STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: March 2, 2020 APPROVED: March 4, 2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Thomson Farm Apartments – 3 Story
STREET ADDRESS: 472 N. Yellowstone Highway CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Automatic Fire Sprinkler Service, Inc.
300 S. Catlin Street, Ste 2
Missoula, MT 59801
IDAHO LICENSE: FPSC-136
CONTACT NAME: John Venche
john@afssmt.com
PHONE NO: (208) 695-6553
SYSTEM DESIGNED BY: John Venche
john@afssmt.com
PHONE NO: (208) 695-6553
TYPE OF SYSTEM: NFPA 13R/Wet HEAD COUNT: 272
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Residential
CONSTRUCTION TYPE: VB AREA SQUARE FOOTAGE: 21,249
SCOPE OF WORK: New apartments
PLAN REVIEW COMMENTS: Approved with the following comments
1. Fire service mains shall be restrained against movement at changes of direction.
(NFPA 13, 10.6)
2. Working Plans per NFPA 13R, 8.1.7(20)
3. Sprinkler protection shall be provided in open–ended corridors and associated
exterior stairways and ramps. (2015 IFC 903.3.1.2.2)
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.