HomeMy WebLinkAboutINSPECTION SUMMARY - 10-00257 - Northgate Apts Bldg #5 - 501-508Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/16/2020 8:53 am
Permit Details Permit Number: 10-00257
Northgate Apts Bldg #5 - 501-508
350 W 6th S
New Multi-Family Residence
Permit Issued Date:
Permit Inspection Statistics
20Total Inspections Completed:
15Total Inspections Passed:
Inspection Pass Rate: 75.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
07/12/2010PassJohn BerryCommercial Footing Inspection
Footing & rebar look goodInspector Comments:
07/14/2010PassTed DyeFoundation Inspection
2 horizontal barsInspector Comments:
07/23/2010PassJohn BerryCommercial Footing Inspection
Floor & pier footings look goodInspector Comments:
08/16/2010PassJohn BerryCommercial Insulation Inspection
Insulation looks goodInspector Comments:
08/16/2010PassJohn BerryCommercial Sheetrock/Drywall Inspection
Insulation looks goodInspector Comments:
08/19/2010FailJohn BerryCommercial Framing/Structure Inspection
-Drywall missing stud backing need dryer vent - as per architect's letter blocking
req'd in staggered sep. wall - gables & overhang sheeting req's nailing - fire caulk
penetrations in chase between units - anchor bolts req'd bearing walls -
upperantry straps missing
Inspector Comments:
08/24/2010FailJohn BerryCommercial Framing/Structure Inspection
Re-Install missing studs in staggered wall both floors Insulation west side looks
good
Inspector Comments:
08/24/2010FailJohn BerryCommercial Framing/Structure Inspection
-HD5's missing - Anchor bolts in bearing walls missing - Gable areas not nailed
per plans
Inspector Comments:
08/26/2010PassJohn BerryCommercial Sheetrock/Drywall Inspection
Drywall looks goodInspector Comments:
10/26/2010FailQuinton OwensCommercial Building Final
Stair handrail in south west unit too low. Finish firecaulking in mech roomsInspector Comments:
10/28/2010PassQuinton OwensCommercial Building Final
bldg Final OKInspector Comments:
Page 1 of 2
(Continued)
Permit Details Permit Number: 10-00257
Northgate Apts Bldg #5 - 501-508
350 W 6th S
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 06/16/2020 8:53 am
Permit
Inspection
Summary
Electrical
08/23/2010PassBret StoddardCommercial Electrical Rough-in
Approved for cover in building #5Inspector Comments:
08/23/2010PassBret StoddardCOM & MFR Electrical Service Inspection
*Service(x2)Approved to be energized for perm powerInspector Comments:
10/22/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final & CO 8 units - Not Doghouse - Not doneInspector Comments:
12/03/2010PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final - doghouseInspector Comments:
Fire
08/23/2010PassBrad JohnsonFire Sprinkler Final Inspection
Sprinkler piping tested @200 psi for 2 hrs approved for coverInspector Comments:
Mechanical
08/20/2010PassJohn BerryHVAC Rough-in
65# 10am -seal 12" return joints inw - Fire caulk upstairs bath exh fans at box
outlet
Inspector Comments:
10/26/2010FailQuinton OwensHVAC Final Inspection
Sensor broken off at bottom of furnacesInspector Comments:
10/28/2010PassQuinton OwensHVAC Final Inspection
Mechanical Final OKInspector Comments:
Plumbing
08/20/2010PassBrad JohnsonPlumbing Rough-in
all piping tested and inspectedInspector Comments:
Page 2 of 2