HomeMy WebLinkAboutLOAD SHORT FORM - 20-00400 - 651 S 2400 W Units 5101-5103 - Summerfield Townhome - 3 UnitsCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Load Short Form 5/5/2020Date:Entire House Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) AH b 1444 14163 10458 565 767 AH A 1478 20335 11034 565 765 AH C 1478 20659 11051 565 776 Entire House 4401 55157 32543 1695 2308 Other equip loads 9993 1902 Equip. @ 0.95 RSM 32585 Latent cooling 691 TOTALS 4401 65150 33276 1695 2308 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Load Short Form 5/5/2020Date:AH A Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA2 Cond N4A318GKF10 AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9707779 Efficiency 96 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh16589 Heating output Btuh31590 Latent cooling Btuh0 Temperature rise °F61 Total cooling Btuh16589 Actual air flow cfm565 Actual air flow cfm765 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.069 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Pwdr 30 374 29 10 2 Kit/din/family 488 7670 3992 213 277 Water softner 23 0 0 0 0 M WIC 64 1111 598 31 41 Master 210 3075 1984 85 138 M Bath 74 566 111 16 8 Room7 59 957 128 27 9 Utility 52 147 542 4 38 Mech 22 0 0 0 0 Bedroom 2 149 2334 1754 65 122 Bedroom 3 167 4101 1898 114 132 Stairs/hall 142 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E AH A 1478 20335 11034 565 765 Other equip loads 2895 551 Equip. @ 0.95 RSM 10960 Latent cooling 0 TOTALS 1478 23231 10960 565 765 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Load Short Form 5/5/2020Date:AH b Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA2 Cond N4A318GKF10 AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9707779 Efficiency 96 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh16589 Heating output Btuh31590 Latent cooling Btuh0 Temperature rise °F61 Total cooling Btuh16589 Actual air flow cfm565 Actual air flow cfm767 Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.073 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech B 22 0 0 0 0 Bedroom 3 B 156 2660 1756 106 129 Stairs/Hall B 142 0 0 0 0 Bath B 59 107 54 4 4 Utility B 52 147 540 6 40 Bedroom 2 B 149 2621 1770 105 130 Kit/din/Family B 488 5284 3805 211 279 M WIC B 51 819 562 33 41 Master B 199 2012 1871 80 137 M Bath B 74 139 71 6 5 W S B 23 0 0 0 0 Pwdr B 30 374 28 15 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E AH b 1444 14163 10458 565 767 Other equip loads 4202 800 Equip. @ 0.95 RSM 10650 Latent cooling 0 TOTALS 1444 18365 10650 565 767 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Load Short Form 5/5/2020Date:AH C Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA2 Cond N4A318GKF10 AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9707779 Efficiency 96 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh16589 Heating output Btuh31590 Latent cooling Btuh0 Temperature rise °F61 Total cooling Btuh16589 Actual air flow cfm565 Actual air flow cfm776 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.070 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech C 22 0 0 0 0 Stairs/Hall C 142 0 0 0 0 Utility C 52 514 574 14 40 Bedroom 2 C 149 4679 1951 128 137 Bedroom 3 C 167 2789 1783 76 125 Pwdr C 30 1233 94 34 7 M WIC C 64 1868 665 51 47 Master C 210 2290 1910 63 134 M Bath C 74 279 83 8 6 Bath C 59 195 62 5 4 Kit/din/Fam C 488 6811 3926 186 276 WS C 23 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E AH C 1478 20659 11051 565 776 Other equip loads 2895 551 Equip. @ 0.95 RSM 10975 Latent cooling 0 TOTALS 1478 23554 10975 565 776 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Building Analysis 5/5/2020Date:Entire House Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 24.5159365.0Walls 12.0781226.8Glazing 5.8376929.9Doors 6.642861.5Ceilings 8.152461.91.9Floors 20.1130993.6Infiltration 7.75008Ducts00Piping00Humidification15.39993Ventilation0Adjustments100.065150Total Cooling Walls Glazing Doors CeilingsOtherInfiltrationDucts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 4.515380.5Walls 40.41392847.9Glazing 2.79147.3Doors 6.823530.8Ceilings 0.2590.0Floors 3.913360.4Infiltration 6.32156Ducts5.51902Ventilation29.810260Internal gains 00Blower0Adjustments100.034445Total Latent Cooling Load = 691 BtuhOverall U-value = 0.052 Btuh/ft²-°F Data entries checked. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Building Analysis 5/5/2020Date:AH A Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 27.764305.0Walls 11.2260426.8Glazing 5.4125629.9Doors 6.214381.5Ceilings 8.118932.02.0Floors 22.351793.6Infiltration 6.61534Ducts00Piping00Humidification12.52895Ventilation0Adjustments100.023231Total Cooling Walls Glazing Doors CeilingsOtherInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 5.46200.5Walls 40.1464347.9Glazing 2.63057.3Doors 6.87890.8Ceilings 0.2200.0Floors 4.65280.4Infiltration 6.1709Ducts4.8551Ventilation29.53420Internal gains 00Blower0Adjustments100.011586Total Latent Cooling Load = 0 BtuhOverall U-value = 0.054 Btuh/ft²-°F Data entries checked. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Building Analysis 5/5/2020Date:AH b Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 16.730765.0Walls 14.2260426.8Glazing 6.8125629.9Doors 7.714091.5Ceilings 7.513771.51.5Floors 14.927413.6Infiltration 9.31700Ducts00Piping00Humidification22.94202Ventilation0Adjustments100.018365Total Cooling Walls Glazing Doors CeilingsOtherInfiltrationDucts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 2.62970.5Walls 41.2464347.9Glazing 2.73057.3Doors 6.97740.8Ceilings 0.2190.0Floors 2.52790.4Infiltration 6.4722Ducts7.1800Ventilation30.43420Internal gains 00Blower0Adjustments100.011258Total Latent Cooling Load = 0 BtuhOverall U-value = 0.049 Btuh/ft²-°F Data entries checked. 2020-May-05 19:04:16 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Building Analysis 5/5/2020Date:AH C Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 27.364305.0Walls 11.1260426.8Glazing 5.3125629.9Doors 6.114381.5Ceilings 8.419762.12.1Floors 22.051793.6Infiltration 7.51775Ducts00Piping00Humidification12.32895Ventilation0Adjustments100.023554Total Cooling Walls Glazing Doors CeilingsOtherInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 5.36200.5Walls 40.0464347.9Glazing 2.63057.3Doors 6.87890.8Ceilings 0.2200.0Floors 4.65280.4Infiltration 6.3726Ducts4.8551Ventilation29.53420Internal gains 00Blower0Adjustments100.011602Total Latent Cooling Load = 0 BtuhOverall U-value = 0.054 Btuh/ft²-°F Data entries checked. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Component Constructions 5/5/2020Date:Entire House Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3240.4833544.9921.00.065673n 4210.4843674.9921.00.065876e 3240.4833544.9921.00.065673s 4690.4848614.9921.00.065975w 15380.48159364.9921.00.0653197all Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35: 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35; foreground = new concrete (0.32); 6.67 ft head ht 933347.9523526.800.350195e 459547.9257726.800.35096w 1392847.9781226.800.350291all Doors11D0: Door, wd sc type 4577.25188529.900.39063e 4577.25188529.900.39063w 9147.25376929.900.390126all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 23530.8442861.5350.00.0202794 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, gar ovr 590.0621512.3038.00.030935 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 00285916.110.00.210178 0023616.110.00.21015 00309516.110.00.210192all 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Component Constructions 5/5/2020Date:AH A Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3110.4832194.9921.00.065646n 1400.4814564.9921.00.065292e 130.481354.9921.00.06527s 1560.4816204.9921.00.065325w 6200.4864304.9921.00.0651290all Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35: 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35; foreground = new concrete (0.32); 6.67 ft head ht 311147.9174526.800.35065e 153247.985926.800.35032w 464347.9260426.800.35097all Doors11D0: Door, wd sc type 1527.2562829.900.39021e 1527.2562829.900.39021w 3057.25125629.900.39042all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 7890.8414381.5350.00.020938 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, gar ovr 200.067252.3038.00.030315 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 00109116.110.00.21068 007616.110.00.2105 00116816.110.00.21072all 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Component Constructions 5/5/2020Date:AH b Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1400.4814564.9921.00.065292e 1560.4816204.9921.00.065325w 2970.4830764.9921.00.065617all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35: 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35; foreground = new concrete (0.32); 6.67 ft head ht 311147.9174526.800.35065e 153247.985926.800.35032w 464347.9260426.800.35097all Doors11D0: Door, wd sc type 1527.2562829.900.39021e 1527.2562829.900.39021w 3057.25125629.900.39042all Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 7740.8414091.5350.00.020919 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, gar ovr 190.067012.3038.00.030305 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 0067616.110.00.21042 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Component Constructions 5/5/2020Date:AH C Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 130.481354.9921.00.06527n 1400.4814564.9921.00.065292e 3110.4832194.9921.00.065646s 1560.4816204.9921.00.065325w 6200.4864304.9921.00.0651290all Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35: 2 glazing, clr low-e outr, argon gas, insulated vinyl frm mat, clr innr, 1/2" gap, 1/8" thk, SHGC .35; foreground = new concrete (0.32); 6.67 ft head ht 311147.9174526.800.35065e 153247.985926.800.35032w 464347.9260426.800.35097all Doors11D0: Door, wd sc type 1527.2562829.900.39021e 1527.2562829.900.39021w 3057.25125629.900.39042all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 7890.8414381.5350.00.020938 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, gar ovr 200.067252.3038.00.030315 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 00109116.110.00.21068 0016016.110.00.21010 00125116.110.00.21078all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Project Summary 5/5/2020Date:Entire House Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh50149 Structure Btuh30386DuctsBtuh5008DuctsBtuh2156Central vent (141 cfm)9993 Btuh Central vent (141 cfm)Btuh1902 Humidification Btuh0 Blower Btuh0PipingBtuh0Equipment load Btuh65150 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh32585 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh739DuctsBtuh-48Central vent (141 cfm)Btuh-2365CoolingHeating44014401Area (ft²)Equipment latent load Btuh6913960539605Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh33276Equiv. AVF (cfm)99185 Req. total capacity at 0.70 SHR ton3.9 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/aModeln/a Cond n/aAHRI ref n/a Coil n/aAHRI ref n/aEfficiencyn/a Efficiency n/aHeating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Project Summary 5/5/2020Date:AH A Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18801 Structure Btuh10325DuctsBtuh1534DuctsBtuh709Central vent (41 cfm)2895 Btuh Central vent (41 cfm)Btuh551Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh23231 