HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00197 - Sammy's - Commercial RemodelPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/23/2020 12:34 pm
Permit Details Permit Number: 10-00197
Sammy's - Commercial Remodel
30 Carlson Ave
Commercial - Remodel
Permit Issued Date: 05/25/2010
Permit Inspection Statistics
8Total Inspections Completed:
4Total Inspections Passed:
Inspection Pass Rate: 50.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
09/10/2010FailJohn BerryCommercial Building Final
-Post occupant load as discussed - Post no exit sign on venue room back door -
Venue room needs rated ceiling tile or drywall on ceiling 2hr or 2 layers 5/8" type
x back rooms also w/openings in ceiling/floor assy - Remove all extension cords &
put covers on open boxes install grab bars in ADA - ADA restroom bathroom sign
Inspector Comments:
01/18/2011FailJohn BerryCommercial Building Final
Install "max occupancy"
99 sign in open area
Inspector Comments:
Electrical
07/14/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover in newly framed wallsInspector Comments:
09/08/2010FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
GFCI protect fridge and range shrink trim breaker for range verify lights for show
case lighting wall mount only
Inspector Comments:
09/09/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and COInspector Comments:
Mechanical
08/10/2010FailJohn BerryHVAC Rough-in
Rough hood installation and exhaust duct looks good clearance OK Exhaust duct
in apt has pin holes in welding that need to be redone Insp reqd for duct welding
before covering
Inspector Comments:
09/10/2010PassJohn BerryHVAC Final Inspection
approved for final and COInspector Comments:
Plumbing
09/08/2010PassBrad JohnsonPlumbing Final Inspection
ApprovedInspector Comments: