9/7/2001
Curt Rowland
Forsgren Engineering
350 North 2ed East
Rexburg, Idaho 83440
Dear Curt,
I have reviewed the site plan for Apex Development and have identified the
following discrepancies:
1. Clearly identify 5' sidewalks along 4s' West.
2. Provide cross section details for 6a` South and 4s' West. 6`h South is to be
a 44' wide residential cross section. 4`" West is to match the existing
street and is a 38' wide cross section with curb and gutter on the East side
only.
3. Please identify the areas of street construction and the amount provided by
the developer.
4. Show all dimensions. Include the dimensions from the buildings to the
property lines. Include dimensions to right-of-way, sidewalks, streets, etc.
5. Identify 7`" South on sheet no. P-2.
6. The trash bin configuration will not work using City of Rexburg service.
Our trucks are side pick-up type and require that dumpsters be parallel to
aisle with room for approach.
7. The painted walkway from the south portion of the project to the
clubhouse will not be allowed. Please remove it from the plans. The
crosswalk at 4s' West will have to do for pedestrian traffic.
8. Please identify handicap ramps. On handicap ramp detail, please show the
tooling required for the blind as per the Americans with Disabilities Act
(ADA).
9. Provide details for inlet at 36" concrete sewer pipe from city ditch.
10. Provide pump and vault details for the transfer of storm water to canal.
Please identify if approval has been given from the canal company for use.
11. Identify easements across 6s' South and 4`h West for all utility lines.
Include dimensions to easements and dimensions of easements.
12. Identify location and size of service lines to the buildings.
13. Include the size of water lines. Show the location and size of the existing
16" water main in a South. Also show a 16" water line connecting at 6th
South and running south to connect with the existing water line in 7`'
South. The City of Rexburg will reimburse the developer for the
additional cost of providing this 16" line.
14. Identify existing electrical, telephone, etc. lines. Also show all new utility
locations, including the size and location of their easements.
15. Identify additional catch basins. The current drawings identify only one
catch basin on 4s' West. Include the size and locations of all storm drain
pipes to the catch basins.
16. I have attached a copy of the City of Rexburg Commercial Driveway
Approach Construction Details to the back of this document. Please show
rebar as per the specs in the curb/gutter, driveway approach and the
sidewalk crossing the approach. Also please identify 6" of crushed gravel
under all sidewalks within the City of Rexburg right-of-way. Show the
approach aprons on the site plan. The current plans show the approach
ending at the right-of-way.
17. Please identify handicap parking and the access from parking to the
buildings. Include any ramp locations.
18. Provide parking aisle dimensions and the size of spaces.
19. Provide calculations for storm water retention system.
20. Include lighting plan for parking lot and streets.
21. At this time I do not have any building plans, so I can't identify if the
amount of parking is adequate.
22. The Fire Department has not finished their review of the plan and may
have additional requirements.
Please provide me with 2 new copies of the corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
9/12/2001
Curt Rowland
Forsgren Engineering
350 North 2' East
Rexburg, Idaho 83440
Dear Curt,
GU-// 01 LL.ea.U.VI/U.tLO LL//
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@d.rexburg.id.us
I have attached a copy of the Fire Department review of the Apex site plan to the
back of this document. If you have any questions, please give me a call at 359-3020 ext.
324.
Sincerely,
Val Christensen
Building Official
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 8-01
Plan Review Review Date: 9-11-01
Building Name: Apex Development Site Plan
Building Address: Approximately 4u' West and 6`h South
Stories: U/K Type of Construction: U/K
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: Approximately 16,560 SQ. FT/Building
1).Required Fire Flow (Appendix III -A): 3,500 GPM for 3 Hours
Comments: This flow may be reduced by 50% with the installation of
an approved sprinkler system in each building.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: One Existing, Five proposed
Fire Hydrant Flows: N/A
Fire Flow Test Location:
Fire Flow Supplied By:
Other Approved Water Source: NONE
Water Supply Acceptable: NONE
Fire Hydrant Location Acceptable: NO
Water Supply Comments: Additional hydrants need to be installed
throughout complex OR fire sprinkler systems installed in each
building.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable Width: YES Length: YES Surface: OKAY
Turning Radius: OR Grade: OR Vehicle Vertical: U/K
Clearance: U/K Turn Arounds: YES
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: Both must be installed and made serviceable prior to
construction or a stop work order will be issued.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: Minimum size is 2A-10BC extinguisher
Comments:
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: Unknown at this time Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: Comments
7).Standpipes (Article 10 Section 1004) Required:
Type Required: Unknown at this time T Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: Unknown
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments
9).Fire Alarm Systems (Article 10 Section 1007)Required: Unknown
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable:
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson Date: 9-11-01
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
10/24/2001
cify o f lexlU,0.0 7
Willie Teuscher
Department of Environmental Quality
900 North Skyline Drive
Idaho Falls, ID 83402
Dear Sill:
STATE OF IDAHO
www o. rexbu rg. id. us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208)359-3022
e-mail rexburg@ci.rexburg.id.us
Kurt Rowland with Forsgren Engineering has asked me to get in contact with you
concerning City of Rexburg approval for allowing 0.32 percent versus 0.40 percent for the slope
of 8" sewer mains in the Newport Apartments project. We have approved this change from
minimum requirement based on approval from your department. If you have any questions please
give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Assistant Engineer
cc: Kurt Rowland