HomeMy WebLinkAboutLIGHTING COMPLIANCE CERTIFICATE - 08-00087 - Upper Valley Industries - CANCELLEDFeb 22 08 01:19p -------------- . ---
r
p.2
0800086
Upper Valley Industries
1G glut' ompliance Certificate
2003 IECC
COMchec*--EZ Solfware Version 3.0 Release 2b
Data filename: C:\PROGRA-1\ChedkICOMCHF—l\UPPERv—].CCK
Section 1: Project lnformation
Project Name:
Desigter/ConttaMor.
Doeumenc Aurbor.
Notes:
Upper Valley Industries
Payne Engineering Inc.
Eldon Payne
April 23, 2007
S ection 2: General Information
Building Use Description by: Activity Type
Project Type New Construction
Checked By/Date
E C E E
1 2008
F 2
OF RF 1RG
Activi TytE31c1
Classroom/Lecture Hal] Floor Area14693
Section 3: Requirements Checklist F:FEB
Dept.Dept.
Use 1 2 2 20081 Interior Lighting1 � Total actual watts must be less than or equal to total allowed watts R EX8lJ R G
I Allowed Watts Actual Watts complies iyilV)
I 20570 20099 YES
J Exterior Lighting PROVE O�
[ 7 I 2. Efcacy greater than 45 lumens/W
I F_rceptions: EL 1 A ECTOR
I
SPecialized lighting highlighting features of historic buildings; signage; sa&ty or security lighting;
I low-vollage landscape lighting.
I
Controls, switching, and Wiring
l 3. Independent comrols 1br each space (switchiowvpancy sensor).
I Exception: Arras that must be continuously illuminated.
] j 4. Master switch at entry to hOrel/motel guest room.
] I 5. individual dwelling units separately metered.
1 I 6. Each space provided with a manual control to provide unirmm light reduction capability.
L'xceptdons:
Only one luminaire in space; An occupant -sensing device controls the area;
I The arra is a corridor, storeroom, restroom, or lobby; Areas that must be continuously illuminated;
{ Aims that use less than 0.6 Wattslsq.fi.
Feb 22 08 01:19p p.3
7. Automatic lighting shutoffcontrul in buildings larger than 5,000 sq,1l.
J 8. Photocell/astronomical time switch on exterior lights.
Exceptions' Areas requiring lighting during daylight hours
] 9. Tandem wired une-lamp and threelamp ballasted luminaires,
Exceptions:
Electronic high -f clueoty ballasts; Luminaires on ernergenty circuits or with no available pair.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent With the building plans, specifications and other
calculations submitted with this permit application. The proposed lighting system has hem designed to meet the 2003
JECC, Chapter 8, requimments in COMcheck--EZ Ven;ion 3.0 Release 2b and to comply with the mandatory requirements
in the Requiremenrs Checklist.
']ADD 'p�kc.l
P�ucipal Lig ing Designer•Natne Si stare D
Feb 22 2008 1:56PM Sundberg 8. associates, In 208-522-6928
Feb 22 08 01:20p
Lighting Application Workslleet
2003 IECC
COMchecir--EZ Sollware Version 3.0 Release 2b
Section 1: Allowed Ughting Power Calculation
A
Area Category
Clasaroom/LectuteHall
8
Floor
Area
.1-1
14693
C
Total
Allowed
Watts
(watts/ft9a
1.4
D
Allowed
Watts
IB x t'a
20570
5 ection 2:
Actual lighting Power Calculation
Total Allowed Watts =
20570
A
Fixture
B
Tixtute Description!
C
Lamps/
D
4 of
E F
Fixture
M
Lamm Descrinlion / W lgage per 1 a n / p9l1ast
F_ISLU_a
Eixprsf Watt. (D x Fl
F1
2 lamp fluor. troim / 48" T8 32W / Elecimnic
2
F2
3 lamp fuor. tro13x / 48" T8 32W / Flectmnic
3
19
t08
61
95
1159
10260
F3
3 lamp recessed guor. / 48" T8 32W / Electronic
3
6
F4
1 lamp down light / Triple 4 -pin 42W 7 Electronic
,
1
95
570
FS
2 lamp fluor, wrap / 48" T B 32W ! Electmnic
2
1
17
42
61
42
F6
2 lamp fluor wrap / 48" T8 32W f Electronic
3
106
61
1037
6466
F7
2lamp over mirror Auer. / 48" T8 32W / Electronic
2
F 10
2 lamp recessed can / Quad 2 -pin I M / Bleclronic
2
4
61
244
Fl l
1 lamp recessed can / Triple 4 -pin 32W ! Electronic
1
36
36
F12
2 lamp industrial fluor. ! 48" TS 32W / FJectronic
1
2
7
32
224
1
61
61
Total Actual Watts = 20099
Section 3: Compliance Calculation
Ffthe Total Allowed A'atis minus the Tosal Actua! ff all$ is greater than or equal to zero, the building complies.
Total Allowed Watts = 20570
Total Actual Watts- 20099
Lighting PASSES: Design 20 better than code Project Compliance= 471
p.4
p.4
®rno �� cuuo Lqo'Fll aunaoerg a, Nssociares, in eub-5k!2-U`JEd P.1
■
^
SUNDBERG & ASSOCIATES
ARCHITECTS
SIXTEENTH & BOULEVARD • P.O. BOX 2269 • IDAHO FALLS, IDAHO 83403
TELEPHONE (208) 522-6901
FAX (208) 522-6928
February 22, 2008
To: Janell
From: Bonnie Goldsberry
Re; Upper Valley Industries Project
Janell:
Please find enclosed the Lighting Compliance Certificate from Payne Engineering, the electrical
consultant for Upper Valley Industries. Thank you.