HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00108 - Premier Performance - GeneratorPermit Inspection Summary Permit Status of (Open) as of Report Date: 06/24/2020 8:51 am Permit Details Permit Number: 10-00108 Premier Performance - Generator 278 Dividend Commercial Electrical Misc. Permit Issued Date: Permit Inspection Statistics 2Total Inspections Completed: 1Total Inspections Passed: Inspection Pass Rate: 50.00% Permit Inspection History *Refer to Individual Inspection Report for more Details Electrical 02/04/2011FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection -No equipment grounding conductor between transfer switch and 200A Swith. 250 . 35 (B)(2) -Need EGC#6 not 8 from generator to transfer. -Breaker blank needed on panel. Inspector Comments: 02/08/2011PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection Approved for final generator installed New#6 pulled from generator to 200 Transfer switch and disconnect. Inspector Comments: