Permit Status of (Open) as of Report Date: 06/29/2020 9:28 am
Permit Details Permit Number: 10-00069
South Gate Apts - Clubhouse - Bld #1
370 W 7th S
New Commercial Building
Permit Issued Date: 12/17/2014
Permit Inspection Statistics
25Total Inspections Completed:
18Total Inspections Passed:
Inspection Pass Rate: 72.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
05/10/2010PassPLL ADMINCommercial Footing Inspection
As per Jon Berry.
Footing looks good.
Inspector Comments:
05/11/2010PassPLL ADMINFoundation Inspection
As per Jon Berry
Foundation looks good.
Inspector Comments:
06/18/2010FailPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry.
6/15/10 - Could not inspect. Mech, Elec, and Plumbing not completed.
6/18/10 - Straps and nailing as noted on drawing. Basement bearing walls need
anchor bolts. Apt. steps rise not to code or plans.
Inspector Comments:
07/09/2010FailPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry.
Residential stairs still not to code.
Bearing basement walls still need anchor bolts.
Inspector Comments:
07/15/2010FailPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry.
Residential stairs still are not per code tread. The rest of the building passed.
Inspector Comments:
07/19/2010PassPLL ADMINCommercial Insulation Inspection
As per Jon Berry.
Exterior walls insulation both floors look good.
Inspector Comments:
07/21/2010PassPLL ADMINCommercial Sheetrock/Drywall Inspection
As per Jon Berry.
Apartment upstairs of club house drywall ok to tape. Washer box in apt needs 2A
rating.
Basement drywall OK to cover. 7/22/10
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 10-00069
South Gate Apts - Clubhouse - Bld #1
370 W 7th S
New Commercial Building
Permit Status of (Open) as of Report Date: 06/29/2020 9:28 am
Permit
Inspection
Summary
07/28/2010PassPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry.
7/19/10 - Framing completed on club house.
7/28/10 - Fire caulking around washer box in residence completed.
Inspector Comments:
08/31/2010PassPLL ADMINSidewalk Inspection
As per Jon Berry.Inspector Comments:
08/31/2010FailPLL ADMINCommercial Building Final
As per Jon Berry.
Ladders req'd in window wells cw 1 1/2 hour rated door required between apt
and clubhouse. inw CW kitchen stove warming only sign CW range hood not insp
cw No ada grab bars cw
Inspector Comments:
09/07/2010FailPLL ADMINCommercial Building Final
As per Jon Berry.
90 min door needed for apt
Inspector Comments:
09/20/2010PassPLL ADMINCommercial Building Final
OK per Jon Berry.Inspector Comments:
Electrical
07/12/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover in the entire building, ground rods installed and also nail
plates, grounding electrode conductor not continuous-need to install continuous
conductor-will re-inspect this on the final. Inspected this on the 9th last week and
they were not done.
Inspector Comments:
07/13/2010PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-500 and 501.Inspector Comments:
08/26/2010FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Need to install a box for the theatre cabinet, need to install the hood fan for the
range, call for a re-inspect when ready.
Inspector Comments:
09/08/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
8/20/10 - Approved for a final and a C.O. in the managers unit only.
9/8/10 - Approved for a final and a C.O.
Inspector Comments:
Fire
09/17/2010PassPLL ADMINFire Department Final Inspection
As per Jon Berry.
7/19/10 - Attic fire stop looks good.
9/17/10 - Fire door installed (90 min)
Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 10-00069
South Gate Apts - Clubhouse - Bld #1
370 W 7th S
New Commercial Building
Permit Status of (Open) as of Report Date: 06/29/2020 9:28 am
Permit
Inspection
Summary
Mechanical
07/19/2010PassPLL ADMINHVAC Rough-in
As per Jon Berry.
HVAC rough looks good.
Inspector Comments:
08/19/2010FailPLL ADMINHVAC Final Inspection
As per Jon Berry.
No access to attic furnaces.
Inspector Comments:
08/26/2010PassPLL ADMINHVAC Final Inspection
As per Jon Berry.
HVAC final completed.
Inspector Comments:
Plumbing
05/10/2010PassPLL ADMINPlumbing Sewer
As per Brad Johnson.Inspector Comments:
05/10/2010PassPLL ADMINPlumbing Water
As per Brad Johnson.Inspector Comments:
05/27/2010PassSAUREY AMANDAPlumbing Underground Inspection
Ground Rough for clubhouse was good; lift station, end of line, and test were all
good. Per Jeff Hackworth.
Inspector Comments:
06/22/2010PassSAUREY AMANDAPlumbing Rough-in
Rough In CompleteInspector Comments:
08/31/2010PassPLL ADMINPlumbing Final Inspection
As per Brad Johnson.Inspector Comments: