Loading...
HomeMy WebLinkAboutSITE PLAN REVIEW - Academy Apartments - 450 S 4th W - Glen ReedMEMO: TO: TO WHOM IT MAY CONCERN FROM: CHRIS HUSKINSON, FIRE INSPECTOR DATE: DECEMBER 2, 2002 RE: GLEN REED APARTMENTS, TO WHOM IT MAY CONCERN: Upon review of the site plan drawings submitted the following items need to be addressed: 1. WATER SUPPLY: This proposed project will require a minimum of four fire hydrants capable of supplying a minimum of 3500 GPM for three hours within 350 of buildings. The drawings only show one proposed fire hydrant and no existing fire hydrants. 2. In addition, the apartment building will be required to have a fire sprinkler system installed. The parking garage may also have to be sprinklered depending upon configuration and proximity to apartment building. Additional plans are required to complete an accurate plan review of this project. If there are any questions please feel free to contact me. Chris Huskinson Fire Inspector