1 have reviewed the plans for the Level 2, 3 and 4 Apartments and have identified
the following discrepancies or questions:
1. Five parking spaces needed for ordinance compliance are missing from Level
4 plan. Please make the necessary changes.
2. Level 4 and Level 2 have dead end parking spaces. These spaces are not
equipped a backing area adjacent to them The vehicles that park in these
spaces will have to back completely out the way they came in. Please make
the necessary changes to the parking plan.
3. The ADA requires that one of your handicapped parking spaces in each
complex be a van accessible space. The aisle adjacent to a van accessible
space is required to be 96" wide. Please identify compact spaces and signage
on plans.
4. Our trash truck is a side loading variety. The trash dumpster for Level 3 may
not be located where it can feasibly be accessed. Please contact John Millar
the City Engineer concerning this issue. His telephone extension is 329.
5. Please identify privacy fencing where parking lots border other properties.
6. All units on the lower floor must be type "A" or type `B" handicapped units.
At least one type "A" unit must be provided in each complex. Please identify
the location of the type "A!' units on the site plan.
7. Please provide literature on stucco for 1 -hr rating.
8. Provide a copy of the structural calculations.
9. Anchor bolts are required at all bearing walls, please identify.
10. The walk in storage space of the type "A" units does not meet ANSI Al17.1,
section 1002.3.2.
11. Under stair guard rails are required as per ANSI Al 17.1 section 307.4. See
figure 307.4.
12. Please provide truss details prior to framing inspection.
uosum3IsnH srigD
Junin ugof o'o
Iumuo fiu!plmg
uasuaISIND IVA
`�IazaourS
17Z£ 'Ixa OZO£-69£ Tu llno u auT aA'B asuald `suoi sonb XUL,
anuq nogjl •sunld paloaum age jo soidoo podum s mou Z gJ.Tm aur apinoid asnald
OI0£-69£(80Z) it, uosur mH sTjgD jouluoo asnald
suoilsanb Xuu aRuq noX jI •shun ,tV>, add oqj uMl w- sagoa4s uioq Toj paau age
rluapl fou pip snip pun loafoid srq� io Lind azam shun 2uillamp «V„ adf jvq
mou-1 iou plp luou4mdoa omA oq L •slsonboi xuj Xuu qqm popnloul oq fou IITm
s!RuTmusp airs asogs, •sOulmuip ails paugpaz sopnlouT matnaz aqL luomoop
siga jo Aonq aqj dol m3mw luauiWdaQ au,q aql jo Sdoo u pagou:4n anuq I g
apo oql haul 01 uorTunluna aaauo fuessaoau aqj opino.Td asuald •opoD
uoTjunrasuoD anug Iuuolitwolul OOOZ oqa poldopu suq ognpl jo 3TvjS aqj 'SI
•DgI OOOZ agl rad sr paaapiwids oq of po.TTnbai;Dw drum ota •{,I
uoTlounj sr
gj uuojjod ol pamollu jou sT zolonzauoD oqZ qua2u s'zaumo
aql su 2utaau piooa.Tjo pairpm io nam2uo aqj io zaumo agI Sq poXolduza
oq szopodsur Inroads aql juga somnbar b" apoD BuTpling lujoilun
L66I agl3o F IOL I uoTTOQS •alglssod se uoos su suoiloodsuT osagl �upmopod
ag Ilrm oqm mou3l sn dal asuald limplam plarl lez 4oru s Aue zoj pa.unbaz
ag osln Ilam dagl, •alaaouoo uo suoi oodsul IuloadS Toj Ino sllno OS laagS -£I
cify
® 'W? W Y n U
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone(208)359-3020
Fax(208)359-3022
e-mail rexburg@srv.net
REXB UR G -MADISON COUNTY
EMERGENCY SERVICES
26 NORTH CENTER STREET
REXB URG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code
Plan Review
Plan Date: 7-01-02
Review Date: 6-19-03
Building Name: LEVEL TWO, THREE, FOUR APARTMENTS
Building Address: PORTER ROAD AND CASPER AVENUE
Stories: 2.5 Type of Construction: V -B
Occupancy Classification: R-2 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 8232 SQUARE FEET (EACH 12-
PLEX) AND 5712 SQUARE FEET (EACH 6 -FLEX)
1. Required Fire Flow (Appendix B): 2500 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED IF STRUCTURES HAVE AN
APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM INSTALLED.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: TWO AND FOUR ARE OKAY, THREE IS UNKNOWN
(DRAWING SHOWS 5 HYDRANTS)
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO (THREE ONLY)
Water Supply Comments: FD REQUESTS HYDRANT FLOW FROM THE
ENGINEERS PRIOR TO CONSTRUCTION FOR VERIFICATION. FOUR
SHOWS HYDRANT BLOCKING DUMPSTERS, PLEASE RELOCATE.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: OK
Complete Road Acceptable: YES
Length: OK Surface: OK
Comments: ALL AREAS ADJACENT TO BUILDINGS AND COMMON DRIVES
SHALL BE MARKED IN RED AND POSTED "NO PARKING FIRE LANE". SEE
ATTACHED DRAWINGS.
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN
Comments: NEED TO PROVIDE MINIMUM OF 2A10BC EXTINGUISHER IN
EACH UNIT
6. Automatic fire extinguishing systems (Section 903) Required: YES
Type of system being installed: NOT SHOWN
Sprinkler system monitoring (Section 907) required: YES
Comments: PLEASE PROVIDE FIRE ALARM AND FIRE SPRINKLER
DRAWINGS PRIOR TO ISSUANCE OF BUILDING PERMIT
7. Standpipes (Section 905) required: NO
Type required: Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: YES
Type of system required: Manual: Automatic: Both: X
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: REQUIRED
Fire Alarm System Acceptable: NO
10. Other corrections that are required by special occupancy or conditions:
1. FIRE ALARM SYSTEM INFORMATION NEEDS TO BE SUBMITTED
THAT INCLUDES: SUBMITTALS OF ALARM CONTROL AND
TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND
SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS
MODEL NUMBERS, AND LISTING INFORMATION FOR EQUIPMENT,
DEVICES AND MATERIALS AND INTERFACE CONNECTIONS. ADA
UNITS SHALL HAVE ALL HORN/STOBE UNITS. SUBMITTALS AND
PLANS MUST BE APPROVED PRIOR TO HAVING A BUILDING
PERMIT ISSUED.
2. FIRE SPR N1,CLER SYSTEM IS REQUIRED. PLANS MUST BE
SUBMITTED TO THE STATE, REVIEWED, AND APPROVED PRIOR
TO HAVING A BUILDING PERMIT ISSUED.
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSKINSON Date: 6-19-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X