HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00108 - Premier Performance - GeneratorPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/24/2020 8:51 am
Permit Details Permit Number: 10-00108
Premier Performance - Generator
278 Dividend
Commercial Electrical Misc.
Permit Issued Date:
Permit Inspection Statistics
2Total Inspections Completed:
1Total Inspections Passed:
Inspection Pass Rate: 50.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Electrical
02/04/2011FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
-No equipment grounding conductor between transfer switch and 200A Swith.
250 . 35 (B)(2) -Need EGC#6 not 8 from generator to transfer. -Breaker blank
needed on panel.
Inspector Comments:
02/08/2011PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for final generator installed New#6 pulled from generator to 200
Transfer switch and disconnect.
Inspector Comments: