HomeMy WebLinkAboutAPPLICANT RESPONSE - 02-00067 - Apex Management - RemodelCURTIS MINER
ARCHITECTURE
October 2, 2001
Mr. Val Christensen
Rexburg City Building Official
Re: Newport Married housing
Following you will find responses to questions or concerns raised during your review of the above project.
Attached you will find (2) two revised sets of plans showing the revisions or modifications requested.
Please use these new plans for your record and permit sets of documents.
Item #1 Section 1006.3.2.3 does not require protected stair assemblies unless the occupant load
exceeds 10. The occupant load for this stair is based on I occupant per 200 square foot
which is 5.3 occupants per level. Occupant loads are per level and are not combined as
stated in UBC 1003.2.3.4. Therefore the detail provided on stairs is not required to be
rated or protected.
Item #2 The room identified as a "Niche" has been modified as required. This area has been
included as part of the Bedroom and is designated as a "Sitting Area". Please see modified
plans.
Item #3 The "B" type bathroom meets all residential requirements. Forward approaches require a
48" approach as indicated. Please refer to attached ANSIA117.1 Type `B" Dwelling
Units.
Item #4 The structural calculation for columns is attached.
Item #5 The plans for the clubhouse will be provided at a later date prior to construction of that
phase.
Item #6 Fire extinguishers are required in each unit as indicated on revised plans. The Manual fire
alarm system requirements will be provided by the installer on a deferred submittal.
Please call with any questions,
Alan Shurtliff,
Project Manager
A Limited Liability Company • Curtis N. Miner AIA, NCARB, Principal Architect
American Institute of Architects, Member • National Council of Architectural Registration Boards, Certified
357 East 1200 South, Orem, Utah 84058 • Phone (801) 229-7907 • Fax (801) 229-0040
10/04/2001 TRU 07:08 FAX 801 229 2015 J M WILLIAMS ASSOCIATES ... MINER CURTIS Q1002/002
J.M. WILLIAMS and ASSOCIATES • Structural Engineering
alm
57 West South Temple • Suite 210 • Salt Lake City, Utah 84101 • (801) 575.6455 • Fax (801) 575-6456
1433 South State Street • Orem. Utah 84097 • (801) M-2014 • Fox (801) 229-2015
PROJECT
DATE
SHEET OF
DESIGNED BY
JOB NO.
4 ��--I I .•. .. .I I .,..I ,. I : I I I I
:.j I I. i. 11 I r4 I I I L .I
L
IIIIi' II ;i Iil�'I I
dA
li,il illl III 1411
���'.
1 I II II
'I 1 I: 1 i: I I
14 n!'XI�aI`-"1�,1_IxlAu
I�'dtl ="71.5
'12n4 �S_leai6'I
I- A-
I� I I• I I '� •- -I - --r-...—:r.l. .1 I
I
i L.I. ., ._•._i .r.. I. I I
li I �
I I
I � I
II I II fll
+ `
L.I.
I, r 1i
. _. I. L.I
I 1
I I -
I I I.� i.:
'
14 1
n A
1
I I
� C I I
,. L.I. ..I.
I I I �
-�'!A'� . -��yQp.pjh I ... -- .-- —
I I I -• I I' i
W1L; ! i- I -.
!
li II '.L1.. 1., illi ��• ili
I ' .'.
�`":'i..rl .I.. I.
-717:
I '1.' .ILI...1.1. I�.i i
i .I.. _y..l' •
I .�
I
'_.1-
1
_I.. I._1_..�___..
I
• rP : II I
I I � I I.I�
I I L iI
Chapter 10. Dwelling Units
1003.122.3 Range or Cooktop. Clear
floor or ground space shall be positioned for
parallel approach.
EXCEPTION: Where a forward ap-
proach clearfloor or ground space is pro-
vided, the clear floor or ground space
shall provide knee and toe clearance
complying with Section 306. Where knee
and toe space is provided, the underside
of the range or cooktop shall be insulated
or otherwise configured to prevent
burns, abrasions, or electrical shock.
1003.122.4 Oven. Clear floor or ground
space shall be positioned for parallel or for-
ward approach.
1003.122.5 Refrigerator/Freezer. Clear
floor orground space shall be positioned for
parallel or forward approach.
1003.122.6 Trash Compactor. Clear floor
or ground space shall be positioned for par-
allel or forward approach.
1004 Dwelling Units with Accessible
Communication Features
1004.1 General. Dwelling units required to have ac-
cessible communication features shall comply with
Section 1004.
1004.2 Dwelling Unit Smoke Detection. Where
provided, dwelling unit smoke detection shall in-
clude audible notification complying with NFPA 72.
1004.3 Building Fire Alarm System. Where a
building fire alarm system is provided, the system
wiring shall be extended to a point within the dwell-
ing unit in the vicinity of the dwelling unit smoke
detection system.
1004.4 Visible Notification Appliances. Visible
notification appliances, where provided within the
dwelling unit as part of the dwelling unit smoke
detection system or the building fire alarm system,
shall comply with Sections 1004.4.1 through
1004.4.4.
1004.4.1 Appliance. Visible notification appli-
ance shall comply with NFPA 72.
1004.4.2 Activation. All visible notification ap-
pliances provided within the dwelling unit for
smoke detection notification shall be activated
upon smoke detection. All visible notification
appliances provided within the dwelling unit for
building fire alarm notification shall be activated
78
ICC/ANSI A117.1-1998
upon activation of the building fire alarm in the
portion of the building containing the dwelling
unit
1004.4.3 Interconnection. The same visible
notification appliances shall be permitted to pro-
vide notification of dwelling unit smoke detec-
tion and building fire alarm activation.
1004.4.4 Prohibited Use. Visible notification
appliances used to indicate dwelling unit smoke
detection or building fire alarm activation shall
not be used for any other purpose within the
dwelling unit.
1004.5 Dwelling Unit Primary Entrance. Commu-
nication features shall be provided at the dwelling
unit primary entrance complying with Sections
1004.5.1 and 1004.5.2.
1004.5.1 Notification. A hard -wired electric
doorbell shall be provided. A button or switch
shall be provided on the public side of the dwell-
ing unit primary entrance. Activation of the but-
ton or switch shall initiate an audible tone within
the dwelling unit.
1004.5.2 Identification. A means for visually
identifying a visitor without opening the dwelling
unit entry door shall be provided. Peepholes,
where used, shall provide a minimum 180 de-
gree range of view.
1004.6 Site, Building, or Floor Entrance. Where
a system permitting voice communication between
a visitor and the occupant of the dwelling unit is pro-
vided at a location other than the dwelling unit entry
door, the system shall comply with Sections
1004.6.1 and 1004.6.2.
1004.6.1 Public or Common -Use Interface.
The public or common -use system interface
shall include the capability of supporting voice
and TTY communication with the dwelling unit
interface.
1004.6.2 Dwelling Unit interface. The dwell-
ing unit system interface shall include a tele-
phone jack capable of supporting voice and
TTY communication with the public or common -
use system interface.
1004.7 Closed -Circuit Communication Sys-
tems. Where a closed-circuit communication sys-
tem is provided, the public or common -use system
interface shall comply with Section 1004.6.1, and
the dwelling unit system interface in units required
to have accessible communication features shall
'comply with Section 1004.6.2.
I0C/AN51 A117.14998
forcing for shower seat is not re-
quired in shower compartments
larger than 36 inches (915 mm) by
36 inches (915 mm). Clearance of
30 inches (760 mm) wide mini-
mum, measured from the face of
the shower compartment, by
48 inches (1220 mm) deep mini-
mum, measured from the shower
head wall shall be provided.
1003.11.3.2 Option B. One of each type of
fixture provided shall comply with Sections
1003.11.3.2.1 through 1003.11.3.2.3. The
accessible fixtures shall be in a singletoileV
bathing area, such that travel between fix-
tures does not require travel through other
parts of the dwelling unit.
1003.11.3.2.1 Lavatory. Lavatories
shall comply with Sections
1003.11.3.2.1.1 through
1003.11.3.2.1.3.
1003.11.32.1.1 Clear Floor or
Ground Space. A clear floor or
ground space complying with Sec-
tion 305.3, positioned for a parallel
approach shall be provided.
EXCEPTION: A lavatory com-
plying with Section 606.
1003.11.3.2.1.2 Position. The
centerline of the lavatory shall align
with the centerline of the clear floor
or ground space.
1003.11.3.2.1.3 Height. The front
of the lavatory shall be 34 inches
(230 mm) maximum above the
floor or ground, measured to the
higher of the fixture rim or counter
surface.
1003.11.3.2.2 Water Closet. The wa-
ter closet shall comply with Section
1003.11.3.1.2.
1003.11.3.2.3 Bathing Facilities.
Where either a bathtub or shower
compartment is provided, it shall con-
form with Section 1003.11.3.2.3.1 or
1003.11.3.2.3.2.
1003.11.3.2.3.1 Bathtub. Clear-
ance in front of bathtubs shall be
30 inches (760 mm) wide minimum
by 48 inches (1220 mm) long mini-
mum measured from the foot end
of the bathtub.
Chapter 10. Dwelling Units
1003.11.32.32 Shower Com-
partment. If a shower compart-
ment is the only bathing facility the
shower compartment shall have
minimum dimensions of 36 inches
(916 mm) minimum by 36 inches
(915 mm) minimum. Reinforcing
for shower seat is not required in
shower compartments larger than
36 inches (915 mm) by 36 inches
(915 mm). Clearance 30 inches
(760 mm) minimum, measured
from the face of the shower
compartment, by 48 inches (1220
mm) minimum, measured from the
shower head wall shall be pro-
vided.
1003.12 Kitchens. Kitchens shall comply with Sec-
tions 1003.12.1 and 1003.12.2.
1003.12.1 Clearance. Clearance complying
with Sections 1003.12.1.1 and 1003.12.1.2
shall be provided.
1003.12.1.1 Galley. Clearance between all
opposing base cabinets, counter tops, ap-
pliances, or walls within kitchen work areas
shall be 40 inches (1015 mm) minimum.
1003.12.1.2 U -Shaped. In kitchens with
counters, appliances, or cabinets on three
contiguous sides, clearance between all
opposing base cabinets, countertops, ap-
pliances, or walls within kitchen work areas
shall be 60 inches (1525 mm) minimum.
1003.12.2 Clear Floor or Ground Space.
Clear floor or ground space at appliances shall
comply with Section 305.3 and Sections
1003.12.2.1 through 1003.12.2.6.
1003.12.2.1 Sink. The sink shall comply
with Sections 1003.12.2.1.1 and
1003.12.2.1.2.
1003.12.2.1.1 Approach. Clear floor
or ground space shall be positioned for
a parallel approach.
EXCEPTION: Sink complying with
Section 606.
1003.12.2.12 Position. The center-
line of the sink shall align with the cent-
erline of the clear floor or ground space.
1003.12.2.2 Dishwasher. Clear floor or
ground space shall be positioned for paral-
lel or forward approach. Clear floor or
ground space shall be positioned beyond
the swing of the dishwasher door.
UFA
Chapter 10. Dwelling Units _ ICC/ANSI A117.1-1998
EXCEPTION: A lavatory and a water
mm) minimum shall be provided
closet in a room containing only a lavato-
measured from the wall behind the
ry and water closet, provided that the
water closet. Forty-eight inches
room does not contain the only lavatory
(1220 mm) minimum shall be pro -
or water closet on the accessible level of
vided measured from a point
the dwelling unit.
18 inches (455 mm) from the cent-
erline of the water closet on the
1003.11.3.1.1 Lavatory. A clear floor
side designated for future installa-
or ground space complying with Sec-
tion of grab bars. Vanities or lavato-
tion 305.3, positioned for a parallel ap-
ries on the wall behind the water
proach and centered on the lavatory
closet are permitted to overlap the
shall be provided.
clear floor or ground space.
EXCEPTIONS:
t. ti lavatory complying with Sec-
1003.11.3.12.3 Parallel or For-
For -
tion 606.
ward Approach. Fifty-six inches
(1420 mm) minimum shall be pro -
2. Cabinetry shall be permitted to
vided measured from the wall
be added under the lavatory,
behind the water closet. Forty-two
provided such cabinetry can be
inches (1065 mm) shall be pro -
removed without removal or re-
vided measured from the center -
placement of the lavatory, and
line of the water closet.
provided the finish floor extends
under such cabinetry.
1003.11.3.1.3. Bathing Facilities.
Where a bathtub or shower compart-
1003.11.3.1.2 Water Closet. The later-
merit is provided it shall conform
al distance from the centerline of the
with Section 1003.11.3.1.3.1,
water closet to a bathtub, or lavatory
1003.11.3.1.3.2, or 1003.11.3.1.3.3.
shall be 18 inches (455 mm) minimum
on one side and 15 inches (380 mm)
1003.11.3.1.3.1 Parallel Ap-
minimum on the other side. Where the
proach Bathtubs. Clearance in
water closet is adjacent to the wall the
front of bathtubs with a parallel ap-
lateral distance from the centerline of
proach shall be 30 inches (760
the water closet to the wall shall be
mm) wide minimum by 60 inches
18 inches (455 mm) and 15 inches (380
(1525 mm) long minimum. A lava -
mm) minimum to a lavatory or bathtub.
tory shall be permitted at the foot
The water closet shall be positioned to
end of the bathtub if a 30 inch (760
allow for future installation of a grab bar
mm) wide minimum by 48 inch (760
on the side with 18 inches (455 mm)
mm by 1220 mm) long minimum
clearance. Clearance areas around the
clearance in front of the bathtub is
water closet shall comply with Section
provided.
1003.11.3.1.2.1, 1003.11.3.1.2.2, or
EXCEPTION: Lavatories com-
1003.11.3.1.2.3.
plying with Section 606 shall be
permitted in the clearance.
1003.11.3.1.2.1 Parallel Ap-
proach. Fifty-six inches (1420
1003.11.3.1.32 Forward Ap-
mm) minimum shall be provided
proach Bathtubs. Clearance in
measured from the wall behind the
front of bathtubs with a forward ap-
water closet. Forty-eight inches
proach shall be 48 inches (1220
(1220 mm) minimum shall be pro-
mm) wide minimum by 60 inches
vided measured from a point
If 525 mm) long minimum. A water
18 inches (455 mm) from the cent-
closet shall be permitted in the
erline of the water closet on the
clearance at the foot end of the
side designated for future installa-
bathtub.
tion of grab bars. Vanities or lavato-
ries on the wall behind the water
1003.11.3.1.3.3 Shower Com -
closet are permitted to overlap the
partment. If a shower compart-
clear floor or ground space.
ment is the only bathing facility, the
shower compartment shall be 36
1003.11.3.1.2.2 Forward Ap-
inches (915 mm) minimum by 36
proach. Sixty-six inches (1675
inches (915 mm) minimum. Rein -
76
ICC/ANSI A117.1-1998
doors shall be measured between the face
of the door and stop, with the door open
90 degrees.
1003.5.2.2 Thresholds. Thresholds shall
comply with Section 303.
EXCEPTION: Thresholds at exterior
sliding doors shall be permitted to be
3/4 inch (19 mm) high maximum provided
they are beveled with a slope not steeper
than 1:2.
1003.5.2.3 Automatic Doors. Automatic
doors shall comply with Section 404.3.
1003.52.4 Double Leaf Doorways.
Where an inactive leaf with operable parts
more than 48 inches (1220 mm) above the
floor or ground is provided, the active leaf
shall provide the clearance required by
Section 1003.5.2.1.
1003.6 Ramps. Ramps shall comply with Section
405.
1003.7 Private Residence Elevators. Elevators
shall comply with Section 1002.7.
EXCEPTION: Elevators complying with Section
407.
1003.8 Wheelchair (Platform) Lifts. Wheelchair
(platform) lifts shall comply with ASME/ANSI A17.1
and with Sections 305 and 309.
1003.9 Operable Parts. Lighting controls, electrical
receptacles, environmental controls, and user con-
trols for security or intercom systems shall comply
with Sections 309.2 and 309.3.
EXCEPTIONS:
1. Electrical receptacles serving a dedicated
use.
2. Appliance mounted controls or switches.
3. A single outlet where all of the following con-
ditions are met:
(a) the outlet is above a length of countertop
that is uninterrupted by a sink or appli-
ance;and
(b) at least one receptacle complying with
Section 1003.9 is provided for that length
of countertop; and
(c) all other receptacles provided for that
length of countertop comply with Section
1003.9.
4. Floor electrical receptacles.
5. Plumbing fixture controls.
6. HVAC diffusers.
7. Ceiling fan mounted controls.
Chapter 10. Dwelling Un'rts
1003.10 Laundry Equipment. Washing machines
and clothes dryers shall comply with Section
1003.10.1.
1003.10.1 Clear Floor or Ground Space. A
clear floor or ground space complying with Sec-
tion 305.3, positioned for parallel approach and
centered on the appliance shall be provided.
1003.11 Toilet and Bathing Fixtures. Toilet and
bathing fixtures shall comply with Sections
1003.11.1 through 1003.11.3.
EXCEPTION: Fixtures on levels not required to
be accessible.
1003.11.1 Clear Floor or Ground Space.
Clear floor or ground space required by Section
1003.11.3.1 or 1003.11.3.2 shall comply with
Section 305.3 and Sections 1003.11.1.1
through 1003.11.1.3.
1003.11.1.1 Doors. Doors shall not swing
into the clear floor or ground space for any
fixture.
EXCEPTION: Where a clear floor or
ground space complying with Section
305.3, excluding knee and toe clear-
ances under elements, is provided within
the room, beyond the arc of the door
swing.
1003.11.1.2 Knee and Toe Clearance.
Clear floor or ground space shall be per-
mitted to include knee and toe clearances
complying with Section 306.
1003.11.1.3 Overlap. Clear floor or ground
spaces shall be permitted to overlap.
1003.11.2 Grab Bar Reinforcement. Rein-
forcement shall be provided for future installa-
tion of grab bars and shower seats at water
closets, bathtubs, and shower compartments.
Where walls are to permit installation of grab
bars and seats complying with Section 604.5,
607.4, or 610, reinforcement shall be provided
for future installation of grabbers meetingthose
requirements.
EXCEPTION: Reinforcement is not required
in a room containing only a lavatory and a
water closet, provided thatthe room does not
contain the only lavatory or water closet on
the accessible level of the dwelling unit.
1003.11.3 Bathroom Fixtures. Bathroom fix-
tures shall comply with either Section
1003.11.3.1 (Option A) or Section 1003.11.3.2
(Option B).
1003.11.3.1 Option A. Each fixture pro-
vided shall comply with Sections
1003.11.3.1.1 through 1003.11.3.1.3.
75
Chapter 10. Dwelling Units
of controls shall not require reaching across
burners.
1002.12.6.5 Oven. For side -opening
ovens, the door latch side shall be next to
a countertop. Ovens shall have controls on
front panels, on either side of the door.
1002.12.6.6 Refrigerator/Freezer. Com-
bination refrigerators and freezers shall
have at least 50 percent of the freezer
space 54 inches (1370 mm) maximum
above the floor or ground. The clear floor or
ground space shall be positioned for a par-
allel approach to the space dedicated to a
refrigerator/freezer with the centerline of
the clear floor or ground space offset
24 inches (610 mm) maximum from the
centerline of the dedicated space.
1002.12.6.7 Trash Compactor. A clear
floor or ground space positioned for parallel
or forward approach shall be provided.
1002.13 Windows. Where operable windows are
provided, at least one window in each sleeping, liv-
ing, or dining space shall have operable parts com-
plying with Section 1002.9. Each required operable
window shall have operable parts complying with
Section 1002.9.
1002.14 Storage Facilities. Where storage facili-
ties are provided, they shall comply with Sections
1002.14.1 through 1002.14.3.
EXCEPTION: Kitchen cabinets shall comply with
Section 1002.12.5.
1002.14.1 Clear Floor or Ground Space. A
clear floor or ground space complying with Sec-
tion 305.3, positioned for either parallel or for-
ward approach, shall be provided at each stor-
age facility.
1002.14.2 Height. A portion of the storage area
of each storage facility shall accommodate a
forward reach or side reach complying with
Section 308.
1002.14.3 Operable Parts. Operable parts on
storage facilities shall comply with Section 309.
