Loading...
HomeMy WebLinkAboutREVIEW REPORT - 02-00062 - Continental Park Apartments - Nine 4-Plexes7/25/2002 Steven Yearsley Forsgren Engineering 350 North 2' East Rexburg, Idaho 83440 Dear Steven, edy v ea.11. l((.!G !/ STATE OF IDAHO www.ci.rexburgJd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the plans for the Continental Park Apartments and have identified the following discrepancies, additions or questions: 1. Provide storm pond calculations. 2. Get with John Millar and work out a Development Agreement. 3. Identify that setbacks are to eaves. 4. Show right-of-way lines. If they do not exist, please provide documentation dedicating the area from the back of the sidewalks towards the street to the City of Rexburg. 5. Identify handicap parking spaces along with signs identifying them and the accessible routes into the buildings. 6. Identify trash facilities. 7. Sheet DT -4 calls out welded wire fabric. Please change this to 1/2" rebar at 18" o.c. in both directions as per the City of Rexburg specifications. Also identify the approach and sidewalk at the approach as 6" thick. The curb and gutter must also be reinforced. Please identify 24 4 rebar in the curb and gutter section. 8. The architectural drawings and the stair drawings must be stamped by a licensed professional. 9. All units on the lower level must be constructed as "Type B" units as per Section 1103.1.9.3 of the 1997 Uniform Building Code (UBC). Please change bathroom configuration for compliance. Please identify grab bar backing, accessible thresholds and all other accessible features. 10. For the "Type A" unit please identify grab bar backing, accessible thresholds and all other accessible features. 11. Please identify smoke detectors as per the UBC and 2A- l OBC fire extinguishers in each apartment unit. 12. Sheet SL3 identifies 2" washers on the anchor bolts. Are these the 2" square washers as identified in the UBC? 13. Please identify firewall construction, including draftstops. Unit separation must be maintained from foundation to roof sheathing. 14. Please identify fire separation at the floors between units. Engineered joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. 15. Please identify attic ventilation as per the UBC. 16. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson Lyle Cook REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (2 08) 359-3010 1997 Uniform Fire Code Plan Review Plan Date: 5-02 Review Date: 7-17-02 Building Name: CONTINENTAL PARK APARTMENTS Building Address: CORNER OF 5' WEST AND 7TH SOUTH Stories: 2.5 Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5400 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75 PERCENT IF BUILDINGS HAVE AN APPROVED AUTOMATIC SPRINKLER SYSTEM 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: TWO PROPOSED Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: Fire Flow Supplied By: Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: Grade: Vehicle Vertical: Clearance: Turn Arounds: Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PROVIDE MINIMUM OF ONE FIRE EXTINGUISHER PER UNIT, MINIMUM SIZE OF 2A10BC EACH 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: NO Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES, SEE COMMENTS Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PROVIDE SMOKE DETECTORS IN EACH SLEEPING ROOM AND ADJACENT HALLWAYS/CORRIDORS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: WITH ABOVE ITEMS COMPLIED WITH Plans Checked By: CHRIS HUSKINSON Date: 7-17-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: