HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00011 - 114 W 3rd S - ElectricalPermit Inspection Summary Permit Status of (Open) as of Report Date: 06/29/2020 10:27 am Permit Details Permit Number: 10-00011 114 W 3rd S - Electrical 114 W 3rd S Commercial Electrical Misc. Permit Issued Date: 12/03/2014 Permit Inspection Statistics 1Total Inspections Completed: 1Total Inspections Passed: Inspection Pass Rate: 100.00% Permit Inspection History *Refer to Individual Inspection Report for more Details Electrical 01/14/2010PassBret StoddardCOM & MFR Electrical Service Inspection Approved for a final-they changed out the main breaker for the entire building, they down sized the main form an 800A to a 600A because the meter packs that this feeds are 200A each and there is 3 of them. I had them parallel the conductor off of the main breaker to the polaris lugs due to the size of conductor they chose-350kcmil. Inspector Comments: