HomeMy WebLinkAboutENGINEERED PLANS - 20-00949 - South Clubhouse - The Gates Apartments - Solar panelsSTREET VIEWAERIAL VIEW
MODULE: (31) TRINA TSM-DD06H.05(II) 325 325W PV Module
INVERTER: (1) SOLAREDGE SE7600H-US String Inverter 240VAC
RACKING: UNIRAC Roof Mounted PV System
OPTIMIZER: (31) SOLAREDGE P340 DC Optimizers
WIND SPEED: 115 MPH
EXPOSURE CATEGORY: CA. ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES.
B. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING
REQUIREMENTS.
C. PRIOR TO COMMENCMENT OF WORK CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS AND NOTIFY DBM OF ANY INCONSISTENCIES.
D. ALL EQUIPMENT SHALL BE INSTALLED AS SHOWN.
F. WIRING SHALL NOT BE INSTALLED WITHIN 10 INCHES OF ROOF DECKING
EXCEPT WHERE DIRECTLY BELOW PV EQUIPMENT
SYSTEM SUMMARY
DESIGN CRITERIA
SCOPE OF WORK
GENERAL NOTES
OCCUPANCY & CONSTRUCTION TYPE
OCCUPANCY - A3
CONSTRUCTION - V-B
SHEET INDEX
PAGE NUMBER PAGE TITLE
PV01 TITLE PAGE
PV02 SITE PLAN
PV03 ONE LINE & ELECTRICAL
PV04 ARRAY & STRINGING DETAIL
PV05 LABEL PLAN
SPECS SPECSHEETS AND DOCUMENTS
2017 NATIONAL ELECTRICAL CODE (NEC)
2015 INTERNATIONAL FIRE CODE (IFC)
2015 INTERNATIONAL BUILDING CODE (IBC)
2015 INTERNATIONAL RESIDENTIAL CODE (IRC)
DC System Size: 10.075 kW
Asphalt/Comp shingle roof pitch: 6 /12
Anchored on 48 inch centers using UL listed racking system
UV resistant cable ties (not zip ties) used for permanent wire management in
accordance with (NEC 110.2,1110.3(A-B), 300.4)
Junction boxes mounted flush w/racking
APPLICABLE CODES
E. WARNINGS PER NEC 690.
Set Reviewed By:
PV-041115-011207
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1PV01
COVER PAGE
12/07/2020
VSE Project Number: U2783-0047-201
Firm License Number: C2269
Vector Structural Engineering has reviewed the existing structure
with loading from the solar array and lag screw connections to the
existing framing. The design of the racking system, connections,
and all other structure is by others. Mechanical, architectural, and
all other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
PHOTOVOLTAIC MODULES **PV Modules cannot be installed over vents
3'
18"
39.53"
66.85 "
FIRE CODE SETBACKS
ARRAY DETAIL
A B C D
AZIMUTH 180°
TILT ANGLE 27°
MODULE COUNT 31
90
120
150
180
210
240
270
300
330
0
30
60
W E
S
N
80
70
50
4O
2010350
320
310
290
280
260
250
230
220
200 190 170 160
140
130
110
100
340
AZIMUTH
180
SITE INDEX**AC DISCONNECT LOCATED 10' OR
LESS FROM UTILITY METER
70'
280'
280'
200'
UTILITY METER
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
MSP (INTERIOR)
INVERTER & DC DISCONNECT
37'-4"
52'-9"
23'-5"
20'
JUNCTION BOX
CONDUIT RUN
PV MODULES
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1PV02
PROPERTY DETAIL
12/07/2020
VSE Project Number: U2783-0047-201
Firm License Number: C2269
Vector Structural Engineering has reviewed the existing structure
with loading from the solar array and lag screw connections to the
existing framing. The design of the racking system, connections,
and all other structure is by others. Mechanical, architectural, and
all other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
+-
JUNCTION BOX
+-
ELECTRICAL NOTES
PHOTOVOLTAIC AC OUTPUT LABEL
AC OUTPUT CURRENT 32A
NOMINAL AC VOLTAGE 240V
#10 PV WIRE #6 BARE COPPER EGC
1 2
3
A.ALL COMPONENTS SHALL COMPLY WITH NEC AS AMENDED.
B.PHASE CONDUCTORS SHALL BE IDENTIFIED
C.ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF UPON ENTRY INTO BOXES, REFER TO MANUFACTURERS INSTALLATION MANUAL FOR REQUIRED TORQUE VALUES
D.THE DC GEC, IF USED, SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUS TO THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM
E.ATTACHMENT TO GROUND ELECTRODE SHALL USE IRREVERSIBLE CLAMP.
