277 Pollard -Rockwell
r8/11' REScheck Software Version 3.7.3
Compliance Certificate
Project Title: H-1200 Std. Plan
Report Date: 11/16/06
Data filename: D:\z - ResChecks\H-1200 Std Plan 11-16-06.rck
Energy Code:
2003 IECC
Location:
Ammon, Idaho
Construction Type:
Single Family
Glazing Area Percentage:
14%
Heating Degree Days:
7918
Construction Site:
Owner/Agent:
Designer/Contractor:
Rockwell Development Inc.
Compliance: Passes Maximum UA: 309 Your Home UA: 242 --> 21.7% Better Than Code (UA)
Ceiling 1: Flat Ceiling or Scissor Truss:
1205
50.0
0.0
31
Wall 1: Wood Frame, 24" o .c.:
1332
22.0
0.0
62
Window 1: Vinyl Frame:Double Pane with Low -E:
104
0.320
33
Door 1: Solid:
40
0.160
6
Door 2: Glass:
33
0.340
11
Basement Wall 1: Solid Concrete or Masonry:
1136
11.0
0.0
66
Window 2: Vinyl Frame:Double Pane:
64
0.490
31
Furnace 1: Forced Hot Air: 93 AFUE
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2003 IECC requirements in
REScheck Version 3.7.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Builder/Designer Company Name Date
Project Notes:
Compiled:l 1/7/06
H-1200 Std. Plan Pagel of 4
Date: 11/16/06
REScheck Software Version 3.7.3
Inspection Checklist
Ceilings:
❑ Ceiling 1: Flat Ceiling or Scissor Truss, R-50.0 cavity insulation
Comments:
Above -Grade Walls:
❑ Wall 1: Wood Frame, 24" o .c., R-22.0 cavity Insulation
Comments:
Basement Walls:
❑ Basement Wall 1: Solid Concrete or Masonry, 8.0' ht17.0' bg/8.0' insul, R-11.0 cavity insulation
Comments:
Windows:
❑ Window is Vinyl Frame:Double Pane with Low -E, U -factor: 0.320
For windows without labeled U -factors, describe features:
#Panes _ Frame Type Thermal Break? — Yes — No
Comments:
❑ Window 2: Vinyl Frame:Double Pane, U -factor: 0.490
For windows without labeled U -factors, describe features:
#Panes — Frame Type Thermal Break? —Yes — No
Comments:
Doors:
❑ Door 1: Solid, U -factor: 0.160
Comments:
❑ Door 2: Glass, U -factor: 0.340
Comments:
Heating and Cooling Equipment:
❑ Furnace 1: Forced Hot Air: 93 AFUE or higher
Make and Model Number:
Air Leakage:
❑ Joints, penetrations, and all other such openings in the building envelope that are sources of air leakage must be sealed.
❑ Recessed lights must be 1) Type IC rated, or 2) Installed inside an appropriate air -tight assembly with a 0.5" clearance from
combustible materials. If non -IC rated, the fixture must be installed with a 3" clearance from Insulation.
Skylights:
❑ Minimum insulation requirement for skylight shafts equal to or greater than 12 Inches is R-19.
Vapor Retarder:
❑ Required on the warm -in -winter side of all non -vented framed ceilings, walls, and floors.
Materials Identification:
❑ Materials and equipment must be installed in accordance with the manufacturer's installation Instructions.
❑ Materials and equipment must be identified so that compliance can be determined.
H-1200 Std. Plan Page 2 of 4
❑ Manufacturer manuals for all installed heating and cooling equipment and service water heating equipment must be provided.
❑ Insulation R -values, glazing U -factors, and heating equipment efficiency must be clearly marked on the building plans or
specifications.
Duct Insulation:
❑ Supply ducts in unconditioned attics or outside the building must be Insulated to R-11.
❑ Return ducts in unconditioned attics or outside the building must be Insulated to R-6.
❑ Supply ducts in unconditioned Spaces must be insulated to R-11.
❑ Return ducts In unconditioned spaces (except basements) must be Insulated to R-2,
❑ Where exterior walls are used as plenums, the wall must be insulated to R-11.
❑ Insulation is not required on return ducts In basements.
Duct Construction:
❑ Duct connections to flanges of air distribution system equipment must be sealed and mechanically fastened.
❑ All joints, seams, and connections must be securely fastened with welds, gaskets, mastics (adhesives),
mastic -plus -embedded -fabric, or tapes. Tapes and mastics must be rated UL 181A or UL 181B.
Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at less than 2 in. w.g. (500
Pa).
❑ The HVAC system must provide a means for balancing air and water systems.
Temperature Controls:
❑ Thermostats are required for each separate HVAC system. A manual or automatic means to partially restrict or shut off the
heating and/or cooling input to each zone or floor shall be provided.
Service Water Heating:
❑ Water heaters with vertical pipe risers must have a heat trap on both the inlet and outlet unless the water heater has an integral
heat trap or is part of a circulating system.
❑ Insulate circulating hot water pipes to the levels in Table 1.
Circulating Hot Water Systems:
❑ Insulate circulating hot water pipes to the levels in Table 1.
Swimming Pools:
❑ All heated swimming pools must have an on/off heater switch and require a cover unless over 20% of the heating energy is from
non-depletable sources. Pool pumps require a time clock.
Heating and Cooling Piping Insulation:
❑ HVAC piping conveying fluids above 105 degrees F or chilled fluids below 55 degrees F must be insulated to the levels in Table
2.
H-1200 Std. Plan Page 3 of 4
Table 1: Minimum Insulation Thickness for Circulating Hot Water Pipes
Table 2: Minimum Insulation Thickness for HVAC Pipes
Fluid Temp,
Insulation Thickness in Inches by Pipe Sizes
Insulation Thickness in Inches by Pipe Sizes
Non -Circulating Runouts
Circulating Mains and
Runouts
Heated Water
1.25' to 2.0"
2.5' to 4"
Heating Systems
Temperature (°F)
Up to V
Up to 1.25'
1.5' to 2.0"
Over 2"
170-180
0.5
1.0
1.5
2.0
140-169
0.5 i
0.5
1.0
1.5
100-139
0.5
0.5
0.5
1.0
Table 2: Minimum Insulation Thickness for HVAC Pipes
NOTES TO FIELD: (Building Department Use Only)
H-1200 Std. Plan Page 4 of 4
Fluid Temp,
Insulation Thickness in Inches by Pipe Sizes
Piping System Types
Range(°F)
2" Runouts V and Less
1.25' to 2.0"
2.5' to 4"
Heating Systems
Low Pressure/Temperature
201-250
1.0
1.5
1.5
2.0
Low Temperature
106-200
0.5
1.0
1.0
1.5
Steam Condensate (for feed water)
Any
1.0
1.0
1.5
2.0
Cooling Systems
Chilled Water, Refrigerant and
40-55
0.5
0.5
0.75
1.0
Brine
Below 40
1.0
1.0
1.5
1.5
NOTES TO FIELD: (Building Department Use Only)
H-1200 Std. Plan Page 4 of 4