Review Action Fax (208) 359-3022
February 26, 2008 oiIQQQ
Permit Number: 08 00040 f-0 DWO-9
Project Name: Chiller Bldg Addition (Qk wwk- ld
Project Type: Commercial Addition
Review Item Actions Required for Approval Approved
Administrative Review
Permit Tech Notes
Parcel #'s RPROOOP0140010
Plumbing contractor signature and estimate
needed.
Electrical contractor signature and estimate
needed.
Mechanical contractor signature and estimate
needed.
0
CITY OF
REXBURG
Amenm} Fonlly Com rrue:,:
February 26, 2008
Permit Number: 08 00040
Project Name: Chiller Bldg Addition
Project Type: Commercial Addition
Review Action
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
Building Department Review
Electrical Service Review 01/29/2008
Electrical Circuits Review 01/29/2008
Electrical Energy Lighting Compliance Review 01/29/2008
Accessibility Review The exiting does not need to meet accessible 02/04/2008
standards as per IBC 1103.2.5.
Energy Conservation Compliance Review The plans show 2 " of rigid insulation on walls. 02/04/2008
Usually we associate R5 for each inch. The
energy review identifies R15. R30 is shown on
energy review. Identify thickness of insulation
to equal R30.
CI I OF
REXBURG
Amena6 FaWly Community
February 26, 2008
Permit Number: 08 00040
Project Name: Chiller Bldg Addition
Project Type: Commercial Addition
Review Action
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Review Item Actions Required for Approval Approved
The plans show 2" of ridgid insulation. Identify
how R15 was reached.
(0
CITY OF
MXBURG
Ami.' F=11Y Community
February 26, 2008
Permit Number: 08 00040
Project Name: Chiller Bldg Addition
Project Type: Commercial Addition
Review Item
Height and Area Review
Exiting Review
Building Type Compliance
Building Code Fire Compliance Review
Structural Review
Water and Sewer Service
Plumbing Sewer Drain Review
Plumbing Potable Water Review
Plumbing Storm Drain Review
Mechanical Review
Review Action
Meets code requirements.
Meets code requirements.
Building is Type IIB. Occupancy is U.
Meets code requirements.
Meets code requirements. Special inspections
are required on foundation walls, structural
masonry, welding and high strength bolting.
All plumbing services are required to tested and
inspected before covering.
All indirect drains are required to discharge to
an approved indirect waste receptor. Floor
drains are not approved as indirect waste
receptors.
The combination waste and vent system is
undersized. Please make proper adjustments
and resubmit plans with the proper sizing.
All water lines that are not used for potable
water are required to be labeled as required by
the Uniform Plumbing Code. All water lines are
required to have the proper Backflow prevention
devices installed, tested and inspected as
requirerd by the Uniform Plumbing Code.
All storm water piping is required to be tested
and inspected before covering.
Not reviewed at this time. In process and to be
handled seperately.
P.O Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
02/04/2008
02/04/2008
02/04/2008
02/04/2008
02/04/2008
eezeuec,
--CITY OF
REXBURG
Amm6m's F WIy Community
February 26, 2008
Permit Number: 08 00040
Project Name: Chiller Bldg Addition
Project Type: Commercial Addition
Review Item
Fire Department Review
Required Fire Flow
Standpipes
Other Comments
Alarm Systems
Commercial Cooking
Automatic Fire Extinguishing Systems
Water Supply
Fire Extinguishers
Fire Access Roads
Parcel#'s RPROOOP0140010
Review Action
RO Box 280
19 E Main Sl.
Rexburg, Idaho 83440
Fhone (208) 359-3020
Fax (208) 359-3022
AcUon-5 Required for Approval Approved
See site plan review. 02/05/2008
N/A 02/05/2008
All keys for the new addition need to be placed 02/05/2008
in the lock box upon completetion of project.
Submit plans to the City of Rexburg for 02/05/2008
approval. Plans are required to be approved
before any working on the fire alarm system.
N/A 02/05/2008
Submit automatic fire sprinkler plans to the 02/05/2008
State Fire Marshall for approval. All plans are
required to be approved before work begins on
the fire suppression system.
See site plan review. 02/05/2008
Fire extinguishers are required for this 02/05/2008
occupancy. Please install all fire extinguishers
prior to final fire inspection. Install according to
the 2006 edition of the International Fire Code
and NFPA.
See site plan review.
02/05/2008
(0
CITY OF
REXBURG
Mmmnw's Famin• Community
February 26, 2008
Review Action
P.o Box 280
19 E Main St.
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
Permit Number: 08 00040
Project Name: Chiller Bldg Addition
Project Type: Commercial Addition
Review Item Actions Required for Approval _ Approved
Planning Staff Review
Development Standards Review Building needs to incorporate horizontal band or
similar element that will reduce the scale of the
building. Band should be of diferent color and or
material from the overall wall.
Development Standards Review No mechanical equipment can be visible from
public right of way. Please provide evidence
that this will not occur. This includes rooftop
equipment as well as any ground equipment.
Development Standards Review Provide landscaping that will further screen or
reduce scale of proposed walls. Of particular
concern are the north and northwest walls. See
site plan reivew notes for recomended
minimum plant sizes.
Parcel #'s RPROOOP0140010