Loading...
HomeMy WebLinkAboutSTAFF REVIEWS - 02-00067 - Apex Management - Remodelf////�//,P.O. Box 280 edy �/...1' rL eo�'12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 ^� www.ci.rexburgJd.us e-mail rexburg@cLrexburgJd.us 9/7/2001 Curt Rowland Forsgren Engineering 350 North 2ed East Rexburg, Idaho 83440 Dear Curt, I have reviewed the site plan for Apex Development and have identified the following discrepancies: 1. Clearly identify 5' sidewalks along 4s' West. 2. Provide cross section details for 6a` South and 4s' West. 6`h South is to be a 44' wide residential cross section. 4`" West is to match the existing street and is a 38' wide cross section with curb and gutter on the East side only. 3. Please identify the areas of street construction and the amount provided by the developer. 4. Show all dimensions. Include the dimensions from the buildings to the property lines. Include dimensions to right-of-way, sidewalks, streets, etc. 5. Identify 7`" South on sheet no. P-2. 6. The trash bin configuration will not work using City of Rexburg service. Our trucks are side pick-up type and require that dumpsters be parallel to aisle with room for approach. 7. The painted walkway from the south portion of the project to the clubhouse will not be allowed. Please remove it from the plans. The crosswalk at 4s' West will have to do for pedestrian traffic. 8. Please identify handicap ramps. On handicap ramp detail, please show the tooling required for the blind as per the Americans with Disabilities Act (ADA). 9. Provide details for inlet at 36" concrete sewer pipe from city ditch. 10. Provide pump and vault details for the transfer of storm water to canal. Please identify if approval has been given from the canal company for use. 11. Identify easements across 6s' South and 4`h West for all utility lines. Include dimensions to easements and dimensions of easements. 12. Identify location and size of service lines to the buildings. 13. Include the size of water lines. Show the location and size of the existing 16" water main in a South. Also show a 16" water line connecting at 6th South and running south to connect with the existing water line in 7`' South. The City of Rexburg will reimburse the developer for the additional cost of providing this 16" line. 14. Identify existing electrical, telephone, etc. lines. Also show all new utility locations, including the size and location of their easements. 15. Identify additional catch basins. The current drawings identify only one catch basin on 4s' West. Include the size and locations of all storm drain pipes to the catch basins. 16. I have attached a copy of the City of Rexburg Commercial Driveway Approach Construction Details to the back of this document. Please show rebar as per the specs in the curb/gutter, driveway approach and the sidewalk crossing the approach. Also please identify 6" of crushed gravel under all sidewalks within the City of Rexburg right-of-way. Show the approach aprons on the site plan. The current plans show the approach ending at the right-of-way. 17. Please identify handicap parking and the access from parking to the buildings. Include any ramp locations. 18. Provide parking aisle dimensions and the size of spaces. 19. Provide calculations for storm water retention system. 20. Include lighting plan for parking lot and streets. 21. At this time I do not have any building plans, so I can't identify if the amount of parking is adequate. 22. The Fire Department has not finished their review of the plan and may have additional requirements. Please provide me with 2 new copies of the corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson 9/12/2001 Curt Rowland Forsgren Engineering 350 North 2' East Rexburg, Idaho 83440 Dear Curt, GU-// 01 LL.ea.U.VI/U.tLO LL// STATE OF IDAHO P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@d.rexburg.id.us I have attached a copy of the Fire Department review of the Apex site plan to the back of this document. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 8-01 Plan Review Review Date: 9-11-01 Building Name: Apex Development Site Plan Building Address: Approximately 4u' West and 6`h South Stories: U/K Type of Construction: U/K Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: Approximately 16,560 SQ. FT/Building 1).Required Fire Flow (Appendix III -A): 3,500 GPM for 3 Hours Comments: This flow may be reduced by 50% with the installation of an approved sprinkler system in each building. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: One Existing, Five proposed Fire Hydrant Flows: N/A Fire Flow Test Location: Fire Flow Supplied By: Other Approved Water Source: NONE Water Supply Acceptable: NONE Fire Hydrant Location Acceptable: NO Water Supply Comments: Additional hydrants need to be installed throughout complex OR fire sprinkler systems installed in each building. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable Width: YES Length: YES Surface: OKAY Turning Radius: OR Grade: OR Vehicle Vertical: U/K Clearance: U/K Turn Arounds: YES Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: Both must be installed and made serviceable prior to construction or a stop work order will be issued. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: Minimum size is 2A-10BC extinguisher Comments: 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: Unknown at this time Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments 7).Standpipes (Article 10 Section 1004) Required: Type Required: Unknown at this time T Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: Unknown Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments 9).Fire Alarm Systems (Article 10 Section 1007)Required: Unknown Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: NO Plans Checked By: Chris Huskinson Date: 9-11-01 Please furnish comments back to the plan reviewer in the following manner: Written Comments: YES New Plans: YES 10/24/2001 cify o f lexlU,0.0 7 Willie Teuscher Department of Environmental Quality 900 North Skyline Drive Idaho Falls, ID 83402 Dear Sill: STATE OF IDAHO www o. rexbu rg. id. us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208)359-3022 e-mail rexburg@ci.rexburg.id.us Kurt Rowland with Forsgren Engineering has asked me to get in contact with you concerning City of Rexburg approval for allowing 0.32 percent versus 0.40 percent for the slope of 8" sewer mains in the Newport Apartments project. We have approved this change from minimum requirement based on approval from your department. If you have any questions please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Assistant Engineer cc: Kurt Rowland