HomeMy WebLinkAboutPLANS REDLINED APPROVED - 20-00638 - 227 S 4th W - Solar PanelsAuthor Name Author Email Author Phone No.:
Larry Beesley Larry.Beesley@rexburg.org 208-372-2176
Description : 227 S 4th W - Solar PanelsAddress : 227 S 4th WRecord Type : Solar PanelsDocument Filename : Permit Plans_Higham,Brock_08072020-Stamped.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report Approved
# 20-00638
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Free text Larry Beesley : Building Open 1 Roof Trusses (designed according to R802.10.1) 35 # Snow and90 mph winds (Local Conditions)
Pg 1 Free text Larry Beesley : Building Open 1 Your roof must meet the snow and wind loads listed below!
Pg 3 Free text Larry Beesley : Building Open 3 Roof Trusses (designed according to R802.10.1) 35 # Snow and90 mph winds (Local Conditions)
Solar Panels
Your roof will need to be approved by a engineer for the structural ability to carry the added weight and also how the roof is built.
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
ACCP
MSP
UM
VICINITY MAP
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
GENERAL SYSTEM INFORMATION:
SYSTEM SIZE:
15000W DC, 12000W AC
MODULES:
(40)PRISMA SOLAR P72-375W
INVERTER:
(10)APSYSTEMS QS1 MICRO INVERTERS,
BRANCH DETAILS:
1X3, 1X3, 1x3 & 1x1MICRO INVERTER BRANCHES
SCOPE OF WORK
SHEET CATALOG
INDEX NO.DESCRIPTION
T-1 COVER PAGE
M-1 MOUNTING DETAIL
M-2 STRUCTURAL DETAIL
E-1 SINGLE LINE DIAGRAM
PL-1 WARNING PLACARDS
SS SPEC SHEET(S)
SITE PLAN LAYOUT
(E) MAIN SERVICE PANEL(INTERIOR)
(N) PV UTILITY DISCONNECT SWITCH(EXTERIOR)
(N) LOAD CENTER(EXTERIOR)
CONDUIT RUN PROPERTY LINE
PHOTOVOLTAIC ARRAY ON THE ROOF
·ELECTRIC CODE:NEC 2017
·FIRE CODE:IFC 2015
·BUILDING CODE:IBC 2015
·RESIDENTIAL CODE:IRC 2012
APPLICABLE CODES
3' FIRE SETBACK
DRIVE WAY
S
4
t
h
W
BROCK HIGHAM - 15.000kW DC, 12.000kW AC
COVER PAGE
T-1SCALE:1/16" = 1'-0"
1.MODULES ARE LISTED UNDER UL 1703 AND
CONFORM TO THE STANDARDS.
2.INVERTERS ARE LISTED UNDER UL 1741 AND
CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING
GENERAL ARRANGEMENT OF THE PV SYSTEM AND
THE ACTUAL SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC 110.26.
5.ALL GROUND WIRING CONNECTED TO THE MAIN
SERVICE GROUNDING IN MAIN SERVICE PANEL/
SERVICE EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 75°C
STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE
FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY
THE CONTRACTOR UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND/OR THE UTILITY.
9.ROOF ACCESS POINT SHALL BE LOCATED IN
AREAS THAT DO NOT REQUIRE THE PLACEMENT
OF GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH
OVERHEAD OBSTRUCTIONS SUCH AS TREES,
WIRES OR SIGNS.
10.PV ARRAY COMBINER/JUNCTION BOX
PROVIDES TRANSITION FROM ARRAY WIRING TO
CONDUIT WIRING
GENERAL NOTES
141'-9"
53'-1"
46'-2"
9'-3"
5'-8"
23'-8"
(E)UTILITY METER(EXTERIOR)
9/15/2020
Sealed For
Existing Roof &
Attachment Only
Digitally signed
by John Calvert
Date: 2020.09.15
22:49:22 -06'00'
Roof Trusses (designed according to R802.10.1) 35 # Snow and 90 mph winds (Local
Conditions)
Your roof must meet the snow and wind loads listed
below!
AERIAL VIEW
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
MOUNTING DETAIL
M-1
SITE INFORMATION - WIND SPEED: 115 MPH AND SNOW LOAD: 50 PSF
SR.
NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ. FT.)ROOF TYPE ATTACHMENT
ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX RAIL
SPAN
OVER
HANG
MP-01 180° 30° 40 854.6
COMPOSITION
SHINGLE FLASH FOOT 2 ATTIC TRUSSES 2 X 4 2'-0" 4'-0" 2'-0"
1.STRUCTURAL ROOF MEMBER LOCATIONS ARE
ESTIMATED AND SHOULD BE LOCATED AND VERIFIED
BY THE CONTRACTOR WHEN LAG BOLT PENETRATION
OR MECHANICAL ATTACHMENT TO THE STRUCTURE IS
REQUIRED.
