Current Building Review Status: REVISIONS
Permit Details Application Number; 19-00$64
East Idaho Credit Union - New Building
310 N 2nd E
Permit Review Status
Plan Reviews Still in Progress
Fire Department Review - Site Plan
Fire Sprinkler Review
Electrical Review
Public Works Review - Site Pian
Planning and Zoning Review - Site Plan
Building - Commercial
Application Received Date: 06/19/2019
Application Approved Date: o7/08/2019
Application Approved Status: ACCEPTED
Status
Fire Alarm Review
of Plajrl Reviews
N/A
corenleted
07/08/2019
Electrical Review
REVISIONS
07/08/2019
Plumbing Review
COMPLETED
07/09/2019
HVAC Review
COMPLETED
07/09/2019
Public Works Review - Site Plan
REVISIONS
07/09/2019
Planning and Zoning Review - Site Plan
REVISIONS
07/15/2019
Building Review
REVISIONS
07/15/2019
Pian Review Details
Building Review Status: REVISIONS Review Date: 07/15/2019
Reviewed By: Quinton Owens
quinton.owens@rexburg,org
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
0 a f O
Service Facilities comply with IBC 1109.12 Please identify accessible service Counter space REVISIONS
per IBC 1109.12.3 & Al 17.1 sect 904.3
*Revisions Response : All accessible needs for customers are provided by personnel in private offices
Ventilation is provided as per IBC Section 1203
i Crawl space ventilation? See also notes on crawl I REVISIONS
spaces in flood hazard area.
*Revisions Response: See revised plan showing flood/ventilation vents
Building Complies with IECC (IBC 1301) i Submitted COMcheck has lighting certificate but
I it does not have thermal energy report. I REVISIONS
Foundation insulation at interior slab on grade?
"Revisions Response: See attache¢ COMcheck See revised A3 302
Building or Structures located in Rood Area have Flood vents are required if crawl space floor is i
Flood Certificate per 1612.5
less than 1 foot above base flood elevation, and REVISIONS
the crawispace floor cannot be more than 2 feet
below lowest adjacent grade (see FEMA TB -11).
* Nobe: Building is in Hood zone and will require
an elevation certificate. Pians show finished
floor elevation at 4870.7 ft.
"Revisions Response : See revised plan showing flood vents
Approval of plans does not constitute approval of variance from code
Page 1 of 2
CITY OF
RMURG
Ow------ --
America's Family Community
Special Inspection Contractor is identified (IBC
1704.2.1)
'Revisions Response
Who is the special inspection contractor?
Building Review (Continued)
REVISIONS
Wood Fram. design. by lice. Eng. and meets. N/A —
reqs. IBC Chp. 23 or Conv. Li -Frame
Concealed spaces are fireblocked/dratistopped Firebiockinr IBC 718 witl be
per Section 718 g approved based j COMPLETED
on inspection.
Special Inspections are required as per IBC With the previous building removed, structural I COMPLETED
Chapter ll fill for new building shall also have compaction
tests done.
Approval of plans does not constitute approval of variance from code