HomeMy WebLinkAboutPLANS REDLINED REVISIONS - 20-00638 - 227 S 4th W - Solar PanelsAuthor Name Author Email Author Phone No.: Bret Stoddard brets@rexburg.org 208-372-2171 Larry Beesley Larry.Beesley@rexburg.org 208-372-2176 Description : 227 S 4th W - Solar PanelsAddress : 227 S 4th WApplication Type : Document Filename : Permit Plans_Higham,Brock_08072020.pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments T-1 Free text Larry Beesley : Building Open 1 3' pathway M-2 Free text Larry Beesley : Building Open 3 The roof will need an engineers approval and be stampedstating that the roof will carry the added loads from the solarpanels. SS-3 Free text Larry Beesley : Building Open 8 Approved flashing system. # 20-00638Solar Panels Your roof will need to be approved by a engineer for the structural ability to carry the added weight and also how the roof is built. Report Date: 31-08-2020 Approval of plans does not constitute approval of variance from code Page 1 of 1 Powered by TCPDF (www.tcpdf.org) ACCP MSP UM VICINITY MAP ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" GENERAL SYSTEM INFORMATION: SYSTEM SIZE: 15000W DC, 12000W AC MODULES: (40)PRISMA SOLAR P72-375W INVERTER: (10)APSYSTEMS QS1 MICRO INVERTERS, BRANCH DETAILS: 1X3, 1X3, 1x3 & 1x1MICRO INVERTER BRANCHES SCOPE OF WORK SHEET CATALOG INDEX NO.DESCRIPTION T-1 COVER PAGE M-1 MOUNTING DETAIL M-2 STRUCTURAL DETAIL E-1 SINGLE LINE DIAGRAM PL-1 WARNING PLACARDS SS SPEC SHEET(S) SITE PLAN LAYOUT (E) MAIN SERVICE PANEL(INTERIOR) (N) PV UTILITY DISCONNECT SWITCH(EXTERIOR) (N) LOAD CENTER(EXTERIOR) CONDUIT RUN PROPERTY LINE PHOTOVOLTAIC ARRAY ON THE ROOF ·ELECTRIC CODE:NEC 2017 ·FIRE CODE:IFC 2015 ·BUILDING CODE:IBC 2015 ·RESIDENTIAL CODE:IRC 2012 APPLICABLE CODES 3' FIRE SETBACK DRIVE WAY S 4 t h W BROCK HIGHAM - 15.000kW DC, 12.000kW AC COVER PAGE T-1SCALE:1/16" = 1'-0" 1.MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2.INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3.DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4.WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC 110.26. 5.ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6.ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8.THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9.ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10.PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING GENERAL NOTES 141'-9" 53'-1" 46'-2" 9'-3" 5'-8" 23'-8" (E)UTILITY METER(EXTERIOR) 3' pathway AERIAL VIEW ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" MOUNTING DETAIL M-1 SITE INFORMATION - WIND SPEED: 115 MPH AND SNOW LOAD: 50 PSF SR. NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 180°30°40 854.6 COMPOSITION SHINGLE FLASH FOOT 2 ATTIC RAFTERS 2 X 4 2'-0"4'-0"2'-0" 1.STRUCTURAL ROOF MEMBER LOCATIONS ARE ESTIMATED AND SHOULD BE LOCATED AND VERIFIED BY THE CONTRACTOR WHEN LAG BOLT PENETRATION OR MECHANICAL ATTACHMENT TO THE STRUCTURE IS REQUIRED. 2.ROOFTOP PENETRATIONS FOR SOLAR RACKING WILL BE COMPLETED AND SEALED WITH APPROVED SEALANT PER CODE BY A LICENSED CONTRACTOR. 3.LAGS MUST HAVE A MINIMUM 2.5" THREAD EMBEDMENT INTO THE STRUCTURAL MEMBER. 4.ALL PV RACKING ATTACHMENTS SHALL BE STAGGERED BY ROW BETWEEN THE ROOF FRAMING MEMBERS AS NECESSARY. 5.ROOF MOUNTED STANDARD RAIL REQUIRES ONE THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL GREATER THAN 40'. 6.ALL CONDUCTORS AND CONDUITS ON THE ROOF SHALL BE MINIMUM 1-1/2" ABOVE THE ROOF SURFACE (INCLUDING CABLES UNDERNEATH MODULES AND RACKING). 7.THE PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL OR BUILDING ROOF VENTS. ROOF ACCESS PATHWAYS AND SETBACKS: IFC 605.11.1.2.1 SIZE OF SOLAR PHOTOVOLTAIC ARRAY. EACH PHOTOVOLTAIC ARRAY SHALL BE LIMITED TO 150 FEET (45 720 MM) BY 150 FEET (45 720 MM). MULTIPLE ARRAYS SHALL BE SEPARATED BY A 3-FOOT-WIDE (914 MM) CLEAR ACCESS PATHWAY. IFC 605.11.1.2.2 HIP ROOF LAYOUTS. PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH HIP ROOF LAYOUTS SHALL BE LOCATED IN A MANNER THAT PROVIDES A 3-FOOT-WIDE (914 MM) CLEAR ACCESS PATHWAY FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE WHERE PANELS AND MODULES ARE LOCATED. THE ACCESS PATHWAY SHALL BE AT A LOCATION ON THE BUILDING CAPABLE OF SUPPORTING THE FIRE FIGHTERS ACCESSING THE ROOF. IFC 605.11.1.2.3 SINGLE-RIDGE ROOFS. PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH A SINGLE RIDGE SHALL BE LOCATED IN A MANNER THAT PROVIDES TWO, 3-FOOT-WIDE (914 MM) ACCESS PATHWAYS FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE WHERE PANELS AND MODULES ARE LOCATED. IFC 605.11.1.2.4 ROOFS WITH HIPS AND VALLEYS. PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH ROOF HIPS AND VALLEYS SHALL NOT BE LOCATED CLOSER THAN 18 INCHES (457 MM) TO A HIP OR A VALLEY WHERE PANELS/MODULES ARE TO BE PLACED ON BOTH SIDES OF A HIP OR VALLEY. WHERE PANELS ARE TO BE LOCATED ON ONLY ONE SIDE OF A HIP OR VALLEY THAT IS OF EQUAL LENGTH, THE PANELS SHALL BE PERMITTED TO BE PLACED DIRECTLY ADJACENT TO THE HIP OR VALLEY. IFC 605.11.1.2.5 ALLOWANCE FOR SMOKE VENTILATION OPERATIONS. PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS SHALL BE LOCATED NOT LESS THAN 3 FEET (914 MM) FROM THE RIDGE IN ORDER TO ALLOW FOR FIRE DEPARTMENT SMOKE VENTILATION OPERATIONS. INSTALLATION NOTES ALUMINIUM RAILS 2 X 4 RAFTERS@ 2'-0"SPACING ARRAY MP-01 SCALE:1/8" = 1'-0" 3' 3'3'-5" 4' NOTE:PENETRATIONS ARE STAGGERED MODULE END CLAMPMID CLAMPMODULE ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" STRUCTURAL DETAIL M-2 DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 40 47.6 1904.00 MID-CLAMP 76 0.050 3.80 END-CLAMP 8 0.050 0.40 RAIL LENGTH 266 0.680 180.88 SPLICE BAR 16 0.360 5.76 FLASH FOOT 2 70 1.88 131.60 MICRO INVERTER 10 9.9 99.00 TOTAL WEIGHT OF THE SYSTEM (LBS)2226.44 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)854.55 WEIGHT PER SQ. FT.(LBS)2.61 WEIGHT PER PENETRATION (LBS)31.81 MID-CLAMP AND END-CLAMP ANATOMY ATTACHMENT DETAIL-FLASH FOOT 2 FLASH FOOT 2SOLAR MODULE STAINLESS STEEL 5/16" LAG SCREW 2.5" EMBEDMENT PILOT HOLE REQUIRED RAIL FLASHING 6" MAX SCALE:NTS GROUNDING LUG MID CLAMP ASSEMBLY MODULE FRAME RAIL MODULE TO MODULE & MODULE TO RAIL GROUNDING MID-CLAMP SCALE: NTS GROUNDING DETAILS IRONRIDGE RAIL IRONRIDGE INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS RAIL TO RAIL T-BOLT 2 X 4 RAFTERS @2'-0" SPACING COMPOSITION SHINGLE ROOF MODULE 5/16" X 3.5" LAG SCREW 1 BOLT PER PENETRATION LOAD BEARING WALL SCALE:NTS ROOF FRAMING DETAILS MODULES DATA PRISMA SOLAR P72-375W MODULE DIMS 78.22"x39.33"x1.37" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT The roof will need an engineers approval and be stamped stating that the roof will carry the added loads from the solar panels. (40)PRISMA SOLAR P72-375W,MODULES WITH (10)APSYSTEMS QS1 MICRO INVERTERS (N)JUNCTION BOX OR EQUI. 2 1 (1) BRANCH OF (3) MICRO-INVERTERS (1) BRANCH OF (3) MICRO-INVERTERS (1) BRANCH OF (3) MICRO-INVERTERS (1) BRANCH OF (1) MICRO-INVERTERS DC CONDUCTORS AC CONDUCTORS EATON BR48L125RP LOAD CENTER INSTALL (4)20A PV 2P BREAKERS 125A LOAD CENTER 20A (ONLY FOR SOLAR, NO LOADS TO BE ADDED) 3 20A 20A 20A (E)200A END FED MAIN PANEL UTILITY GRID (E )20 0 A M A I N BR E A K E R (E) GROUND ELECTRODE LINE SIDE TAP EXISTING 120/240V 1PH 60HZ METER#:ROCKY MOUNTAIN POWER 66789356M (N)100A AC DISCONNECT AC DISCONNECT FUSED,100A,1PH, 120/240V 2P 70A FUSE 3 CONDUIT SCHEDULE TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND 1 NONE (2) 12AWG AC TRUNK CABLE NONE (1) 12AWG AC TRUNK CABLE 2 3/4"EMT OR EQUIV (8) 10AWG THHN/THWN-2 NONE (1) 10AWG THHN/THWN-2 3 1"EMT OR EQUIV (2) 4 AWG THHN/THWN-2 (1)4 AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2 NOTE: MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A LINE SIDE TAP: 100% ALLOWABLE BACKFEED IS =200A OCPD CALCULATIONS: INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS =5x1.25x10=62.50 A =>PV BREAKER = 70A ALLOWABLE BACKFEED 200A =>70A PV BREAKER SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 15000W, AC SYSTEM SIZE - 12000W ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" SINGLE LINE DIAGRAM E-1 1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC 310.10(D). 2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC 310.10(C). 3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED. 5.BREAKER/FUSE SIZES CONFORMS TO NEC 240.6 CODE SECTION. 6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC 250.66. 7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON NEC 690.31(C). 8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON NEC 310.15(B)(2). 9.MAX. SYSTEM VOLTAGE CORRECTION IS PER NEC 690.7. 10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE NEC 310.15(B)(16). ELECTRICAL NOTES MICRO INVERTER SPECIFICATIONS MODEL APSYSTEMS QS1 MICRO INVERTERS POWER RATING 1200W MAX OUTPUT CURRENT 5A CEC WEIGHTED EFFICIENCY 96.5% MAX NO OF MICRO INVERTERS/BRANCH 3 MAX DC VOLTAGE 60V MODULE SPECIFICATION MODEL PRISMA SOLAR P72-375W MODULE POWER @ STC 325W OPEN CIRCUIT VOLTAGE:Voc 44.5V MAX POWER VOLTAGE:Vmp 36.7V SHORT CIRCUIT VOLTAGE:Isc 9.4A MAX POWER CURRENT:Imp 8.86A ELECTRICAL CALCULATIONS AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >> ·REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A) ·CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY ·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) < DERATED CONDUCTOR AMPACITY AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK 1 5 X 3 =15.00 X 1.25 =18.75A 30 X 0.87 X 1 =26.10A 18.75A <26.10A 2 5 X 3 =15.00 X 1.25 =18.75A 40 X 0.87 X 1 =34.80A 18.75A <34.80A 3 5 X 10 =50.00 X 1.25 =62.50A 95 X 0.87 X 1 =82.65A 62.50A <82.65A NOTE: EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT NOTE:EACH APSYSTEMS QS1 MICRO INVERTER IS CONNECTED TO FOUR MODULES NOTE: AC DISCONNECT PLACED WITHIN 10' OF UTILITY METER 10' MAX ACCP MSP UM WARNING PLACARD ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" WARNING PLACARDS PL-1 ! WARNING CAUTION: SOLAR CIRCUIT CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED LABEL LOCATION POINT OF INTERCONNECTION (PER CODE: NEC 705.12(b)(2)(3)(b) [ Not Required if Panel board is rated not less than sum of ampere ratings of all overcurrent devices supplying it] ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED LABEL LOCATION DC DISCONNECT,INVERTER [PER CODE: NEC 690.41)] [To be used when inverter is ungrounded]WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVER-CURRENT DEVICE WARNING:PHOTOVOLTAIC POWER SOURCE LABEL LOCATION CONDUIT, COMBINER BOX [PER CODE: NEC690.31(G)(3)] WARNING-ELECTRIC SHOCK HAZARD NO USER SERVICEABLE PARTS INSIDE CONTACT AUTHORIZED SERVICE PROVIDE FOR ASSISTANCE LABEL LOCATION INVERTER, JUNCTION BOXES(ROOF), AC DISCONNECT [PER CODE: NEC 690.13] LABEL LOCATION DISCONNECT, POINT OF INTERCONNECTION [PER CODE: NEC690.13(B)] LABEL LOCATION AC DISCONNECT , POINT OF INTERCONNECTION [PER CODE: NEC 690.54] LABEL LOCATION MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES. (PER CODE: IFC605.11.1.4) LABEL LOCATION POINT OF INTERCONNECTION [PER CODE: NEC705.12(D)(4)] ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: NEC 690.13(B)] DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: NEC 690.13(B)] LABEL LOCATION WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE, UL969 AS STANDARD TO WEATHER RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN 38" LETTER HEIGHT ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN THE MAIN SERVICE DISCONNECT,PLACED ON THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERATED WITH THE SERVICE PANEL CLOSED. (PER CODE: NEC690.15 ,690.13(B)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM ! ! ! WARNING! SOLAR DISCONNECT RATED AC OPERATING CURRENT AC NOMINAL OPERATING VOLTAGE 50.00 240 AMPS AC VAC PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL LOCATION INVERTER [PER CODE: NEC 690.56(C)(3)] TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRICPV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION AC DISCONNECT , DC DISCONNECT,POINT OF INTERCONNECTION (PER CODE: NEC690.56(C)(1)(A)) ! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !WARNING: SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER EACH SOLAR MODULE ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE RED WITH WHITE LETTERING U.O.N. PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE. FASTENERS APPROVED BY THE LOCAL JURISDICTION MANUAL DISCONNECT FOR PARALLEL GENERATION LABEL LOCATION AC DISCONNECT (E) MAIN SERVICE PANEL (INTERIOR) (N) PV UTILITY DISCONNECT SWITCH(EXTERIOR) (N) LOAD CENTER(EXTERIOR) (E)UTILITY METER(EXTERIOR) SPEC SHEET ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" MODULE SPEC SHEET SS-1 SPEC SHEET ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" INVERTER SPEC SHEET SS-2 SPEC SHEET ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" MOUNT SPEC SHEET SS-3 Approved flashing system. SPEC SHEET ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" RAIL SPEC SHEET SS-4 SPEC SHEET ADDRESS:227 S 4TH W, REXBURG, ID 83440 43.820894, -111.794935 CUSTOMER INFORMATION NAME:BROCK HIGHAM DATE:8/7/2020 SCALE:AS NOTED REV:A AHJ:ID-CITY OF REXBURG PRN NUMBER:RNS-011833 UTILITY:ROCKY MOUNTAIN POWER PRN NUMBER:RNS-011833 DESIGNER /CHECKED BY:MP/SN PAPER SIZE:17"X11" LOAD CENTER SPEC SHEET SS-5