HomeMy WebLinkAboutINVERTER CALCULATIONS REDLINED - 20-00814 - 453 Yale Ave - Solar PanelsAuthor Name Author Email Author Phone No.: Bret Stoddard brets@rexburg.org 208-372-2171 Description : 453 Yale Ave - Solar PanelsAddress : 453 Yale AveRecord Type : Solar PanelsDocument Filename : OCPD-Disconnects Calculations.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 20-00814 Solar Panels Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) SOLAREDGE INVERTER CALCULATIONS FOR OCPD AND DISCONNECTS SE300H-US output: 12.5A @ 240V 12.5A * 1.25 = 15.625 Continous Amps 20A = OCPD 30A = Disconnect SE3800H-US output: 16A @ 240V 16A * 1.25 = 20 Continuous Amps 20A = OCPD 30A = Disconnect SE5000H-US output: 21A @ 240V 21A * 1.25 = 26.25 Continuous Amps 30A = OCPD 30A = Disconnect SE6000H-US output: 25A @ 240V 25A * 1.25 = 31.25 Continuous Amps 35A = OCPD 60A = Disconnect SE7600H-US output: 32A @ 240V 32A * 1.25 = 40 Continuous Amps 40A = OCPD 60A = Disconnect SE10000H-US output: 42A @ 240V 40A * 1.25 = 50 Continuous Amps 50A = OCPD 60A = Disconnect SE11400H-US output: 47.5A @ 240V 47.5A * 1.25 = 59.375 Continuous Amps 60A = OCPD 60A = Disconnect