HomeMy WebLinkAboutLOAD CALC - 20-00196 - 697 Tanglewood Dr - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Load Short Form 3/27/2020Date:Entire House Gene MillerBy: Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor: 170 N Eastern Ave, Idaho Falls,, Idaho Phone: 208-523-5542 Email: derik@alpineheatingair.com Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5050Inside humidity (%) -2962Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Carrier Make Carrier Trade Carrier Comfort 95 Single-Stag...Trade CARRIER Model 59SC5A060S17--14 Cond 24ABB330A003 AHRI ref 5039401 Coil CNPVP3617ALA++TDR AHRI ref 9858218 Efficiency 95.5 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh60000 Sensible cooling Btuh25628 Heating output Btuh46980 Latent cooling Btuh0 Temperature rise °F55 Total cooling Btuh25628 Actual air flow cfm925 Actual air flow cfm1070 Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.059 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech 110 0 0 0 0 Bsmt Bath 62 601 10 18 1 Br 6 WIC 42 587 12 18 1 Bedroom 5 199 1774 191 53 11 Family 723 4141 1019 124 60 Bedroom 4 189 1984 565 59 33 Office 219 1849 77 55 4 Cold Strg 108 0 0 0 0 Bedroom 2 139 2285 1405 68 82 Bedroom 3 128 1358 1314 41 77 Bath 48 404 68 12 4 Master 246 3637 2847 109 167 M Bath 93 867 498 26 29 M WIC 58 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E Kitchen/dining 306 5517 4336 165 254 Great Rm 521 4069 5188 122 304 Utility 67 1786 760 54 44 Entire House 3259 30859 18288 925 1070 Other equip loads 5490 1045 Equip. @ 0.95 RSM 18289 Latent cooling 0 TOTALS 3259 36348 18289 925 1070 2020-Mar-27 19:18:23 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Building Analysis 3/27/2020Date:Entire House Gene MillerBy: Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 35.0127234.4Walls 17.9650424.5Glazing 5.3193729.9Doors 7.226291.5Ceilings 8.028921.71.7Floors 11.541722.0Infiltration 00Ducts00Piping00Humidification15.15490Ventilation0Adjustments100.036348Total Cooling Walls Glazing Doors Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 3.87310.3Walls 56.41090641.2Glazing 2.44707.3Doors 7.514430.8Ceilings 000Floors2.24180.2Infiltration 00Ducts5.41045Ventilation22.34320Internal gains 00Blower0Adjustments100.019333Total Latent Cooling Load = 0 BtuhOverall U-value = 0.051 Btuh/ft²-°F Data entries checked. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Component Constructions 3/27/2020Date:Entire House Gene MillerBy: Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1550.4816044.9921.00.065322n 1870.4819394.9921.00.065389e 1650.4817134.9921.00.065344s 1500.4815504.9921.00.065311w 6570.4868064.9921.00.0651365all 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 150.0512673.7819.00.043335n 230.0517333.8519.00.043450e 150.0512673.7819.00.043335s 200.0516493.8019.00.043434w 740.0559173.8119.00.0431554all Partitions (none) Windows2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 32811.371224.500.32029n 18111.339324.500.32016n 189747.498224.500.32040e 91330.473624.500.32030s 48730.439324.500.32016s 559647.4289624.500.320118w 75947.439324.500.32016w 1016038.3650424.500.320265all Doors 11D0: Door, wd sc type 1657.2568129.900.39023n 1527.2562829.900.39021e 1527.2562829.900.39021w 4707.25193729.900.39065all Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 14430.8426291.5350.00.0201714 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.0221653 0027881.69 001041.6900.02262 0028921.6900.0221714all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Project Summary 3/27/2020Date:Entire House Gene MillerBy: Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542Email: derik@alpineheatingair.comINFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh30859 Structure Btuh18288DuctsBtuh0DuctsBtuh0Central vent (77 cfm)5490 Btuh Central vent (77 cfm)Btuh1045Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh36348 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh18289 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight0Fireplaces Structure Btuh280DuctsBtuh0Central vent (77 cfm)Btuh-1299CoolingHeatingOutside air32593259Area (ft²)Equipment latent load Btuh01859018590Volume (ft³)Air changes/hour 0.100.19 Equipment Total Load (Sen+Lat)Btuh18289Equiv. AVF (cfm)3159 Req. total capacity at 1.00 SHR ton1.5 Heating Equipment Summary Cooling Equipment Summary Make Carrier Make CarrierTradeCarrier Comfort 95 Single-Stag...Trade CARRIERModel59SC5A060S17--14 Cond 24ABB330A003AHRI ref 5039401 Coil CNPVP3617ALA++TDRAHRI ref 9858218Efficiency95.5 AFUE Efficiency 10.5 EER, 13 SEERHeating input Btuh60000 Sensible cooling Btuh25628Heating output Btuh46980 Latent cooling Btuh0Temperature rise °F55 Total cooling Btuh25628Actual air flow cfm925 Actual air flow cfm1070Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.059Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Entire House Mech 2 Exposed wall 360.9 ft 17.5 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft109.8x1.0 5 Room area 3259.0 ft²109.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 374 322 1604 155 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 29 0 712 328 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 23 23 681 165 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 351 335 1267 15 45 45 173 2 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 16 0 393 181 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 450 389 1939 187 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 40 0 982 1897 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 450 450 1733 23 113 113 433 6WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 374 344 1713 165 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 30 0 736 913 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 351 335 1267 15 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 16 0 393 487 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 450 311 1550 150 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 118 0 2896 5596 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 450 434 1649 20 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 16 0 393 759 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 1714 1714 2629 1443 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 1653 1653 2788 0 110 110 185 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 62 62 104 0 0 0 0 0 6 c) AED excursion 746 -1 Envelope loss/gain 26686 13550 792 7 12 a)Infiltration 4172 418 87 9 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 3400 0 Subtotal (lines 6 to 13)30859 18288 879 16 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00-879 -1614Subtotal308591828800 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 30859 18288 0 0 Air required (cfm)Air required (cfm)925 1070 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bsmt Bath Br 6 WIC 2 Exposed wall 3.8 ft 13.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.8x9.3 ft6.8x6.3 5 Room area 62.4 ft²42.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 61 61 234 3 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 34 34 130 2 56 56 217 3WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 62 62 105 0 42 42 71 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 235 1 522 5 12 a)Infiltration 19 2 65 6 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)254 3 587 12 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution34760014Subtotal6011058712 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 601 10 587 12 Air required (cfm)Air required (cfm)18 1 18 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 5 Family 2 Exposed wall 28.5 ft 58.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft16.3x12.3 ft723.4x1.0 5 Room area 199.1 ft²723.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 146 130 479 5 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 16 0 393 181 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 182 182 702 9GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 110 110 425 6 340 324 1224 15 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 16 0 393 759 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 199 199 336 0 723 723 1221 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -14 202 Envelope loss/gain 1632 177 3540 985 12 a)Infiltration 142 14 289 29 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1774 191 3829 1014 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00312614Subtotal177419141411019 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1774 191 4141 1019 Air required (cfm)Air required (cfm)53 11 124 60 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 4 Office 2 Exposed wall 15.8 ft 6.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft188.8x1.0 ft219.2x1.0 5 Room area 188.8 ft²219.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 59 59 225 3 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 142 126 461 4 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 16 0 393 487 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 189 189 319 0 219 219 370 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 17 0 Envelope loss/gain 1173 508 595 3 12 a)Infiltration 79 8 32 3 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1251 516 628 6 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution7334912227114Subtotal1984565184977 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1984 565 1849 77 Air required (cfm)Air required (cfm)59 33 55 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Cold Strg Bedroom 2 2 Exposed wall 35.0 ft 26.7 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft107.6x1.0 ft139.0x1.0 5 Room area 107.6 ft²139.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 14 14 67 6.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 41 41 156 2 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 97 77 383 37 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 20 0 491 948DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 248 248 953 13 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 131 131 651 63 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 27 27 104 1 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 108 108 165 91 139 139 213 117FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 108 108 182 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -9 -45 Envelope loss/gain 1560 98 1805 1127 12 a)Infiltration 175 17 480 48 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)1735 116 2285 1405 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-1735 -116 0 014Subtotal0022851405 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 2285 1405 Air required (cfm)Air required (cfm)0 0 68 82 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 3 Bath 2 Exposed wall 12.3 ft 5.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft128.3x1.0 ft48.3x1.0 5 Room area 128.3 ft²48.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 110 90 450 43 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 20 0 491 948 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 47 47 236 23 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 128 128 197 108 48 48 74 41FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -38 -5 Envelope loss/gain 1138 1062 310 58 12 a)Infiltration 220 22 94 9 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1358 1314 404 68 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal1358131440468 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1358 1314 404 68 Air required (cfm)Air required (cfm)41 77 12 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Master M Bath 2 Exposed wall 33.8 ft 9.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft18.3x13.5 ft10.0x9.3 5 Room area 246.4 ft²92.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 18 18 90 9 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 164 134 669 65 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 30 0 736 913 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 122 97 481 46 83 77 385 37GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 25 0 614 1186 6 0 147 285 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 246 246 378 207 93 93 142 78FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 27 27 46 0 0 0 0 0 6 c) AED excursion -108 68 Envelope loss/gain 3014 2317 674 468 12 a)Infiltration 606 61 166 17 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3619 2837 840 484 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution189261414Subtotal36372847867498 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3637 2847 867 498 Air required (cfm)Air required (cfm)109 167 26 29 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 8...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name M WIC Kitchen/dining 2 Exposed wall 0 ft 49.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.3x9.3 ft25.0x12.3 5 Room area 57.8 ft²306.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 225 196 977 94.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 29 0 712 328.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 90 90 449 43 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 18 18 90 9 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 110 47 236 23GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 42 0 1031 1992 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 58 58 89 49 306 306 470 258FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 25 25 41 0 6 c) AED excursion -3 348 Envelope loss/gain 89 45 4633 3247 12 a)Infiltration 0 0 884 89 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1000 Subtotal (lines 6 to 13)89 45 5517 4336 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-89 -45 0 014Subtotal0055174336 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 5517 4336 Air required (cfm)Air required (cfm)0 0 165 254 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 19:18:23Right-Suite® Universal 2019 19.0.12 RSU28163 Page 9...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Right-J® Worksheet 3/27/2020Date:Entire House Gene MillerBy:Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Great Rm Utility 2 Exposed wall 29.0 ft 17.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft521.3x1.0 ft66.7x1.0 5 Room area 521.3 ft²66.7 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 59 59 292 28 59 36 178 17.