HomeMy WebLinkAboutFIRE REVIEW - 03-00051 - Teton River Village Building #2 - 3 UnitsMEMO:
cily 0/ 5?eXIMPY
STATE OF IDAHO
TO: TO WHOM IT MAY CONCERN
FROM: CHRIS HUSKINSON, FIRE INSPECTOR
DATE: OCTOBER 5, 2003
RE: TETON RIVER VILLAGE- DESERET BOOKSTORE
TO WHOM IT MAY CONCERN:
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
Upon review of the building plan drawings submitted the following items need to be
addressed:
1. Previous building plans show a fire alarm system and a fire suppression system.
New plans do not show these items, please clarify.
2. Add two fire extinguishers as per 2000 IFC, minimum size of 2AlOBC each.
Additional plans are required to complete an accurate plan review of this project. If
there are any -questions please feel free to contact -me.
Chris Huskinson
Fire Inspector
MEMO:
TO: TO WHOM IT MAY CONCERN
FROM: CHRIS HUSKINSON, FIRE INSPECTOR
DATE: MARCH 15, 2003
RE: TETON RIVER VILLAGE
TO WHOM IT MAY CONCERN:
Upon review of the site plan drawings submitted the following items need to be
addressed:
1. WATER SUPPLY: This proposed project shows two very large square footage
structures. The larger of the two will be required to be sprinklered, the existing
building may be required depending upon configuration and occupancy. In order
to determine accurate water supply the following items need to be known:
a. What is the exact occupancy of each building?
b. What is the square footage of each individual occupancy in each building?
c. What is the future development of the lot to the west and north?
d. What type of construction is the proposed building?
e. The drawing does not show adequate numbers or coverage of fire
hydrants. Please provide more fire hydrants.
f. There are also two smaller adjacent buildings to the complex. What is
their occupancy classification? What is the square footage of each
building? The southern most building will be required to have a fire
hydrant within required distances.
2. ACCESS: The access on the northeast side of the property does not provide for
immediate access to proposed buildings. This access needs to be greatly
improved. A minimum of two entrances will be required depending upon density
and use. These access's may be required to be wider and more direct to facilitate
emergency vehicle access. Please provide more complete drawings.
3. The areas adjacent to and around the buildings without any parking shall be
marked with "No Parking, Fire Lane" in addition to having the curbs painted red
and maintained.
Additional plans are required to complete an accurate plan review of this project. If there
are any questions please feel free to contact me.
-----
e� Chris Huskinson
Fire Inspector