HomeMy WebLinkAboutFIRE ALARM PLANS - 20-00363 - BYUI Manwaring - Remodel
(ANSI B) 1/16" = 1'
TDT
JPKPAYNEXXXXXXXX
9/1/2020 9:49:45 AMMANWARING LVL 2 COVER.DWG
PROJECT COVER SHEET
FA-C-01
FIRE ALARM SYSTEM
BRIGHAM YOUNG UNIVERSITY- IDAHO
MANWARING LEVEL 2 REMODEL
BRIGHAM YOUNG UNIVERSITY- IDAHO
4 SQ. 2-1/8" DEEP BOX MINIMUM w/SINGLE GANG MUD RING
MANWARING LEVEL 2 REMODEL
4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING
FIRE ALARM SYSTEM
MOUNTING REQUIREMENT
EXISTING TO REMAINEXISTING TO REMAIN
PART NUMBER
EXISTINGEXISTING
SPSCWL
SPCWL
SPSWL
FIRE ALARM BUILDING RISER DIAGRAM / MATRIX
PROJECT COVER SHEET / INDEX OF DRAWINGS
SWL
NOTIFICATION CIRCUITS
SHEET CONTENTS
FIRE ALARM CONTROL UNIT
SPEAKER/STROBE- CEILING
SPEAKER/STROBE- WALL
SPEAKER ONLY- CEILING
STROBE ONLY- WALL
DESCRIPTION
INDEX OF DRAWINGS
DEVICE SCHEDULE
LEVEL 2
LEVEL
NAC
SYMBOL
CC
SHEET #FACU
NAC
SSSS
FA-C-01FA-R-01 L
S
FA-1-01
COUNTS
PAGE
16
622
123
JPKPAYNETDT9/1/2020 9:49:45 AM(ANSI B) 1/16" = 1'XXXXXXXXMANWARING LVL 2 RISER.DWG
FIRE RISER DIAGRAM / MATRIX
FA-R-01
FIRE ALARM SYSTEM
FIRE ALARM RISER DIAGRAM / MATRIX
BRIGHAM YOUNG UNIVERSITY- IDAHO
MANWARING LEVEL 2 REMODEL
FIRE ALARM CONTROL UNIT- EXISTING
SPEAKER/STROBE-CEILING
SPEAKER/STROBE- WALL
SPEAKER ONLY- CEILING
STROBE ONLY- WALL
DEVICE LEGEND
NAC- EXISTING
DESCRIPTION
SYMBOL
CC
FACU
NAC
SSSS
SL
LOCATED IN MC 171C
COUNTS
16
226
TO NEXT DEVICE
TO NEXT DEVICE
SPCWL - CEILING SPEAKER ONLY
EXISTING
OUT
OUT
(+)(-)
NAC
SWL - WALL STROBE ONLY
E.O.L. 3.9KE.O.L. 4.7K
SP1-20
SP1-1
L2-11
L1-1
30cd15cd
1/2W1/2W
DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT
(+)(-)
IN
IN
SP1-19
STROBE CIRCUIT
L2-10
SP1-2
L1-230cd15cd
SPEAKER CKT
1/2W1/2W
BATTERY
EXISTINGCABINET
SP1-18
SP1-3
L1-330cdL2-975cd
FACU
1/2W1/2W
TO NEXT DEVICE
TO NEXT DEVICETO NEXT DEVICE
TO NEXT DEVICE
SP1-17
L1-4L2-8
15cd15cd
1/2W
SPSCWL - CEILING SPEAKER STROBE
SP1-16
SPSWL - WALL SPEAKER STROBE
L1-5L2-7
15cd30cd
1/2W
OUT
OUTOUT
OUT
(+)(-)
(+)(-)
SP1-15
L1-6L2-6
15cd15cd
1/2W
SP1-14
SP1-4
L1-7
30cd
1/2W1/2W
SP1-13
SP1-5
L1-8L2-5
30cd15cd
1/2W1/2W
(+)(-)
(+)(-)
IN
IN
STROBE CIRCUIT
STROBE CIRCUIT
SP1-6
L1-9L2-4
30cd15cd
IN
IN
1/2W
SPEAKER CKT
SPEAKER CKT
SP1-12
L1-10
SP1-7
75cd
1/2W1/2W
SP1-8
L1-11
L2-3
30cd15cd
1/2W
L1-12
SP1-9
L2-2
30cd15cd
1/2W
SP1-10SP1-11
L1-13
L2-1
30cd15cd
1/2W1/2W
E.O.L. 3.9K
SYSTEM OUTPUTS
SPEAKER CIRCUIT
1 PAIR #14'S TWISTED SHIELDED(2) STROBE CIRCUITS
4 #14'S
BUILDING SPEAKER/STROBES
INPUT/OUTPUT MATRIX
SYSTEM INPUTS
LOSS OF POWER ANY PANEL OR NAC
FIRE ALARM
BUILDING INITIATING DEVICES
LOW BATTERY CONDITIONSOPEN CIRCUIT CONDITIONS
LEVEL 2LEVEL 1
GROUND FAULTS
JPK
PAYNETDT9/2/2020 8:21:21 AM(ANSI B) 1/16" = 1'XXXXXXXXMANWARING LVL 2.DWG
FA-1-01
NOTIFICATION
LEVEL 2
FIRE ALARM SYSTEM
BRIGHAM YOUNG UNIVERSITY- IDAHO
MANWARING LEVEL 2 REMODEL
FIRE ALARM CONTROL UNIT- EXISTING
CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT.
GENERAL NOTES:
CKT.
USE
AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS
SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL
FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION
"FIRE ALARM
INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER
SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION
WITH A FIRE NEED TO BE FREE OF GROUNDS, FAULTS,
ACTUAL MINIMUM OF THREE (3) FEET
THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL
ADDED SPEAKER/STROBE- WALL WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT
. WIRING
DO NOT
ADDED OR REMOVED DEVICES
(ADJUSTMENT ACCOUNTED FOR IN COUNTS ABOVE)
POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT
ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN.
OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR
DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS.
APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ.
PRIOR TO CONNECTION TO FIRE ALARM
ENTER AND EXIT THE CABINET THROUGH A DIFFERENT
CONDITION ALLOW AND TO MINIMIZE PENETRATIONS
SPEAKER/STROBE-CEILING
FURTHERMORE, ALL PL AND NPL CKT WIRING MUST
WIRING DEPICTED ON THESE PLAN IS SCHEMATIC -
WIRE LOCATIONS MAY DIFFER FROM THESE PLANS TESTING AND FINAL INSPECTION ARE COMPLETED.
SPEAKER/STROBE- WALL
SPEAKER ONLY- CEILING
DEDICATED 120 VAC CKTS SHALL BE MARKED AS
MUST BE IN EVERY ROOM
STROBE ONLY- WALL
DEVICE LEGEND
ALARM CONTROL UNIT OR POWER SUPPLY.
KNOCKOUT AND/OR SEPARATE CONDUIT.
WILL BE NOTED AT EACH CONTROL UNIT.
HIGHER CABLES ARE IN THE RACEWAY.
NAC- EXISTING
DESCRIPTIONDESCRIPTION
CLASS "B" WIRING IS REQUIRED.
FROM MECHANICAL DIFFUSERS.
LOCATE SMOKE DETECTORS A
A SMOKE DETECTOR
SYMBOLSYMBOL
FIRE ALARM CKTS
CCC
FACU
NAC
SSSS
L
SS
AND SHORTS
EQUIPMENT.
COUNTSCOUNTS
CKT"
16
2262
10.
4.
2.3.5.6.7.8.9.
1.
SS
MEZZ CAGE
SP1-20
L2-11
30cd
1/2W
1 PAIR #14'S TWISTED/SHIELDED
E.O.L. 3.9KE.O.L. 4.7K
WIRE SCHEDULE
MEZZ
WIRES
2 #14'S
301
OFFICE
A,(2)B
230
1
WIRING NOTE DESCRIPTION
2 TOTAL CONDUCTORS4 TOTAL CONDUCTORS6 TOTAL CONDUCTORS
MEZZANINE
C
C
SS
SP1-6
30cd
L1-9
SPEAKER CIRCUIT
1/2W
SS
STROBE CIRCUIT
SP1-1
30cd
CCL1-1
1/2W
SP1-5SP1-4
30cd75cd
L1-8L1-7
1/2W1/2W
SSSS
DESCRIPTION
OFFICE
229
SP1-19
L2-10
30cd
1/2W
SS
SMALL CONF.
227
===
15cd
L1-6
NOTE
A(2)AA,(2)B
L
AB
C
SP1-2
30cd
L1-2
1/2W
SS
OPEN OFFICE
15cd
L1-5
L
C
SP1-7
L1-10
201
30cd
1/2W SMALL CONF.
SS
226
E.O.L. 3.9K
CC
SMALL CONF.
SP1-10
SP1-9
L1-12L1-13
30cd30cd
1/2W1/2W
SSSS
225 C
SP1-3
30cd
L1-3
1/2W
SS
TRAINING
COMPLETE SPEAKER COVERAGE (9/1/2020)
15cd
L1-4
224
L
TO TRANSPONDER LOCATED IN MC 171C
C
SP1-8
L1-11
30cd
1/2W
SS
SMALL CONF.
OFFICE C
PHOTO
202204
OFFICE
SS
203
223
HS2-2
15cd
SP1-11
15cd
L2-1
1/2W
L
REVISION NOTES:
C
SP1-18
SYSTEM NOTES:
75cd
L2-9
1/2W
SS
OFFICE
205
SMALL CONF.
HS2-3
15cd
L
219
C
SP1-17
C
15cd
L2-8
OFFICE
1/2W
OFFICE
SS
206
220
S
SMALL CONF.
1Z
SP1-12
218
HOSTING
1/2WZ
221
HS2-4
15cd
L
OFFICE
OPEN OFFICE
50'
OFFICE
207
OFFICEOFFICE
214
217216
213
CC
C
SP1-13
SP1-14SP1-15
OFFICE 15cd
L2-515cd
L2-6
1/2W
1/2W1/2WC
SS
SSSP1-16
208
S
30cd
L2-7
1/2W
SS
Z
LEVEL 2
OFFICE
210
OFFICE
OFFICE
OFFICE
212
209
211
25'
KEY PLAN
LEVEL 2
10'