TO: TO WHOM IT MAY CONCERN
FROM: CHRIS HUSKINSON, FIRE INSPECTOR
DATE: OCTOBER 29, 2003
RE: LAMOREAUX APARTMENTS, PHASE H
TO WHOM IT MAY CONCERN:
Upon review of the site plan drawings submitted the following items need to be
addressed:
1. The driveway into the project shall be signed and marked with "No Parking, Fire
Lane" in addition to having the curbs painted red and maintained.
2. Turn-arounds are required to be a minimum of 95 feet in diameter.
3. A minimum of two fire hydrants are required to be accessible year around.
Additional plans may be required to complete an accurate plan review of this project.
If there are any questions please feel free to contact me.