HomeMy WebLinkAboutSTATE APPROVAL - 20-00931 - Gorgeous Garage - Fire Sprinklers.pdf Gorgeous Garage Mezzanine – Rexburg 1 of 1
STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: October 6, 2020 APPROVED: October 16, 2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Gorgeous Garage Mezzanine 1037-0039647
STREET ADDRESS: 366 Dividend Drive CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: 3-D Fire Protection
6312 S. Burgraff Way
Idaho Falls, ID 83401
IDAHO LICENSE: FPSC-008
CONTACT NAME: Travis Capson
Travis.Capson@3Dfire.us
PHONE NO: (208) 881-5421
SYSTEM DESIGNED BY: Travis Capson
Travis.Capson@3Dfire.us
PHONE NO: (208) 881-5421
TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 40
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Ordinary Hazard II
CONSTRUCTION TYPE: Steel AREA SQUARE FOOTAGE: 5,026
SCOPE OF WORK: Existing steel building with an existing system; tying into a new steel
constructed mezzanine. Tie into the existing building to the new mezzanine
will be through the 6" as shown on the drawings. Ordinary Hazard II flowing
eight heads at .20gpm/ft² at 945 ft².
PLAN REVIEW COMMENTS: Approved as submitted.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.