Permit Status of (Open) as of Report Date: 06/16/2020 8:56 am
Permit Details Permit Number: 10-00255
Northgate Apts Bldg #3 - Units 301-308
350 W 6th S
New Multi-Family Residence
Permit Issued Date:
Permit Inspection Statistics
17Total Inspections Completed:
14Total Inspections Passed:
Inspection Pass Rate: 82.35%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
07/15/2010PassTed DyeCommercial Footing Inspection
07/22/2010PassQuinton OwensCommercial Footing Inspection
OK to pourInspector Comments:
08/05/2010PassJohn BerryCommercial Footing Inspection
Interior Footings Look GoodInspector Comments:
09/07/2010FailQuinton OwensCommercial Framing/Structure Inspection
Dryer vent separated above outside storage room. (2nd unit from west end)
Furred out wall on main floor behind tub not completely sealed off.
Separate attic spaces above storage room. OK to insulate.
Inspector Comments:
09/09/2010FailQuinton OwensCommercial Insulation Inspection
Insulation rulers not installed for attic insulation
Soffit vents blocked
Some units ony have 1 soffit vent (2 min required)
Inspector Comments:
09/10/2010PassQuinton OwensCommercial Insulation Inspection
Insulation OK to cover.
All units.
*Patch holes in draft stop. OK.
Inspector Comments:
09/10/2010PassQuinton OwensCommercial Framing/Structure Inspection
2 West units, main floor, furred out wall behind tub. -small joist cavity at top not
closed off. (OK 9/13)
OK to insulate
South units completed.
Inspector Comments:
09/14/2010PassQuinton OwensCommercial Sheetrock/Drywall Inspection
North Units Complete 9/16Inspector Comments:
09/15/2010PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Completed 9/20Inspector Comments:
Page 1 of 2
(Continued)
Permit Details Permit Number: 10-00255
Northgate Apts Bldg #3 - Units 301-308
350 W 6th S
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 06/16/2020 8:56 am
Permit
Inspection
Summary
11/03/2010FailQuinton OwensCommercial Building Final
302 Patch Ceiling at fire sprinkler (north side upstairs bth)
301 Patch Ceiling at bath fan (north side upstairs bth)
305 Smoke detector interconnection problem (north side 2nd unit from west end)
sidewalks not finished
Firecaulk not used at water lines at water heater
302 Gas leak in mech room south east end unit
Firecaulking at drain lines penetrating fire barrier
Inspector Comments:
Electrical
09/07/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover on South side.Inspector Comments:
09/08/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover - doghouse & north side
*Service Approved to be energized.
Inspector Comments:
11/05/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final & C.O. Except doghouseInspector Comments:
12/03/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final doghouseInspector Comments:
Mechanical
09/03/2010PassQuinton OwensHVAC Rough-in
Mech. rough-in OKInspector Comments:
Plumbing
08/03/2010PassBrad JohnsonPlumbing Underground Inspection
Approved for cover.Inspector Comments:
10/26/2010PassBrad JohnsonPlumbing Final Inspection
Approved for plumbing final!Inspector Comments: