2006 IECC
COMcheck Software Version 3.5.3
Interior Lighting Compliance
Certificate
Report Date: 03/24/08
Data filename: Unttled.cck
Section 1: Project Information
Project Type: New Construction0a44
C j w
Project Title : �U -5(il t
Construction Site:
Owner/Agent:
Section 2: General Information
Building Use Description by: Activity Type
Activity Type(s)
Healthcare -Clinic
Section 3: Requirements Checklist
0800047
Madison Women's Clinic
Floor Area
4000
Interior Lighting:
❑ 1. Total proposed wafts must be less than or equal to total allowed wafts.
Allowed Watts Proposed Watts Complies
4000 3968 YES
Controls, Switching, and Wiring:
El 2. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Designer/Contractor:
U
MAR 2 5 2008
CITY OF REx 011
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting In stairways or corridors that are elements of the means of egress.
❑ 3. Master switch at entry to hotellmotel guest room.
4. Individual dwelling units separately metered.
❑ 5. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions:
Only one luminaire in space;
An occupant -sensing device controls the area;
The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
Areas that use less than 0.6 Watts/sq.ft.
D 6. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
❑ 7. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
❑ 8. Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions:
Electronic high -frequency ballasts; Luminaires on emergency circuits or with no available pair.
Project Title:
Data filename: Untitled.cck
Report date: 03/24/08
Page 1 of 3
�(lCOMcheck Software Version 3.5.3
Interior Lighting Application
Worksheet
2006 IECC
Report Date:
Data filename: Untitled.cck
Section 1: Allowed Lighting Power Calculation
A B
C
D
Area Category Floor Area
Allowed
Allowed Watts
((t2)
Watts / ft2
(B x C)
Healthcare -Clinic 4000
1
4000
Total Allowed Watts =
4000
Section 2: Proposed Lighting Power Calculation
A
B C
D E
Fixture ID: Description / Lamp / Wattage Per Lamp / Ballast
Lamps/ # of
Fixture (C X D)
Fixture Fixtures
Watt.
Healthcare -Clinic (4000 sq.ft.)
Linear Fluorescent 1: 48"T8 32W (Super T8) / Electronic
4 31
128 3968
Total Proposed Watts = 3968
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Proposed Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 4000
Total Proposed Watts = 3968
Project Compliance= 32
Interior Lighting PASSES: Design 1 % better than code.
Title: Report date: 03/24/08
Data filename: Untitled.cck Page 3 of 3
Section 4: Compliancr `latement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2006 IECC
requirements in COMcheck Version 3.5.3 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title
Project Title:
Data filename: Untitled.ock
Signature Date
Report date: 03/24/08