Loading...
HomeMy WebLinkAboutSTATE APPROVAL - 20-00931 - Gorgeous Garage - Fire Sprinklers.pdf Gorgeous Garage Mezzanine – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: October 6, 2020 APPROVED: October 16, 2020 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: Gorgeous Garage Mezzanine 1037-0039647 STREET ADDRESS: 366 Dividend Drive CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: 3-D Fire Protection 6312 S. Burgraff Way Idaho Falls, ID 83401 IDAHO LICENSE: FPSC-008 CONTACT NAME: Travis Capson Travis.Capson@3Dfire.us PHONE NO: (208) 881-5421 SYSTEM DESIGNED BY: Travis Capson Travis.Capson@3Dfire.us PHONE NO: (208) 881-5421 TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 40 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Ordinary Hazard II CONSTRUCTION TYPE: Steel AREA SQUARE FOOTAGE: 5,026 SCOPE OF WORK: Existing steel building with an existing system; tying into a new steel constructed mezzanine. Tie into the existing building to the new mezzanine will be through the 6" as shown on the drawings. Ordinary Hazard II flowing eight heads at .20gpm/ft² at 945 ft². PLAN REVIEW COMMENTS: Approved as submitted. Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.