2000 International Fire Code Plan Date: 11-14-03
Plan Review Review Date: 01-05-04
Building Name: TETON PROFESSIONAL PARK
Building Address: TREJO STREET AND HIGHWAY 191
Stories: ONE Type of Construction: V -B
Occupancy Classification: B Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 5975 SQUARE FEET
1. Required Fire Flow (Appendix B): 2000 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED IF AN AUTOMATIC FIRE
SUPPRESSION SYSTEM IS INSTALLED.
2_ Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: EXISTING ON TREJO AND HIGHWAY 191, ONE
PROPOSED
Fire Hydrant Flows: EXISTING OKAY, PROPOSED UNKOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
�7"fi �A"trk , !'fir Ma+i�YMlrli�v�!�Ilylf lvpr i 74 {� W 7.. .H�'N, !' ni. ruv. rs'fl.w tli" Ntana,:MiW!w wti5S4H'rr r.6!WN7' .,., r. n ��• r •.,;
�.�. ,.. .r ��-r�.� , ..,.. ,,, .>"i.t�r. ,�d .: , �..a � , . ,f :.. , �,.u, (*' .fYf�;"1 YW�• 1.�(W t 4!.. � ;� n+m+^�t to 4J i ',Hrn ..werM� 4ri ,um wU~'uw :x. t .aw+rsr to • � ,a' uw
,., .,._.. ,......d . ...:. _.. ..:...� "�9.�p'i,11P'�d�"k3�1,t�"�`��'�,'�„'s��° -�.. _.. �R, g _s,+, hY- x��'7 `�3I�r�,�4 , IK` ��,11''�'�,•���r,�,iil�"`�r��?�t.'..�t�,�'� ,,,sl��ws�!,'�.r.; :::1.:,�24Y�'���5>om!;
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: NO
Water Supply Comments: PROPOSED HYDRANT NEEDS TO BE MOVED
CLOSER TO THE ENTRANCE, PREFERABLY ON THE WEST SIDE OF THE
ENTRANCE. PLEASE PROVIDE ENGINEER'S CALCULATIONS OF WATER
FLOW FOR PROPOSED HYDRANT.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: YES
Complete Road Acceptable: YES
Comments- NONE
Length: YES Surface: YES
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Continents: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required- YES
Location shown: NO
Type provided acceptable: NOT SHOWN
Comments: PROVIDE A MINIMUM OF 2A10BC FIRE EXTINGUISHERS
WITHIN TRAVEL DISTANCES FOR EACH OCCUPANCY.
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being installed:
Sprinkler system monitoring (Section 907) required: NO
Comments:
7. Standpipes (Section 905) required: NO
Type required: Comments:
f, .
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: NO
Type of system required: Manual: Automatic: Both:
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices:, Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring:
Fire Alarm System Acceptable:
10. Other corrections that are required by special occupancy or conditions:
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSKINSON Date: 1-5-04
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X