Loading...
HomeMy WebLinkAboutPLANS REVISED - 20-00686 - 10 Jerry Ave - Solar Panels Wyssling Consulting 76 North Meadowbrook Drive Alpine, UT 84004 Scott E. Wyssling, PE, PP, CME office (201) 874-3483 swyssling@wysslingconsulting.com September 15, 2020 Practical Preppers 834 Red Hill Road Pickens, SC 29671 Re: Engineering Services Moses Residence 10 Jerry Lane, Rexburg, ID 12.000 kW System Size To Whom it May Concern, Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by a Practical Preppers representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by Practical Preppers and will be utilized for approval and construction of the proposed system. 3. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the existing roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Residence: The existing residence is typical wood framing construction with the roof system consisting of truss system with all chords constructed of 2 x 4 dimensional lumber at 24” on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Doug-Fir #2 or better with standard construction components. The existing roofing material consists of composite asphalt shingles. A. Loading Criteria Used  115 MPH wind loading based on ASCE 7-10 Exposure Category “B” at slopes of 28 degrees  7 PSF = Dead Load roofing/framing Live Load = 20 PSF Snow Load = 50 PSF  3 PSF = Dead Load solar panels/mounting hardware Total Dead Load =10 PSF The above values are within acceptable limits of recognized industry standards for similar structures in accordance with the 2015 IBC. Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters when strengthened as calculated, will support the additional panel loading without damage, if installed correctly. Page 2 of 2 B. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent “SnapNrack Solar Installation Manual”, which can be found on the SnapNrack Solar website (http:/snapnrack.com/). If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 lbs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Southern Pine assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 3”, is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 3” with a minimum size of 5/16” lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed no greater than 48” o/c. 4. Panel supports connections shall be staggered to distribute load to adjacent rafters. Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in conformance with the 2015 IBC, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE Idaho License No. 18974 S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 PV01 COVER PAGE PV02 PROPERTY PLAN PV03 ROOF PLAN PV04 ROOF ATTACHMENTS + BOM PV05 MOUNTING DETAIL PV06 ELECTRICAL DIAGRAM PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS DATE: September 3, 2020 PV01 PAGE: SHEET NAME: COVER PAGE DRAWN BY: SoloCAD GENERAL NOTES: 1.INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. 2.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. 3.ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. 5.ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 6.DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. APPLICABLE GOVERNING CODES: DESCRIPTION OF DESIGN: INSTALLATION OF GRID -TIED, UTILITY INTERACTIVE PHOTOVOLTAIC SYSTEM AERIAL VIEW:STREET VIEW:SHEET INDEX: EQUIPMENT: MAX CONTINUOUS AC SYSTEM SIZE: 12 kW AC DC SYSTEM SIZE: 12.24 kW DC (36) Q. Cells Q.Peak DUO BLK-G6 340 PV MODULES (1) Sol-Ark-12K-P INVERTER(S) RACKING: SNAPNRACK RAILING & QUICKBOLT ROOF ATTACHMENT SYSTEM - 48" O.C. 2017 NATIONAL ELECTRIC CODE [NEC] 2015 INTERNATIONAL BUILDING CODE [IBC] 2012 INTERNATIONAL RESIDENTIAL CODE [IRC] 2015 INTERNATIONAL FIRE CODE [IFC] SITE SPECIFICATIONS: OCCUPANCY: R-3 ZONING: RESIDENTIAL EXPOSURE CATEGORY: B 2012 INTERNATIONAL ENERGY CONSERVATION CODE [IECC] S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 BATT JB M MSP ACINV JB DATE: September 3, 2020 PV02 PAGE: SHEET NAME: PROPERTY PLAN DRAWN BY: SoloCAD SCALE: EQUIPMENT LEGEND: INVERTER VISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) UTILITY METER MAIN SERVICE PANEL LC LOAD CENTER FIRE ACCESS PATHWAY (3' TYP) C INV PV AC MSP M COMBINER BOX PROPERTY LINE MP2 PITCH: 28° AZIMUTH: 90° 1 0 J e r r y L n MP1 PITCH: 28° AZIMUTH: 270° F R O N T O F H O M E BATT BATTERY(IES) VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER PCC230 SOL-ARK BATTERIES (X8) 1" = 13.25' 89'-0" 123'-0" S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 BATT JB M MSP ACINV JB MP2 PITCH: 28° AZIMUTH: 90° DATE: September 3, 2020 PV03 PAGE: SHEET NAME: ROOF PLAN DRAWN BY: SoloCAD EQUIPMENT LEGEND: INVERTER VISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) UTILITY METER MAIN SERVICE PANEL LC LOAD CENTER FIRE ACCESS PATHWAY (3' TYP) C INV PV AC MSP M COMBINER BOX F R O N T O F H O M E MP1 PITCH: 28° AZIMUTH: 270° BATT BATTERY(IES) VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER 3' TYP. PCC230 SOL-ARK BATTERIES (X8) JB JB S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 DATE: September 3, 2020 PV04 PAGE: SHEET NAME: ROOF ATTACHMENTS + BOM DRAWN BY: SoloCAD MOUNTING EQUIPMENT QTY: FRAMING TYPE: RAFTER SPACING: RAFTER SIZE: FRAMING INFO: 2x4 24" Manufactured Truss ROOF ATTACHMENT COUNT:(68) PV MODULE COUNT:(36) MID CLAMP COUNT:(64) END CLAMP QTY:(16) SPLICE COUNT:(12) ATTACHMENT SPACING:48 ROOF ATTACHMENT COUNT:68 PV MODULE COUNT:36 ARRAY AREA:MODULE COUNT * 18.06ft² = 650.16 ROOF AREA:2586 ft² PERCENT OF ROOF COVERED:25% ARRAY WEIGHT:MODULE COUNT * 50lbs = 1800 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 26.47 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft² PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: SNAPNRACK RAIL L-FOOT/ATTACHMENT BRACKET (E) ROOF FRAMING 5/16" STAINLESS STEEL LAG BOLT WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER FLASHING PV MODULE (E) COMP SHINGLE ROOF (1 LAYER) SNAPNRACK RAIL END CLAMP PV MODULE MID CLAMP PV MODULE 4" 2 1 2" MIN. DEPTH SNAPNRACK RAIL SNAPNRACK RAIL QUICKBOLT FLASHING & LAG-BOLT 2'-8" MIN - 3'-10" MAX 3 SNAPNRACK RAIL PV MODULE 48" MAX."1'-8" MAX. 21 FRONT VIEW 10" MIN - 1'-4" MAX2'-8" MIN - 3'-10" MAX 10" MIN - 1'-4" MAX SIDE VIEW (E) RAFTER/TOP CHORDS (E) RAFTER/TOP CHORD DETAIL, MOUNTING AND FLASHING END CLAMP DETAILS MID CLAMP DETAILS 3 21 S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 DATE: September 3, 2020 PV05 PAGE: SHEET NAME: MOUNTING DETAIL DRAWN BY: SoloCAD MOUNTING EQUIPMENT QTY: FRAMING TYPE: RAFTER SPACING: RAFTER SIZE: FRAMING INFO: 2x4 24" Manufactured Truss ROOF ATTACHMENT COUNT:(68) PV MODULE COUNT:(36) MID CLAMP COUNT:(64) END CLAMP QTY:(16) SPLICE COUNT:(12) ATTACHMENT SPACING:48 ROOF ATTACHMENT COUNT:68 PV MODULE COUNT:36 ARRAY AREA:MODULE COUNT * 18.06ft² = 650.16 ROOF AREA:2586 ft² PERCENT OF ROOF COVERED:25% ARRAY WEIGHT:MODULE COUNT * 50lbs = 1800 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 26.47 