HomeMy WebLinkAboutSITE PLAN REVIEW - Academy Apartments - 450 S 4th W - Glen ReedMEMO:
TO:
TO WHOM IT MAY CONCERN
FROM:
CHRIS HUSKINSON, FIRE INSPECTOR
DATE:
DECEMBER 2, 2002
RE:
GLEN REED APARTMENTS,
TO WHOM IT MAY CONCERN:
Upon review of the site plan drawings submitted the following items need to be
addressed:
1. WATER SUPPLY: This proposed project will require a minimum of four fire
hydrants capable of supplying a minimum of 3500 GPM for three hours within
350 of buildings. The drawings only show one proposed fire hydrant and no
existing fire hydrants.
2. In addition, the apartment building will be required to have a fire sprinkler system
installed. The parking garage may also have to be sprinklered depending upon
configuration and proximity to apartment building.
Additional plans are required to complete an accurate plan review of this project. If there
are any questions please feel free to contact me.
Chris Huskinson
Fire Inspector