FIRE ALARM INFORMATION - 20-00363 - BYUI Manwaring - Remodel
FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 Manwaring Building Level 2 Remodel BYU-Idaho Fire Alarm System Submittal & Drawings Manwaring Remodel 525 South Center Street Rexburg, Idaho 83460 PROJECT Equipment Manufacturer: Gamewell-FCI Authorized Distributor: Nelson Fire Systems Manwaring Building Level 2 Remodel 1481 S Major St BYU-Idaho SLC, UT 84115 Fire Alarm System 801-468-8300... TABLE OF CONTENTS Data Sheet Part No. Description Gamewell-FCI SWLWhite Strobe Only Wall Mount Gamewell-FCI SPSWL White Speaker Only Wall Mount Gamewell-FCI SPCWL White Speaker Only Ceiling Mount Gamewell-FCI SPSCWL White Speaker/Strobe Ceiling Mount Gamewell-FCI HPFF8 NAC Power Supply Battery Calculations HPFF8 Battery Calc CKT Voltage Drops Drawings Sheet No. Description Cover Page FA-C-01 FireAlarm Cover Riser Diagram FA-R-01 FireAlarm Riser and Matri Level 2 FA--01 Manwaring Remodel 525 South Center Street Rexburg, ID. 83460 L-Series Indoor Horns, Strobes, and Horn Strobes Indoor Selectable-Output Horns, Description Strobes, and Horn Strobes for The L-Series audible visible notification products offer the Wall Applications most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. In addition, this product includes lower current draws and a modern aesthetic design which reduce installation times and maximize prof- its. The following devices offer a variety of design options, so that the L-Series can be used for any application requirement. •White and red plastic housings. •Standard and small footprint devices. •Plain, FIRE, and FUEGO-printed devices. Similar to the entire L-Series product line, the wall-mount horns, strobes, and horn strobes include a variety of fea- tures that increase their application versatility while simpli- fying the installation. All devices offer a plug-in design so that there is minimal intrusion into the backbox. These fea- tures make installations fast and foolproof while eliminating costly and time-consuming ground faults. To further simplify the installation and protect devices from Features construction damage, the L-Series uses a mounting plate for all standard and compact models that include an on- board shorting spring. This feature allows Installers to test •Listed for wall mounting only. wiring continuity before the device is installed. •Offers small profile devices for horns and horn strobes. Installers can also easily adapt devices to suit a wide •Provides an automatic selection of 12- or 24-volt range of application requirements using the following fea- operation at 15 and 30 candela. tures: •Field-selectable candela settings. •Supports a rotary switch for horn tone and two volume •Automatic selection of 12- or 24-volt operation. selections. •Rotary switch for horn tones with two volume selections. •Produces horn rated at 88+ dBA at 16 volts. L-Series Specifications •Uses field-selectable candela settings on wall units: Architect/Engineer Specifications - 15- 30- 75- 95 - 110- 135- 185 General •Includes a mounting plate for all standard and all com- The L-Series standard horns, strobes, and horn strobes pact wall units. shall mount to any of the following enclosures: •Contains a mounting plate with a shorting spring that •standard 2 x 4 x 1 7/8-inch backbox checks the wiring continuity before device installation. •standard 4 x 4 x 1 1/2-inch backbox •4-inch octagon backbox •Features a plug-in design with minimal intrusion into the •double-gang backbox backbox. The L-Series compact products shall mount to a single- •Designed with a tamper-resistant construction. gang 2 x 4 x 1 7/8-inch backbox. A universal mounting •Built with an updated modern design. plate shall be used for mounting ceiling and wall products •Supports electrical compatibility with the existing for all standard models and a separate universal mounting SpectrAlert and the SpectrAlert Advance products. plate shall be used for mounting wall compact models. •Compatible with System Sensor synchronization The notification appliance circuit wiring shall terminate at protocol. the universal mounting plate. Also, the L-Series products, when used with the Sync•Circuit, Module accessory, shall SIGNALING be powered from a non-coded notification appliance circuit FM output and shall operate on a nominal 12 or 24 volts. APPROVED PENDING GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60929 Rev. A page 1 of 4 ©2016 by Honeywell International Inc. All rights reserved L-Series Specifications (Continued) Physical/Electrical Specifications Architect/Engineer Specifications (Continued) General (Continued) Standard Operating When it is used with the Sync•Circuit Module, the following Temperature: 32°F to 120°F (0°C to 49°C) occur: Humidity Range: 10 to 93% non-condensing •12-volt-rated notification appliance circuit outputs shall Strobe Flash Rate: 1 flash per second operate between 8.5 and 17.5 volts. Nominal Voltage: Regulated 12 DC or • 24-volt-rated notification appliance circuit outputs shall 1 regulated 24 DC/FWR operate between 16.5 and 33 volts. 