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh10960 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh143DuctsBtuh-15Central vent (41 cfm)Btuh-685CoolingHeatingOutside air14781478Area (ft²)Equipment latent load Btuh01330513305Volume (ft³)Air changes/hour 0.180.33 Equipment Total Load (Sen+Lat)Btuh10960Equiv. AVF (cfm)3973 Req. total capacity at 1.00 SHR ton0.9 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A ACModelN95ESN0401410AA2CondN4A318GKF10AHRI ref 4705245 Coil END4X24L14A1++TDRAHRI ref 9707779Efficiency96 AFUE Efficiency 11.0 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh16589Heating output Btuh31590 Latent cooling Btuh0Temperature rise °F61 Total cooling Btuh16589Actual air flow cfm565 Actual air flow cfm765Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.069Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Project Summary 5/5/2020Date:AH b Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh12463 Structure Btuh9736DuctsBtuh1700DuctsBtuh722Central vent (59 cfm)4202 Btuh Central vent (59 cfm)Btuh800Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh18365 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh10650 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh453DuctsBtuh-19Central vent (59 cfm)Btuh-994CoolingHeatingOutside air14441444Area (ft²)Equipment latent load Btuh01299412994Volume (ft³)Air changes/hour 0.100.18 Equipment Total Load (Sen+Lat)Btuh10650Equiv. AVF (cfm)2139 Req. total capacity at 1.00 SHR ton0.9 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A ACModelN95ESN0401410AA2CondN4A318GKF10AHRI ref 4705245 Coil END4X24L14A1++TDRAHRI ref 9707779Efficiency96 AFUE Efficiency 11.0 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh16589Heating output Btuh31590 Latent cooling Btuh0Temperature rise °F61 Total cooling Btuh16589Actual air flow cfm565 Actual air flow cfm767Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.073Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Project Summary 5/5/2020Date:AH C Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18884 Structure Btuh10325DuctsBtuh1775DuctsBtuh726Central vent (41 cfm)2895 Btuh Central vent (41 cfm)Btuh551Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh23554 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh10975 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh143DuctsBtuh-15Central vent (41 cfm)Btuh-685CoolingHeatingOutside air14781478Area (ft²)Equipment latent load Btuh01330513305Volume (ft³)Air changes/hour 0.180.33 Equipment Total Load (Sen+Lat)Btuh10975Equiv. AVF (cfm)3973 Req. total capacity at 1.00 SHR ton0.9 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A ACModelN95ESN0401410AA2CondN4A318GKF10AHRI ref 4705245 Coil END4X24L14A1++TDRAHRI ref 9707779Efficiency96 AFUE Efficiency 11.0 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh16589Heating output Btuh31590 Latent cooling Btuh0Temperature rise °F61 Total cooling Btuh16589Actual air flow cfm565 Actual air flow cfm776Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.070Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:Entire House Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Entire House AH b 2 Exposed wall 401.4 ft 84.0 ft3Room height 9.0 ft 9.0 ft 4 Room dimensions 5 Room area 4400.5 ft²1443.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 673 673 3354 324 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 1134 876 4367 421 378 292 1456 140.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 195 0 5235 9333 65 0 1745 3111 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 63 63 1885 457 21 21 628 152 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 673 673 3354 324 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 1134 975 4861 469 378 325 1620 156 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 96 0 2577 4595 32 0 859 1532DD11D011D00.3900.390 ww 29.9129.91 7.257.25 63 63 1885 457 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 2794 2794 4286 2353 919 919 1409 774FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 935 935 2151 59 305 305 701 19 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 1622 178 2859 0 541 42 676 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 237 15 236 0 74 0 0 0 6 c) AED excursion 0 0 Envelope loss/gain 37050 18791 9723 6037 12 a)Infiltration 13099 1336 2741 279 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 12 2760 4 920 Appliances/other 7500 2500 Subtotal (lines 6 to 13)50149 30386 12463 9736 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal5014930386124639736 15 Duct loads 10%7%5008 2156 14%7%1700 722 Total room load 55157 32543 14163 10458 Air required (cfm)Air required (cfm)1695 2308 565 767 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:Entire House Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH A AH C 2 Exposed wall 158.7 ft 158.8 ft3Room height 9.0 ft 9.0 ft 4 Room dimensions 5 Room area 1478.4 ft²1478.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 646 646 3219 311 27 27 135 13.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 378 292 1456 140 378 292 1456 140.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 65 0 1745 3111 65 0 1745 3111 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 21 21 628 152 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 27 27 135 13 646 646 3219 311 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 378 325 1620 156 378 325 1620 156 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 32 0 859 1532 32 0 859 1532DD11D011D00.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 938 938 1438 789 938 938 1438 789FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 315 315 725 20 315 315 725 20 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 541 68 1091 0 541 68 1091 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 82 5 76 0 82 10 160 0 6 c) AED excursion 0 0 Envelope loss/gain 13622 6377 13705 6377 12 a)Infiltration 5179 528 5179 528 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 4 920 Appliances/other 2500 2500 Subtotal (lines 6 to 13)18801 10325 18884 10325 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal18801103251888410325 15 Duct loads 8%7%1534 709 9%7%1775 726 Total room load 20335 11034 20659 11051 Air required (cfm)Air required (cfm)565 765 565 776 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH A Pwdr 2 Exposed wall 158.7 ft 4.0 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft4.0x7.5 5 Room area 1478.4 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 646 646 3219 311 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 378 292 1456 140 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 65 0 1745 3111 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 27 27 135 13 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 378 325 1620 156 36 36 179 17 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 32 0 859 1532 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 938 938 1438 789 0 0 0 0FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 315 315 725 20 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 541 68 1091 0 30 4 64 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 82 5 76 0 0 0 0 0 6 c) AED excursion 0 -2 Envelope loss/gain 13622 6377 244 15 12 a)Infiltration 5179 528 131 13 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 2500 0 Subtotal (lines 6 to 13)18801 10325 374 29 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal188011032537429 15 Duct loads 8%7%1534 709 -0%0%0 0 Total room load 20335 11034 374 29 Air required (cfm)Air required (cfm)565 765 10 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Kit/din/family Water softner 2 Exposed wall 63.8 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft487.8x1.0 ft4.0x5.8 5 Room area 487.8 ft²23.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 232 232 1155 111 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 189 138 688 66 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 30 0 805 1436 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 153 132 658 63 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 488 64 1027 0 23 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -202 0 Envelope loss/gain 5590 1780 0 0 12 a)Infiltration 2080 212 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 2000 0 Subtotal (lines 6 to 13)7670 3992 0 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal7670399200 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 7670 3992 0 0 Air required (cfm)Air required (cfm)213 277 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M WIC Master 2 Exposed wall 9.8 ft 27.9 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft63.8x1.0 ft209.8x1.0 5 Room area 63.8 ft²209.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 11 11 56 5 122 122 606 58.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 59 49 242 23 131 106 526 51.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 10 0 268 479 25 0 671 1197 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 18 18 90 9 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 64 64 98 54 210 210 322 177FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 8 1 20 0 0 0 0 0 6 c) AED excursion -14 -71 Envelope loss/gain 774 556 2125 1412 12 a)Infiltration 318 32 914 93 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)1092 588 3038 1965 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution189371914Subtotal111159830751984 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1111 598 3075 1984 Air required (cfm)Air required (cfm)31 41 85 138 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M Bath Room7 2 Exposed wall 5.5 ft 10.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x5.5 ft5.8x10.3 5 Room area 74.3 ft²58.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 50 50 247 24 92 92 460 44.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 74 74 114 63 59 59 90 50FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 20 4 56 0 6 c) AED excursion -7 -9 Envelope loss/gain 361 79 607 85 12 a)Infiltration 179 18 334 34 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)540 98 941 120 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution251316814Subtotal566111957128 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 566 111 957 128 Air required (cfm)Air required (cfm)16 8 27 9 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Utility Mech 2 Exposed wall 0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft7.8x6.8 ft3.8x5.8 5 Room area 52.3 ft²21.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 52 52 80 44 22 22 33 18FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 13 0 0 0 6 c) AED excursion -36 -1 Envelope loss/gain 80 8 33 17 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)80 508 33 17 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution6734-33 -1714Subtotal14754200 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 147 542 0 0 Air required (cfm)Air required (cfm)4 38 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 8...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 2 Bedroom 3 2 Exposed wall 10.3 ft 27.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.3x14.5 ft10.8x15.5 5 Room area 148.6 ft²166.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 140 140 695 67.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 9 9 45 4 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 92 76 380 37 97 81 403 39 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 16 0 430 766 16 0 430 766DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 149 149 228 125 167 167 256 140FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 149 149 342 9 167 167 383 10 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 180 170 Envelope loss/gain 1380 1117 2211 1197 12 a)Infiltration 334 34 889 91 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)1714 1381 3101 1518 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution6332231214Subtotal1777141331241530 15 Duct loads 31%24%556 341 31%24%978 369 Total room load 2334 1754 4101 1898 Air required (cfm)Air required (cfm)65 122 114 132 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 9...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH A Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Stairs/hall 2 Exposed wall 0 ft3Room height 9.0 heat/coolft 4 Room dimensions ft141.7x1.0 5 Room area 141.7 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.99 0.48 0 0 0 0.W 12F-0sw 0.065 e 4.99 0.48 0 0 0 0.G 2 glazing, clr low-e 0.350 e 26.84 47.86 0 0 0 0 .D 11D0 0.390 e 29.91 7.25 0 0 0 0 11 W 12F-0sw 0.065 s 4.99 0.48 0 0 0 0 W 12F-0sw 0.065 w 4.99 0.48 0 0 0 0 G 2 glazing, clr low-e 0.350 w 26.84 47.86 0 0 0 0D11D00.390 w 29.91 7.25 0 0 0 0 C 16B-50ad 0.020 -1.53 0.84 142 142 217 119F20P-38v 0.030 -2.30 0.06 0 0 0 0 F 22B-10vpl 0.210 -16.11 0.00 0 0 0 0F22B-10vpl 0.210 -16.11 0.00 40 0 0 0 6 c) AED excursion -8 Envelope loss/gain 217 111 12 a)Infiltration 0 0 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)217 111 Less external load 0 0 Less transfer 0 0Redistribution-217 -11114Subtotal00 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 10...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH b Mech B 2 Exposed wall 84.0 ft 0 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft3.8x5.8 5 Room area 1443.8 ft²21.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 378 292 1456 140 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 65 0 1745 3111 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 378 325 1620 156 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 32 0 859 1532 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 919 919 1409 774 22 22 33 18FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 305 305 701 19 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 541 42 676 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 74 0 0 0 13 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 9723 6037 33 17 12 a)Infiltration 2741 279 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 2500 0 Subtotal (lines 6 to 13)12463 9736 33 17 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00-33 -1714Subtotal12463973600 15 Duct loads 14%7%1700 722 -0%0%0 0 Total room load 14163 10458 0 0 Air required (cfm)Air required (cfm)565 767 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 11...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 3 B Stairs/Hall B 2 Exposed wall 10.8 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.8x14.5 ft141.7x1.0 5 Room area 155.9 ft²141.7 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 97 81 403 39 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 16 0 430 766 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 156 156 239 131 142 142 217 119FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 156 156 359 10 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 40 0 0 0 6 c) AED excursion 174 -8 Envelope loss/gain 1430 1119 217 111 12 a)Infiltration 351 36 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1781 1385 217 111 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution2312-217 -11114Subtotal1804139700 15 Duct loads 47%26%856 359 -0%0%0 0 Total room load 2660 1756 0 0 Air required (cfm)Air required (cfm)106 129 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 12...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bath B Utility B 2 Exposed wall 0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.8x10.3 ft7.8x6.8 5 Room area 58.9 ft²52.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 59 59 90 50 52 52 80 44FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 20 0 0 0 0 0 0 0 6 c) AED excursion -4 -38 Envelope loss/gain 90 46 80 6 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)90 46 80 506 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution168673414Subtotal10754147540 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 107 54 147 540 Air required (cfm)Air required (cfm)4 4 6 40 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 13...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 2 B Kit/din/Family B 2 Exposed wall 10.3 ft 38.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.3x14.5 ft487.8x1.0 5 Room area 148.6 ft²487.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 189 138 688 66.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 30 0 805 1436 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 92 76 380 37 153 132 658 63 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 16 0 430 766 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 149 149 228 125 16 16 24 13FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 149 149 342 9 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 488 38 612 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 174 -205 Envelope loss/gain 1380 1111 4044 1679 12 a)Infiltration 334 34 1240 126 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 2000 Subtotal (lines 6 to 13)1714 1375 5284 3805 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution63320014Subtotal1777140852843805 15 Duct loads 47%26%844 362 -0%0%0 0 Total room load 2621 1770 5284 3805 Air required (cfm)Air required (cfm)105 130 211 279 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 14...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M WIC B Master B 2 Exposed wall 6.5 ft 14.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft50.8x1.0 ft198.9x1.0 5 Room area 50.8 ft²198.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 59 49 242 23 131 106 526 51.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 10 0 268 479 25 0 671 1197 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 51 51 78 43 199 199 305 168FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -14 -71 Envelope loss/gain 588 531 1502 1344 12 a)Infiltration 212 22 473 48 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)800 552 1975 1852 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution189371914Subtotal81956220121871 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 819 562 2012 1871 Air required (cfm)Air required (cfm)33 41 80 137 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 15...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M Bath B W S B 2 Exposed wall 0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x5.5 ft4.0x5.8 5 Room area 74.3 ft²23.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 74 74 114 63 0 0 0 0FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 23 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -4 0 Envelope loss/gain 114 58 0 0 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)114 58 0 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution25130014Subtotal1397100 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 139 71 0 0 Air required (cfm)Air required (cfm)6 5 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 16...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH b Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Pwdr B 2 Exposed wall 4.0 ft3Room height 9.0 heat/coolft 4 Room dimensions ft4.0x7.5 5 Room area 30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 0.00 0.00 0 0 0 0.W 12F-0sw 0.065 e 4.99 0.48 0 0 0 0.G 2 glazing, clr low-e 0.350 e 26.84 47.86 0 0 0 0 .D 11D0 0.390 e 29.91 7.25 0 0 0 0 11 W 12F-0sw 0.065 s 0.00 0.00 0 0 0 0 W 12F-0sw 0.065 w 4.99 0.48 36 36 179 17 G 2 glazing, clr low-e 0.350 w 26.84 47.86 0 0 0 0D11D00.390 w 29.91 7.25 0 0 0 0 C 16B-50ad 0.020 -1.53 0.84 0 0 0 0F20P-38v 0.030 -2.30 0.06 0 0 0 0 F 22B-10vpl 0.210 -16.11 0.00 30 4 64 0F22B-10vpl 0.210 -0.00 0.00 0 0 0 0 6 c) AED excursion -2 Envelope loss/gain 244 15 12 a)Infiltration 131 13 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)374 28 Less external load 0 0 Less transfer 0 0Redistribution0014Subtotal37428 15 Duct loads -0%0%0 0 Total room load 374 28 Air required (cfm)15 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 17...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH C Mech C 2 Exposed wall 158.8 ft 5.8 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft3.8x5.8 5 Room area 1478.4 ft²21.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 27 27 135 13 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 378 292 1456 140 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 65 0 1745 3111 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 646 646 3219 311 52 52 258 25 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 378 325 1620 156 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 32 0 859 1532 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 938 938 1438 789 22 22 33 18FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 315 315 725 20 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 541 68 1091 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 82 10 160 0 13 4 56 0 6 c) AED excursion 0 -4 Envelope loss/gain 13705 6377 347 39 12 a)Infiltration 5179 528 188 19 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 2500 0 Subtotal (lines 6 to 13)18884 10325 535 58 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00-535 -5814Subtotal188841032500 15 Duct loads 9%7%1775 726 -0%0%0 0 Total room load 20659 11051 0 0 Air required (cfm)Air required (cfm)565 776 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 18...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Stairs/Hall C Utility C 2 Exposed wall 14.5 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft141.7x1.0 ft7.8x6.8 5 Room area 141.7 ft²52.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 131 131 651 63 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 142 142 217 119 52 52 80 44FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 40 4 66 0 0 0 0 0 6 c) AED excursion -15 -36 Envelope loss/gain 934 167 80 8 12 a)Infiltration 473 48 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1407 215 80 508 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-1407 -215 434 6614Subtotal00514574 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 514 574 Air required (cfm)Air required (cfm)0 0 14 40 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 19...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 2 C Bedroom 3 C 2 Exposed wall 24.8 ft 12.8 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.3x14.5 ft10.8x15.5 5 Room area 148.6 ft²166.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 9 9 45 4.