINGS.2. FIXTURE TO BE CONTINUOUS ROW MOUNTED, LENGTH AS INDICATED ON DRAWINGS. PROVIDE REQUIRED ACCESSORIES/CONNECTORS FOR CONTINUOUS ROW MOUNTING.3. SCBA - STANDARD COLOR BY ARCHITECT/OWNER (COORDINATE COLOR WITH ARCHITECT/OWNER PRIOR TO ORDERING.)4. FIELD ADJUST PENDANT LENGTH AS REQUIRED, VERIFY LENGTH WITH COUNTER AS DIRECTED BY ARCHITECT.5. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR PLACEMENT AND MOUNTING HEIGHT OF FIXTURES.6. CONNECT ALL EMERGENCY FIXTURES TO BOTH NORMAL AND EMERGENCY POWER. CONNECT TO NEAREST EM LIGHTING CIRCUIT. EC SHALL FIELD IDENTIFY AND EXTEND.7. PROVIDE ALL REQUIRED FITTING AND COMPONENTS FOR A CONTINUOUS LIGHTING RUN8. REFER TO PLANS FOR LENGTH9. PROVIDE LOW VOLTAGE TRANSFORMER IN ACCESSIBLE LOCATION BELOW BLEACHERS, CORE DRILL COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS. THROUGH BLEACHER INSTALL LIGHT FIXTURE IN HANDRAIL PER MANUFACTURE RECOMMENDATION.LIGHT FIXTURE SCHEDULE NOTES:1. PROVIDE 0-10V DIMMING CONDUCTORS (GREY & VIOLET) BETWEEN DEVICE AND LIGHT FIXTURE(S) FOR DIMMING AS INDICATED ON DWGS.2. ROUTE ASSOCIATED ROOM LTG CIRCUIT THROUGH RELAY FOR CONTROL, PROVDE 0-10V DIMMING AND LOW VOLTAGE CONNECTIONS AS INDICATED ON DRAWINGS AND DETAILS.3. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.4. MOUNT DEVICE TO BOTTOM OF STRUCTURE.nLIGHT LIGHTING CONTROL SCHEDULE NOTES:nLIGHT LIGHTING CONTROL SCHEDULE GENERAL NOTES:• E.C. SHALL BE RESPONSIBLE FOR PROVIDING ALL LIGHTING CONTROL COMMISSIONING/PROGRAMMING OF ALL nLIGHT COMPONENTS. THE COMMISSIONING/PROGRAMMING SHALL BE DONE BY A nLIGHT CERTIFIED TECHNICIAN. • E.C. SHALL NOTIFY OWNER 1-WEEK PRIOR TO COMMISSIONING/PROGRAMMING OF THE SYSTEM SO THAT THE OWNER CAN PROVIDE REPRESENTATIVES DURING THE COMMISSIONING/PROGRAMMING PERIOD.8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:19 AMEG200ELECTRICALDETAILS, &SCHEDULESJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054LIGHTING CONTROL/OCCUPANCY SENSOR SCHEDULETYPE MFGR. CATALOG #DESCRIPTIONNOTESAPPROVEDEQUALSCEILING SENSORS - LINE VOLTAGECD2 SENSOR SWITCH CMR PDT 9 DUAL-TECHNOLOGY, LINE VOLTAGE, SMALL MOTION 800W MAX LOADCOOPER,WATTSOPPER,HUBBELLWALL SWITCHPODSSP1 SENSOR SWITCH sPODM-** LOW VOLTAGE PUSH-BUTTON SWITCHPOD, 1-POLE2,3,4 COOPER1. PROVIDE ADDITIONAL POWER PACKS; SENSOR SWITCH PP20 AS NEED FOR QTY OF OCCUPANCY SENSORS/SWITCHES.2. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.3. REFER TO MANUFACTURER DOCUMENTATION FOR QTY AND SIZE OF CONDUCTORS BETWEEN LOW VOLTAGE SWITCH, SENSOR(S) AND POWER/RELAY PACKS.4. PROVIDE SECONDARY RELAY PACK; SENSOR SWITCH SP20 AS NEEDED TO PROVIDE DUAL-LEVEL SWITCHING OF FIXTURES.5. PROVIDE 0-10V DIMMING CONDUCTORS (GRAY & VIOLET) BETWEEN SWITCH AND LIGHT FIXTURES FOR DIMMING CONTROL.6. PROGRAM ON/OFF TIMES OF RELAY'S AS DIRECTED BY OWNER. PROVIDE COMMISSIONING AS INDICATED IN GENERAL NOTES BELOW.7. CUSTOM WALL STATION ENGRAVINGS IS REQUIRED FOR WALL STATION(S) AND SHALL BE SPECIFIED/COORDINATED WITH OWNER AFTER PROGRAMING OF SYSTEM.CONTROL & OCCUPANCY SENSOR SCHEDULE NOTES:• E.C. SHALL BE RESPONSIBLE FOR THE PROGRAMMING/COMMISSIONING OF THE LIGHTING CONTROL SYSTEMS TO FUNCTION AS INDICATED ON THE DRAWINGS AND SHALL INCLUDE ALL REQUIRED COST IN THE BASE BID. FOR AREAS WITH DAYLIGHTING CONTROL, THE DAYLIGHTING SET-POINTS SHALL BE COORDINATED WITH THE OWNER FOR EACH AREA PRIOR TO FINAL PROGRAMMING OF THE DAYLIGHTING SENSOR(S). ALL PROGRAMMING/COMMISSIONING SHALL BE DONE BY A FACTORY CERTIFIED OR TRAINED PERSON.• LIGHTING IS SPACES WITH WIRELESS CONTROLS SHALL BE FIELD TUNED TO FOOTCANDLE LEVELS THAT ARE SATISFACTORY TO THE OWNER DURING PROGRAMMING AND COMMISSIONING OF THE WIRELESS CONTROL SYSTEM.GENERAL LIGHTING CONTROL NOTES:SCALE: 1/4" = 1'-0"3MAIN GYM NORTH EXIT - ELEVATION16'8'0"S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPEA = ARC-FAULT BREAKERGP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANELBRK NOTES:TOTAL ESTIMATED DEMAND AMPS:156 ATOTAL AMPS:161 A 154 A 154 ATOTAL LOAD:19.3 kVA 18.4 kVA 18.4 kVA41 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 4239 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 4037 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 3835 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 3633 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 3431 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 3229 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 3027 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 2825 PREPARED SPACE -- -- -- 0 0 -- -- -- PREPARED SPACE 2623 ---- -- -- 769 769 -- -- -- --2421 ---- -- -- 769 769 -- -- -- --2219 WASHER20 A 3 769 769 3 20 A WASHER 2017 ---- -- -- 8454 8454 -- -- -- --1815 ---- -- -- 8454 8454 -- -- -- --1613 DRYER125 A 3 8454 8454 3 125 A DRYER 1411 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 129 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 107 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 85 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 63 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 41 SPARE -- 20 A 1 0 900 1 20 A Receptacle 2CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKTNOTES:MFG & MODEL:SQ. D/NQ SERIESDIMENSIONS:20"W x 5.8"D x *"HFEED:2 1/2' C., 4-4/0+GNDENCLOSURE: BUSSING:SEE SPEC'SMBR AMPS:N/AMOUNTING:WIRES:4PANEL AMPS:225 A JOHN W. HART BUILDING...FED FROM: PHASES:3PANEL TYPE:MLO JOHN W. HART BUILDING...LOCATION: VOLTAGE:120/208 WyeA.I.C. RATING:10,000PROJECT:PANEL: NLPAYNE ENGINEERINGS = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPEA = ARC-FAULT BREAKERGP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANELBRK NOTES:TOTAL ESTIMATED DEMAND AMPS:134 ATOTAL AMPS:134 A 132 A 132 ATOTAL LOAD:16.0 kVA 15.9 kVA 15.9 kVA41 SPARE -- 20 A 1 0 0 -- -- -- --4239 SPARE -- 20 A 1 0 0 -- -- -- --4037 SPARE -- 20 A 1 0 0 3 20 A -- SPARE 3835 SPARE -- 20 A 1 0 0 -- -- -- --3633 SPARE -- 20 A 1 0 0 -- -- -- --3431 DISPLAY SCREEN 20 A 1 180 0 3 20 A -- SPARE 3229 ---- -- -- 1585 1585 -- -- -- --3027 ---- -- -- 1585 1585 -- -- -- --2825 Curtain Hoist 20 A 3 1585 1585 3 20 A Curtain Hoist 2623 ---- -- -- 1585 1585 -- -- -- --2421 ---- -- -- 1585 1585 -- -- -- --2219 Curtain Hoist 20 A 3 1585 1585 3 20 A Curtain Hoist 2017 ---- -- -- 1585 1585 -- -- -- --1815 ---- -- -- 1585 1585 -- -- -- --1613 Curtain Hoist 20 A 3 1585 1585 3 20 A Curtain Hoist 1411 ---- -- -- 1585 1585 -- -- -- --129 ---- -- -- 1585 1585 -- -- -- --107 Curtain Hoist 20 A 3 1585 1585 3 20 A Curtain Hoist 85 ---- -- -- 1585 1585 -- -- -- --63 ---- -- -- 1585 1585 -- -- -- --41 Curtain Hoist 20 A 3 1585 1585 3 20 A Curtain Hoist 2CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKTNOTES:MFG & MODEL:SQ. D/NQ SERIESDIMENSIONS:20"W x 5.8"D x *"HFEED:ENCLOSURE: BUSSING:SEE SPEC'SMBR AMPS:400 AMOUNTING:WIRES:4PANEL AMPS:400 A JOHN W. HART BUILDING MEP-bFED FROM: PHASES:3PANEL TYPE:MBR JOHN W. HART BUILDING PHASE 3...LOCATION: VOLTAGE:120/208 WyeA.I.C. RATING:10,000PROJECT:PANEL: H1PAYNE ENGINEERINGSUPPLY WITH INTEGRAL SPDSUPPLY WITH INTEGRAL SPD1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
PLATFORM FLOORMONITORRECESSED CONTROL BOXRELOCATE EXISTING FIRE ALARM DEVICE TO NEW STAGE LEFT WALL. RE-ESTBALISH FUNCTIONALITYREWORK EXISTING CIRCUITS FROM STAGE FLOOR POCKETS INTO A WIRE GUTTER UNDER THE STAGE. SPLICE AND EXTEND TO EXISTING DIMMER RACKS. REMOVE EXISTING WIRING CABINET.E.C. SHALL DISCONNECT AND REMOVE ALL COMPONENTS FROM THIS WALL THEN REINSTALL ON THE WALL TO THE WEST. INTERCEPT ALL EXISTING CONDUIT AND CONDUCTORS, SPLICE AND EXTEND TO NEW LOCATIONS.E.C. SHALL DISCONNECT AND REMOVE ALL COMPONENTS FROM THIS WALL THEN REINSTALL ON THE WALL TO THE WEST. INTERCEPT ALL EXISTING CONDUIT AND CONDUCTORS, SPLICE AND EXTEND TO NEW LOCATIONS.RELOCATE AUDIO PATCH PANEL TO WEST WALL. INSTALL A 4" CONDUIT UNDER STAGE TO NEW LOCATION WITH PULL CORD. CABLING BY OWNERRELOCATE EXISTING LIGHT SWITCH TO NEW STAGE LEFT WALL. RE-ESTABLISH FUNCTIONALITY W/ EXISTING LOAD.EXISTING PANEL TO REMAINPLATFORM FLOOREXISTING J-BOX TO REMAINEXISTING CONDUITS TO REMAINCONDUITCABLE TRAYSTAGE LEVELNEW CONDUIT SUPPORT BRACKETS. E.C. SHALL CONNECT EXISTING CONDUIT TO NEW SUPPORT BRACKETS THEN PROTECT DURING WALL DEMOLITION. COORDINATE WITH G.C.EXISTING CABLE TRAY TO REMAINREMOVE WIRE WAY, CABLE TRAY AND EMPTY CONDUITS FROM EAST WALL TO ACCOMMODATE REMODELDISCONNECT AND REMOVE EXISTING RECEPTACLE, ALL ASSOCIATED CONDUIT, AND WIREREMOVE THIS PORTION OF CABLE TRAY TO ACCOMMODATE REMODELSTAGE FLOORRELOCATE EXISTING DRY LINE BOX TO EAST WALL. REWORK CONDUIT UNDER THE STAGE. INSTALL NEW CONDUCTORS BETWEEN STAGE LEFT AND STAGE RIGHT. TOTAL OF (12) LINES.WALL MOUNTED TRAYRELOCATE EXISTING A/V PATCH PANELS TO EAST WALL INSTALL A 4" CONDUIT UNDER THE STAGE WITH PULL CORD TO NEW LOCATION. CABLING BY OWNERDISCONNECT AND REMVOE EXISTING RECEPTACLE. REMOVE ALL ASSOCIATED CONDUIT AND WIRE IN CONFLICT WITH REMODEL.RELOCATE J-BOXES AND COMPONENTS TO EAST WALL. INTERCEPT ALL EXISTING OVER HEAD CONDUITS AND REROUTE TO NEW LOCATIONSUNISTRUT ANCHORINSTALL INSULATED BUSHINGS ON ALL CONDUIT ENDS (TYP)4" C TO ABOVE ACCESSABLE CEILING4" C UNDER HALLWAY RAMP AND THROUGH WALLFINISH FLOOR18" CABLE TRAYCEILINGSCALE: 1" = 1'-0"1PLATFORM LEFT ELEVATION-EXISTINGSCALE: 1/2" = 1'-0"2PLATFORM LEFT STAIR ELEVATION-EXISTINGSCALE: 1" = 1'-0"3PLATFORM RIGHT ELEVATION-EXISTING2'1'0"2'1'0"SCALE: 1" = 1'-0"4VERTICAL FIBER TRAY2'1'0"4'2'1'0"8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:21 AMEG201ELECTRICALELEVATIONSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054DETAIL NOTE:EC SHALL FIELD VERIFY ALL EXISTING COMPONENTS, CONDITIONS AND REQUIRED CONDUCTORS AND CABLE TO BE RELOCATED. INCLUDE THESE CONDITIONS IN BASE BID.1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
SJCR3318HJKH1J11920G1HAND DRYER1111111114(TYP)14(TYP)1118DEF1920F1C1D11111111111131323111517HJKH1J1111111131415BCC14" C4" C26333466226355772289101821CD1920C1111EXISTING PANEL MDM TO REMAIN22223422222255544122223ALTERNATE #5A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 EXISTING 1200A FEEDER (4-4"C.,4-#350+GND) TO BE REWORKED TOACCOMMODATE REMODEL. SEE REMODELED PLAN.2 REMOVE EXISTING LIGHTING IN CONFLICT W/ REMODEL REMOVE ALLASSOCIATED CONTROLS, CONDUIT AND WIRE BACK TO NEXT ACTIVEBOX OR SOURCE.3 REMOVE EXISTING DEVICE IN CONFLICT W/ REMODEL. REMOVE ALLASSOCIATED CONDUIT AND WIRE BACK TO NEXT ACTIVE BOX ORSOURCE.4 EXISTING DEVICE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICES TO THIS DEVICE. REPLACEEXISTING DEVICE AND COVER PLATE.5 EXISTING FIXTURE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICE TO THIS FIXTURE.6 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE INCONFLICT W/ REMODEL REMOVE ALL ASSOCIATED CONDUIT ANDCABLING.7 EXISTING ADA AND DOOR ACCESS TO REMAIN.8 EXISTING EQUIPMENT RACK TO SHIFT TO THE EAST REWORK ANDREROUTE SURFACE MOUNTED POWER TO ACCOMMODATE NEWDOOR.9 RELOCATE EXISTING ADA DOOR CONTROL AS REQUIRED TOACCOMMODATE NEW DOOR.10 EXISTING 4" CONDUIT IN CONFLICT W/ REMODEL. CAREFULLYPULLBACK EXISTING FIBER OPTIC CABLE AND INNERDUCTS THENREINSTALL INNERDUCT AND FIBER IN NEW CONDUIT.11 ALL EXISTING ELECTRICAL, FIRE ALARM, AND IT EQUIPMENT WITHINTHIS AREA IS TO BE REMOVED, UNLESS SPECIFICALLY INDICATEDOTHERWISE. WHEN EXISTING SWITCH BOXES OR OUTLET BOXESFALL WITHIN OR VERY NEAR NEW OUTLET/SWITCH LOCATIONS.ELECTRICAL CONTRACTOR MAY UTILIZE EXISTING ROUGH-IN, ETC. INLIEU OF INSTALLING NEW. ELECTRICAL CONTRACTOR SHALLMAINTAIN/RE-ESTABLISH CONTINUITY TO ALL DOWNSTREAMEQUIPMENT/DEVICES THAT ARE TO REMAIN. REMOVE ALLASSOCIATED CONDUITS BACK TO NEXT ACTIVE BOX OR SOURCE.REMOVE ALL UNUSED CONDUIT.12 CAREFULLY REMOVE EXISTING J-BOX E.C. MAY UTILIZE J-BOX IFCOMPATIBLE WITH NEW DESIGN.13 EXISTING PANEL TO REMAIN PROTECT DURING CONSTRUCTION.14 CAREFULLY DISCONNECT, REMOVE, AND CLEAN EXISTING LED FLATPANEL LIGHTING AND UTILIZE LIGHTING IN REMODEL.15 E.C. SHALL PROVIDE NEW PANEL INDEX FOR ALL PANELS MODIFIEDBY THIS REMODEL. NEW INDEX SHALL REFLECT ALL CONNECTEDLOADS.SCALE: 1/8" = 1'-0"3MEN'S & WOMEN'S RESTROOM & NEW WELLNESS CENTER-EXISTINGSCALE: 1/8" = 1'-0"2SPINNING CLASSROOM & ACTIVITY STORAGE-EXISTINGSCALE: 1/8" = 1'-0"1ACTIVITY STORAGE & ALTERNATE-EXISTINGSCALE: 1/8" = 1'-0"4SOUTHEAST EXIT - EXISTINGSCALE: 1/8" = 1'-0"5SOUTHWEST EXIT -EXISTINGNORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER. 2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100 AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS RECYCLING CENTER.3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER.4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE DISPOSED OF LEGALLY BY THE CONTRACTOR. 5. ALL CABLE FROM DATA DEVICES MARKED FOR DEMO SHOULD BE PULLED BACK TO PATCH PANEL AND REMOVED.SPECIAL DEMOLITION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATEREVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:09:52 AMED100LOWERLEVELEXISTINGELECTRICALJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