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft² PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: (E) 120/240 VAC TO UTILITY GRID (E)UTILITY METER AC DC J-BOX ====== STRING (4) 9 MODULES ====== STRING (3) 9 MODULES J-BOX J-BOX ====== STRING (2) 9 MODULES 1 2 3 1 1 2 2 UL 1741 COMPLIANT INTEGRATED RAPID SHUTDOWN DC DISCONNECT Sol-Ark-12K-P J-BOX PCC230 SOL-ARK BATTERY BACKUP (X8) 1 1 2 3 4(2) PV-WIRE - 10 AWG, USE-2, COPPER (OR CODE APPROVED EQUIVALENT) (1) 6 AWG BARE, COPPER (GROUND) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (POSITIVE) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (NEGATIVE) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (GROUND) (1) 3/4" LIQUID TIGHT OR EMT OR FMC (OR CODE APPROVED EQUIVALENT) (4) 10 AWG THHN/THWN-2, COPPER - (POSITIVE) (4) 10 AWG THHN/THWN-2 COPPER - (NEGATIVE) (1) 10 AWG THHN/THWN-2 (GROUND) CONDUIT: 3/4" LIQUID TIGHT OR EMT (OR CODE APPROVED EQUIVALENT) (1) 6 AWG THWN-2 COPPER - (L1) (1) 6 AWG THWN-2 COPPER - (L2) (1) 6 AWG THWN-2 COPPER - (NEUTRAL) (1) 10 AWG THWN-2 COPPER - (GROUND) (1) CONDUIT: 3/4" LIQUID TIGHT OR EMT (OR CODE APPROVED EQUIVALENT) (N) 50A FUSES 4 PV AC DISCONNECT FUSED, AIC 10kA VISIBLE, LOCKABLE, LABELED, OPEN 60A, 240V, 2-POLE (E) LOADS N G SUPPLY SIDE CONNECTION: NEC 230.46, NEC 230.79, NEC 705.12(A) (E) 200A-2P (E)GROUNDING ELECTRODE INTERCONNECTION NOTES 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)] DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. 3. FUSED AC DISCONNECT TO BE USED. (E)200A MAIN SERVICE PANEL (E)200A / 2P MAIN BREAKER 4 ====== STRING (1) 9 MODULES 1 2 J-BOX S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 DATE: September 3, 2020 PV06 PAGE: SHEET NAME: ELECTRICAL DIAGRAM DRAWN BY: SoloCAD WIRE SCHEDULE VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER EQUIPMENT SCHEDULE: TYPE:QTY:DESCRIPTION:RATING: MODULES:(36)Q. Cells Q.Peak DUO BLK-G6 340 340 W INVERTERS:(1)Sol-Ark-12K-P 12000 W AC DISCONNECT(S):(1)PV AC DISCONNECT, 240V, 2-POLE 60 A DC OPTIMIZERS:(36)Tigo TS-4-A-F 15 Adc GROUNDING & GENERAL NOTES: 1. A SECOND FACILITY GROUNDING ELECTRODE IS NOT REQUIRED PER [NEC 690.47(C)(3)] 2. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE 4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 5. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 DATE: September 3, 2020 PV07 PAGE: SHEET NAME: LABELS DRAWN BY: SoloCAD LABEL 10 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(A)] LABEL 11 FOR PV SYSTEMS THAT ONLY SHUT DOWN CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(B)] LABEL 1 AT EACH JUNCTION BOX, COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED UNGROUNDED CONDUCTORS MAY BE EXPOSED DURING SERVICE. NEC. 690.35(F) LABEL 2 FOR PV DISCONNECTING MEANS WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION. NEC 690.17(E), NEC 705.22 LABEL 4 AT POINT OF INTERCONNECTION, MARKED AT AC DISCONNECTING MEANS. NEC 690.54, NEC 690.13 (B) LABEL 5 AT POINT OF INTERCONNECTION FOR EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUTS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FORM MULTIPLE SOURCES, EACH SERVICE EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION SOURCE LOCATIONS. NEC 705.12(D)(3) LABEL 6 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. NEC 690.31(G)(3&4) LABEL 7 PLACED ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. NEC 705.12(D)(2)(3)(B) LABEL 8 SIGN LOCATED AT UTILITY SERVICE