HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00156 - Nauvoo House II Manager UnitPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/23/2020 1:12 pm
Permit Details Permit Number: 10-00156
Nauvoo House II Manager Unit
175 W 5th S
New Single Family Residence
Permit Issued Date: 05/06/2010
Permit Inspection Statistics
27Total Inspections Completed:
15Total Inspections Passed:
Inspection Pass Rate: 55.56%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
07/15/2010PassJohn BerryFoundation Inspection
Foundation & Re-bar look good on MQR & Shop bldgInspector Comments:
11/08/2010FailJohn BerryCommercial Framing/Structure Inspection
-Anchor bolts req 3"x3" washer Hold downs not in place per plans 54.1 Anchor
bolts req'd int. bearing walls - Anchor bolts req'd with in 10" of ends of plates per
plans 51.2
Inspector Comments:
11/08/2010FailJohn BerryCommercial Framing/Structure Inspection
OK washer box must be fire rated - Shop toilet 16" - 18" to side wall w/framing
for grab bars - duct to shop restroom must have fire damper
Inspector Comments:
11/15/2010FailJohn BerryCommercial Framing/Structure Inspection
-Several anchor bolts do not have a 3x3 washers or tightened - hold down not
installed properly OK drywall 5/8 type x behind tub - Anchor bolts req'd w/in 10"
of ends of mud sill
Inspector Comments:
11/16/2010PassQuinton OwensCommercial Sheetrock/Drywall Inspection
-Ceiling 1st layer installed Mech Rough in re-inspect framing re-inspectionInspector Comments:
12/03/2010FailJohn BerryCommercial Framing/Structure Inspection
-Anchor bolts missing - Some AB still have 2" washers - Move drywall to see
anchor bolts - Fire rate washer box - Upstairs insulation ok to cover After
washeer box completed - upstairs framing OK down stairs into walls OK to
drywall
Inspector Comments:
12/10/2010N/AJohn BerryCommercial Framing/Structure Inspection
-A Bolts missing or No 3" washers s/west corner shot rest room, mqr entry door -
washer box ok to cover - OK to drywall except above areas (re-insulate) Need to
inspect above areas before covering
Inspector Comments:
12/15/2010PassJohn BerryCommercial Framing/Structure Inspection
Framing completed Have provisions been made for accessibility in exercise room
Old room accessible
Inspector Comments:
12/17/2010N/ATed DyeCommercial Sheetrock/Drywall Inspection
Lid has 5/8 fire code rock Naided properly (upper floor)Inspector Comments:
12/20/2010PassJohn BerryCommercial Insulation Inspection
Wall insulation looks goodInspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 10-00156
Nauvoo House II Manager Unit
175 W 5th S
New Single Family Residence
Permit Status of (Open) as of Report Date: 06/23/2020 1:12 pm
Permit
Inspection
Summary
01/07/2011PassQuinton OwensCommercial Insulation Inspection
Insulation OK to coverInspector Comments:
01/07/2011PassQuinton OwensCommercial Sheetrock/Drywall Inspection
1st layer installed *(gaps at pipes attached to floor joists) Chase being built
around pipes
Inspector Comments:
02/25/2011FailQuinton OwensCommercial Building Final
CW Handrails not installed CW Check on leak at upstairs window(pink room)
Garage/Shop/Exercise rooms not completed - Landings at ext. Doors to be done
CW Plastic Pipe penetrating rated wall under stairs is not protected for fire rating.
CW rated ceiling in mech room? Openings in drywall
Inspector Comments:
03/02/2011FailJohn BerryCommercial Building Final
Install landings at ext doors - exercise room not completed - handrail req'd both
side of stairs - Finish landscaping - Box in pipe under stairs & change clean out
cover to metal
Inspector Comments:
Electrical
10/18/2010PassBret StoddardCOM & MFR Electrical Service Inspection
Approved for cover * Approved to be energized for permanent powerInspector Comments:
10/18/2010PassBret StoddardCommercial Electrical Rough-in
Approved for coverInspector Comments:
12/15/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover upstairsInspector Comments:
02/22/2011PassPLL ADMINCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Signed by Jane Shau Notes: Exercise room upstairs room was not complete and
ready for final inspection
Inspector Comments:
02/22/2011FailPLL ADMINCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Receptacle in bathroom must be GFCI protected. Must have light fixture installed
Breakers must be labeled & unused openings closed. Bathroom must have
fixtures installed & mounted in a box(all bathrooms) GFCI in upstairs main bath
does not work - install device for upstairs dishwasher no power in counter
Inspector Comments:
05/10/2011FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
-A/C unit no disconnect mounted. -Drinking fountain needs GFCI protection Call
for re-inspect when ready
Inspector Comments:
05/12/2011PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final & C.O.Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 10-00156
Nauvoo House II Manager Unit
175 W 5th S
New Single Family Residence
Permit Status of (Open) as of Report Date: 06/23/2020 1:12 pm
Permit
Inspection
Summary
Mechanical
10/25/2010FailQuinton OwensHVAC Rough-in
- Supply vent to upper east bathroom unfinished - bath vent for west upstairs
bathroom not long enough Pressure Test 32psi @3:07/32psi @ 3:38 Fix leak in
NE corner upstairs - insulation must be dried before covering
Inspector Comments:
11/19/2010FailJohn BerryHVAC Final Inspection
Not readyInspector Comments:
12/15/2010PassJohn BerryHVAC Rough-in
Fire damper required for duct in stop restroom HVAC rough completedInspector Comments:
03/03/2011PassQuinton OwensHVAC Final Inspection
Originally failed on 02/25/2011, but approved on 03/03/2011 Notes: Bath fan not
working under stairs Dryer vent termination cover missing Finish sealing ducts in
mech in and connection at furnace Strap water heater
Inspector Comments:
Plumbing
10/19/2010PassBrad JohnsonPlumbing Rough-in
Good for sheetrock on plumbing onlyInspector Comments:
10/21/2010PassBrad JohnsonPlumbing Rough-in
Approved for coverInspector Comments:
Page 3 of 3