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 131 131 651 63 9 9 45 4 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 92 76 380 37 97 81 403 39 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 16 0 430 766 16 0 430 766DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 149 149 228 125 167 167 256 140FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 149 149 342 9 167 167 383 10 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 173 178 Envelope loss/gain 2030 1172 1561 1142 12 a)Infiltration 807 82 416 42 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)2838 1485 1977 1414 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution730881502314Subtotal3567157221271437 15 Duct loads 31%24%1112 379 31%24%663 346 Total room load 4679 1951 2789 1783 Air required (cfm)Air required (cfm)128 137 76 125 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 20...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Pwdr C M WIC C 2 Exposed wall 11.5 ft 18.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x7.5 ft63.8x1.0 5 Room area 30.0 ft²63.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 11 11 56 5.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 59 49 242 23.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 10 0 268 479 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 68 68 337 32 92 92 460 44 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 36 36 179 17 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 64 64 98 54FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 30 12 185 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 8 2 37 0 6 c) AED excursion -6 -18 Envelope loss/gain 701 44 1161 587 12 a)Infiltration 375 38 587 60 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1076 82 1748 647 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution157121201814Subtotal1233941868665 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1233 94 1868 665 Air required (cfm)Air required (cfm)34 7 51 47 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 21...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Master C M Bath C 2 Exposed wall 15.3 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft209.8x1.0 ft13.5x5.5 5 Room area 209.8 ft²74.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 7 7 34 3 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 131 106 526 51 0 0 0 0.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 25 0 671 1197 0 0 0 0 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 210 210 322 177 74 74 114 63FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -64 -4 Envelope loss/gain 1553 1363 114 58 12 a)Infiltration 498 51 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2050 1874 114 58 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution240371652514Subtotal2290191027983 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2290 1910 279 83 Air required (cfm)Air required (cfm)63 134 8 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 22...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bath C Kit/din/Fam C 2 Exposed wall 0 ft 50.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.8x10.3 ft487.8x1.0 5 Room area 58.9 ft²487.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 189 138 688 66.GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ee 26.8426.84 47.8647.86 0 0 0 0 30 0 805 1436 .DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 11 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 113 113 561 54 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 153 132 658 63 GG 2 glazing, clr low-e 0.3502 glazing, clr low-e 0.350 ww 26.8426.84 47.8647.86 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 59 59 90 50 0 0 0 0FF20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 0 0 0 0 488 51 813 0FF22B-10vpl22B-10vpl 0.2100.210 --16.1116.11 0.000.00 20 0 0 0 0 0 0 0 6 c) AED excursion -3 -195 Envelope loss/gain 90 46 4782 1729 12 a)Infiltration 0 0 1648 168 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 2000 Subtotal (lines 6 to 13)90 46 6430 3897 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution105163822914Subtotal1956268113926 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 195 62 6811 3926 Air required (cfm)Air required (cfm)5 4 186 276 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-May-05 19:04:16Right-Suite® Universal 2019 19.0.12 RSU28163 Page 23...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Right-J® Worksheet 5/5/2020Date:AH C Gene MillerBy:Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name WS C 2 Exposed wall 5.8 ft3Room height 9.0 heat/coolft 4 Room dimensions ft4.0x5.8 5 Room area 23.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.99 0.48 0 0 0 0.W 12F-0sw 0.065 e 4.99 0.48 0 0 0 0.G 2 glazing, clr low-e 0.350 e 26.84 47.86 0 0 0 0 .D 11D0 0.390 e 29.91 7.25 0 0 0 0 11 W 12F-0sw 0.065 s 4.99 0.48 52 52 258 25 W 12F-0sw 0.065 w 4.99 0.48 0 0 0 0 G 2 glazing, clr low-e 0.350 w 26.84 47.86 0 0 0 0D11D00.390 w 29.91 7.25 0 0 0 0 C 16B-50ad 0.020 -1.53 0.84 0 0 0 0F20P-38v 0.030 -2.30 0.06 0 0 0 0 F 22B-10vpl 0.210 -16.11 0.00 23 6 93 0F22B-10vpl 0.210 -16.11 0.00 0 0 0 0 6 c) AED excursion -3 Envelope loss/gain 351 22 12 a)Infiltration 188 19 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)538 41 Less external load 0 0 Less transfer 0 0Redistribution-538 -4114Subtotal00 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Job #: Kartchner 3 Plex Performed by Gene Miller for: Sprinter Heating & Hydronics 3846 East 100 North Rigby, ID 83442 Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 1sgmiller@cableone.net Scale: 1 : 104 Page 1 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-May-05 19:05:08 ...home 2\Kartchner townhomes 2.rup N Main Pwdr Kit/din/family Water softner Kit/din/Family B W S B Pwdr B Kit/din/Fam C WS C Pwdr C Stairs 10 cfm 92 cfm 92 cfm 15 cfm 34 cfm 92 cfm 92 cfm Stairs Stairs 92 cfm 93 cfm 93 cfm 92 cfm Garage Garage Garage 279 cfm 8 " 6 " 6 "14x3.25 2-14x3.25 14x3.25 14x3.25 6 " 6 " 8 "8 " 14x3.25 20 x 8 14x3.25 14x3.25 14x3.25 14x3.25 282 cfm 2-14x3.25 281 cfm 93 cfm 14x3.25 2-14x3.25 14x3.25 2-14x3.25 14x3.25 13 " 6 " 6 " 6 "6 " 6 " 8 " 6 " 6 " 8 " 6 " 8 "8 " 8 " 20 x 8 18 x 8 6 " 6 " 6 " 6 " 8 "6 " 8 " 6 " 6 " 20 x 8 6 " 16 x 8 6 " 6 " 6 " 6 " 6 " 6 " 6 " All systems will provide fresh air with a pipe and damper attached to the return plenum and extended to the exterior of the building and terminated Job #: Kartchner 3 Plex Performed by Gene Miller for: Sprinter Heating & Hydronics 3846 East 100 North Rigby, ID 83442 Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 1sgmiller@cableone.net Scale: 1 : 104 Page 2 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-May-05 19:05:09 ...home 2\Kartchner townhomes 2.rup N 2nd Floor M WIC Master M Bath Room7 Utility Mech Bedroom 2 Bedroom 3 Stairs/hall M WIC B Master B M Bath B Bath B Utility B Mech B Bedroom 2 B Bedroom 3 B Stairs/Hall B M WIC C Master C M Bath C Bath C Utility C Mech C Bedroom 2 C Bedroom 3 C Stairs/Hall C 41 cfm 122 cfm 27 cfm 4 cfm 6 cfm 129 cfm 130 cfm 8 cfm 125 cfm 69 cfm 194 cfm 187 cfm 45 cfm40 cfm 40 cfm 129 cfm 198 cfm 115 cfm 5 cfm 44 cfm 46 cfm 187 cfm 132 cfm 122 cfm16 cfm 51 cfm 41 cfm 38 cfm 66 cfm 66 cfm 69 cfm 69 cfm 69 cfm 69 cfm 69 cfm 69 cfm 67 cfm 67 cfm 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Duct System Summary 5/5/2020Date:AH A Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.283 / 0.207 in H2O in H2O0.283 / 0.207 Lowest friction rate in/100ft0.099in/100ft0.099 Actual air flow cfm765cfm565 Total effective length (TEL)ft496 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3175.021.0VlFx0x08.00.144122651754cBedroom 2 st3245.030.0VlFx0x06.00.1036657949cBedroom 3 st3210.033.3VlFx0x06.00.1166657949cBedroom 3-A st3175.026.8VlFx0x08.00.14092711331cKit/din/family st3240.035.3VlFx0x08.00.10392711331cKit/din/family-A st3175.06.3VlFx0x06.00.15692711331cKit/din/family-B st3255.018.3VlFx0x06.00.104816566hM Bath st3175.023.0VlFx0x06.00.1434131598cM WIC st3220.037.5VlFx0x06.00.1106943992cMaster st3255.031.5VlFx0x06.00.0996943992cMaster-A st3175.05.8VlFx0x06.00.157210374hPwdr st3230.014.8VlFx0x06.00.116927957hRoom7 st3175.011.0VlFx0x06.00.152384542cUtility Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 565 765 0.099 830 13.0 0x0 ShtMetl 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb1 0x 310 46 107.0 0.193 147 3.8 3.25x14 10x9 SJSp rt3 rb7 0x 2240 279 100.8 0.205 441 7.4 2-3.25x14 2-10x18 SJSp rt3 rb13 0x 1320 187 104.5 0.198 591 6.4 3.25x14 10x9 SJSp rt3 rb14 0x 650 122 156.0 0.133 385 5.9 3.25x14 10x9 SJSp rt3 rb15 0x 1140 132 209.5 0.099 416 6.5 3.25x14 10x9 SJSp rt3 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt3 Peak AVF 565 765 0.099 689 12.5 20x8 ShtMetl 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Duct System Summary 5/5/2020Date:AH b Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.279 / 0.211 in H2O in H2O0.279 / 0.211 Lowest friction rate in/100ft0.101in/100ft0.101 Actual air flow cfm767cfm565 Total effective length (TEL)ft486 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2210.015.0VlFx0x06.00.12444107hBath B st2175.021.8VlFx0x08.00.1421301051770cBedroom 2 B st2230.031.3VlFx0x08.00.1071291061756cBedroom 3 B st2240.034.8VlFx0x08.00.10293701268cKit/din/Family B st2175.027.5VlFx0x08.00.13893701268cKit/din/Family B-A st2255.08.3VlFx0x08.00.10693701268cKit/din/Family B-B st2255.017.5VlFx0x06.00.10256139hM Bath B st2175.024.5VlFx0x06.00.1404133562cM WIC B st2245.031.5VlFx0x06.00.1016940936cMaster B st2220.036.5VlFx0x06.00.1096940936cMaster B-A st2175.03.5VlFx0x06.00.156215374hPwdr B st2255.011.0VlFx0x06.00.105406540cUtility B Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 565 767 0.101 767 12.4 18x8 ShtMetl 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb2 0x 100 44 106.8 0.198 138 3.7 3.25x14 10x9 SJSp rt2 rb6 0x 2260 281 107.8 0.196 445 7.5 2-3.25x14 2-10x18 SJSp rt2 rb10 0x 780 115 95.0 0.222 364 5.2 3.25x14 10x9 SJSp rt2 rb11 0x 1450 198 170.8 0.124 314 7.2 2-3.25x14 2-10x18 SJSp rt2 rb12 0x 1060 129 209.3 0.101 408 6.4 3.25x14 10x9 SJSp rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 565 767 0.101 690 12.4 20x8 ShtMetl 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Kartchner 3 PlexJob:Duct System Summary 5/5/2020Date:AH C Gene MillerBy: Kartchner 3 PlexPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.279 / 0.211 in H2O in H2O0.279 / 0.211 Lowest friction rate in/100ft0.137in/100ft0.137 Actual air flow cfm776cfm565 Total effective length (TEL)ft357 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1130.017.5VlFx0x06.00.18945195hBath C st1175.019.0VlFx0x06.00.1446964976cBedroom 2 C st1175.022.3VlFx0x06.00.1426964976cBedroom 2 C-A st1140.031.5VlFx0x08.00.163125761783cBedroom 3 C st1150.035.5VlFx0x06.00.15192621309cKit/din/Fam C st1175.028.3VlFx0x08.00.13792621309cKit/din/Fam C-A st1175.06.5VlFx0x06.00.15492621309cKit/din/Fam C-B st1165.018.0VlFx0x06.00.15368279hM Bath C st1175.027.5VlFx0x06.00.13847511868hM WIC C st1160.032.5VlFx0x06.00.1456731955cMaster C st1130.037.5VlFx0x06.00.1676731955cMaster C-A st1175.03.5VlFx0x06.00.1577341233hPwdr C 00VlFx0x0004014574cUtility C Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 551 736 0.137 828 11.5 16x8 ShtMetl 2020-May-05 19:04:18 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6 ...\Kartchner townhome 2\Kartchner townhomes 2.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 190 45 121.5 0.173 141 3.9 3.25x14 10x9 SJSp rt1 rb4 0x 1210 187 94.8 0.222 591 6.3 3.25x14 10x9 SJSp rt1 rb5 0x 2200 282 153.3 0.137 447 8.1 2-3.25x14 2-10x18 SJSp rt1 rb8 0x 640 69 140.0 0.150 217 4.7 3.25x14 10x9 SJSp rt1 rb9 0x 1400 194 144.3 0.146 613 6.9 3.25x14 10x9 SJSp rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 565 776 0.137 698 11.7 20x8 ShtMetl