EQUIPMENT. NEC 690.56(C) **ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ELECTRICAL DIAGRAM PAGE. ** JUNCTION BOX MAIN SERVICE PANEL AC DISCONNECT (E)SUB PANEL (ONLY IF POINT OF INTERCONNECTION IS MADE WITHIN SUB PANEL) PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS 2 4 4 5 51 84 7 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 6 9 222 5 7 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 5 6 4 LABELING DIAGRAM: LABEL 9 (ONLY IF 3 OR MORE SUPPLY SOURCES TO A BUSBAR) SIGN LOCATED AT LOAD CENTER IF CONTAINS 3 OR MORE POWER SOURCES. NEC 705.12(D)(2)(3)(C) LABELING NOTES: 1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2.LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] 10 11OR 40.66 240 BATT JB M MSP ACINV JB S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: CAUTION DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.10]) DATE: September 3, 2020 PV08 PAGE: SHEET NAME: PLACARD DRAWN BY: SoloCAD 10 Jerry Ln, Rexburg Idaho 83440 F R O N T O F H O M E PV ARRAY BATTERY(IES)MAIN DISTRIBUTION UTILITY DISCONNECT AC DISCONNECT INVERTER & RAPID SHUTDOWN DC DISCONNECT SWITCH S I T E I N F O R M A T I O N : S t e r l i n g M o s e s 1 0 J e r r y L n , R e x b u r g , I d a h o 8 3 4 4 0 M A X C O N T I N U O U S A C S Y S T E M S I Z E : 1 2 k W A C D C S Y S T E M S I Z E : 1 2 . 2 4 k W D C L a t , L o n g : 4 3 . 8 2 6 0 2 6 , - 1 1 1 . 7 6 4 6 8 4 (3 6 ) Q . C e l l s Q . P e a k D U O B L K - G 6 3 4 0 P V M O D U L E S (1 ) S o l - A r k - 1 2 K - P I N V E R T E R ( S ) CO N T R A C T O R I N F O R M A T I O N : Pr a c t i c a l P r e p p e r s 83 4 R e d H i l l R d . Pi c k e n s , S C 2 8 6 7 1 DATE: September 3, 2020 PV09 PAGE: SHEET NAME: SITE PHOTOS DRAWN BY: SoloCAD SITE PHOTOS: Sol-Ark-12K-P Specifica Color Touch Display Two Built -In 500V Charge Controllers 1 - 6 PV Strings Battery Disconnect 48V Battery Input Battery Temp Sensor Auto-Generator Start Rapid Shut Down Signal Current Sensors Included Battery Communication PV Disconnect Wiring Knockouts & WiFi 50A AC In/Out 50A AC Load Out 40A AC Gen In/Smart Load Out STACKABLE, No Glitch, ALL-IN-ONE HYBRID Free Remote Monitoring / Programming Limitless PARALLEL STACKING (1-9), GRID SELL,METER ZERO,TIME OF USE,SMART LOAD, 9.6kW AC COUPLING PEAK SHAVING, 20 kW PEAK POWER, Highly Accelerated Life Testing PROVEN TO LAST WELL BEYOND THE STANDARD 10 YEAR WARRANTY Engineered, Tested, Serviced in U.S.A TALK TO A US BASED ENGINEER 7 DAYS A WEEK No Glitch Switch FASTEST TRANSFER TIME C om p e ti t or C om p a r i s o n 10 Year Warranty 120V 208V 240V 12.00 -4.60 5.00 -2.40 What’s Inside THESE SHEETS, DESIGNS, AND SPECS ARE PROPERTY OF SUN INCORPORATED. NO PART SHA L L B E D U P L I C A T E D O R U S E D F O R N O N E O T H E R T H A N I T S S P E C I F I C P R O J E C T W I T H O U T W R I T T E N C O N S E N T F R O M S U N I N C O R P O R A T E D . M O U N T S H E E T Sheet: 5 File: \\SUN-SERVER\Sun Incorporate d J o b s M a s t e r \ E q u i p m e n t \ M O U N T S \ Q U I C K M O U N T \ Q M P V - d a t a s h e e t - Q M H S S - L S - Q u i c k H o o k S M - w e b . p d f Missing or invalid reference S h e e t : 2 F i l e : \ \ S U N - S E R V E R \ S u n I n c o r p o r a t e d J o b s M a s t e r \ E q u i p m e n t \ M O U N T S \ Q U I C K M O U N T \ Q M P V - d a t a s h e e t - Q M H S S - L S - Q u i c k H o o k S M - w e b . p d f M i s s i n g o r i n v a l i d r e f e r e n c e