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 23 23 681 165 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.783.78 0.050.05 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 68 47 232 22 86 86 426 41 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.853.85 0.050.05 0 0 0 0 0 0 0 0WW12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 14 14 67 6 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0WW15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.783.78 0.050.05 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 135 90 449 43 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 45 0 1104 2134 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.803.80 0.050.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ww 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 521 521 800 439 67 67 102 56FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 10 10 17 0 6 c) AED excursion 394 -57 Envelope loss/gain 3505 3213 1472 229 12 a)Infiltration 521 52 314 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1900 500 Subtotal (lines 6 to 13)4025 5166 1786 760 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution44230014Subtotal406951881786760 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4069 5188 1786 760 Air required (cfm)Air required (cfm)122 304 54 44 Job #: 4-2-51 Stonebridge Performed by Gene Miller for: Alpine Heating And Air 170 N Eastern Ave Idaho Falls,, Idaho Phone: 208-523-5542 derik@alpineheatingair.com Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 87 Page 1 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-Mar-27 19:19:56 ...onebridge\4-2-51 Stonebridge.rup N Basement Mech Bsmt Bath Br 6 WIC Bedroom 5 Family Bedroom 4 Office Cold Strg Stairs 18 cfm 18 cfm 328 cfm 6 " 14x3.25 6 " 6 " 2-14x3.25 6 " 6 " 6 " 26 x 8 12 x 8 18 x 8 6 "6 " 6 " 6 " 6 " 6 " 8 " 6 " 10 x 8 6 " 6 " 8 x 8 8 x 8 26 x 8 6 " 62 cfm 59 cfm 55 cfm 6 " 53 cfm 6 " 62 cfm 6 " 14x3.25 2-14x3.25 14x3.25 18 x 8 2-14x3.25 10 x 8 Job #: 4-2-51 Stonebridge Performed by Gene Miller for: Alpine Heating And Air 170 N Eastern Ave Idaho Falls,, Idaho Phone: 208-523-5542 derik@alpineheatingair.com Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 87 Page 2 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-Mar-27 19:19:56 ...onebridge\4-2-51 Stonebridge.rup N Main Floor Bedroom 2 Bedroom 3 Bath Master M Bath M WIC Kitchen/dining Great Rm Utility 85 cfm 54 cfm 85 cfm 85 cfm 101 cfm 101 cfm 101 cfm 82 cfm 29 cfm 83 cfm 302 cfm 196 cfm 82 cfm 77 cfm 12 cfm 83 cfm 304 cfm77 cfm 2020-Mar-27 19:18:24 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E 4-2-51 StonebridgeJob:Duct System Summary 3/27/2020Date:Entire House Gene MillerBy: Mt. TimpenogasPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor: 170 N Eastern Ave, Idaho Falls,, Idaho Phone: 208-523-5542 Email: derik@alpineheatingair.com CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.316 / 0.174 in H2O in H2O0.316 / 0.174 Lowest friction rate in/100ft0.083in/100ft0.083 Actual air flow cfm1070cfm925 Total effective length (TEL)ft590 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3A340.029.8ShMt0x06.00.086412404hBath st3A325.040.5ShMt0x06.00.08782681405cBedroom 2 st3230.028.0ShMt0x06.00.12377411314cBedroom 3 00ShMt0x0003359565hBedroom 4 st1A180.026.0ShMt0x06.00.15411531774hBedroom 5 st1A190.013.8ShMt0x06.00.155118587hBr 6 WIC st1180.08.5ShMt0x06.00.168118601hBsmt Bath st4265.029.8ShMt0x06.00.10730622070hFamily st3A335.046.0ShMt0x06.00.08330622070hFamily-A st2195.025.5ShMt0x06.00.143101411729cGreat Rm 95.020.3ShMt0x06.00.274101411729cGreat Rm-A st2205.017.5ShMt0x06.00.142101411729cGreat Rm-B st1160.032.5ShMt0x06.00.16485551445cKitchen/dining st1A115.032.5ShMt0x06.00.21485551445cKitchen/dining-A st1170.016.8ShMt0x06.00.16985551445cKitchen/dining-B st4275.036.3ShMt0x06.00.1022926498cM Bath st3A315.051.0ShMt0x06.00.08683551423cMaster st3295.044.8ShMt0x06.00.09383551423cMaster-A st3230.026.5ShMt0x06.00.1234551849hOffice st2205.02.3ShMt0x06.00.15344541786hUtility Bold/italic values have been manually overridden 2020-Mar-27 19:18:24 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...nogas\4-2-51 Stonebridge\4-2-51 Stonebridge.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3A Peak AVF 197 199 0.083 448 7.8 8x8 ShtMetl st3 st3 Peak AVF 348 364 0.083 655 9.8 10x8 ShtMetl st2 st2 Peak AVF 571 670 0.083 670 12.3 18x8 ShtMetl st4 Peak AVF 88 59 0.102 252 8.0 0x0 ShtMetl st2 st1 Peak AVF 254 266 0.154 399 8.6 12x8 ShtMetl st1A Peak AVF 126 96 0.154 283 8.6 8x8 ShtMetl st1 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 1220 304 173.5 0.100 480 8.8 2-3.25x14 2-10x18 SJSp rt2A rb2 30x 2315 302 94.0 0.185 478 7.8 2-3.25x14 2-10x18 SJSp rt2 rb4 0x 1350 196 209.3 0.083 310 7.8 2-3.25x14 2-10x18 SJSp rt2B rb5 0x 410 77 176.3 0.099 243 5.3 3.25x14 10x9 SJSp rt2B rb6 0x 680 82 194.0 0.090 260 5.5 3.25x14 10x9 SJSp rt2B rb1 0x 3280 110 0 0 1037 0 3.25x14 10x9 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2B Peak AVF 244 355 0.083 639 9.7 10x8 ShtMetl rt2A rt2A Peak AVF 366 658 0.083 658 12.2 18x8 ShtMetl rt2 rt1 Peak AVF 597 960 0.083 665 14.1 26x8 ShtMetl rt2 Peak AVF 597 960 0.083 665 14.1 26x8 ShtMetl rt1