HomeMy WebLinkAboutPLAN LAYOUT REDLINED REVISIONS - 20-00637 - Dance Studio - RemodelAuthor Name Author Email Author Phone No.:
Don Allen Don.Allen@rexburg.org 208-372-2174
Ted Dye tedd@rexburg.org 208-372-2172
Bret Stoddard brets@rexburg.org 208-372-2171
Description : 121 E Main St - Dance Studio - RemodelAddress : 121 E Main StApplication Type : Document Filename : Dance Studio Layout.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report Revisions Required
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Free text Ted Dye : Building Open 1 tempered glass
Pg 1 Free text Ted Dye : Building Open 1 exit sign
Pg 1 Free text Ted Dye : Building Open 1 Exit Sign with emergency lighting
Pg 1 Free text Ted Dye : Building Open 1 Add one additionaldoor
Pg 1 Free text Ted Dye : Building Open 1 Total of 2 doors needed for egress
Pg 1 Free text Ted Dye : Building Open 1 Swing doors to exterior withcrash bars on each door.
Pg 1 Free text Ted Dye : Building Open 1 Post Occupant LoadMax. 402
Pg 1 Free text Ted Dye : Building Open 1
Pg 1 Free text Ted Dye : Building Open 1 IBC 1010.1.10
Pg 1 Free text Ted Dye : Building Open 1 Provide handicap bathrooms.
# 20-00637Commercial - Remodel
Report Date: 17-08-2020
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Free text Bret Stoddard :Electrical Open 1 All new wiring must meet the 2017 NEC-specifically article 518.Wiring must be a metallic raceway.
Report Date: 17-08-2020
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
All new wiring must meet
the 2017 NEC-specifically
article 518. Wiring must
be a metallic raceway.
tempered
glass
exit sign
Exit Sign
with
emergency
lighting
Add one
additional
door
Total of 2 doors needed for
egress
Swing doors to exterior with
crash bars on each door.
Post Occupant Load
Max. 402
IBC 1010.1.10
Provide handicap
bathrooms.