F.ALL EXPOSED METAL PARTS SHALL BE GROUNDED USING TIN PLATED COPPER LAY IN LUGS OR GROUNDING CLIPS LISTED FOR THE PURPOSE
G.MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO MOUNTING HARDWARE THAT PROTECTS FROM PHYSICAL DAMAGE
H.#6 FOR AREAS THAT MAY BE SUBJECT TO DAMAGE
I.BOTH ENDS OF ALL METALLIC CONDUIT SHALL BE BONDED PER NEC 250
J.INTERCONNECTION PER NEC 690
K.ALL WIRES WILL BE RATED AT THHN/THWN-2
L.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS
M.PV PRODUCTION TERMINATED IN LOAD SIDES OF ALL AC DISCONNECTS
4
RAPID
SHUTDOWN
DEVICE
DC DISCONNECT
MODULES & OPTIMIZERS IN A SERIES STRING15
MODULES & OPTIMIZERS IN A SERIES STRING16
*DC OPTIMIZERS OUTPUT 1Voc PER MODULE & KEEP VOLTAGE
AT MAX POWER POINT VOLTAGE OF THE INVERTER*
SE7600H-US
NON-FUSED AC DISCONNECT
60A 120/240V
10' OR LESS FROM UTILITY METER
·All Exposed PV rooftop conductors that are not located under the array modules, shall be installed in a listed raceway, and shall include listed junction
boxes at both ends of the raceway to transition from exposed conductors to the listed raceways. In Accordance with NEC 690.31(A) & (B)**
·ROMEX AMPACITY LIMITED TO 60° VALUES. IF USED, SIZE ACCORDING TO NEC TABLE 310.15
·DC Conduit must be marked in accordance with NEC 690.31. Labeling must be every 10' and must comply with NEC 690.31. See PV05 for Label plan
·ALL DC Conductors must be protected with metal conduit
VISIBLE, LOCKABLE, LABELED DISCONNECT
INTEGRATED ARC FAULT
PROTECTION AND RAPID
SHUTDOWN FOR NEC 2014 AND
2017, 690.11 AND 690.12
CONDUCTOR SCHEDULE WITH NEC ELECTRICAL CALCULATIONS
ID DESCRIPTION CONDUCTOR CONDUIT NO. OF CNDRS.
IN CNDT.
RATED
AMPS EGC TEMP. CORR.
FACTOR
FILL ADJ.
FACTOR
CONT.
CURRENT
MAX.
CURRENT
BASE
AMPACITY
DERATED
AMPACITY
WIRE RUN
DISTANCE
1 DC CIRCUIT: SERIES STRING
OUTPUT TO JUNCTION BOX PV WIRE FREE AIR N/A 15.00A #6 BARE COPPER 0.91 N/A 15.00A 18.75A 35A 31.85A 20ft
2 DC CIRCUIT (TRANSITIONED):
JUNCTION BOX TO INVERTER
10 AWG THWN-2
COPPER 3/4" DIA EMT 4 15.00A 10 AWG THWN-2
COPPER 0.91 .8 15.00A 18.75A 35A 25.48A 20ft
3 INVERTER TO AC DISCONNECT 8 AWG THWN-2
COPPER 3/4" DIA EMT 3 32.00A 10 AWG THWN-2
COPPER 0.91 1.0 32.00A 40.00A 50A 45.50A 5ft
4 AC DISCONNECT TO POINT OF
INTERCONNECTION
8 AWG THWN-2
COPPER 3/4" DIA EMT 3 32.00A 10 AWG THWN-2
COPPER 0.91 1.0 32.00A 40.00A 50A 45.50A 5ft
PV MODULE SPECIFICATIONS
MANUFACTURER Trina
MODEL TSM-DD06H.05(II)
MAX POWER-POINT CURRENT (Imp)9.65AMAX POWER-POINT VOLTAGE (Vmp)33.7 VOPEN CIRCUIT VOLTAGE (Voc)41.4 VSHORT CIRCUIT CURRENT (Isc)10.07 AMAX SERIES FUSE (OCPD)20 AMAX POWER (Pmax)325 WMAX VOLTAGE (Vdc)1000 V
INVERTER SPECIFICATIONS
MANUFACTURER SolarEdge
MODEL SE7600H-US (240V)
MAX DC INPUT VOLTAGE 480 V
MAX OUTPUT POWER 7600 W
NOMINAL AC OUTPUT VOLTAGE 240 V
NOMINAL AC OUTPUT CURRENT 32 A
MAX FUSE (OCPD)40 A
MAX DC VOLTAGE =480V
MAX DC CIRCUIT CURRENT =
MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC
CONVERTER (IF INSTALLED) =
DC DISCONNECT CALCS
30A
15A
40A-2P
G
#6 CU GEC
#XX XXX XXX
200A MAIN BUS200A MAIN OCPD
MAIN SERVICE PANEL
TYPICAL LOAD SIDE
CONNECTION
NEC 705.12 (B)(2)
PV BREAKER LOCATED
OPPOSITE MAIN
BREAKER
PV LOAD CALCULATIONS
200A RATED MAIN PANEL
200A x 120% = 240A
240A - 200A =40A
40A AVAILABLE FOR PV
705.12(B)(2)
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1PV03
1LD/ ELECTRICAL DETAIL
3"
4"
ATTACHMENT SPAN AND SUPPORT PLACEMENT ACCORDING TO MANUFACTURER INSTALLATION MANUAL
+ -+ -+ -+ -
Diagram: Grid-Tied System w/ Optimizers
+ -+ -+ -
PV Source Circuit
To Inverter
Junction Box
#10 PV Wire
Equipment Grounding Conductor
Solar Edge DC Optimizers
Attachment Diagram
48" MAX rail span with staggered attachments to distribute weight across support framing
