Permit Inspection History *Refer to Individual Inspection Report for more Details
Electrical
01/14/2010PassBret StoddardCOM & MFR Electrical Service Inspection
Approved for a final-they changed out the main breaker for the entire building,
they down sized the main form an 800A to a 600A because the meter packs that
this feeds are 200A each and there is 3 of them. I had them parallel the
conductor off of the main breaker to the polaris lugs due to the size of conductor
they chose-350kcmil.