2.ROOFTOP PENETRATIONS FOR SOLAR RACKING
WILL BE COMPLETED AND SEALED WITH APPROVED
SEALANT PER CODE BY A LICENSED CONTRACTOR.
3.LAGS MUST HAVE A MINIMUM 2.5" THREAD
EMBEDMENT INTO THE STRUCTURAL MEMBER.
4.ALL PV RACKING ATTACHMENTS SHALL BE
STAGGERED BY ROW BETWEEN THE ROOF FRAMING
MEMBERS AS NECESSARY.
5.ROOF MOUNTED STANDARD RAIL REQUIRES ONE
THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL
GREATER THAN 40'.
6.ALL CONDUCTORS AND CONDUITS ON THE ROOF
SHALL BE MINIMUM 1-1/2" ABOVE THE ROOF
SURFACE (INCLUDING CABLES UNDERNEATH
MODULES AND RACKING).
7.THE PV INSTALLATION SHALL NOT OBSTRUCT ANY
PLUMBING, MECHANICAL OR BUILDING ROOF VENTS.
ROOF ACCESS PATHWAYS AND SETBACKS: IFC
605.11.1.2.1 SIZE OF SOLAR PHOTOVOLTAIC
ARRAY.
EACH PHOTOVOLTAIC ARRAY SHALL BE LIMITED TO
150 FEET (45 720 MM) BY 150 FEET (45 720 MM).
MULTIPLE ARRAYS SHALL BE SEPARATED BY A
3-FOOT-WIDE (914 MM) CLEAR ACCESS PATHWAY.
IFC 605.11.1.2.2 HIP ROOF LAYOUTS.
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS WITH HIP ROOF LAYOUTS SHALL BE
LOCATED IN A MANNER THAT PROVIDES A
3-FOOT-WIDE (914 MM) CLEAR ACCESS PATHWAY
FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE
WHERE PANELS AND MODULES ARE LOCATED. THE
ACCESS PATHWAY SHALL BE AT A LOCATION ON THE
BUILDING CAPABLE OF SUPPORTING THE FIRE
FIGHTERS ACCESSING THE ROOF.
IFC 605.11.1.2.3 SINGLE-RIDGE ROOFS.
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS WITH A SINGLE RIDGE SHALL BE
LOCATED IN A MANNER THAT PROVIDES TWO,
3-FOOT-WIDE (914 MM) ACCESS PATHWAYS FROM
THE EAVE TO THE RIDGE ON EACH ROOF SLOPE
WHERE PANELS AND MODULES ARE LOCATED.
IFC 605.11.1.2.4 ROOFS WITH HIPS AND
VALLEYS. PANELS AND MODULES INSTALLED ON
GROUP R-3 BUILDINGS WITH ROOF HIPS AND
VALLEYS SHALL NOT BE LOCATED CLOSER THAN 18
INCHES (457 MM) TO A HIP OR A VALLEY WHERE
PANELS/MODULES ARE TO BE PLACED ON BOTH
SIDES OF A HIP OR VALLEY. WHERE PANELS ARE TO
BE LOCATED ON ONLY ONE SIDE OF A HIP OR VALLEY
THAT IS OF EQUAL LENGTH, THE PANELS SHALL BE
PERMITTED TO BE PLACED DIRECTLY ADJACENT TO
THE HIP OR VALLEY.
IFC 605.11.1.2.5 ALLOWANCE FOR SMOKE
VENTILATION OPERATIONS.
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS SHALL BE LOCATED NOT LESS THAN 3
FEET (914 MM) FROM THE RIDGE IN ORDER TO
ALLOW FOR FIRE DEPARTMENT SMOKE VENTILATION
OPERATIONS.
INSTALLATION NOTES
ALUMINIUM RAILS
2 X 4 RAFTERS@
2'-0"SPACING
ARRAY MP-01
SCALE:1/8" = 1'-0"
3'
3'3'-5"
4'
NOTE:PENETRATIONS ARE STAGGERED
9/15/2020
Sealed For
Existing Roof &
Attachment Only
MODULE
END CLAMPMID CLAMPMODULE
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
STRUCTURAL DETAIL
M-2
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL WEIGHT
(LBS)
MODULES 40 47.6 1904.00
MID-CLAMP 76 0.050 3.80
END-CLAMP 8 0.050 0.40
RAIL LENGTH 266 0.680 180.88
SPLICE BAR 16 0.360 5.76
FLASH FOOT 2 70 1.88 131.60
MICRO
INVERTER 10 9.9 99.00
TOTAL WEIGHT OF THE SYSTEM (LBS)2226.44
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)854.55
WEIGHT PER SQ. FT.(LBS)2.61
WEIGHT PER PENETRATION (LBS)31.81
MID-CLAMP AND END-CLAMP ANATOMY
ATTACHMENT DETAIL-FLASH FOOT 2
FLASH FOOT 2SOLAR MODULE
STAINLESS STEEL 5/16" LAG SCREW 2.5"
EMBEDMENT
PILOT HOLE REQUIRED
RAIL
FLASHING
6" MAX
SCALE:NTS
GROUNDING LUG
MID CLAMP
ASSEMBLY
MODULE
FRAME
RAIL
MODULE TO MODULE & MODULE TO RAIL
GROUNDING MID-CLAMP
SCALE: NTS
GROUNDING DETAILS
IRONRIDGE RAIL
IRONRIDGE INTERNAL SPLICE
SELF-DRILLING SCREW
SCALE: NTS
RAIL TO RAIL
T-BOLT
2 X 4 RAFTERS
@2'-0" SPACING
COMPOSITION SHINGLE ROOF
MODULE
5/16" X 3.5" LAG SCREW
1 BOLT PER PENETRATION
LOAD BEARING WALL SCALE:NTS
ROOF FRAMING DETAILS
MODULES DATA
PRISMA SOLAR P72-375W
MODULE DIMS 78.22"x39.33"x1.37"
LAG SCREWS 5/16"x3.5":2.5"MIN
EMBEDMENT
9/15/2020
Sealed For
Existing Roof &
Attachment Only
Roof Trusses (designed according
to R802.10.1) 35 # Snow and 90
mph winds (Local Conditions)
(40)PRISMA SOLAR P72-375W,MODULES WITH
(10)APSYSTEMS QS1 MICRO INVERTERS
(N)JUNCTION
BOX OR EQUI.
2 1
(1) BRANCH OF (3) MICRO-INVERTERS
(1) BRANCH OF (3) MICRO-INVERTERS
(1) BRANCH OF (3) MICRO-INVERTERS
(1) BRANCH OF (1) MICRO-INVERTERS
DC CONDUCTORS
AC CONDUCTORS
EATON BR48L125RP
LOAD CENTER INSTALL
(4)20A PV 2P BREAKERS
125A LOAD CENTER
20A
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
3 20A
20A
20A
(E)200A END FED
MAIN PANEL
UTILITY
GRID
(E )20
0
A
M
A
I
N
BR
E
A
K
E
R
(E) GROUND
ELECTRODE
LINE SIDE TAP
EXISTING 120/240V 1PH 60HZ
METER#:ROCKY MOUNTAIN POWER
66789356M
(N)100A AC
DISCONNECT
AC DISCONNECT
FUSED,100A,1PH,
120/240V 2P
70A FUSE
3
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (2) 12AWG AC TRUNK CABLE NONE (1) 12AWG AC TRUNK CABLE
2 3/4"EMT OR EQUIV (8) 10AWG THHN/THWN-2 NONE (1) 10AWG THHN/THWN-2
3 1"EMT OR EQUIV (2) 4 AWG THHN/THWN-2 (1)4 AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2
NOTE:
MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A
LINE SIDE TAP: 100% ALLOWABLE BACKFEED IS =200A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION=
INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS
=5x1.25x10=62.50 A =>PV BREAKER = 70A
ALLOWABLE BACKFEED 200A =>70A PV BREAKER
SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 15000W, AC SYSTEM SIZE - 12000W
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
SINGLE LINE DIAGRAM
E-1
1.CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC 310.10(D).
2.CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR USE
IN WET LOCATIONS PER NEC 310.10(C).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL
BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT
UNLESS OTHERWISE NOTED.
5.BREAKER/FUSE SIZES CONFORMS TO
NEC 240.6 CODE SECTION.
6.AC GROUNDING ELECTRODE
CONDUCTOR SIZED PER NEC 250.66.
7.AMBIENT TEMPERATURE CORRECTION
FACTOR IS BASED ON NEC 690.31(C).
8.AMBIENT TEMPERATURE ADJUSTMENT
FACTOR IS BASED ON NEC 310.15(B)(2).
9.MAX. SYSTEM VOLTAGE CORRECTION IS
PER NEC 690.7.
10.CONDUCTORS ARE SIZED PER WIRE
AMPACITY TABLE NEC 310.15(B)(16).
ELECTRICAL NOTES
MICRO INVERTER SPECIFICATIONS
MODEL APSYSTEMS QS1 MICRO
INVERTERS
POWER RATING 1200W
MAX OUTPUT CURRENT 5A
CEC WEIGHTED EFFICIENCY 96.5%
MAX NO OF MICRO
INVERTERS/BRANCH 3
MAX DC VOLTAGE 60V
MODULE SPECIFICATION
MODEL PRISMA SOLAR
P72-375W
MODULE POWER @ STC 325W
OPEN CIRCUIT VOLTAGE:Voc 44.5V
MAX POWER VOLTAGE:Vmp 36.7V
SHORT CIRCUIT VOLTAGE:Isc 9.4A
MAX POWER CURRENT:Imp 8.86A
ELECTRICAL CALCULATIONS
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
·REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF
INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A)
·CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
1 5 X 3 =15.00 X 1.25 =18.75A 30 X 0.87 X 1 =26.10A 18.75A <26.10A
2 5 X 3 =15.00 X 1.25 =18.75A 40 X 0.87 X 1 =34.80A 18.75A <34.80A
3 5 X 10 =50.00 X 1.25 =62.50A 95 X 0.87 X 1 =82.65A 62.50A <82.65A
NOTE: EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT
NOTE:EACH APSYSTEMS QS1 MICRO INVERTER IS CONNECTED
TO FOUR MODULES
NOTE: AC DISCONNECT PLACED WITHIN 10' OF UTILITY METER
10' MAX
ACCP
MSP
UM
WARNING PLACARD
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
WARNING PLACARDS
PL-1
!
WARNING
CAUTION: SOLAR CIRCUIT
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(b)(2)(3)(b)
[ Not Required if Panel board is rated not less than sum of
ampere ratings of all overcurrent devices supplying it]
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
DC DISCONNECT,INVERTER
[PER CODE: NEC 690.41)]
[To be used when inverter is ungrounded]WARNING
POWER SOURCE OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
[PER CODE: NEC690.31(G)(3)]
WARNING-ELECTRIC SHOCK HAZARD
NO USER SERVICEABLE PARTS INSIDE
CONTACT AUTHORIZED SERVICE
PROVIDE FOR ASSISTANCE
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
[PER CODE: NEC 690.13]
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
[PER CODE: NEC690.13(B)]
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
[PER CODE: NEC 690.54]
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT,
RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY
10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL
COMBINER/JUNCTION BOXES.
(PER CODE: IFC605.11.1.4)
LABEL LOCATION
POINT OF INTERCONNECTION
[PER CODE: NEC705.12(D)(4)]
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.13(B)]
DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR
MODULES ARE EXPOSED TO SUNLIGHT
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.13(B)]
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE,
UL969 AS STANDARD TO WEATHER RATING (UL LISTING
OF MARKINGS NOT REQUIRED), MIN 38" LETTER HEIGHT
ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN
THE MAIN SERVICE DISCONNECT,PLACED ON THE
OUTSIDE OF THE COVER WHEN DISCONNECT IS
OPERATED WITH THE SERVICE PANEL CLOSED.
(PER CODE: NEC690.15 ,690.13(B))
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
!
!
!
WARNING!
SOLAR DISCONNECT
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
50.00
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
LABEL LOCATION
INVERTER
[PER CODE: NEC 690.56(C)(3)]
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRICPV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LABEL LOCATION
AC DISCONNECT , DC DISCONNECT,POINT OF
INTERCONNECTION
(PER CODE: NEC690.56(C)(1)(A))
!
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!WARNING:
SYSTEM UTILIZES
MICRO-INVERTERS
LOCATED UNDER
EACH SOLAR MODULE
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE
RED WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION
MANUAL DISCONNECT FOR PARALLEL
GENERATION
LABEL LOCATION
AC DISCONNECT
(E) MAIN SERVICE PANEL
(INTERIOR)
(N) PV UTILITY DISCONNECT SWITCH(EXTERIOR)
(N) LOAD CENTER(EXTERIOR)
(E)UTILITY METER(EXTERIOR)
SPEC SHEET
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
MODULE SPEC SHEET
SS-1
SPEC SHEET
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
INVERTER SPEC SHEET
SS-2
SPEC SHEET
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
MOUNT SPEC SHEET
SS-3
SPEC SHEET
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
RAIL SPEC SHEET
SS-4
SPEC SHEET
ADDRESS:227 S 4TH W, REXBURG, ID
83440
43.820894, -111.794935
CUSTOMER INFORMATION
NAME:BROCK HIGHAM
DATE:8/7/2020
SCALE:AS NOTED REV:A
AHJ:ID-CITY OF REXBURG
PRN NUMBER:RNS-011833
UTILITY:ROCKY MOUNTAIN POWER
PRN NUMBER:RNS-011833
DESIGNER /CHECKED
BY:MP/SN PAPER SIZE:17"X11"
LOAD CENTER SPEC SHEET