1003 Type B Dwelling Units
1003.1 General. Type B dwelling units shall comply
with Section 1003.
1003.2 Primary Entrance. The accessible primary
entrance shall be on an accessible route from public
and common areas. The primary entrance shall not
be to a bedroom.
74
ICC/ANSI A117.1-1988
1003.3 Accessible Route. Accessible routes with-
in Type B dwelling units shall comply with Sections
1003.3.1 and 1003.3.2.
EXCEPTION: One of the following is not required
to be on an accessible route:
1. A raised floor area in a portion of a living, din-
ing, or sleeping room; or
2. A sunken floor area in a portion of a living,
dining, or sleeping room; or
3. A mezzanine that does not have plumbing
fixtures or an enclosed habitable space.
1003.3.1 Location. At least one accessible
route shall connect all spaces and elements
which are a part of the dwelling unit. Where only
one accessible route is provided, it shall not
pass through restrooms, closets, or similar
spaces.
1003.3.2 Components. Accessible routes
shall consist of one or more of the following ele-
ments: walking surfaces with a slope not steep-
er than 1:20, doorways, ramps, elevators, and
wheelchair (platform) lifts.
1003.4 Walking Surfaces. Walking surfaces that
are part of an accessible route shall comply with
Sections 1003.4.1 and 1003.4.2.
1003.4.1 Width. Clear width of an accessible
route shall comply with Section 403.5.
1003.4.2 Changes in Level. Changes in levet
shall comply with Section 303.
EXCEPTION: Where exterior deck, patio or
balcony surface materials are impervious,
the finished exterior impervious surface shall
be 4 inches (100 mm) maximum below the
finished floor level of the adjacent interior
spaces of the dwelling unit.
1003.5 Doors and Doorways. Doors and door-
ways shall comply with Sections 1003.5.1 and
1003.5.2.
1003.5.1 Primary Entrance Door. The primary
entrance door to the dwelling unit shall comply
with Section 404,
EXCEPTION: Maneuvering clearances re-
quired by Section 404.2.4 shall not be re-
quired on the dwelling unit side of the primary
entrance door.
1003.5.2 User Passage Doorways. Doorways
intended for user passage shall comply with
Sections 1003.5.2.1 through 1003.5.2.4.
1003.5.2.1 Clear Width. Doorways shall
have a clear opening of 313/4 inches (810
mm) minimum. Clear opening of swinging
Oct 11 at 11.09a CURTIS MINER ARCHITECTURE 801-229-0040 P.1
A
CURTIS MINER
ARCHITECTURE
October 11, 2001
Mr. Val Christensen
Rexburg City Building Official
Re: Newport Married housing
The following modification will be applied to this project in response to your phone call on
October 9, 2001 to help clarify item on the original city review.
Item #I Contractor will be instructed to provide 1 hr dwelling separation walls (5/8" typ "x"
gyp. bd. on interior and exterior) at stair/balcony areas and provide a 20 minute
rated door at each trait entrance_
Item #3 Upon further review we do not comply with the forward approach for the "B" type
bathroom residential requirements. Forward approaches require a 48" approach as
indicated. Contractor will be instructed to modify mechanical room by 3" to
provide 48" approach for all Type "B" Dwelling Units bathrooms. Please see
attached addendum.
Please call with any questions,
Alan Shurtliff,
Project Manager
A Limited Liability Company • Curtis N. Miner AIA, NCARB, Principal Architect
American Institute of Architects, Member • National Council of Architectural Registration Boards, Certified
:357 East 1200 South, Orem, Utah 84058 • Phone (801) 229-7907 • Fax (801) 229-0040
Oct 11 01 11:09a CURTIS MINER ARCHITECTURE 801-229-0040
3'-1" 6`2 -
HAS
� 3"
o - � .N
48'x60" ,
PURN CI.BAR
BATH ,4
NITGHEN —
N O
Ln 4
BEDROOM
"B" TYPE BATHROOM DETAIL
SCALE: 1/4'= 1'-0"
MARRIED HOUSING
REXBURG, IDAHO
ADDENDUM #1
SHEET I OF I
DATE: OCTOBER 2001
PROJECT s: GMA0116
p.2
CIL"
CURTIS MINER
ARCHITECTURE-