JFJJJ789BCDC1D1HAND DRYER11112BCDEC1D11101112131415161718212223LM1920DISPLAY CASEDISPLAY CASERACEWAY & RECEPTACLES ON FLOOR1122345665787744491010107777(TYP)(TYP)1010101011LIGHTING CONTACTOR1212A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 ALL EXISTING ELECTRICAL, FIRE ALARM, AND IT EQUIPMENT WITHINTHIS AREA IS TO BE REMOVED, UNLESS SPECIFICALLY INDICATEDOTHERWISE. WHEN EXISTING SWITCH BOXES OR OUTLET BOXESFALL WITHIN OR VERY NEAR NEW OUTLET/SWITCH LOCATIONS.ELECTRICAL CONTRACTOR MAY UTILIZE EXISTING ROUGH-IN, ETC. INLIEU OF INSTALLING NEW. ELECTRICAL CONTRACTOR SHALLMAINTAIN/RE-ESTABLISH CONTINUITY TO ALL DOWNSTREAMEQUIPMENT/DEVICES THAT ARE TO REMAIN. REMOVE ALLASSOCIATED CONDUITS BACK TO NEXT ACTIVE BOX OR SOURCE.REMOVE ALL UNUSED CONDUIT.2 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE INCONFLICT W/ REMODEL REMOVE ALL ASSOCIATED CONDUIT ANDCABLING.3 EXISTING PLUG MOLD TO REMAIN, PROTECT, MAINTAIN, AND/ORRE-ESTABLISH ELECTRICAL SERVICE.4 EXISTING FIRE ALARM DEVICE TO REMAIN, PROTECT, MAINTAIN, ORRE-ESTABLISH SERVICE TO DEVICE5 EXISTING PROGRAM CLOCK TO REMAIN.6 REMOVE EXISTING LIGHTING IN CONFLICT W/ REMODEL REMOVE ALLASSOCIATED CONTROLS, CONDUIT AND WIRE BACK TO NEXT ACTIVEBOX OR SOURCE.7 EXISTING FIXTURE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICE TO THIS FIXTURE.8 EXISTING PANEL TO REMAIN PROTECT DURING CONSTRUCTION.9 EXISTING CAMERA TO REMAIN.10 EXISTING DEVICE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICES TO THIS DEVICE. REPLACEEXISTING DEVICE AND COVER PLATE.11 DISCONNECT AND REMOVE ABANDONED LIGHTING CONTROL12 EXISTING WIRELESS ACCESS POINT TO REMAIN. PROTECT DURINGCONSTRUCTION.SCALE: 1/8" = 1'-0"2WOMEN'S LOCKER ROOM - EXISTINGSCALE: 1/8" = 1'-0"1MEN'S LOCKER ROOM - EXISTING16'8'0"16'8'0"NORTHNORTH16'8'0"NORTHSCALE: 1/8" = 1'-0"3NORTH HALL-EXISTING1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER. 2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100 AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS RECYCLING CENTER.3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER.4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE DISPOSED OF LEGALLY BY THE CONTRACTOR. 5. ALL CABLE FROM DATA DEVICES MARKED FOR DEMO SHOULD BE PULLED BACK TO PATCH PANEL AND REMOVED.SPECIAL DEMOLITION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:09:54 AMED101UPPERLEVELEXISTINGELECTRICALJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
JF3111213141516171821CDEFGHJKLH1J11920F1G1C1D1SCOREBOARDSTAGE ELECTRONICSSTAGE ELECTRONICSSTAGE ELECTRONICSEG2013EG20111111112133345463337EG201222891022524492329222222222229999992222222222299511412131313(TYP)(TYP)(TYP)141414141414EXISTING TELECOM ROOM UNDER BLEACHERS. PROTECT EXISTING CABLING AND PATHWAYA. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 EXISTING DEVICE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICES TO THIS DEVICE. REPLACEEXISTING DEVICE AND COVER PLATE.2 EXISTING FIXTURE TO REMAIN PROTECT, MAINTAIN, ORRE-ESTABLISH ELECTRICAL SERVICE TO THIS FIXTURE.3 REMOVE EXISTING LIGHTING IN CONFLICT W/ REMODEL REMOVE ALLASSOCIATED CONTROLS, CONDUIT AND WIRE BACK TO NEXT ACTIVEBOX OR SOURCE.4 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE INCONFLICT W/ REMODEL REMOVE ALL ASSOCIATED CONDUIT ANDCABLING.5 EXISTING PROGRAM CLOCK TO REMAIN.6 EXISTING BASKETBALL STANDARD RAISE/LOWER CONTROL TO BEMOVED TO STORAGE ROOM 200. REPLACE ALL EXISTING CONTROLCONTACTORS TO ACCOMMODATE RELOCATION.7 EXISTING PANEL TO REMAIN PROTECT DURING CONSTRUCTION.8 EXISTING FLOOR POCKETS IN STAGE FLOOR TO REMAIN.9 EXISTING FIRE ALARM DEVICE TO REMAIN, PROTECT, MAINTAIN, ORRE-ESTABLISH SERVICE TO DEVICE10 EXISTING WIRELESS ACCESS POINT TO REMAIN. PROTECT DURINGCONSTRUCTION.11 REMOVE EXISTING DEVICE IN CONFLICT W/ REMODEL. REMOVE ALLASSOCIATED CONDUIT AND WIRE BACK TO NEXT ACTIVE BOX ORSOURCE.12 EXISTING CAMERA TO REMAIN.13 HOUSE AND THEATRICAL LIGHTING TO REMAIN, PROTECT, MAINTAIN,OR RE-ESTABLISH ELECTRICAL SERVICES TO FIXTURES14 DISCONNECT EXISTING BASKETBALL HOOP. RECONNECT NEWBASKETBALL HOOP WITH EXISTING CIRCUIT. ESTABLISH CONTROLSPER NEW MANUFACTURES DIRECTION.SCALE: 1/8" = 1'-0"1GYM-EXISTINGNORTH16'8'0"1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER. 2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100 AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS RECYCLING CENTER.3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED BY OWNER.4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE DISPOSED OF LEGALLY BY THE CONTRACTOR. 5. ALL CABLE FROM DATA DEVICES MARKED FOR DEMO SHOULD BE PULLED BACK TO PATCH PANEL AND REMOVED.SPECIAL DEMOLITION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:09:55 AMED102MAIN GYMEXISTINGELECTRICALJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
CRCRCRCAMn1SnD2n1SnD2SnD2nDCRCRCRCRCRCRCAMnDCnDCSnD1SnD1SnD1nDSnD1SnD1SnD1SnD1SnD1SnD1SnD1SnD1SnD1SnD1SnD117HJKH1J1ACTIVITY STOR.177CUSTODIAN176EQUIP. RM.178ACACACACALTERNATE #1ALTERNATE #22222217HJKH1J1ACTIVITY STOR.177CUSTODIAN176EQUIP. RM.178(TYP)F2(TYP)F2(TYP)F2ALTERNATE #1ALTERNATE #2218HJKH1J11920G1WOMEN'S181MEN'S183LAUNDRY RM.180WELLNESS CTR OFFICE179DWELLNESS CTR OFFICE179CWELLNESS CTR OFFICE179BSORT & ASSEMBLE179ANEW WELLNESS CENTER1792D-42D-442"42"ACACACCUSTODIAN OFFICE1752D-43D-43D-424"3333333'NL'NL-20,22,24NL-19,21,23NL-14,16,18NL-13,15,17ACNL-244442D-4318HJKH1J11920G1MEN'S183WOMEN'S181LAUNDRY RM.180NEW WELLNESS CENTER179SORT & ASSEMBLE179AWELLNESS CTR OFFICE179BWELLNESS CTR OFFICE179CWELLNESS CTR OFFICE179D(TYP)F3(TYP)F3(TYP)F2(TYP)F2F8F8F8F5F5F5F5F5F5F5F5F5F5F5F5F5F5F5F5F5F5F8F8F8(TYP)F5(TYP)F21111111F5F2F2(TYP)F2F2F2331F6F8F8F6F817HJKH1J1ACTIVITY STOR.177CUSTODIAN176EQUIP. RM.178ALTERNATE #1ALTERNATE #218HJKH1J11920G1WOMEN'S181MEN'S183LAUNDRY RM.180WELLNESS CTR OFFICE179DWELLNESS CTR OFFICE179CWELLNESS CTR OFFICE179BSORT & ASSEMBLE179ANEW WELLNESS CENTER179A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 CONNECT ALL OCCUPANCY SENSORS IN ROOM IN PARALLEL SOTHAT ANY OCC. SENSOR WILL TURN ON ALL ROOM LIGHTING.2 CIRCUIT TO PANEL V. PROVIDE AND INSTALL NEW BREAKERS ASNECESSARY TO ACCOMMODATE DESIGN, PROVIDE AND INSTALLNEW PANEL SCHEDULE.3 CIRCUIT TO PANEL B. PROVIDE AND INSTALL NEW BREAKERS ASNECESSARY TO ACCOMMODATE DESIGN, PROVIDE AND INSTALLNEW PANEL SCHEDULE.4 MAKE ALL REQUIRED CONNECTION TO WASHER AND DRYER.COORDINATE ROUGH IN WITH PRODUCT SHOP DRAWING.SCALE: 1/8" = 1'-0"1ACTIVITY STORAGE & ALTERNATE - POWERSCALE: 1/8" = 1'-0"2ACTIVITY STORAGE & ALTERNATE-LIGHTINGSCALE: 1/8" = 1'-0"4RESTROOM & NEW WELLNESS CENTER - POWERSCALE: 1/8" = 1'-0"5RESTROOM & NEW WELLNESS CENTERSCALE: 1/8" = 1'-0"3ACTIVITY STORAGE & ALTERNATE-FIRE ALARMSCALE: 1/8" = 1'-0"6MEN'S & WOMEN'S RESTROOM & NEW WELLNESS CENTER-FIRE ALARM16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTHA. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL. THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:· A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT, INCLUDINGMANUFACTURER, MODEL NUMBER AND TECHNICAL INFORMATION.· PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES, PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE IN A GOOD WORKMANLIKE MANNER.· TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE USED ON THE PROJECT.· SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE LOCAL AHJ. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE ENGINEER.C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL LISTING.FIRE ALARM EXPANSION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:09:58 AMEE100ACTIVITYSTORAGE,WELLNESSCENTER &RESTROOMSELECTRICALPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
TV2TV2TV2CRCRCRCAMCAMSnD1SnD1SnD1n1nD33SnD1SnD1SnD1SnD1J18DEF1920F1C1D1ACTIVITY STOR.191SPINNING RM.18916D-5MECH.190'B''Y'3333D-43STOR.189A33STOR.190B18DEF1920F1C1D1(TYP)F2S(TYP)F2S(TYP)F2SACTIVITY STOR.191SPINNING RM.189F14F14F14F14F14F14'Y''B'3F2SF2SF2SF2SSTOR.189ASTOR.190BMECH.19018DEF1920F1C1D1ACTIVITY STOR.191SPINNING RM.189STOR.189ASTOR.190B101112131415161718212223LM1920F10TICKET OFFICE220DISPLAY221F2F2F2EF2F2F2NORTH EXITE003F2AF2AF2AF2AF2A'L'22DMX GATEWAY TO EXISTING HOUSE LIGHTING CONTROL NETWORKF4F4F4F4F4F15F15F15F1524EG2003F1652(TYP)(TYP)101112131415161718212223LM19203D-43D-43D-4222ACACAC'L'EXISTING PANEL TO REMAINA. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 SLIM-LINE AV SYSTEM CABINET. PROVIDE DUAL-CHANNEL SURFACEWIREMOLD FROM CEILING DOWN TO CABINET FOR POWER, DATA,AND AV CABLES. WIREMOLD SHALL BE LEGRAND ALA4800 SERIES.PROVIDE (2) DUPLEX OUTLETS IN CABINET. PROVIDE 1 1/2" CHASEBETWEEN WIREMOLD AND CABINET FOR DATA AND AV CABLES.COORDINATE EXACT PLACEMENT WITH CABINET. PROVIDE A #10GREEN INSULATED GROUND CONDUCTOR FROM CABINET TONEAREST ELECTRICAL ROOM GROUND BAR. FIELD VERIFY FINALLOCATION PRIOR TO ROUGH-IN. PROVIDE ALL WIREMOLDACCESSORIES AND COMPONENTS FOR A COMPLETE INSTALLATION.2 CIRCUIT TO PANEL L. PROVIDE AND INSTALL NEW BREAKERS ASNECESSARY TO ACCOMMODATE DESIGN, PROVIDE AND INSTALLNEW PANEL SCHEDULE.3 CIRCUIT TO PANEL Y. PROVIDE AND INSTALL NEW BREAKERS ASNECESSARY TO ACCOMMODATE DESIGN, PROVIDE AND INSTALLNEW PANEL SCHEDULE.4 CONNECT TO EXISTING DISPLAY CASE LIGHTING CIRCUIT ANDCONTROLS.5 CIRCUIT THROUGH LIGHTING CONTACTOR LOCATED NEXT TO PANELL. PROGRAM PER OWNER.SCALE: 1/8" = 1'-0"1SPINNING ROOM & ACTIVITY STORAGE - POWERSCALE: 1/8" = 1'-0"2SPINNING ROOM & ACTIVITY STORAGE-LIGHTINGSCALE: 1/8" = 1'-0"3SPINNING ROOM & ACTIVITY STORAGE-FIRE ALARMA. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL. THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:· A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT, INCLUDINGMANUFACTURER, MODEL NUMBER AND TECHNICAL INFORMATION.· PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES, PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE IN A GOOD WORKMANLIKE MANNER.· TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE USED ON THE PROJECT.· SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE LOCAL AHJ. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE ENGINEER.C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL LISTING.FIRE ALARM EXPANSION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:01 AMEE101SPINNINGROOM &ACTIVITYSTORAGE &NORTHHALLJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054SCALE: 1/8" = 1'-0"4NORTH HALL-LIGHTINGSCALE: 1/8" = 1'-0"5NORTH HALL-POWERNORTHNORTHNORTHNORTHNORTH16'8'0"16'8'0"16'8'0"16'8'0"16'8'0"1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
SP1SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2CRCRSP1SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2SCD2CRCR12BCDEC1D1STORAGE207DMEN'S EMP. LOCKER RM.207AMEN'S STUDENT LOCKER RM.207F5F4SF4SF4SF4SF4SF4SF4SF5F5F5F5F5F5F5EF5F5EF5F5F5F5F5F5F5EF5F5F6F6F5EF5F6F6F5EF5F5F5EF5F5F5EF5F5F5EF5F5F5F5F5F5EF5F5EF5F5F4SF5F7F7F5F511111111111111F4SF4S22F4SF4SF4SF5EF4SF5EF7F712BCDEC1D1MEN'S EMP. LOCKER RM.207AMEN'S STUDENT LOCKER RM.207ACDRYERDRYERSTORAGE207DACACACACAC222222789BCDC1D1WOMEN'S STUDENT LOCKERRM.261WOMEN'S EMPLOYEE LOCKERRM.261ANURSING261BNURSING261DSTORAGE261EF7F7F7F5EF5F4SF4SF4SF4SF4SF4SF4SF4SF5F5EF5F5EF5F5F5F5F5F5EF5F5F5EF6F6F5F5F6F5EF6F5F7F5F5F5F5F5F5F5F5EF5F5F5F5F5F5F5F5F5F5F5F5F5EF5F5F5111111111111F533F7F712BCDEC1D1STORAGE207DMEN'S EMP. LOCKER RM.207AMEN'S STUDENT LOCKER RM.207789BCDC1D1WOMEN'S STUDENT LOCKERRM.261WOMEN'S EMPLOYEE LOCKERRM.261ASTORAGE261ENURSING261DNURSING261B789BCDC1D1WOMEN'S STUDENT LOCKERRM.261WOMEN'S EMPLOYEE LOCKERRM.261ASTORAGE261EACACACACACACACAC33333333NURSING261BNURSING261DACACA. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 CONNECT ALL OCCUPANCY SENSORS IN ROOM IN PARALLEL SOTHAT ANY OCC. SENSOR WILL TURN ON ALL ROOM LIGHTING.2 CIRCUIT TO PANEL F OR PANEL N1. PROVIDE AND INSTALL NEWBREAKERS AS NECESSARY TO ACCOMMODATE DESIGN, PROVIDEAND INSTALL NEW PANEL SCHEDULES.3 CIRCUIT TO PANEL G. PROVIDE AND INSTALL NEW BREAKERS ASNECESSARY TO ACCOMMODATE DESIGN, PROVIDE AND INSTALLNEW PANEL SCHEDULE.SCALE: 1/8" = 1'-0"2MEN'S LOCKER RM-LIGHTINGSCALE: 1/8" = 1'-0"1MEN'S LOCKER RM - POWERSCALE: 1/8" = 1'-0"5WOMEN'S LOCKER RM-LIGHTINGSCALE: 1/8" = 1'-0"3MEN'S LOCKER RM - FIRE ALARMSCALE: 1/8" = 1'-0"6WOMEN'S LOCKER RM - FIRE ALARMNORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"A. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL. THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:· A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT, INCLUDINGMANUFACTURER, MODEL NUMBER AND TECHNICAL INFORMATION.· PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES, PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE IN A GOOD WORKMANLIKE MANNER.· TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE USED ON THE PROJECT.· SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE LOCAL AHJ. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE ENGINEER.C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL LISTING.FIRE ALARM EXPANSION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:06 AMEE102MEN'S &WOMEN'SLOCKERROOMSELECTRICALPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054SCALE: 1/8" = 1'-0"4WOMEN'S LOCKER RM - POWER1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
CRJCAMCAMSnD1SnD2n133SnD1SnD1SnD1n1n1n1131415BCC1EG20144" CSTAIRS003SE. EXITE002STORAGE211RR.212AC1236111821CD1920C1EXISTING PANEL MDM TO REMAIN4'H1'5EXISTING DIMMER RACKS TO REMAIN6910INTERCEPT EXISTING FEEDEREXISTING CAM LOCKSTOR.200HW.2-BCHAIR STOR.290HW.2-A1415BCDC1F9F6(TYP)F2SE. EXITE002STORAGE211RR.212F9F9F96F4SF2F271415BCDC1STORAGE211??SE. EXITE0021821CD1920C1HW.2-BSW. EXITE001STAIR2-DF9'H'F7F7F7F2F2F2F2F2F2F2F2788F1F1STOR.200ALTERNATE #5F1'H1'1821CD1920C1A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 REWORK NEW 4" CONDUITS 12" AFG ROUTE UNDER NEW RAMP 280INTO STORAGE ROOM 281.2 RELOCATE EXISTING ADA PUSH BUTTON.3 NEW CABINET LACTATION EXTEND ALL EXISTING CABLING ANDPOWER.4 PROVIDE & INSTALL NEW (4) - 4" C., 4 - 350 CU + GND FROM J-BOX TOEXISTING PANEL MDM. USE POLARIS TYPE SPLICE BLOCKS TOSPLICE EXISTING FEEDER.5 PROVIDE AND INSTALL (1) 3P 400A BREAKER FOR PANEL H16 CIRCUIT TO EXISTING CIRCUIT IN AREA. PROVIDE AND INSTALL NEWPANEL SCHEDULE AS NEEDED.7 CONNECT TO EXISTING CIRCUIT AND CONTROLS.8 CONNECT TO EXISTING LIGHTING CIRCUIT.9 RELOCATED BASKETBALL STANDARD CONTROLS. PROVIDE NEWCONTROL CONTACTORS AND RECONNECT.10 PROVIDE AND INSTALL 4" C., 4-500KCM + 1#2 GND FEEDER FROMPANEL MDM TO NEW PANEL H111 ETC ARCH WALL STATION PROVIDE 3/4" C., W/ CABLE AS REQUIREDTO DIMMER RACKS.SCALE: 1/8" = 1'-0"1SOUTHEAST EXIT - POWERSCALE: 1/8" = 1'-0"4SOUTHWEST EXIT - POWERSCALE: 1/8" = 1'-0"2SOUTHEAST EXIT - LIGHTINGSCALE: 1/8" = 1'-0"3SE EXIT-FIRE ALARMSCALE: 1/8" = 1'-0"5SOUTHWEST EXIT - LIGHTINGSCALE: 1/8" = 1'-0"6SW EXIT - FIRE ALARM16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTH16'8'0"NORTHA. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL. THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:· A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT, INCLUDINGMANUFACTURER, MODEL NUMBER AND TECHNICAL INFORMATION.· PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES, PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE IN A GOOD WORKMANLIKE MANNER.· TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE USED ON THE PROJECT.· SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE LOCAL AHJ. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE ENGINEER.C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL LISTING.FIRE ALARM EXPANSION NOTES:8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:08 AMEE103SOUTHEAST&SOUTHWESTEXITSJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
JJ3MMMMMMMMMMMMMMMMMMMMJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJ JJJJJJJJJJJJJJ JJJJ JJJJJJJ JJJ JJJJJJCAMCAMCAMCAMCAMCAMJJJCAMTV2SnD1n1n1n1111213141516171821CDEFGHJKLH1J11920F1G1C1D1CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-CURTAINMOTOR-'H1'11111111111111111111H1-26,28,30H1-25,27,29H1-20,22,24H1-19,21,23H1-14,16,18H1-13,15,17H1-7,9,11H1-8,10,12H1-2,4,6H1-1,3,5F1'H'F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17REPROGRAM HOUSE AND THEATRICAL LIGHTING TO OWNERS SATISFACTION, TO ACCOMMODATE NEW CURTAINS.STOR.200PLATFORM210MAIN GYM250AF17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17F17231" C., W/ BELDEN 9729 TO EXISTING DIMMER RACK231"C., W/ BELDEN 9729 TO EXISTING DIMMER RACKDMX DIMMING POWER SUPPLY FOR STAIR RAIL LIGHTS. SUCH AS UNISON FOUNDRY 600V DIMMER.DMX DIMMING POWER SUPPLY FOR STAIR RAIL LIGHTS. SUCH AS UNISON FOUNDRY 600W DIMMER.444444RELOCATED FIRE ALARM DEVICE5665677899H1-31A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 PROVIDE A DEDICATED 20A 3PHASE CIRCUIT TO CURTAIN HOIST.INSTALL 3/4" C., WITH CAT6A CABLE TO CONTROL PANEL.2 PROVIDE AND INSTALL ALL POWER SUPPLIES, CONNECTIONS, ANDTRANSFORMERS AS RECOMMENDED BY THE MANUFACTURER.3 ROUTE THRU E CIRCUIT CONTROL IN ETC SYSTEM.4 MOUNT IN TRUSS AREA OF CATWALK, COORDINATE EXACTLOCATION WITH OWNER PRIOR TO ROUGH IN.5 CONNECT TO EXISTING RECEPTACLE CIRCUIT.6 ETC ARCH WALL STATION PROVIDE 3/4" C., W/ CABLE AS REQUIREDTO DIMMER RACKS.7 PROVIDE AND INSTALL (4) 1" CONDUITS STUBBED THRU TO UNDERPLATFORM FOR OWNER INSTALLED A/V CABLING. COORDINATEEXACT REQUIRMENTS AND LOCATION W/ OWNER.8 RELOCATE EXISTING SCREEN CONTROL AND ADD HOIST CONTROLSTATION AT THIS LOCATION COORDINATE WITH BARBIZON.9 E.C. SHALL COORDINATE POWER SUPPLY DMX CONTROLLER ANDCONNECTION REQUIREMENTS WITH STAIRRAIL SHOP DRAWINGS.SCALE: 1/8" = 1'-0"1MAIN GYMNORTH16'8'0"8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:11 AMEE104MAIN GYMELECTRICALPLANJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054A. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL. THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:· A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT, INCLUDINGMANUFACTURER, MODEL NUMBER AND TECHNICAL INFORMATION.· PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES, PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE IN A GOOD WORKMANLIKE MANNER.· TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE USED ON THE PROJECT.· SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE LOCAL AHJ. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE ENGINEER.C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL LISTING.FIRE ALARM EXPANSION NOTES:SPECIAL NOTES: GYM AND STAGEFOR MORE INFORMATION REFER TO BARBIZON'S DRAWINGS SEE SHEET EE106 AND EE107.1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
MMSCD2SCD2212223242526272829DEFGHJH1F1G1C1D1FHR-15,17,191 1/2"C., 4-#1/0+GNDFHR-10,12,141 1/2"C., 4-#1/0+GNDFHR-6FHR-41122AHU-400AAHU-400B'FHR'(ON ROOF)DEF-133FHR-16FHR-18(ON ROOF)DEF-2771BF13F13F1351B3/4"C., 4-#8-+1-#10GND443/4" C., 4-#8+1-#10GNDD1F13F13F135ED1STEAM GENERATOR63/4" C., 4-#8+1-#10GND3/4" C., 4-#8+1-#10GND6A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM, INCLUDING BUT NOT LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES:KEY NOTES:#1 PROVIDE AND INSTALL A 3/4" CONDUIT FOR CONTROL CABLE. SEEMECHANICAL DRAWINGS FOR DESTINATION.2 PROVIDE AND INSTALL A 120V. 20A CIRCUIT TO EACH AIR HANDLERFOR INTEGRAL LIGHTING AND SERVICE RECEPTACLE. MAKE ALLREQUIRED CONNECTIONS, CONNECT OT SPARE BREAKERS INPANEL "FHR".3 PROVIDE AND INSTALL DUCT DETECTORS IN SUPPLY AND RETURNDUCTS IN THIS UNIT. PROVIDE RELAY MODULE AND WIRE SUCH THATUNIT WILL SHUT DOWN UPON DETECTION. SEE MECH. DRAWINGSFOR QUANTITY AND LOCATION OF ALL DUCTS. CONNECT TO FIREALARM SYSTEM.4 CIRCUIT TO PANEL F OR PANEL N1. PROVIDE AND INSTALL NEW 3P40A BREAKER TO ACCOMMODATE STEAM GENERATOR, PROVIDEAND INSTALL NEW PANEL SCHEDULES.5 CONNECT TO NEAREST LIGHTING CIRCUIT, IN ROOM.6 CIRCUIT TO PANEL G. PROVIDE AND INSTALL NEW 3P 40A BREAKERTO ACCOMMODATE NEW STEAM GENERATOR, PROVIDE ANDINSTALL NEW PANEL SCHEDULE.7 INTERLOCK EX FAN TO OPERATE WITH DRYER.NORTH16'8'0"8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:13 AMEE105HVACUPGRADE&ALTERNATE#3JOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/202020054SCALE: 1/8" = 1'-0"1HVAC UPGRADEMECHANICAL - DRYER EXHAUST FAN SCHEDULEID # VOLTS PH. HP PANEL CIRCUIT FEEDER NOTESDEF 1 120 V 1 1/2 FHR 16 3/4"C.,2#12+1#12GDEF 2 120 V 1 1/2 FHR 18 3/4"C.,2#12+1#12GSCALE: 1/4" = 1'-0"2MEN'S STEAM ROOM LIGHTING-ALT #3SCALE: 1/4" = 1'-0"3MEN'S STEAM ROOM POWER- ALT #3SCALE: 1/4" = 1'-0"4WOMEN'S STEAM ROOM LIGHTING-ALT #3SCALE: 1/4" = 1'-0"5WOMEN'S STEAM ROOM POWER -ALT #38'4'0"8'4'0"8'4'0"8'4'0"1 10/30/2020 Addendum #12 11/6/2020 Addendum #2
8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:13 AMEE106BARBIZONDRAWINGJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #12 11/6/2020 Addendum #2
8270STATEOFIDAHOTODDPAYNEREGISTEREDRPOFESSIONALENGINEEREngineering Inc.Consulting Engineers1823 E. CenterPocatello, Idaho 83201tel (208) 232-4439www.payneengineeringinc.com2"1"0"654321654321EDCBADATE REVISIONPROJECT NUMBERP.E. JOB #204811-23-202011/23/2020 10:10:13 AMEE107BARBIZONDRAWINGJOHN W. HART BUILDING PHASE 3 REMODELREXBURG, IDCONSTRUCTION DOCUMENTS - PERMIT SET - 11/23/2020200541 10/30/2020 Addendum #1