2: Operating Voltage Range 8 to 17.5 V (12 V nominal) or The Indoor L-Series products shall operate between 32 16 to 33 V (24 V nominal) and 120 degrees Fahrenheit from a regulated DC or full- Operating Voltage Range wave rectified unfiltered power supply. Strobes and horn (MDL3) Sync Module: 8.5 to 17 V (12 V nominal) or strobes shall have the following field-selectable candela 16.5 to 33 V settings: (24 V nominal) •15•30•75•95 Input Terminal Wire 12 to 18 AWG Gauge: •110•135•185 Wall-Mount Dimensions Strobe (143 5.6 L × 4.7 W × 1.25 D (including lens): The strobe shall be an L-Series Model _______ listed to mm L×119 mm W × 32 mm D) UL Standard 1971 and shall be approved for fire protective Compact Wall-Mount service. The strobe shall be wired as a primary-signaling 5.26” L x 3.46” W x 1.93” D Dimensions: notification appliance and comply with the Americans with (133 mm L x 88 mm W x 49 mm D) (including lens) Disabilities Act requirements for visible signaling appli- Horn Dimensions: (143 5.6 L × 4.7 W × 1.25 D ances, flashing at 1 Hz over the strobe’s entire operating mm L×119 mm W × 32 mm D) voltage range. The strobe light shall consist of a xenon Compact Horn flash tube and associated lens/reflector system. 5.25” L x 3.45” W x 1.25” D Dimensions: (133mm L x 88mm W x 32mm D) Horn Strobe Combination Notes: The horn strobe shall be an L-Series Model _______ listed 1.Full Wave Rectified (FWR) voltage is a non-regulated, to UL Standard 1971 and UL Standard 464 and shall be time-varying power source that is used on some approved for fire protective service. The horn strobe shall power supply and panel outputs. be wired as a primary-signaling notification appliance and 2.P, S, PC, and SC products will operate at 12 V comply with the Americans with Disabilities Act require- nominal only for 15 cd and 30 cd. ments for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audible options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more synchroniza- tion modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com page 2 of 49021-60929 Rev. A UL Current Draw Table 2 lists the UL maximum Horn current draw. Table 1 lists the UL maximum Strobe current draw. 8-17.5 Sound Volts 16-33 Volts 8-17.5 Volts16-33 Volts PatterndB CandelaDCDC FWR DCDC FWR TemporalHigh 394454 Candela 15884360 TemporalLow283254 Range 301436383 Non-TemporalHigh434754 75N/A107136 Non-TemporalLow293254 95N/A121155 3.1 KHz Temporal High394154 110N/A148179 3.1 KHz TemporalLow293254 135N/A172209 3.1 KHz Non-Temporal High424354 185N/A222257 3.1 KHz Non-TemporalLow282954 Table 1: UL Maximum Strobe Current Draw (mA CodedHigh434754 RMS) 3.1 KHz CodedHigh424354 Table 2: UL Max. Horn Current Draw (mA RMS) UL Current Draw Data Table 3 lists the maximum UL Current Draw (mA RMS) allowed for 2-Wire Horn Strobes, candala range (15-115cd). 8-17.5 Volts16-33 Volts DC Input 15cd30cd15cd30cd75cd95cd110cd135cd185cd EM Temp Hi981585474121142162196245 EM Temp Low931544465111133157184235 EM Cont Hi1061667394139160182211262 EM Cont Low931565171119139162190239 3.1K Temp Hi931565373119140164190242 3.1K Temp Low911544566112133160185235 3.1K Cont Hi991626990135157175208261 3.1k Cont Low931565272119138162192242 16V FWR FWR Input15cd30cd75cd95cd110cd135cd185cd EM Temp Hi83107156177198234287 EM Temp Low6891145165185223271 EM Cont Hi111135185207230264316 EM Cont Low79104157175197235283 3.1K Temp Hi81105155177196234284 3.1K Temp Low 6890145166186222276 3.1K Cont Hi104131177204230264326 3.1k Cont Low77102156177199234291 Table 3: UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Candela Range (15–115 cd) Horn Strobe Tones and Sound Output Data Table 4 lists the horn strobe tones and sound output data. 8–17.516–33 SwitchVoltsVolts PositionSound PatterndBFWR DCDC 1TemporalHigh848989 2TemporalLow758383 3Non-TemporalHigh859090 4Non-TemporalLow768484 53.1 KHz TemporalHigh838888 63.1 KHz TemporalLow768282 73.1 KHz Non-Temporal High848989 83.1 KHz Non-TemporalLow778383 9CodedHigh859090 103.1 KHz CodedHigh848989 Table 4: Horn Strobe Tones and Sound Output Data GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60929 Rev. A page 3 of 4 L Series DimensionsL Series Dimensions Figure 1 Compact ComboFigure 2 Compact Horn L Series DimensionsL Series Dimensions Figure 3 Standard ComboFigure 4 Standard Horn L-Series Ordering Information L-Series Ordering Information Horns Wall Horn Strobes Part Number Description Part NumberDescription HRLStandard Horn, Red P2RL 2-Wire, Standard Horn Strobe, Red HWLStandard Horn, White P2WL2-Wire, Standard Horn Strobe, White HGRLCompact Horn, Red P2GRL2-Wire, Compact Horn Strobe, Red HGWLCompact Horn, White P2GWL2-Wire, Compact Horn Strobe, White Accessories P2RL-P2-Wire, Standard Horn Strobe,Red, Plain TR-2Universal Wall Trim Ring Red Plain P2WL-P2-Wire,Standard Horn Strobe,White, TR-2WUniversal Wall Trim Ring White P2RL-SP2-Wire,Standard Horn Strobe,Red, SBBRLStandard Wall Surface Mount Backbox, FUEGO Red P2WL-SP2-Wire, Standard Horn Strobe, White, SBBWLStandard Wall Surface Mount Backbox, FUEGO White Wall Strobes SBBGRLCompact Wall Surface Mount Backbox, SRLStandard Strobe, Red Red SWLStandard Strobe, White SWLStandard Strobe, WhiteSWLStandard Strobe, White SBBGWLCompact Wall Surface Mount Backbox, SGRLCompact Strobe, Red White SGWLCompact Strobe, White Notes: SRL-PStandard Strobe, Red, Plain All -P models have a plain housing SWL-PStandard Strobe, White, Plain (no “FIRE” marking on cover). SRL-SPStandard Strobe, Red, FUEGO All -SP models have “FUEGO” marking on cover. SWL-CLR-ALERTStandard Strobe, White, ALERT All -ALERT models have “ALERT” marking on cover. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com page 4 of 49021-60929 Rev. A L-Series IndoorWallSpeaker Strobes and Speakers Indoor Selectable-Output Speaker Description Strobes and Dual-Voltage Evacuation The L-Series indoor selectable-output speaker strobes and Speakers for Wall Applications dual-voltage evacuation speakers offer a modern, aes- thetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in wall installation applications and its flexible design enables the Installer to easily perform the following: •Pre-wire mounting plates. •Dress the wires. •Confirm wiring continuity before the Installer plugs-in the speakers. This product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: •The wiring is properly connected. •The rotary switches are set to the selected voltage and power settings. Features •The 7 field-selectable candela settings are configured for wall speaker strobes. •Includes a plug-in feature to reduce ground faults and a The low total harmonic distortion of the speaker offers both protective cover to shield speaker components. high-fidelity and high-volume sound output so that it can be •Contains a universal mounting plate with an on-board used in high ambient noise applications. shorting spring that is used to test the wiring continuity L-Series makes installation easy before an installation. To install the L-Series speakers or speaker strobe, do the •No extension ring required. following: •Field-selectable candela settings on wall units: 1.Attach a universal mounting plate to a 4 x 4 x 2 1/8 - 15- 30- 75- 95 inch backbox. Flush-mount applications do not require - 110- 135- 185 an extension ring. 2.Connect the notification appliance circuit or speaker •Uses an automatic selection of 12- or 24-volt operation wiring to the terminals on the mounting plate. at 15 and 30 candela. 3.To attach the speaker or speaker strobe to the mount- •Provides a rotary switch that simplifies the field selection ing plate, insert the product tabs into the mounting of speaker voltage (25) and 70.7 V) and the follow- RMS plate grooves. ing power settings: 4.Hinge the device into position to lock the product pins –1/4 watt–1/2 watt–1 watt–2 watts into the mounting plate terminals. •Offers speakers with both a high-fidelity and a 5.A catch will temporarily hold the device in place until high-volume sound output. you secure the device with a captured mounting •Compatible with the System Sensor synchronization screw. protocol. L-Series Speaker and Speaker Strobe •Supports electrical compatibility with the existing Specifications SpectrAlert and the SpectrAlert Advance products. Architectural/Engineering Specifications •Designed with a tamper-resistant construction. General The L-Series speaker and speaker strobes shall mount to •Built with an updated modern design. a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate SIGNALING shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. FM APPROVED PENDING GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60931 Rev. A page 1 of 3 ©2016 by Honeywell International Inc. All rights reserved L-Series Speaker and Speaker Strobe Physical Specifications Specifications (Continued) Architectural/Engineering Specifications Operating Temperature: 32°F to 120°F(0°C to 49°C) (Continued) Humidity Range: 10 to 93% non-condensing General (Continued) Dimensions, Wall-Mount:Length Width Depth Also, the L-Series speaker strobes, when used with the 6.5 in,5 in,2.3 in, SP Speaker: Sync•Circuit. Module accessory, shall be powered from a 165 mm127 mm58 mm non-coded notification appliance circuit output and shall With Surface Mount Backbox: 6.6 in,5.1 in,3.2 in, operate on a nominal 12 or 24 volts. 168 mm130 mm82 mm When it is used with the Sync•Circuit Module, either of the 6.5 in,5.0 in,2.3 in, SPS Speaker/Strobe (including lens and speaker): following may occur. 165 mm127 mm58 mm •12-volt rated notification appliance circuit outputs shall 6.6 in,5.1 in,4.55 in, With Surface Mount Backbox: 168 mm130 mm116 mm operate between 8.5 and 17.5 volts. •24-volt rated notification appliance circuit outputs shall Electrical/Operating Specifications operate between 16.5 and 33 volts. 25 Volts or 70.7 Volts Nominal Voltage (speakers): The Indoor L-Series products shall operate between 32° F (nominal) and 120°F from a regulated DC, or full-wave rectified, unfil- Maximum Supervisory tered power supply. Wall-mount speaker strobes shall Voltage (speakers): 50 VDC include the following field-selectable candela settings: Strobe Flash Rate:1 flash per second - 15- 30- 75- 95- 110 Nominal Voltage (strobes):Regulated 12 VDC or - 135- 185 Regulated 24 VDC/FWR Operating Voltage Range Speaker (includes fire alarm panels 8 to 17.5 V (12 V nominal) or The speaker shall be an L-Series model _______ dual- with built-in sync): 16 to 33 V (24 V nominal) voltage transformer speaker capable of operating at 25.0 8.5 to 17.5 V (12 V nominal) Operating Voltage with or 70.7 nominal V. It should be listed to UL Standard MDL3 Sync Module: or 16.5 to 33 V(24 V nominal) RMS 1480 and shall be approved for fire protective service. The 400 to 4,000 Hz Frequency Range: speaker shall have a frequency range of 400 to 4,000 Hz ¼, ½, 1, 2 watts Power: and shall have an operating temperature between 32°F UL Current Draw Data and 120°F. The speaker shall have power taps and voltage Table 1 lists the UL maximum strobe current draw. that are selected by rotary switches. Speaker Strobe Combination 8-17.5 Volts16-33 Volts The speaker strobe shall be an L-Series model Candela FWR DCDC __________ listed to UL Standard 1480 and UL Standard 15884360 1971 and be approved for fire protective signaling sys- 301436383 tems. The speaker shall be capable of operating at 25.0 or 70.7 nominal V selected via rotary switch, and shall 75N/A107136 RMS have a frequency range of 400 to 4,000 Hz. The speaker 95N/A121155 shall have power taps that are selected by rotary switch. 110N/A148179 The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the 135N/A172209 strobe’s entire operating voltage range. The strobe light 185N/A222257 shall consist of a xenon flash tube and associated lens/ Table 1: UL Max. Strobe Current Draw (mA RMS) reflector system. Table 2 lists the speaker strobe sound outputs. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Reverberant UL Anechoic UL Standard 464 and shall be approved for fire protective Setting(dBA @10 ft)(dBA @10 ft) service. The module shall synchronize SpectrAlert strobes 1/4 W7777 at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 1/2 W8080 21/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The 1 W8383 module shall synchronize multiple zones. Daisy-chaining 2 W8686 two or more synchronization modules together will syn- Table 2: Sound Output Speaker Strobe chronize all the zones they control. The module shall not operate on a coded power supply. Table 3 lists the speaker sound outputs. UL Reverberant UL Anechoic Setting(dBA @10 ft)(dBA @10 ft) 1/4 W7979 1/2 W8282 1 W8385 2 W8888 Table 3: Sound Output Speaker GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com page 2 of 39021-60931 Rev. A DimensionsSurface Mounting Figure 1 shows the speaker dimensions. Figure 3 illustrates the wall-mount speaker and speaker strobes with the SBBSPRL surface mount backbox. Figure 2 shows the speaker dimensions. L-Series Ordering Information Speakers and Speaker Strobes Wall Mount Part Number Description SPWLWhite, Speaker only SPRLRed, Speaker only SPSWLWhite, Speaker Strobe SPSWLWhite, Speaker StrobeSPSWLWhite, Speaker Strobe SPSRLRed, Speaker Strobe SPSRL-PPlain Speaker Strobe SPSWL-PWhite, Plain Speaker Strobe SPSWL-ALERTWhite, Speaker Strobe, Amber Lens SPSWL-CLR-ALERT White Speaker Strobe Clear Lens SPSRL-SPWhite, Speaker Strobe, Fuego Accessories RFPWWhite, 7 in × 9.5 in Retrofit Plate RFPRed, 7 in × 9.5 in Retrofit Plate SBBSPWWhite, Surface Mount Back Box for Speakers and Speaker Strobes SBBSPRRed, Surface Mount Back Box for Speakers and Speaker Strobes TRWWhite, Wall Mount Trim Ring TRRed, Wall Mount Trim Ring Notes: All -P models have a plain housing (no “FIRE” marking on the cover). GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60931 Rev. A page 3 of 3 L-Series Indoor Ceiling Speaker Strobes and Dual Speakers Indoor Selectable-Output Speaker Description Strobes and Dual Voltage Evacuation The L-Series indoor selectable-output speaker strobes and Speakers for Ceiling Applications dual-voltage evacuation speakers offer a modern, aes- thetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in ceiling applica- tions and its flexible design enables the Installer to easily perform the following: •Pre-wire mounting plates. •Dress the wires. •Confirm wiring continuity before the Installer plugs-in the speakers. In addition, this product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: •The wiring is properly connected. •The rotary switches are set to the selected voltage and power settings. Features •The 7 field-selectable candela settings are configured •Includes a plug-in feature and protective cover to reduce for wall speaker strobes. ground faults. The low total harmonic distortion of the SP speaker offers •Contains a universal mounting plate with an on-board both high-fidelity and high-volume sound output so that it shorting spring that is used to test the wiring continuity can be used in high ambient noise applications. before an installation. L-Series makes installation easy •No extension ring required. To install the L-Series speakers or speaker strobe, do the •Field-selectable candela settings on ceiling units: following: - 15- 30- 75- 95 1.Attach a universal mounting plate to a 4 x 4 x 2 1/8 - 115- 150- 177 inch backbox. Flush-mount applications do not require an extension ring. •Uses an automatic selection of 12- or 24-volt operation 2.Connect the notification appliance circuit or speaker at 15 and 30 candela. wiring to the terminals on the mounting plate. •Provides a rotary switch that simplifies the field selection 3.To attach the speaker or speaker strobe to the mount- of speaker voltage (25) and 70.7 V) and the follow- RMS ing plate, insert the product tabs into the mounting ing power settings: plate grooves. –1/4 watt–1/2 watt–1 watt–2 watts 4.Hinge the device into position to lock the product pins •Offers speakers with both high-fidelity and high-volume into the mounting plate terminals. sound output. 5.A catch temporarily holds the device in place until you secure the device with a captured mounting screw. •Compatible with the System Sensor synchronization protocol. L-Series Speaker and Speaker Strobe •Supports electrical compatibility with the existing Specifications SpectrAlert and the SpectrAlert Advance products. Architectural/Engineering Specifications •Designed with a tamper-resistant construction. General •Built with an updated modern design. The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate SIGNALING shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. FM APPROVED PENDING GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60930 Rev. A page 1 of 3 ©2016 by Honeywell International Inc. All rights reserved L-Series Speaker and Speaker Strobe Physical Specifications Specifications (Continued) Operating Temperature:32°F to 120°F (0°C to 49°C) Architectural/Engineering Specifications Humidity Range:10 to 93% non-condensing (Continued) Dimensions,Ceiling-Mount:DiameterDepth General (Continued) 173 mm25 mm SPC Speaker6.8 in, 1.0 in, Also, the L-Series speaker strobes, when used with the box176 mm89 mm With Surface Mount Back6.9 in, 3.5 in, Sync•Circuit. Module accessory, shall be powered from a 173 mm73 mm SPSC Speaker Strobe6.8 in, 2.8 in, non-coded notification appliance circuit output and shall Backbox176 mm136 mm With Surface Mount 6.9 in, 5.37 in, operate on a nominal 12 or 24 volts. When these devices Electrical/Operating Specifications are used with the Sync•Circuit Module, either of the follow- ing may occur. Nominal Voltage (speakers):25 Volts or 70.7 Volts •12-volt rated notification appliance circuit outputs shall (nominal) operate between 8.5 and 17.5 volts. Maximum Supervisory •24-volt rated notification appliance circuit outputs shall Voltage (speakers):50 VDC operate between 16.5 and 33 volts. Strobe Flash Rate:1 flash per second Nominal Voltage (strobes):Regulated 12 VDC or The Indoor L-Series products shall operate between 32° F Regulated 24 VDC/FWR and 120°F from a regulated DC, or full-wave rectified, unfil- Operating Voltage Range tered power supply. Speaker strobes shall have the follow- (includes fire alarm panels ing field-selectable candela settings: with built-in sync):8 to 17.5 V (12 V nominal) or - 15- 30- 75- 95- 115 16 to 33 V (24 V nominal) - 150- 177 Operating Voltage with MDL3 Sync Module:8.5 to 17.5 V (12 V nominal) Speaker or 16.5 to 33 V (24 V The speaker shall be an L-Series model _______ dual- nominal) Frequency Range voltage transformer speaker capable of operating at 25.0 Frequency Range:400 to 4,000 Hz or 70.7 nominal V. It should be listed to UL Standard RMS Power:¼, ½, 1, 2 watts 1480 and shall be approved for fire protective service. The UL Current Draw Data speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F Table 1 lists the UL maximum strobe current draw. and 120°F. The speaker shall have power taps and voltage 8-17.5 Volts16-33 Volts that are selected by rotary switches. Candela FWR DCDC Speaker Strobe Combination The speaker strobe shall be an L-Series model 15874160 __________ listed to UL Standard 1480 and UL Standard 301536386 1971 and be approved for fire protective signaling sys- 75NA111142 tems. The speaker shall be capable of operating at 25.0 or 95NA134164 70.7 nominal V selected via rotary switch, and shall RMS have a frequency range of 400 to 4,000 Hz. The speaker 115NA158191 shall have power taps that are selected by rotary switch. 150NA189228 The strobe shall comply with the NFPA 72 requirements for 177NA226264 visible signaling appliances, flashing at 1 Hz over the Table 1: UL Max. Strobe Current Draw (mA RMS) strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/ Table 2 lists the ceiling mount speaker sound outputs. reflector system. UL Reverberant UL Anechoic Synchronization Module Setting(dBA @10 ft)(dBA @10 ft) The module shall be a Sync•Circuit model MDL3 listed to 1/4 W7979 UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes 1/2 W8282 at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 2 1 W8585 1/8-inch back box. The module shall also control two Style 2 W8888 Y (Class B) circuits or one Style Z (Class A) circuit. The Table 2: Ceiling-Mount Speaker Sound Output module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will syn- Table 3 lists the ceiling-mount speaker strobe sound out- chronize all the zones they control. The module shall not puts. operate on a coded power supply. UL Reverberant UL Anechoic Setting(dBA @10 ft)(dBA @10 ft) 1/4 W7777 1/2 W8080 1 W8383 2 W8686 Table 3: Ceiling-Mount Speaker Strobe Sound Output GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com page 2 of 39021-60930 Rev. A DimensionsSurface Mounting Figure 1 shows the speaker dimensions. Figure 3 illustrates the ceiling-mount speaker and speaker strobes with the SBBCR/SBBCWL surface mount back- box. Figure 2 shows the speaker dimensions. L-Series Ordering Information SpectrAlert Speakers and Strobes Ceiling Mount Part Number Description SPCWLWhite Speaker only SPCWLWhite Speaker onlySPCWLWhite Speaker only SPCRLRed Speaker only SPSCWLWhite Speaker Strobe SPSCWLWhite Speaker StrobeSPSCWLWhite Speaker Strobe SPSCRLRed Speaker Strobe SPSCWL-PPlain, Speaker Strobe SPSCWL-SPFuego, Speaker Strobe SPSCWL-CLR-ALERT Alert, Speaker Strobe,Clear Lens Accessories SBBCWLWhite, Universal Ceiling Surface Mount Back Box SBBCRLRed, Universal Ceiling Surface Mount Back Box TRC-2WWhite, Universal Ceiling Trim Ring TRC-2Red, Universal Ceiling Trim Ring GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60930 Rev. A page 3 of 3 HPFF8 NAC Expander/Power Supply Description The Gamewell-FCI, HPFF8 is a Notification Appliance Cir- cuit (NAC) expansion panel designed to extend the power capabilities of existing NACs and provide power for the auxiliary devices. The HPFF8 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone. The HPFF8 is available in 8.0 amps. It provides regulated and filtered 24VDC power to each of the four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each (the total output cannot exceed 8.0 amps). The auxil- iary output is rated at 2.0 amps. This output is continuously supplied, even in alarm, and therefore must be taken into HPFF8 account for power supply loading and battery size calcula- tions. Features The NAC outputs may be configured as any of the follow- •Four (4) supervised notification application circuits ing: (NACs) capable of supplying +24VDC at 3.0 amp •Four Class B (Style Y) maximum each •Two Class A (Style Z) •NAC output circuits may be configured as any of the •Two Class B and one Class A following: •Four Class A with the optional HPP31076 Class A - Four Class B (Style Y)- Two Class B & one Class A adapter installed - Two Class A (Style Z)- Four Class A with the These power supplies contain an internal Battery charger optional HPP31076 Class A capable of charging up to 26.0 amp-hour (AH) batteries. adapter installed •Four field-programmable operational modes The HPFF8 is mounted in lockable wall cabinet units that •2.0 amp auxiliary continuously supplied output can accommodate up to two (2), 18AH batteries. A multi- •Two (2) fully supervised input/output control circuits pack option allows for up to four chassis mount units •Temporal coding and sync protocols compatible with installed in a single lockable SBB-D4 enclosure. These the following notification appliance brands: chassis mount units have a "CM" suffix, HPFF8CM and - System Sensor- Faraday can accommodate two 12AH batteries. Power supplies are - Gamewell- Amseco available in either 120VAC/60 Hz or 240VAC/50 Hz. - Cooper-Wheelock- Gentex One of the most challenging aspects of a retrofit applica- •Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults tion is locating the existing End-of-Line (EOL) resistor. In •Trouble indication for supervision of the following: these applications that have EOL values, other than the - NAC circuits- Auxiliary output 3.9k normally used with the HPFF8, a single resistor - AC input- Charger matching the existing EOL can be used as a reference for - Battery voltage- Open contacts in the initiat- all the outputs. This feature speeds the installation and the ing device signal inputs (for - Earth ground faults by system checkout, because the actual EOL does not need FACP trouble notification) individual status LED's to be located and changed in the circuit. The reference •Separate Trouble and AC Fail Form-C relay Contacts resistor must be within the range of 1.9k to 25k. An ISO 9001-2000 Compan y SIGNALING FM APPROVED 7315-1637:0102 S24562 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60521 Rev. B page 1 of 2 ©2010 by Honeywell International Inc. All rights reserved. Features (Continued) Specifications (Continued) NAC Output Ratings: 24VDC fully regulated, 3.0A max per circuit (8.0A total) •The Trouble Form-C relay contacts selectable for imme- diate or a 2 hour delay with AC failure End-of-Line Resistor 2K to 25k ohm, ½ watt Range: •26 AH battery charger capability; the wall cabinet supports two 12V 18AH batteries, while the multi-pack Common Trouble Relay/AC equipment cabinets supports two 12V 12AH batteries. 