Rail PV Module
Module Overhang Cantilever = 33% of MAX rail span
25%
25%
50%
ROOF SURFACE FLASHING
5/16" STAINLESS STEEL LAG BOLT
AND FLAT WASHER
SOLAR MODULE
5'5"
4'
4"
NOTE: FOR MORE DETAILS SEE NEC 690.31 (E)(1)
4" BETWEEN ROOF
AND PANELS
JUNCTION BOX
RAIL MOUNT
TERMINAL BLOCK
HEYCO-TITE UL LISTED/RECOGNIZED AND
CSA CERTIFIED LIQUID TIGHT CORDGRIPS
Photovoltaic Array String Detail
(16) Modules String A
(15) Modules String B
GROUNDING DETAIL
PV ATTIC DETAIL
ATTACHMENT DETAIL
JUNCTION BOX DETAIL
*See Attached Data Sheets For More Information
STRINGING DETAIL
A
B
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1PV04
ARRAY/STRINGING DETAIL
12/07/2020
VSE Project Number: U2783-0047-201
Firm License Number: C2269
Vector Structural Engineering has reviewed the existing structure
with loading from the solar array and lag screw connections to the
existing framing. The design of the racking system, connections,
and all other structure is by others. Mechanical, architectural, and
all other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
LOCATION: (1) COMBINER BOX (2) JUNCTION BOX
LOCATION: STRING INVERTER (IF USED)
LOCATION: MAIN SERVICE
LOCATION: (1) MAIN SERVICE
(3) BREAKER PANEL (4) DISCONNECT SWITCH
LOCATION: DC CONDUIT (EVERY 10 FEET)
(REFLECTIVE CONDUIT LABEL)
PER NEC 690.31(B)(1-4)LOCATION: (1) MAIN SERVICE (5) INVERTER (IF USED)
(2) AC COMBINER PANEL MAIN SERVICE & ALL BACK FED PANEL BOARDS
LOCATION: (1) MAIN SERVICE
(2) AC COMBINER PANEL
(3) ALL BACKFED PANELS
I
LABEL NOTESLABEL NOTES
4.5"
H
4.5"
4.5"
4.5"
3"
4.5"
FE
D
CBA
MAIN SERVICE PANEL
FOR ILLUSTRATION ONLY
(NOT ACTUAL MSP)
PV SUB PANEL
(IF USED)
AC
DISCONNECT
(IF USED)
STRING
INVERTER
(IF USED)
JUNCTION
BOX
(IF USED)
A
A
A AC
D
E
H
G
H
A
F
I
I J
J
FOR MICRO INVERTERS ONLY
(NO KNIFE SWITCH DISCONNECT)
J
4.5"
PHOTOVOLTAIC AC DISCONNECT
MAXIMUM AC OPERATING CURRENT:
NOMINAL AC OPERATING VOLTAGE:
J
G
32A
240V
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY
K
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
(2017 NEC 690.56(C)(1)(a)) (YELLOW WITH BLACK LETTERING)
K
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: DUAL POWER SOURCE
SECOND SOURCE IS A PHOTOVOLTAIC SYSTEM
"RAPID SHUTDOWN
SWITCH FOR SOLAR PV SYSTEM"
"PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN"
WARNING:
DO NOT ADD ADDITIONAL CIRCUITS TO PANEL
CAUTION:
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING:
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE SOLAR BREAKER
A.RED BACKGROUND WITH WHITE LETTERING
OR YELLOW / ORANGE BACKGROUND WITH
BLACK LETTERING
B.MINIMUM 3/8" LETTER HEIGHT
C.ALL CAPITAL LETTERS
D.NON BOLD TEXT
E.MATERIAL SUITABLE FOR ENVIRONMENT
F.SIGNS MUST BE REFLECTIVE
G.SIGNS MUST NOT BE HAND WRITTEN
MAX DC VOLTAGE =480V
MAX DC CIRCUIT CURRENT =
MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC
CONVERTER (IF INSTALLED) =
DC DISCONNECT CALCS
30A
15A
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1PV05
LABEL PLAN
SOLAR MODULE SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1SPECS
SPEC SHEETS
INVERTER SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1SPECS
SPEC SHEETS
OPTIMIZER SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1SPECS
SPEC SHEETS
RACKING SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT PORTICADE CONSTRUCTION
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
SI
T
E
I
N
F
O
R
M
A
T
I
O
N
:
Th
e
G
a
t
e
s
A
p
a
r
t
m
e
n
t
s
S
o
u
t
h
C
l
u
b
h
o
u
s
e
37
0
W
7
t
h
S
,
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
SY
S
T
E
M
I
N
F
O
R
M
A
T
I
O
N
:
10
.
0
7
5
k
W
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
2020-PORT
DATE:
11/24/2020
DESIGNED BY:
J. Fairchild
SHEET NAME:
PAGE #REVISION:
1SPECS
SPEC SHEETS