HomeMy WebLinkAboutCONCRETE TEST 8 - 19-00740 - The Grove at Thomson Farms - Blackoak - 20 Units - Bldg 5Project Name: Client: Mix Number: Project Number: Ticket Number: Load Amount: Admixtures: Tested By: Date and Time: Compressive Strength of Concrete Test Specimens Field Test Data: (ASTM C143, C138, C173, C231, C31, C1064, and C511) Slump (Inches): Entrained Air (%): Concrete Temperature: Ambient Temperature: Test Results:Minimum:Maximum: Cylinder # Lab Test Data: (ASTM C39, C42, C617, and C1231) Break Age Cylinder Diameter (in) Area (in² ) Break Date Maximum Load (lbs) Break Type Compressive Strength (psi)Required 28 day Strength (psi) °F °F Reviewed By: Supplier: Test Location: Unit Weight (PCF):Set # : Cylinders Picked Up By: Date and Time: Hi / Low Temperatures Remarks: 28-day Average Strength 5,317 PSI The Grove Still Water Equity Partnership 192 20001 17955 10 of 20 CY MAAE90 J. Denton 9/24/2020 5.5 4.3 69 55 5 5 7 381A 381E 381C 381B 381D 4 4 4 4 10/01/20 10/22/20 10/22/20 10/22/20 51,650 65,320 68,180 67,015 2 4,0004,108 5,196 5,424 5,331 Digitally signed by Jacob Christensen Date: 2020.10.22 08:48:38 -06'00' 12.57 Walters Sidewalk west of building 5 7 28 28 28 H 12.57 12.57 12.57 Contractor was informed of low air L. Steiner 09/25/2020 5 2 1