2.0A at 28VDC or 120VAC Fail Relay: •NAC Overload protection and indication Input Control Circuit: 16-30VDC @ 5mA min. •Up to four chassis mount units (HPFF8CM) can be Temperature Rating: 32°F to 120°F (0°C to 49°C installed in the SBB-D4 backbox Relative Humidity: 10% to 93% •Wall mount units can be configured to internally house non-condensing the following: Cabinet Dimensions: - one AOM-2SF single control module HPFF8 Cabinet: 16.65” W x 19.0” H x 5.2” D - one AOM-2R single relay module (42.29 W x 48.26 H 13.23 D cm) SBB-D4 Cabinet: 24” W x 45.9” H x 5.15” D Specifications (60.96 W x 116.52 H x 13.1D cm) Ordering Information Primary Input Power: 120VAC/60Hz, 3.6A or 220VAC/50Hz, 1.5A Part Number Description Secondary Power: 24 volt operation: HPFF8 two (2), 7-24 AH batteries8A fire rated power supply operating at 120VAC/60 Hz. Unit includes red Battery Charging Capacity: Up to 26 AH batteries enclosure with HPP lock and key mounted HPFF8CM 8A fire rated power supply - chassis HPFF8CM8A fire rated power supply - chassis Battery Space: 8A fire rated power supply - chassis mounted operating at 120VAC/60 Hz. mounted operating at 120VAC/60 Hz. mounted operating at 120VAC/60 Hz. HPFF8 Cabinet: Up to two 18AH batteriesUnit includes mounting hardware for Unit includes mounting hardware for Unit includes mounting hardware for installation in the SBB-D4 enclosure installation in the SBB-D4 enclosure SBB-D4 Cabinet: Up to two 12AH batteries HPFF8E 8A fire rated power supply operating at per supply 240VAC/50 Hz Total Output Power: 8.0A max HPFF8CME 8A fire rated power supply chassis Standby Current: 0.030 A mounted operating at 240VAC/50 Hz Auxiliary Power Output: 0.15A under all conditions HPP31076 Class A (Style Z) NAC module FCI-VDR-D4 2.0A if load is removed dur-Vented door, PK-625 lock and key for ing operation (external relay SBB-D4 backbox, black or AC Fail Relay is required) SBB-D4 Backbox, accepts up to 4 chassis, black GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60521 Rev. B page 2 of 2 System Current Draw - HPFF8 Upubm!Dvssfou Tuboecz1/186!B Bmbsn2/949!B Tfdpoebsz!Opo.Bmbsn!DvssfouTfdpoebsz!Bmbsn!Dvssfou EfwjdfRuzEsbx!!!Opo.Bmbsn!!RuzEsbx!!Bmbsn!! 2/!Tztufn!Npevmft IQGG9!Nbjo!Djsdvju!Cpbse2y1/186111/186112y1/317111/31711 2/!M2 TQTDXM261y1/111111y1/16511 TQTDXM41:y1/111111/11111:y1/182111/74:11 TQTDXM862y1/111111/111112y1/248111/24811 TQTDXM2261y1/111111y1/29611 TDXM264y1/111111/111114y1/165111/27311 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 OBD!$2!Upubmt!)Nby!4!Bnqt*;1/111111/:4911 3/!/ TQTDXM261y1/111111y1/16511 TQTDXM411y1/111111y1/18211 TQTDXM861y1/111111y1/24811 TQTDXM2261y1/111111y1/29611 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 OBD!$3!Upubmt!)Nby!4!Bnqt*;1/111111/11111 4/!M3 TQTDXM267y1/111111/111117y1/165111/43511 22y1/111111/111112y1/182111/18211 TQTDXM862y1/111111/111112y1/248111/24811 TQTDXM2261y1/111111y1/29611 TDXM264y1/111111/111114y1/165111/27311 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 OBD!$4!Upubmt!)Nby!4!Bnqt*;1/111111/7:511 5/!/ TQTDXM261y1/111111y1/16511 TQTDXM411y1/111111y1/18211 TQTDXM861y1/111111y1/24811 TQTDXM2261y1/111111y1/29611 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 !!!1y1/111111y1/11111 OBD!$5!Upubmt!)Nby!4!Bnqt*;1/111111/11111 7/!Bvyjmjbsz!Qpxfs QS.41y1/111111y1/14111 GJSFSBZ61111y1/148111y1/11961 DP2335US1y1/131111y1/15111 F4TNSDP0F4TB1y1/161111y1/11111 Bvyjmjbsz!Efwjdf1y1/111111y1/11111 UC5!Upubmt!)Nby!3!Bnqt*;1/111111/11111 8/!Dpnqbujcmf!Efwjdft!opu!mjtufe Puifs!dpnqbujcmf!efwjdft1y1/111111y1/11111 Puifs!dpnqbujcmf!efwjdft1y1/111111y1/11111 Puifs!dpnqbujcmf!efwjdft1y1/111111y1/11111 Upubm!Opo.Bmbsn!Mpbe;!1/186Upubm!Bmbsn!Mpbe;!2/949 Secondary Power Requirements HPFF8 Power Supply Protected Premises:BYU-I Manwaring RemodelDate:9.3.2020 Address:525 Center Street City:RexburgState:IDZip:83460 Prepared By:Nelson Fire SystemsPhone:801.468.8300 Address:1481 S Major StreetEmail: Office@nelsonfire.com City:Salt Lake CityState:UTZip:84115 2.71 Secondary Load Requirements Amp Hours Total Secondary Load from the calculation table below. Current DrawTime (hours)Total (AH) Secondary Standby Load Required Standby Time x 24 hours 0.075 A 1.80 Secondary Alarm Load Required Alarm Time (hours) x 1.838 A 0.250 hours 0.46 Total Secondary Load 2.26 x 1.2 Derating factor 2.71 Secondary Load Requirements AH Battery Selection 8 Amp Hours Select batteries from the list below. 8.0 AH BAT-1270 Battery (12 volt) TRUE Page 2 of 131 Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 7% Spare Battery Capacity Secondary Standby Load Secondary Secondary Alarm Load Standby Load Spare Battery 27% Capacity 66% Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Spare Battery CapacityBattery Selection (AH) - Secondary Load Requirements (AH) 5.29 Secondary Standby Load2.16Secondary Standby Load (AH) * Derating Factor Secondary Alarm LoadSecondary Alarm Load (AH) * Derating Factor 0.55 Page 3 of 131 (ANSI B) 1/16" = 1' TDT JPKPAYNEXXXXXXXX 9/1/2020 9:49:45 AMMANWARING LVL 2 COVER.DWG PROJECT COVER SHEET FA-C-01 FIRE ALARM SYSTEM BRIGHAM YOUNG UNIVERSITY- IDAHO MANWARING LEVEL 2 REMODEL BRIGHAM YOUNG UNIVERSITY- IDAHO 4 SQ. 2-1/8" DEEP BOX MINIMUM w/SINGLE GANG MUD RING MANWARING LEVEL 2 REMODEL 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING FIRE ALARM SYSTEM MOUNTING REQUIREMENT EXISTING TO REMAINEXISTING TO REMAIN PART NUMBER EXISTINGEXISTING SPSCWL SPCWL SPSWL FIRE ALARM BUILDING RISER DIAGRAM / MATRIX PROJECT COVER SHEET / INDEX OF DRAWINGS SWL NOTIFICATION CIRCUITS SHEET CONTENTS FIRE ALARM CONTROL UNIT SPEAKER/STROBE- CEILING SPEAKER/STROBE- WALL SPEAKER ONLY- CEILING STROBE ONLY- WALL DESCRIPTION INDEX OF DRAWINGS DEVICE SCHEDULE LEVEL 2 LEVEL NAC SYMBOL CC SHEET #FACU NAC SSSS FA-C-01FA-R-01 L S FA-1-01 COUNTS PAGE 16 622 123 JPKPAYNETDT9/1/2020 9:49:45 AM(ANSI B) 1/16" = 1'XXXXXXXXMANWARING LVL 2 RISER.DWG FIRE RISER DIAGRAM / MATRIX FA-R-01 FIRE ALARM SYSTEM FIRE ALARM RISER DIAGRAM / MATRIX BRIGHAM YOUNG UNIVERSITY- IDAHO MANWARING LEVEL 2 REMODEL FIRE ALARM CONTROL UNIT- EXISTING SPEAKER/STROBE-CEILING SPEAKER/STROBE- WALL SPEAKER ONLY- CEILING STROBE ONLY- WALL DEVICE LEGEND NAC- EXISTING DESCRIPTION SYMBOL CC FACU NAC SSSS SL LOCATED IN MC 171C COUNTS 16 226 TO NEXT DEVICE TO NEXT DEVICE SPCWL - CEILING SPEAKER ONLY EXISTING OUT OUT (+)(-) NAC SWL - WALL STROBE ONLY E.O.L. 3.9KE.O.L. 4.7K SP1-20 SP1-1 L2-11 L1-1 30cd15cd 1/2W1/2W DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT (+)(-) IN IN SP1-19 STROBE CIRCUIT L2-10 SP1-2 L1-230cd15cd SPEAKER CKT 1/2W1/2W BATTERY EXISTINGCABINET SP1-18 SP1-3 L1-330cdL2-975cd FACU 1/2W1/2W TO NEXT DEVICE TO NEXT DEVICETO NEXT DEVICE TO NEXT DEVICE SP1-17 L1-4L2-8 15cd15cd 1/2W SPSCWL - CEILING SPEAKER STROBE SP1-16 SPSWL - WALL SPEAKER STROBE L1-5L2-7 15cd30cd 1/2W OUT OUTOUT OUT (+)(-) (+)(-) SP1-15 L1-6L2-6 15cd15cd 1/2W SP1-14 SP1-4 L1-7 30cd 1/2W1/2W SP1-13 SP1-5 L1-8L2-5 30cd15cd 1/2W1/2W (+)(-) (+)(-) IN IN STROBE CIRCUIT STROBE CIRCUIT SP1-6 L1-9L2-4 30cd15cd IN IN 1/2W SPEAKER CKT SPEAKER CKT SP1-12 L1-10 SP1-7 75cd 1/2W1/2W SP1-8 L1-11 L2-3 30cd15cd 1/2W L1-12 SP1-9 L2-2 30cd15cd 1/2W SP1-10SP1-11 L1-13 L2-1 30cd15cd 1/2W1/2W E.O.L. 3.9K SYSTEM OUTPUTS SPEAKER CIRCUIT 1 PAIR #14'S TWISTED SHIELDED(2) STROBE CIRCUITS 4 #14'S BUILDING SPEAKER/STROBES INPUT/OUTPUT MATRIX SYSTEM INPUTS LOSS OF POWER ANY PANEL OR NAC FIRE ALARM BUILDING INITIATING DEVICES LOW BATTERY CONDITIONSOPEN CIRCUIT CONDITIONS LEVEL 2LEVEL 1 GROUND FAULTS JPK PAYNETDT9/2/2020 8:21:21 AM(ANSI B) 1/16" = 1'XXXXXXXXMANWARING LVL 2.DWG FA-1-01 NOTIFICATION LEVEL 2 FIRE ALARM SYSTEM BRIGHAM YOUNG UNIVERSITY- IDAHO MANWARING LEVEL 2 REMODEL FIRE ALARM CONTROL UNIT- EXISTING CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. GENERAL NOTES: CKT. USE AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION "FIRE ALARM INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION WITH A FIRE NEED TO BE FREE OF GROUNDS, FAULTS, ACTUAL MINIMUM OF THREE (3) FEET THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL ADDED SPEAKER/STROBE- WALL WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT . WIRING DO NOT ADDED OR REMOVED DEVICES (ADJUSTMENT ACCOUNTED FOR IN COUNTS ABOVE) POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. PRIOR TO CONNECTION TO FIRE ALARM ENTER AND EXIT THE CABINET THROUGH A DIFFERENT CONDITION ALLOW AND TO MINIMIZE PENETRATIONS SPEAKER/STROBE-CEILING FURTHERMORE, ALL PL AND NPL CKT WIRING MUST WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - WIRE LOCATIONS MAY DIFFER FROM THESE PLANS TESTING AND FINAL INSPECTION ARE COMPLETED. SPEAKER/STROBE- WALL SPEAKER ONLY- CEILING DEDICATED 120 VAC CKTS SHALL BE MARKED AS MUST BE IN EVERY ROOM STROBE ONLY- WALL DEVICE LEGEND ALARM CONTROL UNIT OR POWER SUPPLY. KNOCKOUT AND/OR SEPARATE CONDUIT. WILL BE NOTED AT EACH CONTROL UNIT. HIGHER CABLES ARE IN THE RACEWAY. NAC- EXISTING DESCRIPTIONDESCRIPTION CLASS "B" WIRING IS REQUIRED. FROM MECHANICAL DIFFUSERS. LOCATE SMOKE DETECTORS A A SMOKE DETECTOR SYMBOLSYMBOL FIRE ALARM CKTS CCC FACU NAC SSSS L SS AND SHORTS EQUIPMENT. COUNTSCOUNTS CKT" 16 2262 10. 4. 2.3.5.6.7.8.9. 1. SS MEZZ CAGE SP1-20 L2-11 30cd 1/2W 1 PAIR #14'S TWISTED/SHIELDED E.O.L. 3.9KE.O.L. 4.7K WIRE SCHEDULE MEZZ WIRES 2 #14'S 301 OFFICE A,(2)B 230 1 WIRING NOTE DESCRIPTION 2 TOTAL CONDUCTORS4 TOTAL CONDUCTORS6 TOTAL CONDUCTORS MEZZANINE C C SS SP1-6 30cd L1-9 SPEAKER CIRCUIT 1/2W SS STROBE CIRCUIT SP1-1 30cd CCL1-1 1/2W SP1-5SP1-4 30cd75cd L1-8L1-7 1/2W1/2W SSSS DESCRIPTION OFFICE 229 SP1-19 L2-10 30cd 1/2W SS SMALL CONF. 227 === 15cd L1-6 NOTE A(2)AA,(2)B L AB C SP1-2 30cd L1-2 1/2W SS OPEN OFFICE 15cd L1-5 L C SP1-7 L1-10 201 30cd 1/2W SMALL CONF. SS 226 E.O.L. 3.9K CC SMALL CONF. SP1-10 SP1-9 L1-12L1-13 30cd30cd 1/2W1/2W SSSS 225 C SP1-3 30cd L1-3 1/2W SS TRAINING COMPLETE SPEAKER COVERAGE (9/1/2020) 15cd L1-4 224 L TO TRANSPONDER LOCATED IN MC 171C C SP1-8 L1-11 30cd 1/2W SS SMALL CONF. OFFICE C PHOTO 202204 OFFICE SS 203 223 HS2-2 15cd SP1-11 15cd L2-1 1/2W L REVISION NOTES: C SP1-18 SYSTEM NOTES: 75cd L2-9 1/2W SS OFFICE 205 SMALL CONF. HS2-3 15cd L 219 C SP1-17 C 15cd L2-8 OFFICE 1/2W OFFICE SS 206 220 S SMALL CONF. 1Z SP1-12 218 HOSTING 1/2WZ 221 HS2-4 15cd L OFFICE OPEN OFFICE 50' OFFICE 207 OFFICEOFFICE 214 217216 213 CC C SP1-13 SP1-14SP1-15 OFFICE 15cd L2-515cd L2-6 1/2W 1/2W1/2WC SS SSSP1-16 208 S 30cd L2-7 1/2W SS Z LEVEL 2 OFFICE 210 OFFICE OFFICE OFFICE 212 209 211 25' KEY PLAN LEVEL 2 10'