Loading...
HomeMy WebLinkAboutLOAD SHORT FORM - 20-00469 - 2313 W 860 S - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Load Short Form 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960603BN Cond GSX130301B AHRI ref 7365096 Coil ARUF30B14A AHRI ref 5383471 Efficiency 96.1 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh60000 Sensible cooling Btuh27000 Heating output Btuh58000 Latent cooling Btuh0 Temperature rise °F70 Total cooling Btuh27000 Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.096 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 374 3055 1634 93 156 Room2 81 543 108 16 10 Room3 189 2337 727 71 70 Room4 231 2811 656 85 63 Room5 64 965 118 29 11 Room6 147 2859 745 87 71 Room7 173 3178 786 96 75 Room9 33 1091 72 33 7 Room10 797 12802 4562 389 436 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N Entire House d 2090 29641 9408 900 900 Other equip loads 11987 973 Equip. @ 0.94 RSM 9759 Latent cooling 0 TOTALS 2090 41628 9759 900 900 2020-Jun-11 13:47:30 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Building Analysis 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F)SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation Humidification % of loadBtuhBtuh/ft²Component 27.1112634.9Walls 14.2591324.3Glazing 1.247911.4Doors 4.619241.5Ceilings 12.552194.14.1Floors 11.648441.9Infiltration 00Ducts00Piping16.16702Humidification12.75284Ventilation0Adjustments100.041628Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 10.410820.5Walls 44.1458018.8Glazing 1.11172.8Doors 10.210630.8Ceilings 000Floors4.34460.2Infiltration 00Ducts9.4973Ventilation20.42120Internal gains 00Blower0Adjustments100.010382Total Latent Cooling Load = 0 BtuhOverall U-value = 0.064 Btuh/ft²-°F Data entries checked. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Component Constructions 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F) SimplifiedMethod)H(34-Daily range (°F) Semi-tightConstruction quality60-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1180.4712284.9421.00.065249n 1810.4718824.9421.00.065381e 1340.4713934.9421.00.065282s 1810.4718824.9421.00.065381w 6130.4763864.9421.00.0651293all Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1220.4712754.9422.00.065258n 1200.4712454.9422.00.065252e 1070.4711124.9422.00.065225s 1200.4712454.9422.00.065252w 4680.4748774.9422.00.065987all Partitions (none) Windows61C: 61C; NFRC rated (SHGC=0.32); 6.67 ft head ht 0.32078n 82710.6190524.30 23810.654724.300.32023n 84918.9109424.300.32045s 183718.9236624.300.32097s 375015.4591324.300.320243all Doors metal: Door, mtl pur core type 1172.7847911.410.50.15042n Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 10630.8419241.5250.00.0201266 Floors22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 00344427.010.00.355128 00177427.010.00.35566 00521927.010.00.355193all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Project Summary 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75Design TD °F76 Design TD °F14Daily range HRelative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh29641 Structure Btuh9408DuctsBtuh0DuctsBtuh0Central vent (75 cfm)5284 Btuh Central vent (75 cfm)Btuh973Outside air Outside airHumidificationBtuh6702Blower Btuh0PipingBtuh0Equipment load Btuh41628 Use manufacturer's data nRate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh9759 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight0Fireplaces Structure Btuh180DuctsBtuh0Central vent (75 cfm)Btuh-1353CoolingHeatingOutside air20902090Area (ft²)Equipment latent load Btuh01880918809Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh9759Equiv. AVF (cfm)3469 Req. total capacity at 1.00 SHR ton0.8 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI...Model GMSS960603BN Cond GSX130301BAHRI ref 7365096 Coil ARUF30B14AAHRI ref 5383471Efficiency96.1 AFUE Efficiency 11.0 EER, 13 SEERHeating input Btuh60000 Sensible cooling Btuh27000Heating output Btuh58000 Latent cooling Btuh0Temperature rise °F70 Total cooling Btuh27000Actual air flow cfm900 Actual air flow cfm900Air flow factor cfm/Btuh0.030 Air flow factor cfm/Btuh0.096Static pressure in H2O0.70 Static pressure in H2O0.70Space thermostat Load sensible heat ratio 1.00 2020-Jun-11 13:47:30 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:AED Assessment 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bulb (°F))H(34-Daily range (°F) 60-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 45.8%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 830 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Right-J® Worksheet 6/11/2020Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Entire House Room1 2 Exposed wall 285.0 ft 29.3 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft374.4x1.0 5 Room area 2089.9 ft²374.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 327 249 1228 118 0 0 0 0.GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 78 0 1905 827 0 0 0 0.WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 323 258 1275 122 0 0 0 0 .GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 23 0 547 238 0 0 0 0 11 DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 42 42 479 117 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 381 381 1882 181 143 143 704 68 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 252 252 1245 120 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 327 282 1393 134 122 93 460 44 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 45 0 1094 849 28 0 689 535WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 323 225 1112 107 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 97 0 2366 1837 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 381 381 1882 181 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 252 252 1245 120 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1266 1266 1924 1063 374 374 569 315FF22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 830 128 3444 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 438 66 1774 0 63 5 134 0 6 c) AED excursion 830 167 Envelope loss/gain 24797 6842 2556 1128 12 a)Infiltration 4844 446 499 46 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 2 460 Appliances/other 1200 0 Subtotal (lines 6 to 13)29641 9408 3055 1634 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal29641940830551634 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 29641 9408 3055 1634 Air required (cfm)Air required (cfm)900 900 93 156 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Right-J® Worksheet 6/11/2020Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room2 Room3 2 Exposed wall 6.8 ft 27.8 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft11.8x6.8 ft11.8x16.0 5 Room area 80.9 ft²189.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0.WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 11 DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 62 62 304 29 144 127 629 60 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 17 0 405 315WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 107 107 526 51WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 81 81 123 68 189 189 288 159FF22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 4 1 16 0 6 c) AED excursion 0 99 Envelope loss/gain 427 97 1864 684 12 a)Infiltration 116 11 473 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)543 108 2337 727 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal5431082337727 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 543 108 2337 727 Air required (cfm)Air required (cfm)16 10 71 70 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 3S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Right-J® Worksheet 6/11/2020Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room4 Room5 2 Exposed wall 30.5 ft 11.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft16.3x14.2 ft11.0x5.8 5 Room area 231.4 ft²64.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 128 99 490 47 0 0 0 0.GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 28 0 689 299 0 0 0 0.WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 11 DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 99 99 489 47 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 147 147 726 70 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 231 231 352 194 64 64 98 54FF22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 10 1 36 0 42 7 192 0 6 c) AED excursion -2 0 Envelope loss/gain 2293 609 779 101 12 a)Infiltration 518 48 187 17 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2811 656 965 118 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal2811656965118 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2811 656 965 118 Air required (cfm)Air required (cfm)85 63 29 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 4S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Right-J® Worksheet 6/11/2020Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room6 Room7 2 Exposed wall 24.3 ft 27.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.3x11.0 ft15.5x11.2 5 Room area 146.7 ft²173.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 99 74 366 35 101 76 373 36.GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 25 0 608 264 25 0 608 264.WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0 11 DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 120 120 593 57 20 20 96 9 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 128 128 630 60WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 147 147 223 123 173 173 263 145FF22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 147 24 657 0 173 27 741 0 6 c) AED excursion -2 -2 Envelope loss/gain 2446 477 2711 513 12 a)Infiltration 414 38 467 43 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)2859 745 3178 786 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal28597453178786 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2859 745 3178 786 Air required (cfm)Air required (cfm)87 71 96 75 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jun-11 13:47:30Right-Suite® Universal 2019 19.0.13 RSU20477 Page 5S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Right-J® Worksheet 6/11/2020Date:Entire House Vince ByramBy:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room9 Room10 2 Exposed wall 12.3 ft 115.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x3.8 ft797.4x1.0 5 Room area 32.6 ft²797.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0.GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 0 0 0 0.WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 35 35 170 16 288 224 1104 106 .GG 61C61C 0.3200.320 nn 24.3224.32 10.5610.56 0 0 0 0 23 0 547 238 11 DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 42 42 479 117 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 252 252 1245 120WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 323 225 1112 107 GG 61C61C 0.3200.320 ss 24.3224.32 18.8818.88 0 0 0 0 97 0 2366 1837WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0WWFrm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 77 77 378 36 176 176 867 83 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 6 6 9 5FF22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 33 12 333 0 797 115 3112 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 0 570 Envelope loss/gain 881 52 10842 3182 12 a)Infiltration 210 19 1960 181 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13)1091 72 12802 4562 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal109172128024562 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1091 72 12802 4562 Air required (cfm)Air required (cfm)33 7 389 436 Job #: SF12B7 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 71 Page 1 Right-Suite® Universa l 2019 19.0.13 RSU20477 2020-Jun-11 13:47:47 ...Wrightsoft\SF12B7 ROCKFORD A.rup N main Room9 Room10 87 cfm 356 cfm 87 cfm 33 cfm 87 cfm87 cfm 87 cfm Job #: SF12B7 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 71 Page 2 Right-Suite® Universal 2019 19.0.13 RSU20477 2020-Jun-11 13:47:47 ...Wrightsoft\SF12B7 ROCKFORD A.rup N 2nd story Room1 Room2 Room3 Room4 Room5 Room6 Room7 Room8 6" mechanical fresh damper 116 cfm 87 cfm 156 cfm 16 cfm 71 cfm 85 cfm 29 cfm 96 cfm 254 cfm 96 cfm 156 cfm 12 x 8 12 x 8 14x3.25 6 " 12 x 8 2-14x3.25 6 " 6 " 6 "6 " 6 "6 " 6 " 6 " 6 " 12 x 8 6 " 12 x 8 14x3.25 12 x 8 12 x 8 6 " 14x3.25 6 " 14x3.25 12 x 8 2020-Jun-11 13:47:31 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 1 S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N SF12B7Job:Duct System Summary 6/11/2020Date:Entire House Vince ByramBy: Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.306 / 0.394 in H2O in H2O0.306 / 0.394 Lowest friction rate in/100ft0.155in/100ft0.155 Actual air flow cfm900cfm900 Total effective length (TEL)ft452 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2130.035.5ShMt0x06.00.185156931634cRoom1 st2165.026.0ShMt0x06.00.1608778912cRoom10 st1140.031.8ShMt0x06.00.1788778912cRoom10-A st2A160.037.5ShMt0x06.00.1558778912cRoom10-B st1150.07.8ShMt0x06.00.1948778912cRoom10-C st2140.014.8ShMt0x06.00.1988778912cRoom10-D st2150.022.3ShMt0x06.00.1781016543hRoom2 st1A160.030.5ShMt0x06.00.16170712337hRoom3 st1A150.016.3ShMt0x06.00.18463852811hRoom4 st2B170.018.5ShMt0x06.00.1621129965hRoom5 st2A150.028.7ShMt0x06.00.17171872859hRoom6-A st2160.020.0ShMt0x06.00.17075963178hRoom7 st1130.014.3ShMt0x06.00.2127331091hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 555 586 0.155 879 10.3 12x8 ShtMetl st2A Peak AVF 194 170 0.155 291 6.8 12x8 ShtMetl st2 st1 Peak AVF 345 314 0.161 517 8.4 12x8 ShtMetl st1A Peak AVF 156 132 0.161 234 6.3 12x8 ShtMetl st1 st2B Peak AVF 29 11 0.162 44 3.3 12x8 ShtMetl st2A 2020-Jun-11 13:47:31 Right-Suite® Universal 2019 19.0.13 RSU20477 Page 2 S:\High Country\Wrightsoft\SF12B7 ROCKFORD A.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 1560 132 90.2 0.437 495 5.1 3.25x14 10x9 SJSp rt1 rb5 0x 3440 356 190.0 0.207 563 8.1 2-3.25x14 2-10x18 SJSp rt1 rb1 0x 1870 254 148.7 0.265 804 6.8 3.25x14 10x9 SJSp rt2 rb2 0x 960 75 184.8 0.213 305 4.9 3.25x14 10x9 SJSp rt2A rb4 0x 1160 83 254.2 0.155 368 5.6 3.25x14 10x9 SJSp rt2A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 500 488 0.207 751 9.2 12x8 ShtMetl rt2 Peak AVF 400 412 0.155 617 9.0 12x8 ShtMetl rt2A Peak AVF 213 158 0.155 319 7.1 12x8 ShtMetl rt2